RPC2 Communications Module Rack PDU SNMP OIDs Technical Bulletin

advertisement
RPC2 Communications Module
Rack PDU SNMP OIDs
Technical Bulletin
For important safety information, visit:
www.emersonnetworkpower.com/ComplianceRegulatoryInfo
This document supports versions up to and including release 10.0.0.2.
Emerson, Emerson Network Power, the Emerson Network Power logo, MPH2 and RPC2 are trademarks or service marks
of Emerson Electric Co. Avocent, DSView, MergePoint Unity and Trellis are trademarks or service marks of Avocent
Corporation. Liebert, MPH, MPX, NForm and SiteScan are trademarks or service marks of Liebert Corporation This
document may contain confidential and/or proprietary information of Avocent Corporation, and its receipt or possession does
not convey any right to reproduce, disclose its contents, or to manufacture or sell anything that it may describe. Reproduction,
disclosure, or use without specific authorization from Avocent Corporation is strictly prohibited. ©2016 Avocent Corporation.
All rights reserved.
I
TABLE OF CONTENTS
Overview
1
SNMP
1
Configuration
1
MIB File
2
RPC2 Configuration SNMP OID Tables
5
LIEBERT‐GP‐PDU-MIB::lgpPduTable
6
LIEBERT‐GP‐PDU-MIB::lgpPduPsTable
10
LIEBERT‐GP‐PDU-MIB::lgpPduRbTable
15
LIEBERT-GP-PDU-MIB::lgpPduRcpTable
20
LIEBERT‐GP‐PDU-MIB::lgpPduAuxMeasTable
28
LIEBERT‐GP‐PDU-MIB::lgpPduAuxMeasOrderTable
33
II.....RPC2 Communications Module SNMP, MIB, OID Technical Bulletin
Overview
This document is a supplement to the RPC2 Communications Module User Guide and is intended to assist
with using Simple Network Management Protocol (SNMP), Management Information Base (MIB) and Object
Identifiers (OIDs) with your RPC2 communications module and MPH2 rack PDU. For more information on
using your RPC2 communications module or MPH2 rack PDU, please refer to their respective user guides.
SNMP
An SNMP manager queries an agent using User Datagram Protocol (UDP) within an IP network for specific
information, and the agent will answer the query. For example:
C:\>snmpget - v2c - cpublic - mALL -OenU 10.88.1.69
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.35.1.1
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.35.1.1 = STRING: MPHR3341
C:\>
NOTE: Not all OIDs in an MIB file will return values when queried.
The SNMP agent can also send trap or notification messages.
Configuration
You must define on the rack PDU the devices which have access to SNMP information. You can do this from
the System tab of the RPC2 communications module.
To configure SNMP access:
1. From the System tab of the RPC2 module user interface (UI), click SNMP-V1V2 Access.
-orClick SNMP-V3 Access.
2. Set the desired configuration settings and click the green Save checkmark.
To configure SNMP traps:
1. From the System tab of the RPC2 module user interface (UI), click SNMP-V1V2 Traps.
-orClick SNMP-V3 Traps.
2. Set the desired configuration settings and click the green Save checkmark.
NOTE: The IP address 0.0.0.0 is used to authorize a user.
NOTE: The Community string is a passphrase which needs to be configured from the management
software.
2.....RPC2 Communications Module SNMP, MIB, OID Technical Bulletin
SNMP-V1V2 Access Page
MIB File
The Management Information Base (MIB) file is a database used to manage data points. All data points are
organized in a directory tree. The MIB file organizes data points by name, but each data point name is also
assigned a hierarchical number based on its location in the tree. The complete numerical path of a data point is
that data point's object identifier (OID).
The following is an example of a MIB file: <?xml version="1.0"?>-<MIBData>
-<Instances>
<!-- lgpPduRbEntryId.1.1 -->
-<Instance valueType="Gauge" oid=".1.3.6.1.4.1.476.1.42.3.8.40.20.1.5.1.1"
name="lgpPduRbEntryId.1.1">
-<Value>
<![CDATA[1]]>
Overview.....3
</Value>
</Instance>
<!-- lgpPduRbEntryId.1.2 -->
-<Instance valueType="Gauge" oid=".1.3.6.1.4.1.476.1.42.3.8.40.20.1.5.1.2"
name="lgpPduRbEntryId.1.2">
-<Value>
<![CDATA[2]]>
</Value>
</Instance>
<!-- lgpPduRbEntryUsrLabel.1.1 -->
-<Instance valueType="OctetString" oid=".1.3.6.1.4.1.476.1.42.3.8.40.20.1.8.1.1"
name="lgpPduRbEntryUsrLabel.1.1">
-<Value>
<![CDATA[Branch A]]>
</Value>
</Instance>
<!-- lgpPduRbEntryUsrLabel.1.2 -->
-<Instance valueType="OctetString" oid=".1.3.6.1.4.1.476.1.42.3.8.40.20.1.8.1.2"
name="lgpPduRbEntryUsrLabel.1.2">
-<Value>
<![CDATA[Branch B]]>
</Value>
</Instance>
<!-- lgpPduRbEntrySysAssignLabel.1.1 -->
-<Instance valueType="OctetString" oid=".1.3.6.1.4.1.476.1.42.3.8.40.20.1.20.1.1"
name="lgpPduRbEntrySysAssignLabel.1.1">
-<Value>
<![CDATA[1-A]]></Value>
</Instance>
<!-- lgpPduRbEntrySysAssignLabel.1.2 -->
-<Instance valueType="OctetString" oid=".1.3.6.1.4.1.476.1.42.3.8.40.20.1.20.1.2"
name="lgpPduRbEntrySysAssignLabel.1.2">
-<Value>
<![CDATA[1-B]]>
</Value>
</Instance>
<!-- lgpPduRbEntryPositionRelative.1.1 -->
4.....RPC2 Communications Module SNMP, MIB, OID Technical Bulletin
-<Instance valueType="Gauge" oid=".1.3.6.1.4.1.476.1.42.3.8.40.20.1.25.1.1"
name="lgpPduRbEntryPositionRelative.1.1">
-<Value>
<![CDATA[1]]>
</Value>
</Instance>
<!-- lgpPduRbEntryPositionRelative.1.2 -->
-<Instance valueType="Gauge" oid=".1.3.6.1.4.1.476.1.42.3.8.40.20.1.25.1.2"
name="lgpPduRbEntryPositionRelative.1.2">
-<Value><![CDATA[2]]>
</Value>
</Instance><!-- lgpPduRbEntrySerialNum.1.1 -->
-<Instance valueType="OctetString" oid=".1.3.6.1.4.1.476.1.42.3.8.40.20.1.30.1.1"
name="lgpPduRbEntrySerialNum.1.1">
-<Value>
<![CDATA[418321G3-A]]>
</Value>
</Instance>
<!-- lgpPduRbEntrySerialNum.1.2 -->
-<Instance valueType="OctetString" oid=".1.3.6.1.4.1.476.1.42.3.8.40.20.1.30.1.2"
name="lgpPduRbEntrySerialNum.1.2">
-<Value>
<![CDATA[418321G3-B]]>
</Value>
</Instance>
</Instances>
</MIBData>
Within the Emerson Network Power MIB Archive you’ll find the following two enterprise-specific MIB files:
•
LIEBERT_GP_PDU.MIB
•
LIEBERT_GP_REGISTRATION.MIB
These files can be downloaded from http://www.emersonnetworkpower.com/en-US/Support/SoftwareDownloads/ACPower-UPS/Rack-PDU/Pages/MPH2-Managed-Rack-PDU.aspx
In addition to these files, you need the SNMPv2‐SMI, which is standardized by IETF and can be downloaded
from http://www.net-snmp.org/docs/mibs/SNMPv2‐MIB.txt
NOTE: You should compile the SNMv2 MIB first followed by the Liebert_GP_Reg MIB then the Liebert_
GP_PDU.MIB.
RPC2 Configuration SNMP OID Tables
The following tables display information about the OIDs of the Liebert_GP_PDU.MIB.
NOTE: The following OIDs are not completely defined in that a set of row indices need to be appended in
order to index into the correct row of the table. For example, lgpPduRcpEntryUsrLabel would give an OID
of .1.3.6.1.4.1.476.1.42.3.8.50.20.1.10.X.Y.Z, where X=PDU number in an array, Y=Branch number, and
Z=Receptacle number. The maximum dimension and range of the row indices are model and OID specific
and can be determined through MIB browser analysis.
