INPUT CABLING AND PROTECTION Table below applies to: 1. A stand-alone UPS or 2. A UPS equipped with a Maintenance Bypass Cabinet (without transformer) Max. System Load Rating Input Voltage – 208VAC Max. Current Min. Input Protection in UPS mode Circuit Breaker Input Voltage – 240VAC Max. Current Min. Input Protection in UPS mode Circuit Breaker 4kVA 18 amps 50 amps 15 amps 50 amps 8kVA 36 amps 50 amps 31 amps 50 amps 12kVA 53 amps 75 amps 46 amps 75 amps 16kVA 70 amps 100 amps 62 amps 2 Terminal Block Details 90 amps 2 Maximum: 35mm (2 AWG); Minimum: 16mm (6 AWG) Torque Rating: 2.5-3.0 Nm (22-26 in/lbs) UPS With Maintenance Bypass Cabinet (With Transformer) Single Input Feed: All UPS ratings must use 100A input circuit breaker protection. Dual Input Feed: See table below. Max.System Load Rating UPS Feed Input Voltage – 208VAC Input Voltage – 240VAC Max. Current Min. Input Protection Max. Current Min. Input Protection in UPS mode Circuit Breaker in UPS mode Circuit Breaker Bypass Feed 208V or 240V Min. Input Protection Circuit Breaker 4kVA 18 amps 50 amps 15 amps 50 amps 100 amps 8kVA 36 amps 50 amps 31 amps 50 amps 100 amps 12kVA 53 amps 75 amps 46 amps 75 amps 100 amps 16kVA 70 amps 100 amps 62 amps 90 amps 100 amps 35mm2 (2 Terminal Block Details 16mm2 (6 Maximum: AWG); Minimum: AWG) Torque Rating: 2.5-3.0 Nm (22-26 in/lbs) Bypass Voltage Jumper Position (TB2) Bypass Voltage Selection 208VAC 240VAC (Factory Default) (Field Change) Jumper/link on upper two screws Jumper/link on lower two screws Liebert Corporation 1050 Dearborn Drive P.O. Box 29186 Columbus, OH 43229 © 2005 Liebert Corporation All rights reserved throughout the world. Specifications subject to change without notice. ® Liebert and the Liebert logo are registered trademarks of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners. Telephone: 1-800-877-9222 Facsimile: 1-614-841-6022 www.liebert.com While every precaution has been taken to ensure the accuracy and completeness of this literature, Liebert Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions. SL-23951 (7/05) Rev. 3 THIS LABEL MUST BE REMOVED PRIOR TO OPERATING THE UPS OUTPUT CABLING UPS Output Terminal Block (TB3) Connection to External Panel Boards 208VAC If connected equipment operates at 208VAC only, use a single-phase panel board connected to the UPS as follows. Setup 1 - 208VAC Max output current = 77A Panel Board Input 1 208VAC 1 2 208VAC 3 L 2 L 3 4 GEC Grounding Electrode Conductor (Field connection must be made) UPS Output TB3 4 GEC 5 5 G G 208VAC and 120VAC If connected equipment is a combination of 208VAC and 120VAC, use a three-phase panel board connected to the UPS as follows. Setup 2 - 120VAC Max output current = 67A each 120VAC circuit 208VAC also available as shown connected in Setup 1 120VAC 120 VAC GEC Grounding Electrode Conductor (Field connection must be made) Panel Board Input 1 2 3 4 120VAC (N to L3 only) 208VAC (L1 to L2) 120VAC (N to L1) Note: L2 to N is 88VAC L3 1 L2 2 L1 3 N 4 GEC 5 G 5 G UPS Output TB3 CAUTION: It is important for the installing electrician to clearly identify the connections for future reference. Refer to NEC 215-8 and 210-4(d). 240VAC and/or 120VAC If connected equipment operates at 240VAC only or 120VAC only or is a combination of both, use a single-phase panel board connected to the UPS as follows. Setup 3 - 240VAC Max output current = 67A 120VAC also available as shown connected in Setup 2 240VAC 2 3 4 GEC Grounding Electrode Conductor (Field connection must be made) Panel Board Input UPS Output TB3 L 1 1 5 G 120VAC 240VAC 120VAC 2 L 3 N 4 GEC 5 G