# TRANSFORMER GROUND SIZING TABLE 208/120 VOLT SECONDARY KVA AWG/KCMIL 3 WIRE 4 WIRE 4W1 2W1A M-E ENGINEERS, INC. M-E ENGINEERS, INC. UCCS GENERATOR LOCATION: ELEC RM. A144 480Y/277V, 3PH-4W+GND LOCATION: ELEC. RM. A126 208Y/120V, 3PH-4W+GND MOUNTING: SURFACE MLO MOUNTING: SURFACE MLO RATING: EXISTING 225A BUS RATING: EXISTING UCCS GENERATOR 225A BUS VA VA N DESCRIPTION # TYPE BRKR LT 20A/1P 1 LTG - EQUIP REPAIR 1 3 SPARE 20A/1P 1 5 SPARE 20A/1P 1 7 SPARE 20A/1P 9 LTG - CONTROL 114 LT 20A/1P 11 LTG - CONTROL 108 LT 20A/1P 13 LTG - EQUIP/ STORAGE LT 20A/1P 15 LTG - EDIT ROOMS LT 20A/1P 17 LTG - CORRIDOR LT 20A/1P 19 LTG - CORRIDOR LT 20A/1P 21 LTG - STAIRWELL LT 20A/1P PHASE C PHASE B PHASE A 4432 3052 2124 3330 3420 3420 2400 1100 1440 3400 2520 3400 2680 1104 1724 4432 900 4432 3620 4432 20A/1P 23 SPARE LT 25 EXTERIOR UP LIGHTING 20A/1P 4432 # DESCRIPTION N BRKR TYPE TYPE BRKR 20A/1P LT LOW VOLTAGE SWITCHING 2 1 CONT ROOM R 20A/1P 20A/1P LT LTG - NIGHT LITES 4 3 CONT ROOM R 20A/1P 20A/1P LT LTG - LOADING EXT 6 5 CONT ROOM R 20A/1P 20A/1P LT LTG - LOADING EXT 8 7 CONT ROOM R 20A/1P 20A/1P LT LTG - LOADING EXT 10 9 CONT ROOM R 20A/1P 20A/1P LT LTG - PRINTERS 12 11 CONT ROOM R 20A/1P 20A/1P LT LTG - COMPUTER 14 13 CONT ROOM R 20A/1P 20A/1P LT LTG - COMPUTER 16 15 AUDIO BOOTH R 20A/1P 20A/1P LT LTG - COMPUTER 18 17 ANNIC BOOTH R 20A/1P 20A/1P LT POLE LIGHTS EXT 20 19 ON LINE EDIT R 20A/1P 20A/1P LT POLE LIGHTS EXT 22 21 ON LINE EDIT R 20A/1P 20A/1P LT WALL LIGHTS 24 23 ON LINE EDIT R 20A/1P 20A/1P SPARE 26 25 ON LINE EDIT R 20A/1P N DESCRIPTION # 27 SPARE 20A/1P 20A/1P SPARE 28 27 ON LINE EDIT R 20A/1P 29 SPARE 20A/1P 20A/1P SPARE 30 29 TAPE CONT R 20A/1P 31 SPARE 20A/1P 20A/1P SPARE 32 31 TAPE CONT R 20A/1P 33 SPARE 20A/1P 20A/1P SPARE 34 33 ELEV MACHINE R 20A/1P 35 SPARE 20A/1P 20A/1P SPARE 36 35 ELEC CAB LT 20A/1P 37 SPACE SPACE 38 37 ELEV PIT LT 20A/1P 39 SPACE SPACE 40 39 ELEC/ JAN R 20A/1P 41 SPACE SPACE 42 41 ELEV PIT STAND R 20A/1P VA 43 FLOOR BOX TELE R 20A/1P AMPS 45 TELECONFERENCE R 20A/1P OPTIONS: 47 TELECONFERENCE R 20A/1P * ALL LOADS EXISTING U.O.N. 49 TELECONFERENCE R 20A/1P TOTAL CONNECTED PHASE LOAD 26588 22076 13130 96.0 79.7 47.4 KVA AMPS TOTAL CONNECTED LOAD 61.79 74.3 51 TELECONFERENCE R 20A/1P LONG CONTINUOUS LOADS * 25% 15.45 18.6 53 TELECONFERENCE R 20A/1P NOTES: 55 TELECONFERENCE R 20A/1P 1. EXISTING LOAD MADE SPARE. 57 TELECONFERENCE R 20A/1P 59 TELECONFERENCE R 20A/1P 61 TELECONFERENCE R 20A/1P 63 TELECONFERENCE R 20A/1P 65 TELECONFERENCE R 20A/1P 67 TELECONFERENCE R 20A/1P 69 TELECONFERENCE R 20A/1P 71 TELECONFERENCE R 20A/1P 73 TELECONFERENCE R 20A/1P LARGEST MOTOR LOAD * 25% (RECEPTACLE LOADS - 10KVA) * 50% KITCHEN LOADS * 0% 92.9 77.24 TOTAL LOAD MOTOR CONTROL CENTER "MCC-1 SECTION - 1" LOAD SCHEDULE DESCRIPTION CKT MOTOR CONTROL CENTER "MCC-1 SECTION - 2" LOAD SCHEDULE CKT - 1 PUMP P - 1B 11.0 7.6 2 PUMP P - 8A 11.0 11.0 DESCRIPTION SPACE 2 PUMP P - 9A 3 PUMP P - 9B 7.6 3 PUMP P - 6B 4 PUMP P - 13A 11.0 4 SPARE - 5 B-1 7.6 5 SPACE - 6 PUMP P - 13B 11.0 6 PUMP P - 7A 7 B-2 7.6 7 SPARE 8 B-3 3.4 8 PUMP P - 1A 11.0 4.8 4.8 - 9 FC - 402 1.8 9 PUMP P - 7B 10 PUMP P - 11A 7.6 10 SPACE 11 PUMP P - 11B 7.6 11 PUMP P - 4B 12 EF - 402 7.6 12 PUMP P - 5B 4.8 13 PUMP P - 10A 7.6 13 PUMP P - 8B 11.0 14 EF - 403 4.8 14 PUMP P - 4A 4.8 15 CT - 1 46.0 15 SPACE 16 TCAC - 1 15.2 16 PUMP P - 15 11.0 17 BFP FOR B - 3 17 EF - 401 1.8 18 FC - 401 1.8 18 SPACE - 19 PUMP P - 2B 14.0 19 SPACE 20 PUMP P - 3B 3.4 SUB TOTAL 21 PUMP P - 2A 14.0 LCL x 25% 22 PUMP P - 10A 7.6 LML x 25% 23 AHU - 1R 65.0 RECEPTACLE DIVERSITY 24 AHU - 2R 65.0 KITCHEN DIVERSITY 25 PUMP P - 6A 11.0 TOTAL LOAD 26 PUMP P - 5A 4.8 27 PUMP P - 14 3.4 28 PUMP P - 3A 3.4 29 SPACE 30 MCC-1 SECTION - 2 91.8 SUB TOTAL 439.2 LCL x 25% LML x 25% 16.3 RECEPTACLE DIVERSITY KITCHEN DIVERSITY TOTAL LOAD 455.5 180 180 180 180 180 180 180 180 180 180 180 180 180 180 180 180 720 180 180 180 180 180 360 180 696 180 360 180 500 380 720 280 720 720 360 720 360 360 360 360 360 360 180 360 180 360 180 360 540 360 360 360 720 360 360 360 360 360 360 360 R TAPE CONT 2 20A/1P R TAPE CONT 4 20A/1P R TAPE CONT 6 20A/1P R TAPE CONT 8 20A/1P R TAPE CONT 10 20A/1P R TAPE CONT 12 20A/1P R CONT ROOM 14 20A/1P R ON LINE EDIT 16 20A/1P R TAPE CONT 18 20A/1P R STUDIO 20 20A/1P R SET SHOP 22 20A/1P R SET SHOP 24 SPARE 26 R DATA 28 20A/1P R DATA 30 20A/1P M ELEV PIT SUMP 32 20A/1P R CONTROL 34 20A/1P EQ DIMMER CONTROL 36 20A/1P R TELECONFERENCE 38 20A/1P R TELECONFERENCE 40 20A/1P R FLOOR BOX TELE 42 20A/1P R CONTROL 44 20A/1P R TELECONFERENCE 46 20A/1P R CONTROL 48 20A/1P R STUDIO 50 20A/1P R STUDIO 52 20A/1P R STUDIO 54 20A/1P R TELECONFERENCE 56 20A/1P R TELECONFERENCE 58 20A/1P R TELECONFERENCE 60 20A/1P SPARE 62 20A/1P SPARE 64 20A/1P SPARE 66 20A/1P SPARE 68 20A/1P SPARE 70 20A/1P SPARE 72 SPACE 74 360 20A/1P SPACE 76 77 SPARE 20A/1P SPACE 78 79 SURGE SUPPRESSOR 40A/3P SPACE 80 81 - - - SPACE 82 83 - - - SPACE 84 7276 6660 7000 VA 60.6 55.5 58.3 AMPS OPTIONS: KVA AMPS TOTAL CONNECTED LOAD 20.94 58.1 LONG CONTINUOUS LOADS * 25% 0.17 0.5 LARGEST MOTOR LOAD * 25% 0.17 0.5 (RECEPTACLE LOADS - 10KVA) * 50% -4.54 -12.6 16.74 46.5 * ALL LOADS EXISTING U.O.N. NOTES: 1. EXISTING BREAKER MADE SPARE. KITCHEN LOADS * 0% TOTAL LOAD 4.8 - 91.8 LOAD CALCULATION FOR EXISTING SERVICE 480Y/277V, 3 PHASE, 4 WIRE, 3000A SERVICE 2.8 94.6 # TYPE 20A/1P 360 180 DESCRIPTION BRKR 20A/1P 20A/1P 180 AMPS 1 - 180 75 SPARE TOTAL CONNECTED PHASE LOAD AMPS PHASE C PHASE B PHASE A 180 MAXIMUM DEMAND LOAD RECORDED BY THE UTILITY COMPANY AVERAGED OVER A 15 MIN PERIOD FROM THE LAST 12 MONTHS: MAXIMUM DEMAND LOAD * 25%: EXISTING LOAD PER NEC 220.87: NEW LOAD TO BE ADDED FROM NEW WORK: TOTAL CALCULATED LOAD FOR THIS PROJECT: 738.7 AMPS 184.7 AMPS 923.4 AMPS + 9.9 AMPS 933.3 AMPS N 1 2W1Ca UCCS GENERATOR 2W1Cb M-E ENGINEERS, INC. UCCS GENERATOR LOCATION: TELCOM RM 208Y/120V, 3PH-4W+GND LOCATION: TELECOM RM 208Y/120V, 3PH-4W+GND MOUNTING: SURFACE 250A MCB MOUNTING: SURFACE MLO RATING: 10K AIC 400A BUS RATING: 10K AIC 400A BUS VA N # TYPE BRKR 1 ADMIN SERV 1 REC DESCRIPTION R 20A/1P 3 ADMIN SERV 1 REC R 20A/1P 5 ADMIN SERV 2 REC R 20A/1P 7 ADMIN SERV 2 REC R 20A/1P 9 ADMIN SERV 3 REC R 20A/1P 11 ADMIN SERV 3 REC R 20A/1P 13 ADMIN SERV 4 REC R 20A/1P 15 ADMIN SERV 4 REC R 20A/1P 17 ADMIN SERV 4 REC R 20A/1P 19 SPARE 20A/1P 21 SPARE 20A/1P 23 SPARE 20A/1P 25 ADMIN SERV 5 REC R 20A/1P 27 ADMIN SERV 5 REC R 20A/1P 29 COMP NET 1 GB 1 PLUGMOLD R 20A/1P 31 COMP NET 1 GBA 2 PLUGMOLD R 20A/1P 33 COMP NET 1 GBA 2 PLUGMOLD R 20A/1P 35 COMP NET 5 GB 1 PLUGMOLD R 20A/1P 37 COMP DIAL 1 GB 1 PLUGMOLD R 20A/1P 39 MEDIA MASTER 1 GBA 2 PLUGMOLD R 20A/1P 41 MEDIA MASTER 2 GBA 2 PLUGMOLD R 20A/1P PHASE A 475 VA PHASE B PHASE C 475 200 240 475 250 475 800 200 200 250 475 1190 800 300 200 200 625 475 475 180 775 180 200 485 800 550 550 200 200 610 529 M-E ENGINEERS, INC. 800 800 800 200 1000 400 FEED-THRU PANEL 2W1Cb PHASE LOAD 21130 25100 15350 TOTAL CONNECTED PHASE LOAD 28514 28695 237.6 239.1 BRKR TYPE TYPE BRKR 20A/1P R COMP SERV 1 REC 2 1 MEDIA MASTER 3 GBA 2 PLUGMOLD R 20A/1P 20A/1P R COMP SERV 1 REC 4 3 MEDIA MASTER 4 GBA 2 PLUGMOLD R 20A/1P 20A/1P R COMP SERV 1 REC 6 5 MEDIA MASTER 5 GBA 2 PLUGMOLD R 20A/1P 20A/1P R COMP SERV 3 REC 8 7 MEDIA MASTER 6 GBA 2 PLUGMOLD R 20A/1P 20A/1P R COMP SERV 3 REC 10 9 MEDIA MASTER 7 GBA 2 PLUGMOLD R 20A/1P 20A/1P R COMP SERV 4 REC 12 11 MEDIA MASTER 8 GBA 2 PLUGMOLD R 20A/1P 20A/1P R COMP SERV 4 REC 14 13 MEDIA TRANS 1 & 2 PLUGMOLD EQ 20A/1P 20A/1P R COMP SERV 5 REC 16 15 MEDIA TRANS 3, 4 & 5 EQ 20A/1P 20A/1P R COMP SERV 5 REC 18 17 MEDIA TRANS 6 & 7 EQ 20A/1P 20A/1P R COMP SERV 6 REC 20 19 MEDIA TRANS 8 & 9 EQ 20A/1P 20A/1P EQ COMP