OID Column Number
70.1.3.6.1.4.1.476.1.42.3.8.10.5
Data Point Name
lgpPduGrpSysStatus.0
Gauge32
Syntax
ro
Access
LIEBERT‐GP‐PDU-MIB::lgpPduTable
•
•
•
•
•
•
There is a failure within the system that is unexpected under normal
abnormalOperation(32): One or more PDUs are operating abnormally.
alarm(s) as soon as possible and take appropriate action.
one or more active alarms. Appropriate personnel should investigate the
normalWithAlarm(16): One or more PDUs are operating normally with
the warning(s) as soon as possible and take ppropriate action.
one or more active warnings. Appropriate personnel should investigate
normalWithWarning(8): One or more PDUs are operating normally with
more PDUs in the cluster/group.
at this time or there is no support for this piece of information from 1 or
unknownNoSupport(4): The state of one or more PDUs are not known
the PDU is in this state. This statecontrol and monitoring commands.
Control and monitoring operations may be inhibited or unavailable while
startUp(2): One or more PDUs are in the startup state (initializing).
normally with no active warnings or alarms.
normalOperation(1): One or more PDUs in the cluster are operating
the cluster.
The value is a logical OR of all of the following potential states of each PDU in
right-most digit). The state ispresent in the PDU when the bit is on (value =1).
description below. The bit position is big‐endian (least significant digit is the
Note the bitposition is given parenthetically next to the operational state in the
'lgpPduTable' which represents the combined statuses of all PDUs for this agent.
Bit‐wise logical OR of all of the 'lgpPduEntrySysStatus' columns in the
Description
startUp
(2)
Default
Units
Range
Comment
6.....RPC2 Communications Module SNMP, MIB, OID Technical Bulletin
OID Column Number
.1.3.6.1.4.1.476.1.42.3.8.19
.1.3.6.1.4.1.476.1.42.3.8.20.1.5
.1.3.6.1.4.1.476.1.42.3.8.20.1.10
.1.3.6.1.4.1.476.1.42.3.8.20.1.15
.1.3.6.1.4.1.476.1.42.3.8.20.1.20
.1.3.6.1.4.1.476.1.42.3.8.20.1.25
Data Point Name
lgpPduTableCount.0
lgpPduEntryId.1
lgpPduEntryUsrLabel.1
lgpPduEntrySysAssignLabel.1
lgpPduEntryPositionRelative.1
lgpPduEntrySysStatus.1
Gauge32
Gauge32
String
String
Gauge32
Gauge32
Syntax
ro
ro
ro
ro
ro
ro
Access
when the PDU (s) are fully initialized and ready to accept.
unknownCommFailure(64): The state of one will clear automatically
•
•
startUp(2) - The PDU is in the startup state (initializing). Control and
warnings or alarms.
normalOperation(1): The PDU is operating normally with no active
most digit). The state is present in the PDU when the bit is on (value=1).
position is assumed to be a big‐endian format (least significant digit is the right-
parenthetically next to the operational state in the description below. The bit
all of the following potential states of the PDU. Note the bitposition is given
Bit-field of the various operational states of the PDU. The value is a logical OR of
Indicates the PDU's relative position within the array.
System assigned identifier representing the PDU.
User assigned label representing the PDU.
Internal index representing a unique identifier for each PDU represented by this
agent. The value is assigned by the agent at the time of discovery.
Number of PDUs being monitored by this agent. This is the number of entries in
the lgpPduTable.
•
likely inhibited.
cause as soon as possible. The normal functioning of the system is
operating conditions. Appropriate personnel should investigate the
Description
1
1
<MPH>
or
<MPH2>
or
<MPX>
Default
Units
1-4
0-48 characters
Range
The value is
independent of any
user assigned label
or tag.
Default assignment
depends upon
device discovered at
power up. The
allowed characters
include
alphanumeric,
space, and ~!#$_+`={}|[]\\:;'?,.\/%^&*()
@
Comment
RPC2 Configuration SNMP OID Tables.....7
OID Column Number
.1.3.6.1.4.1.476.1.42.3.8.20.1.35
.1.3.6.1.4.1.476.1.42.3.8.20.1.40
.1.3.6.1.4.1.476.1.42.3.8.20.1.45
.1.3.6.1.4.1.476.1.42.3.8.20.1.50
Data Point Name
lgpPduEntryUsrTag1.1
lgpPduEntryUsrTag2.1
lgpPduEntrySerialNumber.1
lgpPduEntryRbCount.1
Gauge32
String
String
String
Syntax
ro
ro
rw
rw
Access
likely inhibited.
cause as soon as possible. The normal functioning of the system is
operating conditions. Appropriate personnel should investigate the
there is some failure within the system that is unexpected under normal
abnormalOperation(32): The PDU is operating abnormally. That is
soon as possible and take appropriate action.
active alarms. Appropriate personnel should investigate the alarm(s) as
normalWithAlarm(16): The PDU is operating normally with one or more
warning(s) as soon as possible and take appropriate action.
more active warnings. Appropriate personnel should investigate the
normalWithWarning(8): The PDU is operating normally with one or
Number of receptacle branches within this PDU.
Serial number for this RPC2 module assigned at time of manufacture and is
globally unique with respect to all RPC2 modules.
A configuration parameter to set user assigned tag
A configuration parameter to set user assigned tag for the PDU. This value may
be useful for enduser grouping or asset tracking purposes. The value for this tag
does not need to be unique for this unit or across other units.
•
•
•
fully initialized and ready to accept control and monitoring commands.
in this state. This state will clear automatically when the PDU(s) are
monitoring operations maybe inhibited or unavailable while the PDU is
Description
<empty>
<empty>
Default
Units
1-7
0-48 characters
0-48 characters
Range
Maximum seven
branches are
supported.
The agent serial
numbers for each
member of the array
is reported.
The allowed
characters include
alphanumeric,
space, and ~!#$_+`={}|[]\\:;'?,.\/%^&*()
@
The allowed
characters include
alphanumeric,
space, and ~!#$_+`={}|[]\\:;'?,.\/%^&*()
@
Comment
8.....RPC2 Communications Module SNMP, MIB, OID Technical Bulletin
OID Column Number
.1.3.6.1.4.1.476.1.42.3.8.20.1.55
Data Point Name
lgpPduEntrySWOverCurrentProtection.1
Integer
Syntax
rw
Access
Locked & On: No change.
Unlocked & Off: Receptacle shall be locked.
Unlocked & On: If the receptacle is drawing current, then no change. If
•
•
•
No action will be taken if the feature is disabled.
that receptacle is not drawing current, then turn it off and lock it.
Locked & Off: No change.
•
Alarm condition, the following action will be taken on the receptacles:
receptacles. If the feature is enabled, in case of PDU Over Current Warning or
violated. Only admin users shall have the authorization to unlock such
the 'PDU Over Current Warning' or 'PDU Over Current Alarm' threshold is
Protection (SOCP) feature to prevent unused receptacles from turning on when
A configuration parameter to enable or disable the Software Over Current
Description
disabled
(0)
Default
Units
0-1
Range
Only applicable to
PDUs having
receptacle
measurement and
control.
Comment
RPC2 Configuration SNMP OID Tables.....9
OID Column Number
.1.3.6.1.4.1.476.1.42.3.8.30.19
.1.3.6.1.4.1.476.1.42.3.8.30.20.1.10
.1.3.6.1.4.1.476.1.42.3.8.30.20.1.15
.1.3.6.1.4.1.476.1.42.3.8.30.20.1.20
.1.3.6.1.4.1.476.1.42.3.8.30.20.1.25
Data Point Name
lgpPduPsTableCount.0
lgpPduPsEntryId.1.1
lgpPduPsEntrySysAssignLabel.1.1
gpPduPsEntryModel.1.1
lgpPduPsEntryWiringType.1.1
Integer
String
String
Gauge32
Gauge32
Syntax
rw
ro
ro
ro
ro
Access
LIEBERT‐GP‐PDU-MIB::lgpPduPsTable
•
•
•
•
•
three-phase-5-wire‐L1-L2-L3-N-PE
(2P4W).
Three-phase input with four wires
three‐phase-4-wire-L1-L2-L3-PE (3):
phase input with three wires (2P3W).
two-phase-3-wire-L1-L2-PE (2): Two-
(1P3W).
Singlephase input with three wires
single-phase-3-‐wire‐L1-N-PE (1):
physical wiring type.
must configure this object to specify the
specified or configured. The end user
not-specified (0): The type has not been
poles/phase and wires of the PDU power source.
Enumerations that describe the number of
Model number assigned at the time of
manufacture.
System assigned identifier for this power source.
The value is independent of any user assigned
label or tag. The exact format of this label is
system dependent and is subject to change;
therefore, it should not be referenced for
programmatic use.
This is a unique entry id representing a given
PDU power source for the PDU.
Number of power sources in the lgpPduPsTable.
Description
0
<x>
Default
Units
0-5
1-3
Range
Some UL Listed 3P4W PDUs may be
equipped with a 3P5W plug type, e.g. L2130P, where the neutral is unused. It’s not
recommended this object be written.
