Emerson® Wireless Solutions Installation Manual Table of Contents 1.0 INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 1.1 Integration with Monitoring System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 2.0 INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 2.1 What’s Included . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 2.2 Tools And Materials Required . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 2.3 Locating the Wireless Gateway . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 2.4 Mounting the Power Supply and Wireless Gateway . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 2.4.1 2.4.2 2.4.3 2.4.4 Mount the DIN Rail . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Mount the Wireless Gateway and Power Supply on the DIN Rail . . . . . . . . . . . . . . . . . . . . . . Removing the Wireless Gateway from the DIN Rail . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Connect Power and Communication Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 4 5 6 2.5 Mount the Remote Antenna (Optional-Indoor Only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 2.6 Record Each Wireless Node’s MAC Address and Location . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 2.7 Mount the Wireless Nodes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 3.0 COMMISSIONING THE WIRELESS SOLUTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10 3.1 Wireless Gateway . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 3.2 Wireless Nodes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 3.3 Wireless Monitoring System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 3.4 Wireless Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Figures Figure 1 Figure 2 Figure 3 Figure 4 Figure 5 Figure 6 Figure 7 Figure 8 Wirelss Gateway and power supply dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Snap wireless gateway onto DIN rail . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Remove wireless gateway from DIN rail . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Serial connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Convert from full to half duplex . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Remote antenna dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Wireless node and sensor string routing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . i 3 4 5 6 7 7 8 9 ii Introduction 1.0 INTRODUCTION This document details installing: • New Emerson® wireless solutions, including wireless gateway and wireless nodes • Adding wireless nodes and wireless gateways, if necessary, to expand an existing wireless network. Emerson’s wireless solutions are designed to be installed indoors only, using traditional work practices to ensure accurate measurements. The system will consist of a wireless gateway and wireless nodes. Wireless Gateway The wireless gateway provides several functions, including interfacing with the monitoring system, managing communication with the wireless nodes and collecting data from the wireless nodes. A wireless node consists of the radio for the wireless communication with the gateway and the sensor string (cable with three temperature sensors). Together these devices create a system to provide an easy-to-deploy, adaptable solution to monitor an environment. Emerson wireless devices based on IEC 62591 (WirelessHART) technology use small amounts of bandwidth, enabling high-priority communications. Security and reliability have been engineered into the WirelessHART standard utilizing proven industry standards. However, one of the most important features Emerson wireless solutions is the extremely low power requirement. Wireless Nodes Each wireless node is a battery-powered radio with a sensor string for monitoring the conditioned space. Emerson recommends placing the radio on top of the rack and attaching the sensor string to the rack door with the temperature sensors strategically spaced to provide top, middle and bottom monitoring of a rack. 1.1 Integration with Monitoring System The wireless network must be integrated with a monitoring system. An Emerson wireless network is compatible with: • Liebert® SiteScan® Web • Emerson’s Trellis™ • Building Management Systems 1 Emerson® Wireless Solutions Installation 2.0 INSTALLATION 2.1 What’s Included Wireless Gateway Components • 1410 wireless gateway with DIN rail mount • Basic Antenna 1410 Mount Kit • • • • • Power Supply (100-240 VAC) 50/60Hz with DIN rail mount DIN Rail, 3-1/8" (79mm) Input Power Cord with 5-15 Plug Power Cable from Power Supply to Wireless Gateway Mounting Hardware Remote Antenna Kit—Optional • • • • Antenna Mounting Bracket Mounting Hardware 10 ft. (3m) Lead Cable Wireless Node Components • 52WM-3T with Three Temperature Sensor String • Mounting Hardware 2.2 Tools And Materials Required • • • • • 2.3 Ethernet (LAN) Cable Network Connection Input Power Backed Up with a UPS Screwdrivers Drill and Bits Locating the Wireless Gateway The wireless gateway should be mounted indoors above any obstruction that might interfere with the radio connection to wireless nodes. General guidelines include: • • • • • Mount the wireless gateway and power supply where they are easily accessible Mount the wireless gateway and power supply indoors on a solid, non-metallic surface 2.5 feet (0.76m) above any obstruction (higher placement increases wireless range) 2.5 feet (0.76m) from a vertical surface that might cause radio interference DIN rail must be grounded in accordance with national and local electrical codes. Attaching the wireless gateway to the DIN rail grounds the gateway. • Away from metal obstructions, such as metal partitions or wide cabinets • Maximize the number of wireless nodes in line-of-sight with the wireless gateway. This may lead to longer battery life, more efficient network formation and faster startup. • Mount near an input power source—100-240VAC with UPS backup Emerson® Wireless Solutions 2 Installation 2.4 Mounting the Power Supply and Wireless Gateway 2.4.1 Mount the DIN Rail 1. Determine the mounting location. Consider the size of the wireless gateway and power supply and radio reception as determined in the design phase. 