SERV 7 REC 22 21 TELECOM SW 1 EQ 20A/1P 20A/1P EQ COMP SERV 7 SHUNT TRIP 24 23 TELECOM SW 1 EQ 20A/1P 20A/1P R COMP LAB 1 REC 26 25 BLADES EQ 20A/1P 20A/1P R COMP LAB 1 REC 28 27 RECEPTACLES R 20A/1P 20A/1P R COMP LAB 2 REC 30 29 SPARE 20A/1P 20A/1P R COMP LAB 2 REC 32 31 SPARE 20A/1P 20A/1P R COMP LAB 3 REC 34 33 BLADES 20A/1P R COMP LAB 4 REC 36 35 - 20A/1P R COMP LAB 5 REC 38 37 BLADES 20A/1P R COMP LAB 6 REC 40 39 - 20A/1P R COMP LAB 6 REC 42 41 DESCRIPTION # N N # DESCRIPTION EQ 30A/2P - - EQ 30A/2P - - PHASE A 500 PHASE B PHASE C 500 200 500 1000 500 800 500 200 500 1000 800 1150 540 200 500 200 180 800 500 200 500 360 360 1000 800 1440 300 400 250 1000 360 1000 360 500 TOTAL CONNECTED LOAD AMPS 79.62 221.0 R COMP LAB 7 REC 2 20A/1P R COMP LAB 7 REC 4 20A/1P R COMP LAB 7 REC 6 20A/1P R COMP LAB 8 REC 8 20A/1P R COMP LAB 8 REC 10 20A/1P R COMP LAB 8 REC 12 20A/1P R COMP LAB 9 REC 14 20A/1P R MEDIA DIST 1A PLUGMOLD 16 20A/1P R MEDIA DIST 1B PLUGMOLD 18 20A/1P R MEDIA DIST 1C PLUGMOLD 20 20A/1P R MEDIA DIST 2A PLUGMOLD 22 20A/1P R MEDIA DIST 2B PLUGMOLD 24 20A/1P R MEDIA DIST 2C PLUGMOLD 26 20A/1P R MEDIA DIST 3 & 4A REC 28 20A/1P R MEDIA DIST 4B & 4C REC 30 20A/1P R MEDIA DIST 5 REC 32 20A/1P COMP NET 34 20A/1P COMP NET 36 80A/3P SPARE 38 500 20A/1P - - - 40 - - - 42 VA FEED-THRU PANEL 2W1Cc PHASE LOAD 15200 18700 7280 22410 VA TOTAL CONNECTED PHASE LOAD 21130 25100 15350 VA 186.8 AMPS 176.1 209.2 127.9 AMPS TOTAL CONNECTED LOAD VA KVA AMPS 61.58 170.9 -4.78 -13.3 56.80 157.7 * ALL LOADS ARE EXISTING U.O.N. * FEED-THRU LUGS LONG CONTINUOUS LOADS * 25% LARGEST MOTOR LOAD * 25% LARGEST MOTOR LOAD * 25% (RECEPTACLE LOADS - 10KVA) * 50% -13.56 (RECEPTACLE LOADS - 10KVA) * 50% -37.6 KITCHEN LOADS * 0% KITCHEN LOADS * 0% TOTAL LOAD 66.06 TOTAL LOAD 183.4 2W1Cc UCCS GENERATOR GW1 M-E ENGINEERS, INC. UCCS GENERATOR LOCATION: TELECOM RM 208Y/120V, 3PH-4W+GND LOCATION: MAIN ELEC RM 480Y/277V, 3PH-4W+GND MOUNTING: SURFACE MLO MOUNTING: SURFACE 400A MCB RATING: 10K AIC 400A BUS RATING: 35K AIC DESCRIPTION TYPE BRKR R 20A/1P PHASE A VA BRKR TYPE 60A/3P EQ 40A/2P - - - 1 MACHINE ROOM 3 SPARE 5 - - 7 MACHINE ROOM R 20A/1P 9 MACHINE ROOM R 20A/1P 11 MACHINE ROOM R PHASE B PHASE C 1080 1080 360 500 800 N # DESCRIPTION TYPE BRKR LT 20A/1P LTG MACHINE RM LT 20A/1P 3KVA TRANSFORMER EQ 20A/1P 7 CRAC-1 EQ 60A/3P 10 9 - - - SIMPLEX PANEL 12 11 - POWER POLE 14 13 CRAC-2 POWER POLE 16 SPACE 1 LTG MACHINE RM - - 4 3 - - 6 5 20A/1P R LOBBY MEDIA REC 8 20A/1P EQ CLOCK TOWER CHIME CAB 20A/1P EQ 20A/1P EQ 20A/1P EQ - 15 - - - 18 17 - - - SPACE 20 19 SPARE 20A/1P 21 SPACE SPACE 22 21 SPARE 20A/1P 23 SPACE SPACE 24 23 SPARE 20A/1P 25 SPACE SPACE 26 25 SPARE 20A/1P 27 SPACE SPACE 28 29 SPACE SPACE 31 SPACE - 400 N 2 60A/3P 100A/2P 1080 # - 15 - 20A/1P DESCRIPTION SURGE SUPPRESSOR EQ 13 UPS SYSTEM 5800 - 5800 17 SPACE 19 MACHINE ROOM R 20A/1P 1080 33 SPACE 5800 35 SPACE 5800 39 SPARE 41 - 100A/2P EQ - - 100A/2P EQ - - 5800 37 SPACE 50A/2P - 5800 - TOTAL CONNECTED PHASE LOAD M-E ENGINEERS, INC. 400A BUS VA # 15200 18700 7280 VA 126.7 155.8 60.7 AMPS PHASE A PHASE B PHASE C 1840 KVA AMPS 41.18 114.3 2080 15430 15430 2 SPARE 4 LT LTG STUDIO A116 6 15A/3P M CU-1 8 - - - 10 - - - 12 M CU-2 14 - - - 16 - - - 18 20A/1P SPARE 20 20A/1P SPARE 22 JACKET WATER HEATER 24 - 26 27 SPACE SPACE 28 30 29 SPACE SPACE 30 SPACE 32 31 SPACE SPACE 32 UPS SYSTEM 34 33 SPACE SPACE 34 - 36 35 SPACE SPACE 36 UPS SYSTEM 38 37 2W1CA P 125A/3P SPACE 38 - 40 39 - - - SPACE 40 SPACE 42 41 - - - SPACE 42 15430 1142 1142 15430 1142 15430 1142 3210 20A/2P EQ - - 3210 28514 28695 22410 66708 63919 62448 VA 240.8 230.8 225.4 AMPS * ALL LOADS ARE EXISTING U.O.N. TOTAL CONNECTED LOAD KVA AMPS 193.08 232.2 1.7 LARGEST MOTOR LOAD * 25% LARGEST MOTOR LOAD * 25% 0.86 1.0 (RECEPTACLE LOADS - 10KVA) * 50% (RECEPTACLE LOADS - 10KVA) * 50% -13.56 -16.3 181.81 218.7 KITCHEN LOADS * 0% 114.3 # 15A/3P TOTAL CONNECTED PHASE LOAD 15430 DESCRIPTION SPARE 20A/1P 1142 1.44 41.18 1848 1142 LONG CONTINUOUS LOADS * 25% TOTAL LOAD TYPE 20A/1P 1836 LONG CONTINUOUS LOADS * 25% KITCHEN LOADS * 0% BRKR 20A/1P OPTIONS: TOTAL CONNECTED LOAD N OPTIONS: * ALL LOADS ARE EXISTING U.O.N. * FEED-THRU LUGS LONG CONTINUOUS LOADS * 25% N # TYPE OPTIONS: KVA DESCRIPTION BRKR 20A/1P TOTAL LOAD N ” GENERAL NOTES 11'-1" ± 3 S100 METAL CAP FLASHING NEW EXTERIOR PAVING BY OWNER BOND BM. W/ 2 - #5 CONT. CHAIN LINK FENCE AND GATE - SEE 2/S100 #5 AT 16" FULL HT. 8" MAS. WALL EXIST. CONC. FTG. BRICK VENEER TYPES AND BANDING TO MATCH EXIST. COORDINATE W/ OWNER NEW GENERATOR SEE MECH. AND ELECT. DWGS. 2 S100 #4x2'-6"+3'-6" AT 12" O.C. 3" CLR. 8" 27'-0" CONC. SLAB - TOP OF SLAB EL. = 100'-0" #5 AT 16" O.C. W/ HOOK INTO FTG. TOE 2 - #5 TOP AND BOT. #4 AT 18" O.C. VERT. 5 - #5 TOP - CONT. 3 - #5 BOT. - CONT. #5 AT 16" O.C. 3'-0" THICKENED EDGE OF CONC. SLAB SEE DETAILS CLR. COORD. W/ EQUIP. MANUF. #4 AT 16" O.C. HORIZ. EA. FACE #5 CONT. UNDER LEDGE 5'-3" ± 100'-0" 3" CLR. 1'-10" 1'-0" EXIST. TREE TO REMAIN - TAKE PRECAUTIONS TO NOT DAMAGE TREE DURING CONSTRUCTION 2'-2" 1 1/2"=1'-0" S100 94'-0" 1 96'-0" S100 12'-0" NORTH GENERATOR - SEE PLAN - CONNECT TO SLAB PER MANUFACTURER'S RECOMMENDATIONS 3'-6" (TYP.) EXIST. SCREEN WALL __'-__" 3'-0" CLR. CHAIN LINK FENCE AND POSTS BY CONTRACTOR 2" CLR. FINISHED GRADE VARIES EXIST. WEEP/DRAIN HOLE IS BELOW TOP OF SLAB 2 LOC. #4 AT 12" O.C. EA. WAY 2 - #5 TOP AND BOT. 1 1/2" CLR. MATCH ELEVATION AT EAST EDGE OF SLAB 2 1 8" 1/2"=1'-0" S100 EXIST. BRICK VENEER EXIST. CONC. RETAINING WALL EXIST. PAVING 3" CLR. 1 CONNECT NEW PVC PIPE TO WEEP/DRAIN HOLE AND DAYLIGHT AT SOUTH WALL - SEE 1/S100 (SLOPE 1/4" / FT. MIN.) 2 1'-0" 8" CONC. SLAB INDICATES TOP OF WALL ELEVATION. INDICATES TOP OF FOOTING ELEVATION. #4 #13 #3 #10 #5 #6 #19 #16 #7 #22 #8 #25 #9 #29 #10 #32 #11 #36 8. See sheet S200 for concrete specifications. TYPICAL MINIMUM REINFORCING BAR LAP LENGTHS In inches. Use for normal weight concrete f'c = 4500 psi, unless noted otherwise. BAR SIZE #3 #4 #5 #6 #7 #8 #9 #10 #11 TOP BARS Non-staggered 25 33 41 49 71 81 91 102 114 Staggered 19 25 31 37 54 62 70 79 87 OTHER BARS Non-staggered 19 25 31 37 54 62 70 79 87 Staggered 15 19 24 29 42 48 54 61 67 "Top Bars" are any horizontal reinforcing bars so placed that more than 12" of fresh concrete is cast in the member below the splice. #4 AT 12" O.C. (TYP.) 2 6" BRICK LEDGE - SEE 1/S100 IT EMERGENCY GENERATOR FOUNDATION / SCREEN WALL PLAN __'-__" English Metric 1'-0" FDN. WALL 1/4" = 1'-0" 4 1/2" TO EDGE OF POST 1. Material and workmanship shall be in accordance with the requirements of "Building Code Requirements for Structural Concrete" (ACI 318-08). 2. All concrete shall have a minimum cementitious materials content of 470 lbs. per cubic yard unless otherwise specified. 3. Bar bending details and placing drawings shall be in accordance with the "Manual of Standard Practice for Detailing Reinforced Concrete Structures" (ACI 315, latest edition). 4. Provide bar supports and spacers to place all bars in proper location, and wire adequately at intersections to hold bars firmly in position while concrete is placed. Vertical dowels shall be supported in place prior to placing concrete. 5. Bar supports and spacers which rest on or against exposed surface shall be hot dipped galvanized or plastic coated. 6. Continuous bars shall lap and dowels shall project adequately to provide a Class B splice but not less than 12 inches unless shown otherwise on the drawings. Do not splice near maximum stress locations. 