(light yellow.Pro mar 200 egg shell) Denim. Pro mar 200. SW6523 egg shell (EXISTING) FLUSH SURFACE NEMA RATING: 1 3R ISOLATED GROUND BUS: MAIN C.B.: 150 AMP LOCATION: 2ND. FL. ELEC. RM. BUS SIZE: 225 AMP BRANCH BREAKERS DESCRIPTION R ----- SIZE P 30 1 R PROOFER OVEN R ----R STAGE FLOOR BOX MI EXISTING LOAD 3 3 5 2 7 9 2 11 13 20 R ----- 20 MI ----MI ----- 20 MI SERVICE ROOM 20 3 1 19 21 R FLOOR BOX IN LOBBY R PROJ. SCREEN - DINING 20 20 1 1 23 25 R PROJECTOR - DINING 20 1 27 MI SERVICE ROOM 20 20 1 1 29 31 20 20 1 1 33 35 SPARE 20 20 1 1 37 39 SPARE 20 1 41 MI LIVING WALL R RECEPT-OFFICE 224 R A/V 4-PLEX R PROOFER 120V A LOAD 696 696 460 1000 360 1000 360 1000 180 500 900 360 360 180 180 500 360 500 500 360 1000 900 1000 360 500 1000 1000 - CIR. SIZE 2 50 4 6 50 10000 VA 1.00 10.0 R RECEPTACLES (REMAINING) 17902 VA 0 VA 0.50 1.25 9.0 0.0 0 VA 0 VA 1.00 1.25 0.0 0.0 7500 VA 1.00 7.5 6300 5370 2 DESCRIPTION CD ALL HOT WORK ACTIVITIES DURING CONSTRUCTION, E.G. USING HE AT GUNS, SOLDERING, BRAZING, WELDING, GRINDING, P OWER DRIVEN STUDS, METAL CUTTING USING POWE R TOOLS OR OTHER ACTIVITIES INVOLVING FLA MES OR SPARKS REQUIRE AND APPROVED HOT WORK PERMIT. IF A HOT P ERMIT IS RE QUIRED, THE CONTRACTOR SHALL FOLLOW THE PROCEDURES. 2. THE PROJECT STAGING ARE A AND CONSTRUCTION ACTIVITIES SHALL NOT CAUSE OBSTRUCTION OF THE PATHS OF EGRESS INSIDE THE BUILDING, BLOCK EXIT DISCHARGE FROM THE BUILDING OR IMP EDE EMERGENCY VEHICLE ACCESS TO THE AREA. 3. IF THE CONSTRUCTION GENE RATES DUST OR FUMES INSIDE THE BUILDING, NECESSA RY MEASURES ARE TO BE TAK EN TO PREVENT THE NUISANCE ACTUATION OF ANY NEA RBY SMOKE OR DUCT DETECTORS. PLEASE CONTACT THE FIRE SYSTEM GROUP TO MAKE NECES SARY ACTIONS. IF SMOKE DETE CTORS ARE COVERED THEY MUST BE REMOVED AND THE END OF EACH WORK DAY. 4. ALL PENETRATIONS THROUGH FIRE RATED CORRIDORS OR FLOOR/CEILING ASSE MBLIES SHALL BE FIRE STOPPED WITH A MATCHING RATING. 5. PROTECT SPRINKLERS AGAINST MECHANICAL DAMAGE AND PAINT OVERSPRAY. 6. ALL WORK SHALL COMPLY WITH UCB AND OIT DIV.27 STANDARDS, UBC 2009, IB C 2012 AND NEC 2014. CONTACT FACILITIES MANAGEMENT FOR ALL INSPE CTIONS. 7. ALL EXISTING CONDUIT AND WIRE NOT BEING REUSED SHALL BE REMOVED IN ITS ENTIRETY BACK TO SOURCE. 8. ALL EXISTING DEVICES TO REMAIN SHALL BE RECONNECTED AS REQUIRED AFTER DEMOLITION IS COMP LETE. PROV IDE NEW CONDUIT AND WIRE AS REQUIRED. 9. NEW CONSTRUCTION SHALL NOT BLOCK OR LIMIT ACCESS TO EXISTING COMMUNICATION P ATHWAYS. ALL NEW E LECTRICAL INSTALLATION SHA LL COMPLY WITH OIT STANDA RDS FOR EMI DISTANCES BETW EEN THE ELECTRICAL AND COMMUNICATION WIRING. 