This string is displayed on the PDU’s
nameplate barcode.
Format is x=PDU {1-4}
Comment
10.....RPC2 Communications Module SNMP, MIB, OID Technical Bulletin
OID Column Number
.1.3.6.1.4.1.476.1.42.3.8.30.20.1.30
.1.3.6.1.4.1.476.1.42.3.8.30.20.1.35
.1.3.6.1.4.1.476.1.42.3.8.30.20.1.40
.1.3.6.1.4.1.476.1.42.3.8.30.20.1.50
.1.3.6.1.4.1.476.1.42.3.8.30.20.1.55
.1.3.6.1.4.1.476.1.42.3.8.30.20.1.60
.1.3.6.1.4.1.476.1.42.3.8.30.20.1.65
.1.3.6.1.4.1.476.1.42.3.8.30.20.1.70
.1.3.6.1.4.1.476.1.42.3.8.30.20.1.75
.1.3.6.1.4.1.476.1.42.3.8.30.20.1.80
Data Point Name
lgpPduPsEntryEpInputRated.1.1
lgpPduPsEntryEcInputRated.1.1
lgpPduPsEntryFreqRated.1.1
lgpPduPsEntryEnergyAccum.1.1
lgpPduPsEntrySerialNum.1.1
lgpPduPsEntryFirmwareVersion.1.1
lgpPduPsEntryPwrTotal.1.1
lgpPduPsEntryEcNeutral.1.1
lgpPduPsEntryEcNeutralThrshldOvrWarn.1.1
lgpPduPsEntryEcNeutralThrshldOvrAlarm.1.1
Gauge32
Gauge32
Gauge32
Gauge32
String
String
Gauge32
Gauge32
Gauge32
Gauge32
Syntax
rw
rw
ro
ro
ro
ro
rw
ro
ro
ro
Access
0.1 RMS
Amperes
%
40
45
Neutral current calculated from the summation of
phase currents of this PDU.
A configuration parameter to set the threshold at
which an overcurrent warning is activated. If the
measured line current is equal to or over this
percentage of the full scale rated value,
lgpPduPsEntryEcInputRated, an overcurrent
warning is activated.
A configuration parameter to set the threshold at
which an overcurrent alarm is activated. If the
measured line current is equal to or over this
%
Watts
Total input power calculated from the summation
of all phases of this PDU.
Version of firmware installed on the device.
Serial number for this PDU assigned at time of
manufacture and is globally unique with respect to
all PDU units.
0-100
0-100
0
Must be greater than
lgpPduPsEntryEcNeutralThrshldOvrWarn.
A configuration parameter to set the
threshold at which an overcurrent warning
is activated. If the
Supported for three-phase PDUs only.
This firmware version is unique compared
to the agent’s firmware version.
This string is displayed on the PDU’s
nameplate barcode.
If the energy has not been reset and has
not overflowed the 32-bit value, then this is
the total energy since installation. This
value persists across boot and power
cycle events.
Total accumulated energy of this PDU since the
last energy reset. Writing a value of zero causes
the accumulated energy to be reset. Writing a
nonzero value is invalid and shall result in a write
error and the total energy value remains
unchanged.
0.1
kiloWatthour (kWh)
Irrespective of region, all PDUs can
operate at either 50Hz or 60Hz.
50 or 60
Rated line frequency for this PDU assigned at the
time of manufacture.
Comment
For UL-listed PDUs, the value is derated
to 80% of actual plug/cord rating.
50 or 60
Range
Rated input line current, depending upon the
PDU’s power source, assigned at the time of
manufacture.
Hertz
(Hz)
Units
Either the nominal or maximum value of the
range is reported, whichever is greater.
Twophase
two-phase-4-wire-L1-L2-N-PE (5):
Default
Rated phase or line voltage, either line-to-neutral
or line-to-line depending upon the PDU’s power
source, assigned at the time of manufacture.
•
(3P4W).
(4): Three-phase input with five wires
Description
RPC2 Configuration SNMP OID Tables.....11
OID Column Number
.1.3.6.1.4.1.476.1.42.3.8.30.20.1.85
.1.3.6.1.4.1.476.1.42.3.8.30.20.1.90
.1.3.6.1.4.1.476.1.42.3.8.30.20.1.95
1.3.6.1.4.1.476.1.42.3.8.30.40.1.10
.1.3.6.1.4.1.476.1.42.3.8.30.40.1.15
.1.3.6.1.4.1.476.1.42.3.8.30.40.1.19
.1.3.6.1.4.1.476.1.42.3.8.30.40.1.20
Data Point Name
lgpPduPsEntryUnbalancedLoadThrshldAlarm.1.1
lgpPduPsEntryApTotal.1.1
lgpPduPsEntryPfTotal.1.1
lgpPduPsLineEntryId.1.1.1
lgpPduPsLineEntryLine.1.1.1
lgpPduPsLineEntryEpLNTenths.1.1.1
lgpPduPsLineEntryEpLN.1.1.1
Gauge32
Gauge32
Integer
Gauge32
Integer
Gauge32
Gauge32
Syntax
ro
ro
ro
ro
ro
ro
rw
Access
phase2(2): Line 2-N or Line2-3.
phase3(3): Line 3-N or Line3-1.
•
•
The voltage applied to the line-to-neutral phase
measured in volts RMS (Root Mean Squared).
The voltage applied to the line-to-neutral phase
measured in tenth volts RMS (Root Mean
Squared).
phase1(1): Line 1-N or Line1-2.
•
table. The line/phases are as follows:
lgpPduPsLineEntryIndex of the same row in the
the table. Note that this always matches the
represents for all measurements in a given row of
PDU’s power source that the measurement
Enumerations that describe the line/phase of the
Unique identifier for the PDU's power source.
Power Factor of all the phases measured as the
average of the phases’ ratio of real power to
apparent power.
The summation of apparent power consumed by
all the phases.
A configuration parameter to set the maximum
acceptable percentage of 'Unbalanced Load'
between any two phases. This setting shall
trigger an alarm when the % difference between
any two phases is greater than than this value. If
this value is 0% then the alarm shall be
deactivated.
percentage of the full scale rated value,
lgpPduPsEntryEcInputRated, an overcurrent
alarm is activated.
Description
0.00
0
Default
Volts
RMS
0.1 RMS
Volts
RMS
VoltsAmperes
(VA)
%
Units
1-3
1-3
0.00-1.00
0-100
Range
Comment
12.....RPC2 Communications Module SNMP, MIB, OID Technical Bulletin
OID Column Number
.1.3.6.1.4.1.476.1.42.3.8.30.40.1.21
.1.3.6.1.4.1.476.1.42.3.8.30.40.1.22
.1.3.6.1.4.1.476.1.42.3.8.30.40.1.35
.1.3.6.1.4.1.476.1.42.3.8.30.40.1.36
.1.3.6.1.4.1.476.1.42.3.8.30.40.1.37
.1.3.6.1.4.1.476.1.42.3.8.30.40.1.38
.1.3.6.1.4.1.476.1.42.3.8.30.40.1.39
.1.3.6.1.4.1.476.1.42.3.8.30.40.1.60
.1.3.6.1.4.1.476.1.42.3.8.30.40.1.61
.1.3.6.1.4.1.476.1.42.3.8.30.40.1.62
.1.3.6.1.4.1.476.1.42.3.8.30.40.1.63
Data Point Name
lgpPduPsLineEntryEc.1.1.1
lgpPduPsLineEntryEcHundredths.1.1.1
lgpPduPsLineEntryEcThrshldUndrAlarm.1.1.1
lgpPduPsLineEntryEcThrshldOvrWarn.1.1.1
lgpPduPsLineEntryEcThrshldOvrAlarm.1.1.1
lgpPduPsLineEntryEcAvailBeforeAlarm.1.1.1
lgpPduPsLineEntryEcUsedBeforeAlarm.1.1.1
lgpPduPsLineEntryEpLL.1.1.1
lgpPduPsLineEntryEpLLTenths.1.1.1
lgpPduPsLineEntryEcAvailBeforeAlarmHundredths.1.1.1
lgpPduPsLineEntryPwrLN.1.1.1
Gauge32
Gauge32
Gauge32
Gauge32
Gauge32
Gauge32
Gauge32
Gauge32
Gauge32
Gauge32
Gauge32
Syntax
ro
ro
ro
ro
ro
ro
rw
rw
rw
ro
ro
Access
%
%
0.1 RMS
Amperes
0.1%
A configuration parameter to set the threshold at
which an overcurrent warning is activated. If the
measured line current is equal to or over this
percentage of the full scale rated value,
lgpPduPsEntryEcInputRated, an overcurrent
warning is activated.