7. Reinforcing bar sizes shown are english designation. The bars may be furnished with the following equivalent metric markings: "Staggered" laps are laps located such that no more than half of the total reinforcement is spliced within the lap length. MASONRY GENERAL NOTES 1. Grout shall be proportioned by volume and shall have sufficient water added to produce consistency for pouring without segregation. Grout shall be composed of one part Portland cement to which may be added not more than one-tenth part hydrated lime or lime putty, and two and one fourth to three parts sand. 2. Reinforcing steel shall conform to ASTM A-615, Grade 60 or ASTM A-706. 3. Reinforcing bars shall be lapped 48 bar diameters minimum when spliced. All vertical bar lengths to be 4'-8" plus required lap. 4. When a foundation dowel does not line up with the vertical core to be reinforced, it shall not be bent over, but shall be grouted into a core in direct vertical alignment, even though it is in an adjacent cell to the vertical wall reinforcing. 5. Vertical reinforcing bars shall be held in position at top and bottom. All debris and projecting mortar shall be cleaned out before pouring grout. 6. Vertical cells to be filled shall have vertical alignment to maintain a continuous unobstructed cell area not less than 2" x 3". 7. Cells containing reinforcing shall be solidly filled with grout in pours not to exceed 4'-8" and pours shall be stopped 1-1/2" below the top of a course to form a key at pour joints. 8. Grout shall be consolidated by mechanical vibration during placing before lossof plasticity in a manner to fill grout space. Grout pours greater than 12 inches shall be reconsolidated by mechanical vibration to minimize voids due to water loss. Grout pours 12 inches or less in height shall be mechanically vibrated, or puddle. 9. Mortar for all exterior walls and bearing walls shall be Type S. 10. Specified Compressive Strength, f'm, of concrete masonry shall be 1500 psi at the age of 28 days. 11. Brick masonry units minimum f'm shall be 1500 psi. 12. All concrete block below grade shall be grouted solid. 13. See specifications for horizontal joint reinforcing and other masonry reinforcing not shown on structural drawings. 14. Masonry design is based on full allowable design stresses. 15. See sheet S201 for masonry specifications. 2'-6" SPECIAL INSPECTION GENERAL NOTES #4 AT 12" O.C. 1. A statement of special inspections for structural items has been prepared by HCDA Engineering, Inc. for submittal to the Building Official. This was submitted as a condition for permit issuance in accordance with the Structural Testing and Special Inspection requirements of the International Building Code, 2012 edition. 2. The Structural Engineer will perform periodic observations of construction. These observations shall not replace required inspections by the Building Official. These observations also do not serve as "Special Inspections" as required by section 1704 of the International Building Code. 3. Steel Fabricators shall be approved in accordance with IBC section 1704.2.2 of the International Building Code, 2012 Edition, or are required to have shop inspections of the fabricated items for the project by the special inspector hired by the Owner as required by section 1704.2. #5 TOP AND BOT. 3" CLR. (FIELD VERIFY) 8" 1'-6" MIN. #4 AT 12" O.C. EA. WAY JOB NO.: 3 S100 1/2"=1'-0" DESIGN LOADS Active Soil Pressure 35 pcf University of Colorado Colorado Springs 1420 Austin Bluffs Parkway Colorado Springs, CO 80918 1 1/2" CLR. TYP. 3'-0" 3" CLR. 4'-0" 8" CONCRETE GENERAL NOTES 1'-0" (VERIFY IN FIELD) 2" CLR. 4" BRICK LEDGE 2'-0" MIN. NEW PVC CONNECTED TO EXIST. WEEP/DRAIN HOLE SEE 2/S100 2 - #5 TOP AND BOT. 2 1 1. Recommendations for foundation type and design criteria, including bearing pressures, were provided by "Consultation, Generator Pad Construction, Engineering and Applied Science Building, University of Colorado Colorado Springs, Colorado Springs, Colorado", dated November 27, 2015, by CTL/Thompson, Inc., a separate consultant to the Owner. 2. Maximum bearing pressure used in footing design: 1,500 psf. 3. All footings shall bear on solid undisturbed soil or on approved compacted fill. 5. The geotechnical engineer shall perform an open excavation inspection prior to placing foundations to ensure the bearing capacity is satisfactory. 6. In case conditions found at the site vary from those indicated on the drawings, the Architect is to be notified so that adjustments to the foundation can be made to meet actual field conditions. 8. No footings or foundation wall shall be placed without adequate notification to allow Engineer to observe reinforcing if he deems necessary. 9. No concrete shall be placed in excavation containing water or on frozen ground. 10. Backfill shall be placed against both sides of walls simultaneously. Walls with uneven backfill shall be backfilled evenly until the grade on the lower side of the wall is reached before continuing with backfill operations. EL POMAR IT EMERGENCY GENERATOR #5x6'-0" DOWELS AT 16" O.C. (PROJECT 3'-0") FOUNDATION GENERAL NOTES 12'-8" ± 9'-0" TOP OF EXISTING WALL EL. = 109'-0"± COORD. W/ EQUIP. MANUF. CLR 3'-0" EXISTING SITE RETAINING / SCREEN WALL AT EAST SIDE OF ENGINEERNG AND APPLIED SCIENCE BUILDING 1. Material and workmanship shall be in accordance with the requirements of "The International Building Code", 2012 Edition. 2. Contractor shall field measure and verify all existing conditions and dimensions at job site. 3. In case existing conditions or dimensions vary from those shown on drawing, Contractor shall notify the Engineer so proper adjustments can be made. 4. Where the Structural Drawings appear to conflict with OSHA requirements, the Structural Drawings represent final conditions only; the contractor shall shore existing walls and new excavations as may be necessary to comply with OSHA. 5. Take all necessary precautions to avoid existing utilities during excavation, shoring, and construction. DATE: 15194 12/16/2015 DRAWN: JEB, DJH CHECKED: ABB SCALE: AS NOTED REVISIONS: SHEET # S100 SECTION 03 20 00 CONCRETE REINFORCEMENT SECTION 03 30 00 CAST-IN-PLACE CONCRETE (cont'd) SECTION 03 30 00 CAST-IN-PLACE CONCRETE (cont'd) PART 1 - GENERAL PART 2 - PRODUCTS 3.02 A. 1.01 SUMMARY A. Section Includes: Concrete Reinforcement 2.01 A. 1.01 1.02 1.03 REFERENCE STANDARDS Design and construction shall follow recommendations of ACI 301. QUALITY ASSURANCE Contractor shall assume all responsibility for the strength and safety of the formwork. Provide necessary design, construction, materials and maintenance to produce the required concrete work safely. ENVIRONMENTAL REQUIREMENTS Contractor shall take special precautions to protect and keep finished interior concrete slab and blotter layer beneath slab dry until installation of finished floor. 1.02 A. SUBMITTALS Submit shop drawings. Show size, configuration, pertinent dimensions, number, exact position, and spacing of reinforcement and the exact location of all openings, framing, or special conditions affecting the work. 1.03 A. QUALITY ASSURANCE Reference Standards: 1. Detailing, fabrication, and placement: Follow ACI 301, 315 and 318, latest editions, unless otherwise noted herein or on the drawings. 2. Bar Bending Details and Placing Drawings: In accordance with the "Manual of Standard Practice for Detailing Reinforced Concrete Structures" (ACI 315, latest edition). PART 2 - PRODUCTS 2.01 A. FORMWORK MATERIALS Plywood, steel, or dressed lumber. 2.02 A. FORMWORK ACCESSORIES Form Ties: Adjustable in length to permit tightening of forms and of such type to leave no metal closer than 1" to the surface nor holes or depressions larger than 7/8" in diameter. B. 2.03 A. Clamps, Brackets, Braces, Washers, Wedges, Walers, Etc.: Contractor's option. MISCELLANEOUS MATERIALS Form Oil: Non-staining. Contractor's option. 