2. Hold the DIN rail against the wall and mark two hole locations. 3. Drill the holes to accept the mounting screws. 4. If using the provided hardware, the holes must accommodate a 1/4" drywall anchor; in sheet metal, drill pilot holes for a #10 screw. 5. Screw the rail to the wall. 6. Ground the DIN rail according to national and local electric codes. NOTE The most effective grounding method is a direct connection to earth ground with minimal impedance. Grounding to the wireless gateway is accomplished through the DIN rail clip on the back of the gateway. Figure 1 Wireless Gateway and power supply dimensions 4.8" (121.9mm) 2.25" (57.2mm) 1.44" (37mm) Antenna Connector +V -V DC OK 24V 1.0A DC OK 6.46" (164mm) + 3.54" (90mm) +V ADJ MW Mean Well 100-240VAC 0.55A 50/60Hz DIN Rail Slot N L Front Bottom (Side View) Bottom (Front View) 1-3/8" (35mm) 3-1/8" (79mm) 3 Emerson® Wireless Solutions Installation 2.4.2 Mount the Wireless Gateway and Power Supply on the DIN Rail 1. Fit the wireless gateway onto the DIN rail with the antenna connection at the top. 2. Open the spring-loaded sliding latch on the back of the gateway to secure it to the rail. 3. Orient the power supply as shown in Figure 2 and secure it to the DIN rail. This orientation makes it easier to connect the input power wires from the power supply to the wireless gateway. 4. Tilt the wireless gateway at a slight angle, allowing the lower lip of the chassis to catch the bottom of the DIN rail. 5. Pressure the wireless gateway to snap the back of the unit securely onto the DIN rail. Figure 2 Snap wireless gateway onto DIN rail Emerson® Wireless Solutions 4 Installation 2.4.3 Removing the Wireless Gateway from the DIN Rail To remove the unit the wireless gateway: 1. Place a flat or rounded tool, such as a screwdriver, into the DIN clip and apply a slight downward pressure on the tool. 2. Once the unit is released from the DIN rail pull backwards and down to disengage it from the DIN rail. Figure 3 Remove wireless gateway from DIN rail 5 Emerson® Wireless Solutions Installation 2.4.4 Connect Power and Communication Wiring 1. Use a small flat-bladed screwdriver to loosen the two terminal block screws on the wireless gateway and the two terminal block screws on the power supply indicated in Figure 4. 2. Insert the stripped ends of the factory-supplied power cable into the terminal blocks as shown in Figure 4 and tighten them: Connect V- to V- and V+ to V+ 3. Loosen the ground, neutral and line-in screws on the power supply. 4. Connect the factory-supplied input power cord (with integrated plug) to the power supply and tighten the terminal block screws: Connect green to ground, white to N and black to L. 5. Screw the antenna onto the stub at the top of the wireless gateway. 6. Connect the CAT 5e network cable to RJ-45 Port 1 on the wireless gateway (see Figure 4). An optional RS-485 serial communication cable may be connected to the wireless gateway to link it to the communication module. See Serial Communication (Optional) on page 7. NOTE The Ethernet connection permits configuring the wireless network and collecting data. The serial communication cable does not permit configuration. Figure 4 Wiring diagram Antenna Stub Factory-Supplied Power Cable +V -V DC OK 24V 1.0A DC OK + +V ADJ MW Mean Well 100-240VAC 0.55A 50/60Hz N Network Cable L Input Power Emerson® Wireless Solutions Serial Cable 6 Installation Serial Communication (Optional) 1. Use 18 AWG twisted pair wiring; maximum length is 4,000 ft. (1220 m) 2. Connect Terminal A to the negative terminal on the Communication Module 3. Connect Terminal B to the positive terminal on the Communication Module (see Figure 5). Figure 5 Serial connection 24VDC (Nominal) Power Input + Serial Modbus Communication Module + - S A B Convert Full Duplex to Half Duplex If the Communication Module uses a four-wire full duplex configuration, see Figure 6 - Convert from full to half duplex to convert to a 2-wire Half Duplex configuration. Figure 6 Convert from full to half duplex TX Terminal A RX - TX + Terminal B RX + 7 Emerson® Wireless Solutions Installation 2.5 Mount the Remote Antenna (Optional-Indoor Only) 1. Attach the remote antenna bracket to a solid, rigid, non-metallic surface using the included hardware or four field-supplied screws or bolts. 2. Mount the remote antenna on the bracket as shown in Figure 7. 3. Secure the remote antenna with the supplied nut. 4. Connect one end of the 10 ft. (3m) lead cable to the remote antenna as shown in Figure 7. 