A configuration parameter to set the threshold at
which an overcurrent alarm is activated. If the
measured line current is equal to or over this
percentage of the full scale rated value,
lgpPduPsEntryEcInputRated, an overcurrent
alarm is activated.
The amount that the line current may increase
from its present value before an over current
alarm occurs.
The percent of line current utilization relative to
the over current alarm threshold.
0.1 RMS
Volts
0.01 RMS
Amperes
Watts
The voltage applied to the line-to-line phase
measured in tenth volts RMS (Root Mean
Squared).
The amount that the line current may increase
from its present value before an over current
alarm occurs.
Real power consumed by the line-to-neutral
phase.
Volts
RMS
%
A configuration parameter to set the threshold at
which an undercurrent alarm is activated. If the
measured line current is equal to or below this
percentage of the full scale rated value,
lgpPduPsEntryEcInputRated, an undercurrent
alarm is activated.
The voltage applied to the line-to-line phase
measured in volts RMS (Root Mean Squared).
0.01 RMS
Amperes
Current drawn through the phase/line measured
in tenth Amperes RMS (Root Mean Squared).
Units
0.1 RMS
Amperes
Default
Current drawn through the phase/line measured
in Amperes RMS (Root Mean Squared).
Description
0.0.-100.0
0-100
0-100
0-100
Range
Must be greater than
lgpPduPsEntryEcThrshldUnderAlarm and
greater than
lgpPduPsEntryEcThrshldOverWarn
Must be greater than
lgpPduPsEntryEcThrshldUnderAlarm and
less than
lgpPduPsEntryEcThrshldOverAlarm
Must be less than
lgpPduPsEntryEcThrshldOverWarn and
less than
lgpPduPsEntryEcThrshldOverAlarm
Comment
RPC2 Configuration SNMP OID Tables.....13
OID Column Number
.1.3.6.1.4.1.476.1.42.3.8.30.40.1.64
.1.3.6.1.4.1.476.1.42.3.8.30.40.1.65
.1.3.6.1.4.1.476.1.42.3.8.30.40.1.66
.1.3.6.1.4.1.476.1.42.3.8.30.40.1.67
.1.3.6.1.4.1.476.1.42.3.8.30.40.1.68
Data Point Name
lgpPduPsLineEntryPwrLL.1.1.1
lgpPduPsLineEntryApLN.1.1.1
lgpPduPsLineEntryApLL.1.1.1
lgpPduPsLineEntryPfLN.1.1.1
lgpPduPsLineEntryPfLL.1.1.1
Integer
Integer
Gauge32
Gauge32
Gauge32
Syntax
ro
ro
ro
ro
ro
Access
0.00
0.00
Power factor of the line-to-line phase measured
as the ratio of real power to apparent power.
RMS
VoltsAmperes
(VA)
Apparent power consumed by the line-to-line
phase.
Power factor of the line-to-neutral phase
measured as the ratio of real power to apparent
power.
RMS
VoltsAmperes
(VA)
Apparent power consumed by the line-to-neutral
phase.
Units
Watts
Default
Real power consumed by the line-to-line phase.
Description
0.00-1.00
0.00- 1.00
Range
Comment
14.....RPC2 Communications Module SNMP, MIB, OID Technical Bulletin
OID Column Number
.1.3.6.1.4.1.476.1.42.3.8.40.19
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.5
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.8
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.20
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.25
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.30
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.35
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.40
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.41
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.42
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.45
Data Point Name
lgpPduRbTableCount.0
lgpPduRbEntryId.1.1
lgpPduRbEntryUsrLabel.1.1
lgpPduRbEntrySysAssignLabel.1.1
lgpPduRbEntryPositionRelative.1.1
lgpPduRbEntrySerialNum.1.1
lgpPduRbEntryModel.1.1
lgpPduRbEntryFirmwareVersion.1.1
lgpPduRbEntryUsrTag1.1.1
lgpPduRbEntryUsrTag2.1.1
lgpPduRbEntryReceptacleType.1.1
Integer
String
String
String
String
String
Gauge32
String
String
Gauge32
Gauge32
Syntax
ro
rw
rw
ro
ro
ro
ro
ro
rw
ro
ro
Access
LIEBERT‐GP‐PDU-MIB::lgpPduRbTable
on this receptacle branch.
Enumerations that describe the type of receptacles installed
A configuration parameter to set user assigned tag for the
receptacle branch. This value may be useful for end‐user
grouping or asset tracking purposes. The value for this tag
does not need to be unique for this unit or across other units.
A configuration parameter to set user assigned tag for the
receptacle branch. This value may be useful for end‐user
grouping or asset tracking purposes. The value for this tag
does not need to be unique for this unit or across other units.
Version of firmware installed on the device’s receptacle
branch hardware.
Model number of receptacle branch device assigned at the
time of manufacture.
A globally unique serial number for this receptacle branch.
This number is assigned to the branch at the time of
manufacture and cannot be modified.
0
<empty>
<x-y>
System assigned identifier for this receptacle branch. The
value is independent of any user assigned label or tag. The
exact format of this label is system dependent and is subject
to change; therefore, it should not be referenced for
programmatic use.
Indicates the relative position of the receptacle branch within
the PDU.
<Branch
x>, where
x=A-G
Default
A configuration parameter to set user assigned label
representing the receptacle branch.
A unique id assigned at device discovery representing the
receptacle branch within the collection of branches being
monitored by this agent. The uniqueness of this id is within the
scope of PDUs being managed by a single agent.
Number of receptacle branches in the lgpPduRbTable.
Description
Units
0-7
0-48
characters
0-48
characters
1-7
x=PDU {1-4},
y=Branch
{AG}
0-48
characters
1-7
Range
The allowed characters include
alphanumeric, space, and ~!#$_+`={}|[]\\:;'?,.\/%^&*()@
The allowed characters include
alphanumeric, space, and ~!#$_+`={}|[]\\:;'?,.\/%^&*()@
MPXBRM are hot-swappable
receptacle branches and have
unique serial numbers.
For MPXBRM, the Branch alpha
character maps to the numerical id
as follows: {A thru G} -> {1 thru 7}
The allowed characters include
alphanumeric, space, and ~!#$_+`={}|[]\\:;'?,.\/%^&*()@
Comment
RPC2 Configuration SNMP OID Tables.....15
OID Column Number
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.50
Data Point Name
lgpPduRbEntryCapabilities.1.1
Integer
Syntax
ro
Access
iec-C19-sheet-J-16-Amp(3)
iec-C13-sheet-F-10-Amp-and-iec-C19- sheet-J-16-
•
•
cee-7-type-E-schuko(7)
Amp(6)
nema-5-20R-20-Amp‐and-iec-C19‐sheet-J- 16-
Amp(5)
nema-5-20R-20-Amp‐and-iec-C13‐sheet- F-10-
no-optional-capabilities(1): Does not support
receptacle measurement and control.
measurement-only(2): Supports receptacle
measurements.
measurement-and-control(3): Supports eceptacle
•
•
•
•
•
control-only (4): Supports receptacle control.
current-measurement-only(5): Supports urrent
•
•
measurements and receptacle control.
not-specified(0)
•
performance capabilities.
Enumerations that describe the supported receptacle branch
•
•
•
iec-C13‐-sheet-F-10-Amp (2)
•
Amp(4)
nema-5-20R-20-Amp(1)
SNMP enumeration defined to the type.
the agent monitoring this PDU does not have a
receptacle type has not been specified/configured or
not-specified(0): If this value is returned, either the
•
•
Description
0
Default
Units
0-6
Range
All PDUs support input
measurements. MPH models do
not support voltage and powerrelated measurements at the
branches.
Comment
16.....RPC2 Communications Module SNMP, MIB, OID Technical Bulletin
OID Column Number
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.55
Data Point Name
lgpPduRbEntryLineSource.1.1
Integer
Syntax
ro
Access
current measurements.
current‐measurement-and-control(6): supports
•
•
•
•
•
•
•
•
•
line-2-line-3-and-line-2-neutral(8): The load for this
and line-to-neutral configuration.
mixed receptacle branch is supplied by a line-to-line
line-1-line-2-and-line-1‐neutral(7): The load for this
is supplied by a line‐to-line configuration.
line-3‐line-1(6): The load for this receptacle branch
is supplied by a line-to-line configuration.
line-2-line-3(5): The load for this receptacle branch
is supplied by a line-to-line configuration.
line-1-line-2(4): The load for this receptacle branch
supplied by a line-to-neutral configuration.
line-3-N (3): The load for this receptacle branch is
neutral).
supplied by a lie-‐to-neutral configuration. (line 2 to
line-2-N(2): The load for this receptacle branch is
supplied by a line-to-neutral configuration.
line-1-N(1): The load for this receptacle branch is
specified or configured.
to the load for this receptacle branch has not been
not-specified (0): The line source supplying power
phasing supplying power to this receptacle branch.