1.04 B. DELIVERY, STORAGE AND HANDLING Unload and store reinforcing bars so they will be kept free of mud. Store on timber skids while awaiting use. PART 2 - PRODUCTS 2.01 A. MATERIALS Reinforcing Bars: Conform to Structural General Notes on the drawings. B. Bar Supports and Spacers: Contractor's option. Refer to Structural General Notes on the drawings. PART 3 - EXECUTION C. Tie Wire: No. 14 or No. 16 gauge, black, soft iron wire. 3.01 A. D. Welded Wire Fabric: Conform to ASTM A185. Welded wire fabric shall be supplied in flat sheets. Refer to individual specification Sections and drawings for size and gauge of fabric. 2.02 A. MATERIALS Concrete Materials: 1. General: Use ready-mixed concrete conforming with ASTM C94. No on-job mixed concrete will be allowed. 2. Cement: Conform to ASTM C150, Type I / II Cement. 3. Aggregates: Fine aggregate (natural sand) and coarse aggregate (gravel or crushed stone), shall conform to ASTM C33. Maximum coarse aggregate size shall be as indicated in mix design. 4. Air Entraining Agent: Conform to ASTM C260. 5. Chemical Admixtures: Conform to ASTM C494. 6. Mineral Admixtures: Conform to ASTM C618. Miscellaneous Materials: 1. Curing Compound: Conform to ASTM C309, Type 1. Ensure compatibility of proposed curing compound with any finish or treatment to be applied to concrete surface. 2. Floor Sealer at Non-Colored Concrete: a. BASF Kure-N-Harden b. US Spec Industraseal c. or approved substitute 3. Polyethylene Sheeting: 6 mil minimum thickness, White color. MIXES Design: Conform to Structural General Notes on the drawings. Proportion ingredients for mixes in accordance with ACI 301, Section 4.2.3. Obtain this information in accordance with the latest ASTM Specifications. Should a special mix be required due to structural requirements, weather, or materials, the Contractor shall submit samples of cement and aggregate to be used to an approved testing laboratory. At the expense of the Owner, the testing laboratory will make an analysis of the materials and design the proper mix to be used. B. Patching: Patch voids, form tie holes, honeycombs, or damaged areas in accordance with the ACI Standard 301, Section 5. Cut out large defective areas a minimum of one (1) inch deep, and patch as specified. Add white cement to patching grout as required to match color of existing concrete where patches are exposed to view. Patch tie holes. C. Laitance: Remove deposits of laitance occurring on the top of the concrete surfaces as soon as the concrete has hardened sufficiently to prevent injury to the concrete. Repair areas where laitance is removed as specified in Article 3.02 Paragraph B. D. Unexposed Concrete Surfaces: Treat surfaces of concrete wall, slabs, beams, and columns, which are to be covered by subsequent work, as specified in Article 3.02 Paragraph B. Below grade unexposed concrete surfaces to be coated with fluid applied waterproofing shall be filled to the extent required by the manufacturer of the waterproofing material. E. Exposed Concrete Surfaces: Concrete surfaces, both interior and exterior, to remain exposed shall be carefully protected from damage and soiling during the progress of the work. Patch where required as specified in Article 3.02 Paragraph B. Upon completion of the work, any damaged or soiled surface shall be recleaned as required. At the discretion of the Owner, exposed concrete surfaces may be ordered to be "sack rubbed" if formed surfaces are not satisfactory in appearance, at no additional cost to the Owner. 3.03 A. B. B. C. D. 3.02 PLACEMENT Walls, Footings: The use of earth as a form will not be allowed unless specifically detailed on drawings. Lap forming with dressed lumber or plywood will not be allowed. Forms shall conform to shape, lines and dimensions of the members shown on the drawings and shall be substantial and sufficiently tight to prevent leakage of concrete. Properly brace or tie to maintain position, shape, and lateral stability, and provide sufficient strength to carry construction operations and material dead loads without deflection or vibration. Forms shall be designed to be capable of needed adjustments and shall be carefully watched as work proceeds with all faults promptly corrected. Where finished concrete is to remain exposed, joints shall be regularly spaced and held to a minimum both horizontally and vertically. Provide access panels in formwork for cleanout or pouring as required. Install voids where indicated. Rustication Joints, Molding or Bevels: Securely nail within the forms using finish nails. All exposed exterior corners of concrete, including top of foundation walls, shall be chamfered 3/4" unless otherwise indicated. PART 3 - EXECUTION 3.01 3.02 A. B. EXAMINATION Provide 48 hours minimum notice to the Engineer to allow observation of concrete reinforcement before placing concrete. PLACEMENT Bending: Bend reinforcement cold. Bars shall be full length as required and accurately bent according to details. Bars shall be bent only once. No bar partially embedded in concrete shall be field bent except as shown on the drawings or specifically permitted by the Engineer. Tolerances: Conform to placing tolerance specifications of ACI 301. Construction Joints: Use construction joints at temporary stopping of concrete placement or as shown on the drawings. Submit to the Engineer for approval, the locations of desired construction joints. Leave joints in reinforced structural members rough and provide longitudinal or vertical keys at least 1-1/2" deep. 1. Install continuous waterstop between pours wherever exterior grade is above interior finish floor level or crawlspace floor. a. Waterstop field splices shall be heat fused welded using a Teflon covered thermostatically controlled waterstop splicing iron at approximately 380 degrees F. Follow approved waterstop manufacturer recommendations. Lapping of waterstop, use of adhesives, or solvents shall not be allowed. 3.03 WELDED WIRE FABRIC Lay welded wire fabric continuously, with edges and ends overlapping adjoining sheets a minimum of one full mesh plus 2", tied and placed over all piping and conduit. Properly support the fabric by chairs or other approved methods to the center of all the slabs during the depositing of concrete. Where required, construct bulkheads at construction joints and screeds to place the fabric in the proper position. 3.04 CLEANING Clean reinforcement prior to placing concrete to remove scale, oil, ice, or other coatings that will destroy or reduce the bond, including concrete from previous concrete placements. Anchors, Inserts, Blockouts, and Built-In Items: Anchor bolts, inserts, form blockouts and other items built into the concrete shall be securely fastened to formwork or held in place with templates. Insertion into concrete after placement will not be allowed. 3.05 FORM COATING Coat the surface of formwork prior to concrete placement. Apply coating in strict accordance with manufacturer's directions. Apply coating prior to the placing of the reinforcement. Promptly remove any excess coating material. SECTION 03 10 00 CONCRETE FORMS AND ACCESSORIES 3.03 A. FORM REMOVAL Remove forms in such a manner as to ensure the complete safety of the structure. Forms in general may be removed from vertical surfaces after 24 hours from time of placing and from horizontal surfaces 72 hours from time of concrete placement. 