10. ALL EXISTING COMMUNICATION WIRING SHALL BE DE MOLISHED BY CU OIT CONTRACTORS ONLY. 11. SAW-CUT SLURRY, SEDIMENT/SOILS , AND ALL OTHE R MATERIALS AND PROCESS WA TERS MUST BE CAPTURED FOR P ROPER DISPOSAL AND NOT ALLOWED TO BE DISCHARGED TO STORM DRA INS , GUTTERS, PARKING LOTS, OR OTHER STORM CONVEYANCES. USE P ROPER BE ST MANAGEMENT PRA CTICES (BMP’S ) TO PROTECT FROM CONTAMINATED RUN-OFF. 12. ANY ELECTRICAL WORK THAT WILL INTERFERE WITH OR INTERRUPT THE OPERATION OF B UILDINGS, OR SERVICES, MUST BE COORDINATED WITH THE OWNER AND CONTRACTOR AT LEAST 14 CALENDA R DAYS IN ADV ANCE FOR PROPER SCHEDULING. THE CONTRACTOR SHALL SUBMIT A REQUEST FOR THE OUTAGE TO THE OWNER DETAILING THE REASONS FOR THE OUTA GE, AREAS AFFECTED, AND SEQUENCE OF PROCEDURES TO ACCOMPLISH WORK. THE CONTRACTOR SHALL OBTAIN WRITTEN AUTHORIZATION FROM THE OWNER FOR ALL PROPO SED OUTAGES. THESE CONNECTIONS MAY HAVE TO BE DONE AT ANY HOUR OF A NY DAY AT NO INCREASE IN PRICE. OUTAGE S SHALL BE MINIMUM TIME PE RIODS. ALL PREPARA TIO N WORK SHALL BE PLANNED AND EXECUTED PRIOR TO ACTUAL OUTAGE. IN ALL CASES ALL MA TERIAL SHA LL BE FURNISHED BY THE CONTRACTOR. SUB MIT WRITTE N PLAN WITH TIME LINE FOR REMOVA L, INSTALLATION AND CONNECTION OF GENE RATOR SETS. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ANY AND ALL TEMPORARY POWER REQUIRED. 13. ALL OUTAGES REQUIRE A DE TAILED MOP . THE MOP SHALL DETAIL ALL WORK PROPOSED BY THE CONTRA CTOR, INCLUDING TIME SEQUE NCE, TA SKS, RESPONSIBILITIES AND ES TIMATED COMPLETION TIMES. THE MOP SHALL INCLUDE A DETAILED BREAKDOWN OF THE UNIVERSITY/CONTRACTOR COORDINA TION CHECKPOINTS AND PROP OSED SAFETY MEASURES. THE MOP SHALL BE SUBMITTED FOR REV IEW AND APPROVAL PRIOR TO SCHEDULING THE OUTAGE. 14. ALL STRUCTURAL ELEMENTS MUST BE X-RAYED TO A VOID RE BAR LOCATIONS PRIOR TO ANY SAW CUTS OR CORE DRILLING. SPARE ----MICROWAVE/OVEN COMBO ----- R OVERHEAD DOOR WEST OVERHEAD DOOR EAST R 4-PLEX SOUND BOOTH R R 20 2 1 12 14 20 20 1 1 16 18 20 20 1 1 20 22 20 20 1 1 24 26 20 20 1 1 28 20 1 1 20 20 1 1 R 1 34 36 20 RECEPT-304 AV RACK RECEPT-317, E.W.C. EXISTING LOAD ----- R 30 32 38 40 1000 P 8 10 1000 42 5940 4316 6896 12520 10616 12266 Total Connected V.A. 35402 =Total Connected VA all Phases R RECEPTACLES (1ST 10000) H ELECTRIC HEAT 3120 1000 0.0 MI ELECTRICAL MISC. 3120 1000 KVA MR MOTORS (REMAINING) C - 1250 D.F. ML MOTOR (LARGEST) CONNECTED B - 1250 1.25 LIGHTING A 2150 0 VA L RIGHT PHASE LOAD C 2150 6580 CD B 2150 15 17 MI EXISTING LOAD MI ----- CIR. 20 3 1 20 1 R RECEPT-306 R R RECEPT-306 SOUND PNL SHUNT-TRIP RECE R 1 1 RECEPT-304, 304A, 306 R 1 RECEPT-304 R SOUND PNL SHUNT-TRIP RECE R 1 MI R STAGE LIGHTING RECEPT ----- R STAGE LIGHTING RECEPT R STAGE LIGHTING RECEPT R R AMPS PANEL SERVICE FEEDER: 45KVA TRANSFORMER CONDUCTOR: (4#1/0) NOTES CD LEFT PHASE LOAD 1. A.I.C. RATING: 10,000 (G.E. A-SERIES II) SERVICE ENTRANCE RATED: NOTES VOLTAGE: 120/208V-3PH-4W PANEL "MR2" NOTES MOUNTING: 1. NEW LOAD ON EXISTING SPARE BREAKER. 