Enumerations that describe the PDU’s voltage source
•
measurements only.
Description
Default
Units
Range
Comment
RPC2 Configuration SNMP OID Tables.....17
OID Column Number
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.60
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.70
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.75
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.80
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.85
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.100
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.115
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.120
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.125
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.130
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.135
Data Point Name
lgpPduRbEntryRcpCount.1.1
lgpPduRbEntryEpRated.1.1
lgpPduRbEntryEcRated.1.1
lgpPduRbEntryFreqRated.1.1
lgpPduRbEntryEnergyAccum.1.1
lgpPduRbEntryEpLNTenths.1.1
lgpPduRbEntryPwr.1.1
lgpPduRbEntryAp.1.1
lgpPduRbEntryPf.1.1
lgpPduRbEntryEcHundredths.1.1
lgpPduRbEntryEcThrshldUndrAlm.1.1
Gauge32
Gauge32
Integer
Gauge32
Gauge32
Gauge32
Gauge32
Gauge32
Gauge32
Gauge32
Gauge32
Syntax
rw
ro
ro
ro
ro
ro
rw
ro
ro
ro
ro
Access
and line-to-neutral configuration.
mixed receptacle branch is supplied by a line-to-line
line-3-line-1-and-line-3-neutral(9): The load for this
%
A configuration parameter to set the threshold at which an
undercurrent alarm is activated. If the measured receptacle
branch current is equal to or below this percentage of the full
scale rated value, lgpPduRbEntryEcRated, an undercurrent
0
0.01 RMS
Amperes
0.00
RMS
VoltsAmperes
(VA)
Watts
Current drawn from the receptacle branch measured in
hundredths Amperes RMS (Root Mean Squared).
Power factor of the receptacle branch measured as the ratio
of real power to apparent power.
Apparent power consumed by the receptacle branch.
Real power consumed by the receptacle branch.
0.1 RMS
Volts
The line-to-neutral voltage applied to the branch measured in
tenth volts RMS (Root Mean Squared).
60 Hertz
(Hz)
Units
0.1
kiloWatthour (kWh)
50 or 60
Default
Total accumulated energy of the receptacle branch since the
last energy reset. Writing a value of zero causes the
accumulated energy to be reset. Writing a non-zero value is
invalid and shall result in a write error and the total energy
value remains unchanged.
Rated line frequency for the receptacle branch and its
associated receptacles assigned at the time of manufacture.
Rated input line current for the receptacle branch assigned at
the time of manufacture.
Rated phase or line voltage, either line-to-neutral or line-toline, for the receptacle branch assigned at the time of
manufacture.
The number of receptacles on this receptacle branch.
•
and line-to-neutral configuration.
mixed receptacle branch is supplied by a line-to-line
Description
0-100
0.00-1.00
50 or 60
Range
Must be less than
lgpPduRbEntryEcThrshldOvrAlm
and less than
lgpPduRbEntryEcThrshldOvrWarn
If the energy has not been reset
and has not overflowed the 32-bit
value, then this is the total energy
since installation. This value
persists across boot and power
cycle events.
Irrespective of region, all PDUs
can operate at either 50Hz or
60Hz.
Either the nominal or maximum
value of the range is reported,
whichever is greater.
Comment
18.....RPC2 Communications Module SNMP, MIB, OID Technical Bulletin
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.140
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.145
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.150
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.160
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.170
.1.3.6.1.4.1.476.1.42.3.8.40.20.1.175
lgpPduRbEntryEcThrshldOvrWarn.1.1
lgpPduRbEntryEcThrshldOvrAlm.1.1
lgpPduRbEntryEcAvailBeforeAlarmHundredths.1.1
lgpPduRbEntryEcUsedBeforeAlarm.1.1
lgpPduRbEntryEpLLTenths.1.1
lgpPduRbEntrySwOverCurrentProtection.1.1
lgpPduRbLineTable
OID Column Number
Data Point Name
Integer
Gauge32
Gauge32
Gauge32
Gauge32
Gauge32
Syntax
rw
ro
ro
ro
rw
rw
Access
Unlocked & On: If load present, no change. If no
•
deprecated MIB table
No action will be taken if the feature is disable(0).
load, turn it off and lock it.
Unlocked & Off: Turn it off and Lock it.
change.
Locked & On: No change. l Locked & Off: No
•
•
receptacles:
condition, the following action will be taken on the
enable(1), in case of an overcurrent warning or alarm
Over Current Protection (SOCP) feature. If the feature is
disable(0)
0.1 RMS
Volts
The receptacle branch line-to-line measurement of Volts RMS
(Root Mean Squared).
A configuration parameter to enable or disable the Software
0.1%
The percent of receptacle branch current utilization relative to
the overcurrent alarm threshold.
%
0.01 RMS
Amperes
95
A configuration parameter to set the threshold at which an
overcurrent alarm is activated. If the measured receptacle
branch current is equal to or over this percentage of the full
scale rated value, lgpPduRbEntryEcRated, an over current
alarm is activated.
%
Units
The amount that the receptacle branch current may increase
from its present value before an overcurrent alarm occurs.
90
Default
A configuration parameter to set the threshold at which an
overcurrent warning is activated. If the measured receptacle
branch current is equal to or over this percentage of the full
scale rated value, lgpPduRbEntryEcRated, an overcurrent
warning is activated.
alarm is activated.
Description
0-1
0.0-100.0
0-100
0-100
Range
Only applicable to PDUs having
receptacle measurement and
control.
Must be greater than
lgpPduRbEntryEcThrshldUndrAlm
and greater than
lgpPduRbEntryEcThrshldOvrWarn
Must be less than
lgpPduRbEntryEcThrshldOvrAlm
and greater than
lgpPduRbEntryEcThrshldUndrAlm
Comment
RPC2 Configuration SNMP OID Tables.....19
OID Column Number
.1.3.6.1.4.1.476.1.42.3.8.50.19
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.5
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.10
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.15
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.20
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.25
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.30
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.40
Data Point Name
llgpPduRcpTableCount.0
lgpPduRcpEntryId.1.1.1
lgpPduRcpEntryUsrLabel.1.1.1
lgpPduRcpEntryUsrTag1.1.1.1
lgpPduRcpEntryUsrTag2.1.1.1
lgpPduRcpEntrySysAssignLabel.1.1.1
lgpPduRcpEntryPosition.1.1.1
lgpPduRcpEntryType.1.1.1
Integer
Gauge32
String
String
String
String
Gauge32
Gauge32
Syntax
ro
ro
ro
rw
rw
rw
ro
ro
Access
LIEBERT-GP-PDU-MIB::lgpPduRcpTable
<x-y-z>
A configuration parameter to set user assigned
tag to assist in identifying or grouping this
receptacle within the end-users domain.
System assigned identifier representing the
receptacle. The value is independent of any user
assigned label or tag. The exact format of this
label is system dependent and is subject to
change; therefore, it should not be referenced for
programmatic use.
•
not-specified(0)
abbreviations.
well-known industry standard terms and
receptacle. The enumerations are specified in
Enumerations that describe the type or form of the
0
<empty>
A configuration parameter to set user assigned
tag to assist in identifying or grouping this
receptacle within the end-users domain.
A number representing the physical position of the
receptacle within the receptacle branch.
<empty>
A configuration parameter to set user assigned
label for the receptacle.
Default
<Receptacle
x-y-z>,
where
x=PDU {1-4},
y=Branch
{AF},
z=Receptacle
{1-48}.
A unique id assigned at runtime representing the
receptacle identification number.
Number of receptacles in the lgpPduRcpTable.
Description
Units
0-3;7
1-48
{1-48}
z=Receptacle
y=Branch {AG},
x=PDU {1-4},
0-48 characters
0-48 characters
0-48 characters
Range
For nema-5-20R-20-Amp(1) used for
UL Listed PDUs, the current rating is
derated to 80% or 16Amps. For iecC13-sheet-F-10-Amp(2) used for UL
Listed PDUs, the current rating is
12Amps.