3.04 REUSE Clean reusable form material prior to construction of forms. No form material will be acceptable for reuse if, in the opinion of the Owner, it will not produce a finished surface required by these Specifications. B. FIELD QUALITY CONTROL Special Inspection of reinforcement shall be performed if required by the Building Official. This inspection shall be performed by an approved special inspector selected and paid for by the Owner. Admixtures: 1. General: No admixtures will be allowed except as specified herein, unless authorized by the Engineer. All requests for approval or substitution must be made by the Contractor and be accompanied by sufficient information and test data for evaluation. No calcium chloride, thyocyanates, or admixtures containing more than 0.05 percent chloride ions shall be added to concrete. 2. Acceptable Manufacturers: Admixtures shall be approved by the Engineer and supplied by one of the following manufacturers: a. Master Builders b. Cormix Construction Chemicals c. Sika d. Euclid e. W. R. Grace f. Degussa g. US Spec 3. Accelerating Admixtures: Do not use unless authorized by the Engineer. Conform to ASTM C494, Type C or E. Dosage shall be per manufacturer's recommendations. 4. Water Reducing and Retarding Admixtures: Do not use unless authorized by the Engineer. Conform to ASTM C494, Type A or D. Dosage shall be per manufacturer's recommendations and as set forth in approved mix designs. 5. Fly ash as a substitute for cement will be permitted in mix designs, unless otherwise noted. Fly ash shall conform to ASTM C618, Class C or F. Substitution of fly ash for cement shall not exceed twenty (20) percent of total cementitious materials by weight where permitted in mix design. Minimum replacement factor shall be 1 to 1. C. Chloride Ion Content: The maximum water soluble chloride ion concentration in the concrete mix shall not exceed 0.15 percent by weight of cement. D. Slump: Design mix to provide slumps indicated under mix type at placement. Concrete to be placed by pumping shall have a maximum slump as specified at the end of the hose. E. Mixing: Ready-mixed concrete shall conform to provisions of ASTM C94. 2.03 PART 1 - GENERAL 1.01 SUMMARY Section Includes: Cast-in-Place Concrete 1.02 A. REFERENCES Reference Standards: Follow American Concrete Institute (ACI) Standards 301, 305R, 306R, 308R and 309, latest edition, except as modified by these specifications. 1.03 A. SUBMITTALS Quality Control Submittals: 1. Mix Designs: Prior to placing concrete, the Contractor shall submit concrete mixes to the Engineer for approval. Separate mix designs shall be submitted for each application of concrete to be used in the project. Submittals shall include all information used in designing the mixes. See Article 2.02 for design procedures. 2. Test Reports: Reports of control tests, special tests or core tests specified under Article 3.09 shall be distributed by the testing laboratory as listed under Section 01 45 00. END OF SECTION 03100-1 1.04 A. QUALITY ASSURANCE Design Criteria: See Article 2.02. B. Testing Agency: Testing shall be done by an approved testing laboratory selected and paid by the Owner. 1.05 A. DELIVERY, STORAGE AND HANDLING Hauling Time: Discharge concrete transmitted in a truck mixer, agitator or other transportation device within 1-1/2 hours after the mixing water has been added to the cement and aggregate. B. Additional Water: Deliver concrete to the job in exact quantities required by the design mix. Should additional water be required before placing the concrete, the Contractor shall have sole authority to authorize the addition of water. Any added water shall not exceed the maximum water / cement ratio or maximum slump of the approved mix design and, under no circumstance shall more than one half gallon per yard be added. Any additional water added to the mix after leaving the batch plant shall be indicated on the truck ticket and signed by the Contractor. Where extra water is added to the concrete it shall be mixed thoroughly for 40 revolutions of the drum or 3-1/2 minutes at mixing speed, whichever is greater. 1.06 A. PROJECT CONDITIONS Protection: Protect newly finished concrete from rain or hail damage. Cover adjacent masonry walls, glazing, and other finish materials with polyethylene sheeting or otherwise protect from damage due to placing of concrete slabs or sidewalks. A. CONCRETE MIX TYPES General: Water reducing admixtures shall be used in mix designs as indicated and shall be optional for mixes not specifically noted. Mix designs shall be identified by the mix identification letter indicated below. Concrete shall have a minimum cementitious material content of 470 lbs. per cubic yard unless noted otherwise. Mix A - For footings, foundation walls, and concrete slabs. 4500 psi Type I / II Cement 3/4" maximum aggregate size 6% plus or minus 1-1/2% entrained air 4" maximum slump Maximum Water / Cement Ratio of 0.45 in this mix. Fly Ash may be substituted in specified amounts in this mix. PART 3 - EXECUTION 3.01 A. CONCRETE PLACEMENT Placement: Place concrete in approximately uniform horizontal layers not over two (2) feet in height. Piling up of the concrete in the forms or chuting in such a manner to separate the aggregates will not be permitted. B. The recommendations of ACI 301, Section 5, shall be followed for placing concrete into forms. No concrete shall be dropped over four (4) feet. Accumulations of water on the surface of the concrete due to water gain, segregation, or other causes, during placement or consolidation, shall be prevented as far as possible by adjustments in the mixture. Provision shall be made for removal of such water as may accumulate. C. Consolidation: Consolidate concrete during and immediately after placement by means of mechanical vibrators. Supplement by hand spading at corners and angles of the forms, around embedded fixtures, and in other difficult areas. Mechanical vibrator to cycle at 10,000 cycles per minute or more. Use and type of vibrators shall conform to ACI 309, "Recommended Practice for Consolidation of Concrete". CURING AND PROTECTION General: Protect exposed surfaces of concrete from premature drying and frost. Protect freshly placed concrete from rain and rapid drying. Adhere to special conditions as specified under Article 1.06. Protection: Protect concrete surfaces from staining, cracking, chipping and other damage during progress of work. Leave concrete in good condition upon completion. 3.04 A. FIELD QUALITY CONTROL General: Testing shall be done by an approved testing laboratory, selected and paid for by the Owner. Contractor shall make additional slump tests as required to maintain specified slump for each mix design. B. Tests: (the following are guidelines for testing paid by the Owner and as recommended to be performed by the Contractor.) 1. Test Priority: Control tests shall be used to determine the concrete quality throughout the project; however, special tests have precedence over control tests, and core tests shall have precedence over all previous tests. Reports of tests shall be distributed to the owner and engineer. 2. Slump Tests: In addition to the Owner's testing, the Contractor shall provide necessary equipment and make tests in conformity with ASTM C143 as frequently as required to ensure specified slump for each mix design. The tests shall be made by a person thoroughly familiar with the requirements specified. Should the slump not comply with the limits stated in Article 2.03, the batch shall be rejected. The Contractor shall keep an accurate record of the time, location in the work, and the results of slump tests, which shall be available for inspection by the Owner and the Engineer. 