2 3 35402 VA 26.5 73.5 ALL SINGLE PHASE SHARED NEUTRAL CIRCUITS SHALL BE SUPPLIED WITH BREAKER HANDLE TIES PER NEC 210.4 TOTAL ESTIMATED LOAD FIXTURE SCHEDULE KEY LAMP(S) DESCRIPTION FINISH VOLT MOUNTING MFR CAT. NO. A 40W 4300lm LED 3500K 2x4 LED TROFFER WITH FROSTED ACRYLIC CENTER BACKET AND INTEGRAL 0-10V DIMMING DRIVER WHITE UNV RECESSED IN GRID WILLIAMS LT-24-L43/835-AF-DIMUNV B 14.5W 1100lm LED 3500K 6" DIA. LED DOWNLIGHT WITH INTEGRAL 0-10V DIMMING DRIVER CLEAR UNV RECESSED IN GYP. PRESCOLITE LF6LEDG4-6LFLED5G435K-WT C 150W 12200lm LED 3500K 29" DIA. DECORATIVE LED PENDANT WITH 10% UPLIGHT AND INTEGRAL 0-10V DIMMING DRIVER SATIN NICKEL UNV CABLE PENDANT VISA CP2000-CBL-LNW-SNAIRP-UP10 D (1) 14W T5 3500K 24" ADA ARCHITECTURAL FLUORESCENT VANITY LIGHT WITH ACRYLIC LENS AND DAMP LOCATION LABEL SATIN NICKEL UNV WALL OXYGEN LIGHTING ADELPHI 2-5170-224 F 18W LED 3000K DECORATIVE LED WALL SCONCE WITH ITEGRAL 0-10V DIMMING DRIVER. ADA COMPLIANT SATIN NICKEL UNV WALL (MOUNTED HORIZONTAL) +6'-4" A.F.F. OXYGEN LIGHTING PROFILE 3-507-24 WITH DIMMING DRIVER EM1 FURNISHED WITH UNIT EMERGENCY EGRESS LIGHT WITH BATTERY AND SELF DIAGNOSTICS WHITE UNV WALL DUAL-LITE EV-2I GENERAL NOTES A EQUIPMENT SHOWN IS FOR ILLUSTRATIVE PURPOSES ONLY. PROVIDE QUANTITIES AS SHOWN ELSEWHERE ON THE DRAWINGS, AS CALLED FOR IN THE SPECIFICATIONS, AND/OR AS NECESSARY FOR A FULLY FUNCTIONAL AND OPERATING SYSTEM(S) READY FOR THE OWNERS USE B ALL POWER REQUIREMENTS INCLUDING BUT NOT LIMITED TO POWER SUPPLIES, POWER DISTRIBUTION AND POWER CORDS ARE TO BE PROVIDED BY CONTRACTOR UNLESS NOTED OTHERWISE. POWER REQUIREMENTS ARE ASSUMED AND MAY NOT BE SHOWN HEREIN C DATA PATCH CABLES REQUIRED TO CONNECT A DEVICE TO A DATA NETWORK OUTLET SHALL BE PROVIDED BY THE CONTRACTOR D THE CONTRACTOR(S) SHALL PROVIDE ALL REQUIREMENTS SHOWN IN BLACK; THIS IS TO INCLUDE BUT NOT LIMITED TO DEVICES, CABLING, TERMINATIONS AND PROGRAMMING. DEVICES SHOWN IN GRAY INDICATE REQUIREMENTS THAT ARE EITHER EXISTING AND/OR PROVIDED BY OTHERS E SOME ANCILLARY EQUIPMENT IS SHOWN HEREIN FOR CLARITY BUT NOT ALL ANCILLARY EQUIPMENT IS SHOWN WITHIN THIS DRAWING. REFER TO EQUIPMENT SCHEDULES FOR EQUIPMENT REQUIREMENTS. PROVIDE AUXILIARY EQUIPMENT AS REQUIRED TO PROVIDE A FULLY FUNCTIONAL AND OPERATING SYSTEM READY FOR THE OWNERS USE F SOME TRANSMISSION EXTENSION EQUIPMENT IS SHOWN HEREIN FOR CLARITY BUT NOT ALL TRANSMISSION EXTENSION EQUIPMENT MAY BE SHOWN WITHIN THIS DRAWING. TRANSMISSION EXTENSION EQUIPMENT SHALL INCLUDE BUT NOT LIMITED TO EXTENDERS, AMPLIFIERS AND/OR SIGNAL REPEATERS. PROVIDE TRANSMISSION EXTENSION EQUIPMENT AS REQUIRED TO PROVIDE A FULLY FUNCTIONAL AND OPERATING SYSTEM READY FOR THE OWNERS USE G PROVIDE HDMI TRANSMISSION EQUIPMENT AS REQUIRED TO PROVIDE A FULLY FUNCTIONAL AND OPERATING SYSTEM READY FOR THE OWNERS USE. HDMI TRANSMISSION EQUIPMENT SHALL INCLUDE BUT NOT BE LIMITED TO SPECIALIZED CABLE, CATEGORY CABLE TRANSMITTERS/RECEIVERS AND/OR FIBER CABLE TRANSMITTERS/RECEIVERS