For MPXBRM, the Branch alpha
character maps to the numerical id as
follows: {A thru G} -> {1 thru 7}
The allowed characters include
alphanumeric, space, and ~!#$_+`-={}|[]
\\:;'?,.\/%^&*()@
The allowed characters include
alphanumeric, space, and ~!#$_+`-={}|[]
\\:;'?,.\/%^&*()@
Should be uniquely defined. The
allowed characters include
alphanumeric, space, and ~!#$_+`-={}|[]
\\:;'?,.\/%^&*()@
Comment
20.....RPC2 Communications Module SNMP, MIB, OID Technical Bulletin
OID Column Number
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.45
Data Point Name
lgpPduRcpEntryLineSource.1.1.1
Integer
Syntax
ro
Access
cee-7-type-E-schuko(7)
•
•
•
•
•
•
•
configuration.
receptacle is supplied by a line‐to-line
line-2-line-3(5): The load for this
configuration.
receptacle is supplied by a line‐to-line
line-1-line-2(4): The load for this
configuration.
is supplied by a line-to‐neutral
line-3-N(3): The load for this receptacle
configuration.
is supplied by a line-to‐neutral
line-2-N(2): The load for this receptacle
configuration.
is supplied by a line-to‐neutral
line-1-N(1): The load for this receptacle
specified/configured.
receptacle has not been
supplying power to the load for this
not-specified(0): The line source
receptacle.
source phase that is supplying power to this
Enumerations that describe the PDU’s voltage
iec-C19-sheet-J-16-Amp(3)
sheet-F-10-Amp(2)
nema-5-20R-20-Amp(1) l iec-C13-
•
•
Description
0
Default
Units
0-6
Range
Line-to-line configurations are only
supported by UL Listed PDUs.
Comment
RPC2 Configuration SNMP OID Tables.....21
OID Column Number
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.50
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.55
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.56
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.60
Data Point Name
lgpPduRcpEntryCapabilities.1.1.1
lgpPduRcpEntryEp.1.1.1
lgpPduRcpEntryEpTenths.1.1.1
lgpPduRcpEntryEc.1.1.1
Gauge32
Gauge32
Gauge32
Integer
Syntax
ro
ro
ro
ro
Access
configuration.
receptacle is supplied by a line‐to-line
Line-3-line-1(6): The load for this
0.1 RMS
Volts
0.1 RMS
Amperes
Voltage applied to the receptacle measured in
tenth volts RMS (Root Mean Squared).
Current drawn from the receptacle measured in
Amperes RMS (Root Mean Squared).
0
Units
RMS
Volts
receptacle control.
Supports current measurements and
current‐measurement-and-control(6):
current measurements only.
current-measurement-only(5): Supports
control.
control-only (4): Supports receptacle
receptacle control.
receptacle measurements and
measurement-and-control(3): Supports
receptacle measurements.
measurement-only(2): Supports
control.
Default
Voltage applied to the receptacle measured in
volts RMS (Root Mean Squared).
•
•
•
•
•
no-optional-capabilities(1): Does not
•
support receptacle measurement and
not-specified(0)
•
capabilities.
Enumerations that describe the receptacle
•
Description
0-6
Range
All PDUs support input measurements.
MPH models do not support voltage
and power-related measurements at
the receptacles.
Comment
22.....RPC2 Communications Module SNMP, MIB, OID Technical Bulletin
OID Column Number
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.61
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.65
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.70
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.75
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.80
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.85
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.90
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.95
Data Point Name
lgpPduRcpEntryEcHundredths.1.1.1
lgpPduRcpEntryPwrOut.1.1.1
lgpPduRcpEntryApOut.1.1.1
lgpPduRcpEntryPf.1.1.1
lgpPduRcpEntryFreq.1.1.1
lgpPduRcpEntryEnergyAccum.1.1.1
lgpPduRcpEntryPwrOnDelay.1.1.1
lgpPduRcpEntryPwrState.1.1.1
Integer
Gauge32
Gauge32
Gauge32
Gauge32
Gauge32
Gauge32
Gauge32
Syntax
ro
rw
rw
ro
ro
ro
ro
ro
Access
•
•
•
•
states.
power state is off. The power will be on
off-pending-on-delay(3): The current
receptacle is on.
on(2): The current power state of the
receptacle is off.
off(1): The current power state of the
unknown.
unknown(0): The current power state is
Enumerations that describe the receptacle power
0
second
0
A configuration parameter to set the amount of
time to wait before power is applied to the
receptacle after the PDU is power cycled or
rebooted. This can be used to stagger the power
on sequence of multiple receptacles in order to
mitigate in-rush current draw.
45.0-75.0
0.1
kiloWatthour
(kW-hr)
0.1 Hertz
(Hz)
The measured line frequency of the receptacle’s
voltage source.
Total accumulated energy of receptacle since the
last energy reset. Writing a value of zero causes
the accumulated energy to be reset. Writing a
nonzero value is invalid and shall result in a write
error and the total energy value remains
unchanged.
0.00
Power factor of receptacle’s load measured as
the ratio of real power to apparent power.
RMS
VoltsAmperes
(VA)
Apparent power consumed by the receptacle’s
load.
0.01 RMS
Amperes
Units
Watts
Default
Real power consumed by the receptacle’s load.
Current drawn from the receptacle measured in
hundredths Amperes RMS (Root Mean Squared).
Description
0-3
0-2400
0.00-1.00
Range
If the energy has not been reset and
has not overflowed the 32-bit value,
then this is the total energy since
installation. This value persists across
boot and power cycle events.
Irrespective of region, all PDUs can
operate at either 50Hz or 60Hz.
If no current measured, 0.00 is
reported.
Comment
RPC2 Configuration SNMP OID Tables.....23
OID Column Number
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.96
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.100
Data Point Name
lgpPduRcpEntryPwrUpState.1.1.1
lgpPduRcpEntryControl.1.1.1
Integer
Gauge32
Syntax
rw
rw
Access
expiration of the power on delay.
switched to the previous state after
last-state(3): The receptacle shall be
state upon power cycle.
off(2): The receptacle shall be in the off
lgpPduRcpEntryPwrOnDelay.
power on delay,
to the on state after the expiration of the
on(1): The receptacle shall be switched
•
•
•
momentarily and then back on.
power to the receptacle is turned off
currently in a power-cycle state. The
cycle-power(2): The receptacle is
power state of the receptacle is on.
on(1): The current and configured
power state of the receptacle is off.
off(0): The current and configured
state of the receptacle.
that describe the current or configured power
A configuration parameter to set enumerations
•
•
•
shall return after a power cycle of the PDU.
that describe the state to which the receptacle
A configuration parameter to set enumerations
receptacle.
lgpPduRcpEntryPwrOnDelay of this
at the expiration of
Description
1
3
Default
Units
0-2
1-3
Range
For cycle-power(2) mode, a default
eight second off duration is fixed.
Comment
24.....RPC2 Communications Module SNMP, MIB, OID Technical Bulletin
OID Column Number
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.105
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.150
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.151
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.152
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.159
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.160
Data Point Name
lgpPduRcpEntryControlLock.1.1.1
lgpPduRcpEntryEcThrshldUnderAlarm.1.1.1
lgpPduRcpEntryEcThrshldOverWarn.1.1.1
lgpPduRcpEntryEcThrshldOverAlarm.1.1.1
lgpPduRcpEntryEcAvailBeforeAlarmHundredths.1.1.1
lgpPduRcpEntryEcAvailBeforeAlarm.1.1.1
Gauge32
Gauge32
Gauge32
Gauge32
Gauge32
Integer
Syntax
ro
ro
rw
rw
rw
rw
Access
0.1 RMS
The amount that the current may increase from its
present value before an overcurrent alarm
occurs.
%
0.01 RMS
Amperes
95
A configuration parameter to set the threshold at
which an overcurrent alarm is activated. If the
measured current is equal to or over this
percentage of the full scale rated value, derived
from lgpPduRcpEntryType, an overcurrent alarm
is activated.
%
%
Units
The amount that the current may increase from its
present value before an overcurrent alarm
occurs.
90
A configuration parameter to set the threshold at
which an overcurrent warning is activated. If the
measured current is equal to or over this
percentage of the full scale rated value, derived
from lgpPduRcpEntryType, an overcurrent
warning is activated.
1
0
cannot be changed.
then its current or configured state
locked(2): If the receptacle is'locked'
may change the receptacles state.
then a user with proper permissions
'unlocked',
unlocked(1): If the receptacle is
receptacle is not known at this time.
unknown(0): The lock state of the
Default
A configuration parameter to set the threshold at
which an undercurrent alarm is activated. If the
measured current is equal to or below this
percentage of the full scale rated value, derived
from lgpPduRcpEntryType, an undercurrent
alarm is activated.
•
•
•
•
receptacle.
Enumerations that describe the locked state of the
Description
0-100
0-100
0-100
0-2
Range
Must be greater than
lgpPduRcpEntryEcThrshldUnderAlarm
and greater than
lgpPduRcpEntryEcThrshldOverWarn
Must be greater than
lgpPduRcpEntryEcThrshldUnderAlarm
and less than
lgpPduRcpEntryEcThrshldOverAlarm
Must be less than
lgpPduRcpEntryEcThrshldOverWarn
and less than
lgpPduRcpEntryEcThrshldOverAlarm
Comment
RPC2 Configuration SNMP OID Tables.....25
OID Column Number
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.161
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.162
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.200
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.205
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.210
Data Point Name
lgpPduRcpEntryEcUsedBeforeAlarm.1.1.1
lgpPduRcpEntryEcCrestFactor.1.1.1
lgpPduRcpEntryBlinkLED.1.1.1
lgpPduRcpEntrySwOverTemperatureProtection.1.1.1
lgpPduRcpEntryOperationCondition.1.1.1
Integer
Integer
Integer
Gauge32
Gauge32
Syntax
ro
rw
rw
ro
ro
Access
Unlocked & Off: No Change;
Unlocked & On: Turn it off.