3. Control Tests: Control tests of concrete work shall be made on every fifty (50) cubic yards or fraction thereof of concrete placed. In any case, a minimum of once during each day's pour. Samples shall be taken only after any extra water has been added and thoroughly mixed. Each test shall consist of six standard six (6) inch test cylinders cast and cured in accordance with ASTM C31 and ASTM C172. Two (2) cylinders shall be broken at the end of seven (7) days after placing, two (2) cylinders shall be broken at the end of 28 days after placing, and the remaining two cylinders shall be stored until their disposition is determined by the Engineer. In general, the two (2) remaining cylinders will be broken only when the previous test reports indicated unsatisfactory results. When the 7 or 28 day tests indicate unsatisfactory results, all concrete work may be stopped until proper corrective measures have been taken to insure quality concrete in future work and all corrections deemed necessary have been made. Tests shall be made at the time control tests are taken and so stated in the reports to determine the slump, air content, unit weight, and temperature of the concrete. All tests shall be made in accordance with ASTM C143, C173 or C231, C138, and C1064 respectively. C. Special Inspection: Special Inspection of Structural Concrete Construction shall be performed if required by the Building Official. This inspection shall be performed by an approved special inspector selected and paid for by the Owner. END OF SECTION 03200-2 SECTION 03 30 00 CAST-IN-PLACE CONCRETE TREATMENT OF FORMED SURFACES Form Removal: Finish concrete surfaces covered by formwork immediately after forms have been removed. Do not expose more surface area than can be finished in one working day. END OF SECTION 03300-4 JOB NO.: University of Colorado Colorado Springs 1420 Austin Bluffs Parkway Colorado Springs, CO 80918 PART 1 - GENERAL EL POMAR IT EMERGENCY GENERATOR SECTION 03 10 00 CONCRETE FORMS AND ACCESSORIES DATE: 15194 12/16/2015 DRAWN: JEB CHECKED: ABB SCALE: AS NOTED REVISIONS: SHEET # S200 SECTION 04 10 00 MORTAR AND MASONRY GROUT SECTION 04 15 00 PART 1 - GENERAL PART 1 - GENERAL PART 1 - GENERAL 1.01 SUMMARY A. Section Includes: Mortar and Grout for Unit Masonry. 1.01 SUMMARY A. Section Includes: 1. Wall Ties and Reinforcing 2. Weep Hole Materials 3. Control Joints 4. Masonry Flashing 5. Column Isolation Material 1.01 SUMMARY A. Section Includes: 1. Sample Masonry Panels 2. Reinforced Unit Masonry 3. Integrally Colored Regular Face Block Masonry 4. Integrally Colored Split Face Block Masonry 5. Ground Face Block 1.02 1.02 MASONRY ACCESSORIES SECTION 04 20 00 UNIT MASONRY SECTION 04 20 00 UNIT MASONRY PART 2 - PRODUCTS 2.01 QUALITY ASSURANCE Tests Reports: Reports of quality control tests will be distributed by the testing laboratory. 1.03 DELIVERY, STORAGE AND HANDLING Store accessories off the ground and under cover. PART 2 - PRODUCTS PART 2 - PRODUCTS 2.01 MATERIALS A. Portland Cement: Conform to ASTM C150, Type I. Masonry cement not allowed. 2.01 WALL TIES AND REINFORCING A. Acceptable Manufacturers: 1. Dur-O-Wal, Inc. 2. Hohmann & Barnard, Inc. 3. approved substitute B. Hydrated Lime: Conform to ASTM C207, Type N. REFERENCES Reference Standards: Comply with listed recommendations of the following: 1. ASTM 2. Brick Institute of America 3. National Concrete Masonry Association 1.03 SUBMITTALS A. Samples: Immediately after start of construction of the project, submit CMU color samples to match the existing building for selection. Cut and deliver samples of selected exterior wall masonry units to the Owner for preparation of color sample boards. Samples shall be 4” x 8” and shall be cut to 1/2" thickness. Provide and deliver a single cut sample of each type of integrally colored and ground face block. Manufacturer shall not make exterior masonry units until samples have been approved by Owner. C. Aggregates for Mortar: Conform to ASTM C144. D. Water: Potable and free from deleterious amounts of acids, alkalies, or organic materials. E. Aggregates for Grout: Conform to ASTM C404. B. Finishes: Hot-dipped per ASTM A153 - Class B 2 (1.50 oz. / sq. ft.) at exterior walls. All others regular mill galvanized per ASTM A641. C. Horizontal Reinforcing: Dur-O-Wal or equivalent of other acceptable manufacturer. Use prefabricated corners and tees. Type as follows: Single Wythe Walls: D/A 320 Ladur Type F. Accelerators and Antifreeze Compounds: Not permitted. G. Other Admixtures: Only with permission of Engineer. 2.02 MIXES A. Mortar: Type S containing Type I Portland cement, hydrated lime, and aggregate in the proportions, by volume, specified in ASTM C270 and IBC Table 2103.8. The use of accelerators or antifreezes will not be permitted. Hydrated lime in excess of the proportionate amount specified in ASTM C270 will not be allowed regardless of the compressive strength developed by the mix. B. Site-Mixed Grout for Masonry: 1. Proportion by volume with sufficient water added to produce consistency for pouring without segregation. 2. Coarse Grout: Coarse grout may be used only in grout spaces in brick masonry 2" or more in horizontal dimension and grout spaces in filled-cell construction 3" or more in both horizontal dimensions. Coarse grout shall be composed of one part Portland cement with not more than one-tenth part hydrated lime or lime putty added, and two to three parts sand, and not more than two parts gravel. 3. Fine Grout: Use fine grout in all locations where coarse grout may not be used. Fine grout shall be composed of one part Portland cement, with not more than one-tenth part hydrated lime or lime putty added, and two and one-fourth to three parts sand. 4. Grout shall attain a minimum strength at 28 days of 2,000 psi. D. Dovetail Anchors: Dur-O-Wal D/A 720-724 3/16" diameter. Size for 2" minimum embedment in horizontal mortar joint. Provide D/A 100 22 gauge dovetail anchor slots for anchors. E. Masonry Veneer Wall Ties: Size for 2" minimum embedment in mortar. Fasten with corrosion resistant self-tapping screws. 2.03 2.04 MASONRY FLASHING Dur-O-Wal DCF 1501B composite thru-wall flashing with 2” wide D/A 1502 flashing tape and non-butyl mastic. PREPARATION All equipment for mixing, transportation, and placing mortar shall be cleaned before starting work. B. Pre-Construction Masonry Prisms: Prior to start of construction, a set of six (6) masonry prisms shall be constructed in one continuous operation and tested in accordance with ASTM C1314, Method B. Prism shall be constructed by single mason from single batch of materials and under the observation of a representative of the Testing Agency. Testing Agency shall divide prisms into one set of five (5) prisms and one set of three (3) prisms. Materials, workmanship, mortar bedding, joint thickness, and tooling for prisms shall conform to this Specification. Prisms shall contain no masonry grout. 3.01 WALL TIES AND REINFORCING A. Block Walls: Reinforce by use of horizontal steel reinforcement placed continuously in every second horizontal block course or 16” maximum on center vertically Use preformed corners and tees at corners and intersections (except at control or expansion joints),. lapped minimum of 6". B. Mixing: Mix Cementitious materials and aggregate for at least three (3) minutes and not more than five (5) minutes in a mechanical batch mixer, with the minimum amount of water to produce a workable consistency. 3.03 FIELD QUALITY CONTROL 1. Compressive strength shall be sampled and tested in accordance with ASTM C1019. 2. Testing Agency: Grout tests will be conducted by a testing laboratory selected and paid by the Owner. 3. Test Specimens: Take grout samples as grout is being placed into the wall. Construct three (3) test specimens in accordance with ASTM C1019 under the observation of the testing agency. Cure, protect, and store specimens on-site for 48 hours. Protect from freezing and variations in temperature until collected by testing agency. 