5. Connect the other end of the lead cable to the wireless gateway (see Detail A in Figure 7). Figure 7 Remote antenna dimensions Dimensions are for reference only. Ø .64" (16.38mm) Ø .34" (8.76mm) 4 Places 2" (50mm) 3.2" (81mm) 2.4" (60mm) 14.79" (375.6mm) 2" (50mm) 3.9" (100mm) Mounting Bracket 1.26" (32.1mm) Antenna Diameter Nut secures antenna to the bracket DETAIL A .31" (8mm) Lead Cable Connection to Remote Antenna Antenna with Mounting Bracket Emerson® Wireless Solutions .36" (9.2mm) Drill .39" (10mm) hole if required for routing lead cable 8 Installation 2.6 Record Each Wireless Node’s MAC Address and Location Before beginning to install the wireless nodes, record each unit’s MAC address and physical location. This information should be noted on the document used to design the wireless network. Recording each wireless node’s MAC address and physical location eases data collection and troubleshooting. For example, if a sensor reports high temperatures in a rack, knowing where that sensor is installed enables correcting the cause before the equipment overheats. A wireless node’s MAC address may be difficult to see after installation. The MAC address location and part number are shown at right. 2.7 Mount the Wireless Nodes MAC Address Part # Location The wireless nodes may be placed so that the sensors monitor either the Location intake (cold) air or the exhaust (hot) air. These instructions are for monitoring the intake air. To monitor exhaust air, place the wireless nodes and sensor string on the rear of the rack. When fully installed, a wireless node is positioned on top of the rack with the fewest possible obstructions that might degrade the radio signal. The sensor string runs down the inner side of the rack door, along the door hinge side and along the door’s midline. 1. Record each wireless node’s MAC address and physical location in the facility. 2. Attach the wireless node on top of the rack, either with supplied hook-and loop-fasteners or with cable fasteners. (The wireless node has slots on each end for the cable fasteners). NOTE The hook-and-look fastener has adhesive to attach to the wireless node. Do not attach the fastener so that it covers any of the labeling. If necessary, clean the rack and the wireless node with the included alcohol swab. 3. Route the sensor string through an opening in the rack—protect the wiring from being pinched. 4. Attach the sensor string to the inside of the rack door with at least one cable fastener, leaving enough cable slack so that the door will open without stretching or pinching the wire. 5. Space the sensors evenly on the rack door. Keep the cable straight and tight while securing the sensor string. 6. Trim excess cable fastener material and discard it. Figure 8 Wireless node and sensor string routing Wireless node on top of rack Slack in wire permits door to open Sensor String on Rack Door Rack Door 9 Emerson® Wireless Solutions Commissioning the Wireless Solutions 3.0 COMMISSIONING THE WIRELESS SOLUTIONS Liebert Services will commission the wireless network components: • Wireless Gateway • Wireless Nodes • Wireless Monitoring System (procedures vary according to system) Liebert Services will perform the following steps. 3.1 Wireless Gateway • Verify proper input power and UPS backup. • Verify all devices are connected with a reliability at or above 99%. • Verify that at least 15% of the wireless nodes are communicating directly with the wireless gateway instead of through a neighbor wireless node. The design rule is 25% of wireless nodes due to the dynamic nature of the environment; the commission rule is 15%. • Load the Modbus register mapping into the wireless gateway. 3.2 Wireless Nodes • Verify that the wireless nodes are properly installed. • Configure Network ID and Join Key, giving each wireless node proper security to join a unique wireless network. • Verify through the wireless gateway that each wireless node has at least two neighbors. • The design rule is three neighbors, due to the dynamic nature of the environment; the commission rule is two neighbors. • Verify through the wireless gateway that the data is updating at the desired rate. 3.3 Wireless Monitoring System • Verify data from the wireless gateway appears in the monitoring application. • Interface with BMS contractor to verify operation and setup with BMS system. 3.4 Wireless Network When complete, all wireless connections between wireless nodes can be viewed live in the DCIM application. The effective range of the wireless network may exceed the design distance. The self-organizing technology essentially places a wireless engineer inside of each WirelessHART compliant wireless node that dynamically responds to the current state of the environment. The self-organizing technology will always use the best possible links and the conservative application of design rules ensures an adequate number of potential connections from which the best connections can be chosen by the radios, without the user needing to be a wireless expert. Emerson® Wireless Solutions 10 While every precaution has been taken to ensure the accuracy and completeness of this literature, Liebert Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions. © 2013 Liebert Corporation All rights reserved throughout the world. Specifications subject to change without notice. ® Liebert is a registered trademark of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners. SL-53705_REV0_07-15 Emerson Network Power Liebert www.emerson.com Technical Support / Service Web Site www.liebert.com Monitoring liebert.monitoring@emerson.com 800-222-5877 Outside North America: +00800 1155 4499 Single-Phase UPS & Server Cabinets liebert.upstech@emerson.com 800-222-5877 Outside North America: +00800 1155 4499 Three-Phase UPS & Power Systems 800-543-2378 Outside North America: 614-841-6598 Environmental Systems 800-543-2778 Outside the United States: 614-888-0246 Locations United States 1050 Dearborn Drive P.O. Box 29186 Columbus, OH 43229 Europe Via Leonardo Da Vinci 8 Zona Industriale Tognana 35028 Piove Di Sacco (PD) Italy +39 049 9719 111 Fax: +39 049 5841 257 Asia 29/F, The Orient Square Building F. Ortigas Jr. Road, Ortigas Center Pasig City 1605 Philippines +63 2 687 6615 Fax: +63 2 730 95