Locked & On: Turn it off and keep it
•
•
•
•
•
condition due to over/under current
normalWithWarning(2): A warning
without any alarm or warning.
normalOperation(1): Normal operation
condition of the receptacle.
Enumerations that describe the operating
feature is disabled.
locked. No action will be taken if the
Locked & Off: No Change;
•
receptacles:
condition, the following actions will be taken on
enabled, in case of Over Temperature Alarm
Protection (SWOTP) feature. If the feature is
(0) the receptacle SW Over Temperature
disable(0)
noAction(1)
A configuration parameter to blink the receptacle
LED. Writing blinkLED(2) will cause the LED to
blink for a predefined amount of time. Reading this
object will always return noAction(1).
A configuration parameter to enable(1) or disable
0.00
Default
Receptacle current crest factor, which is the ratio
of peak amplitude of the current waveform
divided by its RMS value.
The percent of current utilization relative to the
overcurrent alarm threshold.
Description
0.1%
Amperes
Units
1-4
0-1
0.00-3.00
0.0-100.0
Range
SWOTP requires a temperature sensor
to be operable.
The blink duration is ten seconds.
Comment
26.....RPC2 Communications Module SNMP, MIB, OID Technical Bulletin
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.215
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.220
.1.3.6.1.4.1.476.1.42.3.8.50.20.1.225
lgpPduRcpEntryCriticality.1.1.1
lgpPduRcpEntryPostOnDelay.1.1.1
lgpPduRcpEntryPostOffDelay.1.1.1
lgpPduAuxSensorTable
OID Column Number
Data Point Name
Gauge32
Gauge32
Integer
Syntax
rw
rw
rw
Access
0
0
A configuration parameter to set the time interval
to wait after a command is issued to switch on a
receptacle. A value of zero implies that there is no
delay, i.e. the receptacle is turned on immediately
upon command issue.
A configuration parameter to set the time interval
to waits after a command is issued to switch off a
receptacle. A value of zero implies that there is no
delay, i.e. the receptacle is turned off immediately
upon command issue.
deprecated MIB section
notCritical(1)
still drawing current.
'lgpPduRcpEntryPwrState=off(1)' but
receptacle is in
abnormal(4): A condition in which the
due to over/under current.
normalWithAlarm(3): An alarm condition
Default
A configuration parameter to mark a receptacle as
critical(0) or notCritical(1).
•
•
•
Description
seconds
seconds
Units
0-2400
0-2400
0-1
Range
Comment
RPC2 Configuration SNMP OID Tables.....27
OID Column Number
.1.3.6.1.4.1.476.1.42.3.8.60.5
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.10
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.15
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.20
Data Point Name
lgpPduAuxSensorCount.0
lgpPduAuxMeasType.1.1.1
lgpPduAuxMeasSensorSysAssignLabel.1.1.1
lgpPduAuxMeasUsrLabel.1.1.1
String
String
Integer
Gauge32
Syntax
rw
ro
ro
ro
Access
pressure.
in this row of the table measures differential
l differential-pressure(5): The measurement
contact closure.
this row of the table measures the state of a
contact-closure(4): The measurement in
door.
row of the table measures the state of a
door-closure(3): The measurement in this
of the table measures relative humidity.
humidity(2): The measurement in this row
row of the table measures temperature.
temperature(1): The measurement in this
is unknown.
not-specified(0): The type of measurement
User assigned auxiliary sensor measurement label.
Label assigned to the auxiliary sensor at runtime by
the system. The value is independent of any user
assigned label or asset tag.
•
•
•
•
•
•
type.
Enumerations that describe the sensor measurement
Number of auxiliary sensors in the
lgpPduAuxSensorTable.
Description
LIEBERT‐GP‐PDU-MIB::lgpPduAuxMeasTable
<sensor
serial
number>
<sensor
type>
Default
Units
0-48
characters
0-40
Range
The allowed characters include alphanumeric,
space, and ~!#$_+`-={}|[]\\:;'?,.\/%^&*()@
Up to ten sensors supported per agent
Comment
28.....RPC2 Communications Module SNMP, MIB, OID Technical Bulletin
OID Column Number
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.25
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.30
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.35
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.40
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.50
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.55
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.60
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.65
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.70
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.75
Data Point Name
lgpPduAuxMeasUsrTag1.1.1.1
lgpPduAuxMeasUsrTag2.1.1.1
lgpPduAuxMeasSensorSerialNum.1.1.1
lgpPduAuxMeasTempDegF.1.1.1
lgpPduAuxMeasTempThrshldUndrAlmDegF.1.1.1
lgpPduAuxMeasTempThrshldOvrAlmDegF.1.1.1
lgpPduAuxMeasTempThrshldUndrWarnDegF.1.1.1
lgpPduAuxMeasTempThrshldOvrWarnDegF.1.1.1
lgpPduAuxMeasTempDegC.1.1.1
lgpPduAuxMeasTempThrshldUndrAlmDegC.1.1.1
Integer
Integer
Integer
Integer
Integer
Integer
Integer
String
String
String
Syntax
rw
ro
rw
rw
rw
rw
ro
ro
rw
rw
Access
<empty>
<empty>
User assigned Tag to assist in identifying or grouping
this auxiliary sensor measurement within the endusers domain.
User assigned Tag to assist in identifying or grouping
this auxiliary sensor measurement within the endusers domain.
0.1° F
64.4
98.6
68.0
95.0
20.0
18.0
Under temperature alarm threshold. An alarm is
activated if the temperature is equal to or below this
value.
Over temperature alarm threshold. An alarm is
activated if the temperature is equal to or above this
value.
Under temperature warning threshold. A warning is
activated if the temperature is equal to or below this
value.
Over temperature warning threshold. A warning is
activated if the temperature is equal to or above this
value.
Temperature measured at the temperature sensor
reported in degrees Celsius.
Under temperature alarm threshold. An alarm is
activated if the temperature is equal to or below this
value.
0.1° C
0.1° C
0.1° F
0.1° F
0.1° F
0.1° F
Units
Temperature measured at the temperature sensor
reported in degrees Fahrenheit.
Sensor's globally unique serial number assigned at
the time of manufacture.
Default
Description
1.0-85.0
1.0-85.0
33.8-185.0
33.8-185.0
33.8-185.0
33.8-185.0
33.8-185.0
0-48
characters
0-48
characters
Range
Must be less than
lgpPduAuxMeasTempThrshldOvrAlmDegC
and less than
lgpPduAuxMeasTempThrshldOvrWarnDegC
and less than
Must be less than
lgpPduAuxMeasTempThrshldOvrAlmDegF
and less than
lgpPduAuxMeasTempThrshldOvrWarnDegF
and less than
lgpPduAuxMeasTempThrshldUndrWarnDegF
Must be less than
lgpPduAuxMeasTempThrshldOvrAlmDegF
and less than
lgpPduAuxMeasTempThrshldOvrWarnDegF
and less than
lgpPduAuxMeasTempThrshldUndrWarnDegF
Must be less than
lgpPduAuxMeasTempThrshldOvrAlmDegF
and less than
lgpPduAuxMeasTempThrshldOvrWarnDegF
and less than
lgpPduAuxMeasTempThrshldUndrWarnDegF
Must be less than
lgpPduAuxMeasTempThrshldOvrAlmDegF
and less than
lgpPduAuxMeasTempThrshldOvrWarnDegF
and less than
lgpPduAuxMeasTempThrshldUndrWarnDegF
The allowed characters include alphanumeric,
space, and ~!#$_+`-={}|[]\\:;'?,.\/%^&*()@
The allowed characters include alphanumeric,
space, and ~!#$_+`-={}|[]\\:;'?,.\/%^&*()@
Comment
RPC2 Configuration SNMP OID Tables.....29
OID Column Number
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.80
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.85
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.90
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.95
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.100
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.105
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.110
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.115
Data Point Name
lgpPduAuxMeasTempThrshldOvrAlmDegC.1.1.1
lgpPduAuxMeasTempThrshldUndrWarnDegC.1.1.1
lgpPduAuxMeasTempThrshldOvrWarnDegC.1.1.1
lgpPduAuxMeasHum.1.1.1
lgpPduAuxMeasHumThrshldUndrAlm.1.1.1
lgpPduAuxMeasHumThrshldOvrAlm.1 .1.1
lgpPduAuxMeasHumThrshldUndrWarn.1.1.1
lgpPduAuxMeasHumThrshldOvrWarn.1.1.1
Gauge32
Gauge32
Gauge32
Gauge32
Gauge32
Integer
Integer
Integer
Syntax
rw
rw
rw
rw
ro
rw
rw
rw
Access
30.0
60.0
34.0
56.0
Over relative humidity alarm threshold. An alarm is
activated if the relative humidity is equal to or above
this value.