4. Frequency: Minimum of one (1) sample consisting of three (3) specimens shall be built and tested for each 5,000 square feet of wall area as masonry construction progresses. 3.03 WEEP HOLES AND MASONRY FLASHING Install cotton rope weep material 24” on center horizontally. Rope shall project 1/4" past face of veneer. Lay ropes full depth of veneer course and lay excess length of rope in cavity parallel with veneer. Install flashing below weep holes in mortar bed, beginning 1/2" back from face of masonry extending minimum of 8" up face of gypsum sheathing or other backing. Tape top edge of flashing with flashing tape at gypsum sheathing; set top edge of flashing in mortar joint at masonry backing. CONTROL JOINTS Provide control joints in masonry walls where indicated on the drawings. Joints shall be installed completely through and full height of masonry unless indicated otherwise. Horizontal reinforcing shall not continue across control joints. Extend control joints through bond beams. Bond beam reinforcing shall continue through control joint. Keep the control joint face free of mortar by using a continuous wood strip (3/8" x 3/4" deep) temporarily set in the wall. Control joints shall receive caulking. END OF SECTION END OF SECTION Lay masonry plumb and true to lines to the tolerances indicated. Provide full mortar joints. Mortar beds shall be spread smooth or only slightly furrowed. In laying masonry, avoid adjustment to units after being set in position. Where an adjustment must be made after the mortar has started to harden, remove mortar and replace with fresh mortar. Where cutting of units is necessary, make cuts with a motor-driven masonry saw. Joints shall be plumb or level. Tool joints in interior or exterior masonry work, which is to be left exposed, with a round tool to a depth as directed to make a smooth and concave joint. Use 100% solid units wherever cores of hollow units would be exposed to view or weather. Use finished ends wherever ends of block are exposed to view. B. Masonry Veneer: Where masonry veneer occurs over masonry walls, bond veneer to backing with masonry veneer ties located and installed as indicated in Section 04 15 00. C. Built-in Members: Sleeves of proper size shall be provided to permit passage of pipes though walls. Build in wall sleeves, anchors, plates, lintels and other steel members. Built-in members shall be properly set in masonry courses as walls progress. D. Reinforced Masonry: Where indicated on the drawings, reinforce block cores or cavities with deformed steel reinforcing bars and grout as indicated. Reinforced hollow unit masonry shall be built to preserve the unobstructed vertical continuity of the cells to be filled. Maintain a clear, unobstructed vertical opening area measuring not less than 2" x 3". Hold vertical reinforcement in position at top and bottom and at intervals not exceeding 192 bar diameters. Testing Agency shall cure and test prisms in accordance with ASTM C1314, Method B. The set of three (3) prisms shall be tested at the age of seven (7) days. The second set of three (3) prisms shall be tested at the age of 28 days. Testing Agency's report, prepared in accordance with ASTM C1314, shall include relationship between average 7 day strength and average 28 day strength of the prism sets, which is to be used for evaluating prism tests during construction. If average strength of prisms tested at 28 days is less than specified compressive strength of masonry (f'm), the masonry materials proposed for use in the structure will be rejected, and the Contractor shall submit alternate materials for approval by the owner that the Contractor believes will achieve specified f'm strength. If accepted by the owner, new prism sets shall be constructed using the alternate materials and prism testing process shall be repeated at the Contractor's expense. Masonry flashing shall occur over openings in exterior masonry walls, over exterior masonry bond beams, and at the bottom or sill of exterior masonry walls. Lap and apply mastic over end joints in flashing. Where masonry meets another wall system or vertical reinforcement in grouted cell, form an end dam by turning flashing up at least 6”. Lap and apply mastic over area and seal to end masonry units. Keep wall cavity free of mortar droppings to keep weep pathways open. C. Retempering: Mortars that have stiffened because of evaporation of water from the mortar shall be retempered by adding water as frequently as needed to restore required consistency. Mortar shall be used within 2-1/2 hours after initial mixing. 3.03 INSTALLATION A. General: Unless indicated otherwise on the drawings, lay masonry units one-half running bond. Adjust masonry dimensions as required to eliminate small cuts and to maintain one-half bond. Prism thickness shall be same thickness of concrete block most commonly used for exterior walls, bearing walls, and shear walls in the structure. Height of prisms shall be at least twice the thickness, contain at least two mortar joints, and be minimum 15 inches high. If directed by Testing Agency, top and bottom courses of prisms shall be cut block to limit prism height to 15 inches. B. Masonry over Concrete: Anchor masonry occurring against concrete by use of dovetailed anchors inserted in dovetail anchor slots built into the concrete. Space anchors 16" on center vertically and 24" on center horizontally. 3.02 MORTAR MEASUREMENT AND MIXING A. Measurement: Method of measuring materials shall be by either volume or weight and such that specified proportions can be controlled and accurately maintained. PREPARATION Surface Preparation: Remove dirt, ice, loose rust and scale from walls, ties and reinforcing prior to installation. The sample panels shall be constructed, cleaned, allowed to cure, and water repellent and graffiti control coating applied prior to owner's approval. PART 3 - EXECUTION 3.02 3.02 Include in base bid, the cost to construct a maximum of two (2) masonry sample panels, if required by the owner. PART 3 - EXECUTION 3.01 EXAMINATION Verification of Conditions: Before beginning work, inspect foundations or other bearing surfaces for proper grades and elevations, freedom from dirt and other foreign material. 1.04 QUALITY ASSURANCE A. Mock Ups: Furnish materials specified in quantity sufficient to construct a minimum 6' x 6' sample exterior masonry wall panel including types of masonry units if directed by the owner. Make such modifications as necessary to achieve panels satisfactory to the owner. The panel shall be erected at a location on the site to be designated by the owner and shall be maintained by the Contractor until ordered removed. WEEP HOLE MATERIAL 3/8" diameter by 12” long cotton rope. CONTROL JOINTS 3/8" thick non-asphaltic fiberboard. 3.01 B. Quality Control Submittals: 1. Test Reports: Reports of masonry prism tests shall be distributed by the testing laboratory. 2. Certificates: Furnish manufacturer's certification and test results indicating that masonry units meet specified ASTM requirements. F. Reinforcing Steel: Furnished under Section 03 20 00. 2.02 PART 3 - EXECUTION Masonry construction shall not begin before prism test results are received from testing laboratory verifying the specified compressive strength of masonry. Compressive strength f'm, of concrete masonry shall be minimum 1,500 psi at age of 28 days. 1.05 DELIVERY, STORAGE AND HANDLING Inspect masonry units upon delivery and handle carefully to avoid chipping and breakage. Store on pallets until ready for use. Cover and protect against wetting prior to use, allowing air circulation under stacked units. Do not store near masonry cutting operations. 