Under relative humidity warning threshold. A warning
is activated if the relative humidity is equal to or
below this value.
Over relative humidity warning threshold. A warning
is activated if the relative humidity is equal to or
above this value.
0.1%
RH
0.1%
RH
0.1%
RH
0.1%
RH
Under relative humidity alarm threshold. An alarm is
activated if the relative humidity is equal to or below
this value.
0.0-100.0%
0.0-100.0%
0.0-100.0%
0.0-100.0%
0.0-100.0%
1.0-85.0
0.1%
RH
35.0
Over temperature warning threshold. A warning is
activated if the temperature is equal to or above this
value.
0.1° C
1.0-85.0
Relative humidity measured at the humidity sensor.
20.0
Under temperature warning threshold. A warning is
activated if the temperature is equal to or below this
value.
0.1° C
Range
1.0-85.0
37.0
Over temperature alarm threshold. An alarm is
activated if the temperature is equal to or above this
value
Units
0.1° C
Default
Description
Must be less than
lgpPduAuxMeasHumThrshldOvrAlm and
greater than
lgpPduAuxMeasHumThrshldUndrWarn and
greater than
lgpPduAuxMeasHumThrshldUndrAlm
Must be less than
lgpPduAuxMeasHumThrshldOvrAlm and less
than lgpPduAuxMeasHumThrshldOvrWarn
and less than
lgpPduAuxMeasHumThrshldUndrWarn
Must be less than
lgpPduAuxMeasHumThrshldOvrAlm and less
than lgpPduAuxMeasHumThrshldOvrWarn
and less than
lgpPduAuxMeasHumThrshldUndrWarn
Must be less than
lgpPduAuxMeasHumThrshldOvrAlm and less
than lgpPduAuxMeasHumThrshldOvrWarn
and less than
lgpPduAuxMeasHumThrshldUndrWarn
Must be less than
lgpPduAuxMeasTempThrshldOvrAlmDegC
and less than
lgpPduAuxMeasTempThrshldOvrWarnDegC
and less than
lgpPduAuxMeasTempThrshldUndrWarnDegC
Must be less than
lgpPduAuxMeasTempThrshldOvrAlmDegC
and less than
lgpPduAuxMeasTempThrshldOvrWarnDegC
and less than
lgpPduAuxMeasTempThrshldUndrWarnDegC
Must be less than
lgpPduAuxMeasTempThrshldOvrAlmDegC
and less than
lgpPduAuxMeasTempThrshldOvrWarnDegC
and less than
lgpPduAuxMeasTempThrshldUndrWarnDegC
lgpPduAuxMeasTempThrshldUndrWarnDegC
Comment
30.....RPC2 Communications Module SNMP, MIB, OID Technical Bulletin
OID Column Number
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.120
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.125
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.130
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.135
Data Point Name
lgpPduAuxMeasDrClosureState.2.1.1
lgpPduAuxMeasDrClosureConfig.2.1.1
lgpPduAuxMeasCntctClosureState.2.2.1
lgpPduAuxMeasCntctClosureConfig.2.2.1
Integer
Integer
Integer
Integer
Syntax
rw
ro
rw
ro
Access
closed(2): The door is in the closed state.
•
when the door state becomes open.
alarm-when-open (1): Activate an alarm
in alarm.
disabled(0):The door state will never result
closed state.
closed(2): The contact closure is in the
state.
open(1): The contact closure is in the open
is unknown.
not-specified(0): The contact closure state
•
never result in alarm.
disabled(0): The contact closure state will
measurement should activate an alarm
provides the ability to select when a contact closure
Configure contact closure state alarms. This object
•
•
•
The state of a contact closure sensor measurement.
•
•
closure measurement should cause an alarm.
This object provides the ability to select when a door
A configuration parameter for the door state alarms.
open(1): The door is in the open state.
unknown.
not-specified(0): The door state is
•
•
sensor measurement.
Enumerations that describe the state of the door
Description
disabled
(0)
notspecified
(0)
0
Default
Units
0-2
0-2
0-1
0-2
Range
Comment
RPC2 Configuration SNMP OID Tables.....31
OID Column Number
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.145
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.150
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.155
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.110
.1.3.6.1.4.1.476.1.42.3.8.60.15.1.115
Data Point Name
lgpPduAuxMeasDiffPressure.2.3.1
lgpPduAuxMeasDiffPressureThrshldUndrAlm.2.3.1
lgpPduAuxMeasDiffPressureThrshldOvrAlm.2.3.1
lgpPduAuxMeasDiffPressureThrshldUndrWarn.2.3.1
lgpPduAuxMeasDiffPressureThrshldOvrWarn.2.3.1
Integer32
Integer32
Integer32
Integer32
Integer32
Syntax
rw
rw
rw
rw
ro
Access
+100.0
-50.0
+50.0
Over differential pressure alarm threshold. An alarm
is activated if the differential pressure is equal to or
above this value.
Under differential pressure warning threshold. A
warning is activated if the differential pressure is
equal to or below this value.
Over differential pressure warning threshold. A
warning is activated if the differential pressure is
equal to or above this value.
pA
pA
pA
pA
-100.0
Under differential pressure alarm threshold. An alarm
is activated if the differential pressure is equal to or
below this value.
Units
pA
closed.
when the contact closure state becomes
alarm-when-closed(2): Activate an alarm
open.
when the contact closure state becomes
alarm-when-open(1): Activate an alarm
Default
Pressure difference measured at the differential
pressure sensor.
•
•
Description
-125.0 to
+125.0
-125.0 to
+125.0
-125.0 to
+125.0
-125.0 to
+125.0
-125.0 to
+125.0
Range
Must be less than
lgpPduAuxMeasDiffPressureThrshOvrAlm
and greater than
lgpPduAuxMeasDiffPressureThrshUndrWarn
and greater than
lgpPduAuxMeasDiffPressureThrshUndrAlm
Must be less than
lgpPduAuxMeasDiffPressureThrshOvrAlm
and less than
lgpPduAuxMeasDiffPressureThrshOvrWarn
and less than
lgpPduAuxMeasDiffPressureThrshUndrWarn
Must be less than
lgpPduAuxMeasDiffPressureThrshOvrAlm
and less than
lgpPduAuxMeasDiffPressureThrshOvrWarn
and less than
lgpPduAuxMeasDiffPressureThrshUndrWarn
Must be less than
lgpPduAuxMeasDiffPressureThrshOvrAlm
and less than
lgpPduAuxMeasDiffPressureThrshOvrWarn
and less than
lgpPduAuxMeasDiffPressureThrshUndrWarn
Comment
32.....RPC2 Communications Module SNMP, MIB, OID Technical Bulletin
OID Column Number
.1.3.6.1.4.1.476.1.42.3.8.60.20.1.15
Data Point Name
lgpPduAuxMeasOrderSensorSerialNum.1.1
String
Syntax
rw
Access
The sensor's globally unique serial number is assigned at the time of
manufacture. The sensor represented by this serial number will be, if
discovered by the agent placed in the lgpPduAuxMeasTable at the location
specified by the index entries herein. An empty string in this object indicates
an open display position that can be occupied by any sensor not given a
specific display position in this table.
Description
LIEBERT‐GP‐PDU-MIB::lgpPduAuxMeasOrderTable
Default
Units
Range
Comment
RPC2 Configuration SNMP OID Tables.....33
34.....RPC2 Communications Module SNMP, MIB, OID Technical Bulletin
Technical Support Site
If you encounter any installation or operational issues with your product, check the pertinent section of this
manual to see if the issue can be resolved by following outlined procedures. For additional assistance, visit
www.avocent.com/support.
Avocent Community Support Site
To search product knowledge content,
visit community.emerson.com/networkpower/support/avocent.
About Emerson Network Power
Emerson Network Power, a business of Emerson (NYSE:EMR), delivers software, hardware and services that maximize
availability, capacity and efficiency for data centers, healthcare and industrial facilities. A trusted industry leader in smart
infrastructure technologies, Emerson Network Power provides innovative data center infrastructure management solutions
that bridge the gap between IT and facility management and deliver efficiency and uncompromised availability regardless of
capacity demands. Our solutions are supported globally by local Emerson Network Power service technicians. Learn more
about Emerson Network Power products and services at www.EmersonNetworkPower.com.
590-1340-501A
Download