1.06 JOB CONDITIONS A. Environmental Requirements: 1. Cold Weather Protection During Installation: a. Preparation: Before beginning work, remove ice or snow formed on masonry bed by carefully applying heat until top surface is dry to touch. Remove frozen or damaged masonry. b. Air Temperature 40 degrees F. to 25 degrees F.: Heat sand or mixing water to minimum of 70 degrees F. and maximum of 160 degrees F. c. Air Temperature 25 degrees F. to 20 degrees F.: Heat sand and mixing water to minimum of 70 degrees F. and maximum of 160 degrees F. Use salamander or other sources of heat on both sides of walls under construction. Use windbreaks when wind is in excess of 15 mph. d. Air temperature 20 degrees F. and Below: Heat sand and mixing water to minimum of 70 degrees F. and maximum of 160 degrees F. Provide enclosure and auxiliary heat to maintain air temperature above 32 degrees F. Temperature of units when laid shall be not less than 20 degrees F. e. Grout: Place grout in masonry at a minimum temperature of 70 degrees F. and a maximum temperature of 120 degrees F. Maintain grouted masonry above 32 degrees F. for 24 hours following placement of grout. f. Admixtures: No mortar admixtures will be permitted without the written approval of the owner. g. Frozen Work: The above paragraphs are designed to permit masonry work to continue during periods of cold temperature. Any frozen masonry work will be prima facie evidence that the above requirements have not been complied with. The Contractor shall be required to remove and replace all frozen materials as directed by the owner. 2. Cold Weather Protection After Installation: a. Mean Daily Air Temperature 40 degrees F. to 25 degrees F.: Cover and protect masonry from rain or snow for 24 hours. b. Mean Daily Air Temperature 25 degrees F. to 20 degrees F.: Cover masonry completely with insulating blankets for 24 hours. c. Mean Daily Air Temperature 20 degrees F. and below: Maintain masonry temperature above 32 degrees F. for 24 hours by enclosure and supplementary heat, by electric heating blankets, infra-red heat lamps or other approved method. 3. Hot Weather Protection During Installation: When air temperature exceeds 99 degrees F. in the shade, protect freshly laid masonry from direct exposure to wind and sun. 4. Moisture Protection During Installation: Where exposed to weather, the top of masonry walls shall be covered at the end of each day's work using a waterproof material weighted down to ensure its remaining in place. Maintain such protection until final capping of the wall. B. Protection of Completed Work From Physical Damage: Protect projecting masonry susceptible to damage after setting by suitable planking well supported. Jambs and sill of openings used for passage shall be securely boxed. Replace masonry work showing damage or disfiguration during the progress of work in its entirety. No patching or hiding of defects will be permitted. Fill cells containing reinforcement solidly with grout. Pour grout in lifts of 4' maximum. Consolidate grout at time of pouring by mechanical vibration. Reconsolidate by mechanical vibration to minimize voids due to water loss. When the grouting is stopped for one hour or longer, stop pouring of grout 1-1/2" below the top of the uppermost unit. E. Allowable Tolerances: 1. Maximum variation from plumb: a. In lines and surfaces of columns, walls, and arises: 1) 1/4" in 10' 2) 3/8" in any story or 20' maximum 3) 1/2" in 40' b. For external corners, expansion joints and other conspicuous lines: 1) 1/4" in any story or 20' maximum 2) 1/2" in 40' 2. Maximum variation from level or grades for exposed lintels, sills, parapets, horizontal grooves, and other conspicuous lines: a. 1/4" in any bay or 20' b. 1/2" in 40' 3. Maximum variation of linear building line from an established position in plan and related portions of columns, walls and partitions: a. 1/2" in any bay or 20' maximum b. 3/4" in 40' F. Cutting and Patching: Cutting and patching of masonry shall be done by mason at his own expense wherever necessary for other trades. Such work shall be done by experienced mechanics. No cutting and patching shall be done which will injure the strength or appearance of finished work. No cutting of finished masonry for the purpose of building-in members will be allowed. 3.04 FIELD QUALITY CONTROL A. General: Compressive strength of masonry shall be tested in accordance with ASTM C1314. B. Testing Agency: preconstruction prism tests will be conducted by a testing laboratory selected and paid by the Owner. C. Additional special inspection requirements can be found in the Statement of Special Inspections. 3.05 POINTING AND CLEANING A. Cut out defective joints and holes in exposed masonry and repoint with mortar. Take care to match color of exposed joints in masonry, which will not be painted or otherwise covered. B. Final Cleaning of Masonry: 1. Clean mortar, dirt and construction film from masonry using stiff brush and water when mortar is at least 7 days and not more than 14 days old. 2. Remove efflorescence or other stain in accordance with masonry unit manufacturer's recommendations. 3.06 FINAL CLEANING DEVIATIONS FOR MASONRY AND DECORATIVE FACED BLOCK A. Deviations from final cleaning methods specified in Article 3.05 must be requested in writing and approved by the Owner prior to starting masonry work. Should the use of commercial brick cleaners be requested, the written request must be accompanied by the following information: 1. Description of cleaning solution proposed, including manufacturer's name, descriptive literature, and dilution ratio. 2. Description of cleaning procedure proposed including wetting of walls as required to prevent chemical penetration into masonry. 3. Written approval from the masonry unit manufacturer. Statement to include same information required for this Article. 4. Statement from mason assuming responsibility for any deleterious effects to masonry or mortar, such as staining, darkening or fading of masonry units or mortar color, caused as a result of use of proposed products or methods of application. University of Colorado Colorado Springs 1420 Austin Bluffs Parkway Colorado Springs, CO 80918 1.03 SUBMITTALS Submit manufacturer's product data for each component and material required plainly identified. A. Standard Gray Smooth-Face Block: 1. Weight: Lightweight block conforming to ASTM C90. 2. Classification: Type 1. 3. Nominal Size: 8" high x 16" long x width as shown on drawings. 4. Minimum Net Compressive Strength: 2,200 psi. 5. Acceptable Manufacturers: Cla-Lite, McKinney Concrete Products, Inc., Valley Block Co., Best Block Co., or approved substitute. EL POMAR IT EMERGENCY GENERATOR 1.02 SUBMITTALS A. Mortar Mix Design: Submit five (5) copies of design mix including cement tests and aggregate tests results for Engineer's review. All tests must be done with material to be used on this project. Design charts or graphs prepared for other projects will not be accepted. Submit mortar and / or grout cube compression tests if requested by Engineer. If premixed cement and lime are proposed, submit full product data or mix proportions. MASONRY UNITS B. No high pressure cleaning of brick or decorative faced block will be permitted. Pressure to be 100 psi maximum. C. Muriatic Acid will not be permitted. 3.07 AREA CLEAN-UP Upon completion of pointing and cleaning, leave the work area and surrounding surfaces clean and free of mortar spots, droppings, and broken masonry. JOB NO.: DATE: 15194 12/16/2015 DRAWN: JEB CHECKED: ABB SCALE: AS NOTED REVISIONS: END OF SECTION SHEET # S201