GENERAL NOTES
PACK ANNULAR
SPACE WITH
MINERAL WOOL
WALL
ESCUTCHEON
PIPE
WALL
ESCUTCHEON
SKYLIGHT
5’−0"
ROOF
2.
THE ARCHITECTURAL BACKGROUND PROVIDED ON THESE SHEETS IS FOR GENERAL REFERENCE ONLY. CONTRACTOR SHALL
VERIFY ALL BACKGROUNDS WITH ARCHITECTURAL SHEETS AND SITE VISIT.
3.
SYSTEM DESIGN TO BE PER NFPA−13, 2010 EDITION AND THESE DRAWINGS AND SPECIFICATIONS.
4.
CONTRACTOR SHALL OBTAIN SIGNED OWNER’S CERTIFICATE AS PER NFPA−13 AND SPECIFICATIONS.
5.
REFER TO SPECIFICATIONS SECTION 21 1300 FOR ADDITIONAL INFORMATION REGARDING THE FIRE PROTECTION SYSTEM.
6.
SEE PROJECT SPECIFICATIONS FOR SYSTEM TESTING REQUIREMENTS (HYDROSTATIC, TRIP TESTING ETC.).
9777 Pyramid Court, Suite 200
7. PIPING:
7.1.
SPRINKLER CONTRACTOR SHALL COORDINATE LOCATION OF ALL PIPING AND SPRINKLERS WITH OTHER TRADES, HVAC
SYSTEMS IN PARTICULAR. COORDINATION SHALL OCCUR DURING DESIGN AND LAYOUT, AS WELL AS IN THE FIELD.
7.2.
SPRINKLER PIPING SHALL BE ROUGHED−IN PRIOR TO OR CONCURRENTLY WITH THE INSTALLATION OF MAJOR DUCTWORK.
INSTALLATION OF SPRINKLERS BELOW OBSTRUCTING DUCTWORK MAY OCCUR LATER.
7.3.
SIZING AND ACTUAL ROUTING OF ALL NEW SPRINKLER SYSTEM PIPING IS THE RESPONSIBILITY OF THE CONTRACTOR AND
SUBJECT TO APPROVAL BY THE ENGINEER.
7.4.
WET SYSTEM PIPING AND FITTINGS SHALL MEET THE REQUIREMENTS OF NFPA−13, EXCEPT THAT PRESS−FIT AND POZ−LOK
SYSTEMS ARE NOT APPROVED FOR THIS PROJECT.
7.5.
ALL PIPING 4 INCH AND LARGER TO BE SCHEDULE 40 STEEL; ALL PIPING 3 INCH AND SMALLER TO BE CPVC EXCEPT AS NOTED
BELOW:
7.5.1. ALL EXPOSED PIPING TO BE SCHEDULE 40 STEEL.
7.5.2. ALL LOCATIONS NOT LISTED FOR CPVC SHALL BE SCHEDULE 40 STEEL.
7.5.3. WHERE SUNLIGHT, CHEMICALS, OR PHYSICAL ABUSE COULD BE EXPECTED, ONLY SCHEDULE 40 STEEL PIPE SHALL BE USED.
7.6.
PIPING PENETRATIONS THROUGH RATED WALLS SHALL BE SEALED IN ACCORDANCE WITH SPECIFICATIONS (SEE ALSO DETAIL
3/F100).
7.7.
PAINTING OF PIPE TO BE BY DIVISION 9.
NOTE:
HOLES THROUGH WALLS SHALL BE A MINIMUM OF 1 IN. LARGER, AND MAXIMUM
OF 2 IN. LARGER IN DIAMETER THAN THE OUTSIDE DIAMETER OF THE PIPE
PASSING THRU THE RATED WALL. THIS SPACE SHALL BE FILLED WITH MINERAL
WOOL AND SEALED WITH AN APPROVED LISTED FIRE CAULK OR SEALANT. ALL
PENETRATIONS OF FIRE RATED WALLS AND ASSEMBLIES SHALL BE UL LISTED
FOR THAT PURPOSE, FOR BOTH THE TYPE OF PIPE MATERIAL AND WALL OR
CEILING/FLOOR CONSTRUCTION. LISTED ALTERNATE METHODS WILL BE
ACCEPTED.
GYP BOARD
STEEL STUD
CEILING SPACE
THIS PROJECT INCLUDES THE DESIGN AND PROVISION OF A NEW WET−PIPE SPRINKLER SYSTEM THROUGHOUT THE
UNSPRINKLERED PORTIONS OF THE BUILDING INDICATED ON THE FOLLOWING DRAWINGS.
Englewood, CO 80112
Phone: 720.873.5700
Fax: 720.873.5701
Web: www.ulteig.com
8. HANGERS:
8.1.
HANGERS, HANGER RODS, CLAMPS, AND INSERTS SHALL BE IN ACCORDANCE WITH NFPA−13, 2010 EDITION.
8.2.
CPVC HANGERS SHALL BE IN ACCORDANCE WITH MANUFACTURER’S GUIDELINES. SEE DETAIL 4/F100.
8.3.
TRAPEZE−STYLE HANGING ASSEMBLIES MAY BE USED, BUT ONLY WITH DOCUMENTATION ON THE SHOP DRAWINGS VALIDATING
THE SIZING OF THE TRAPEZE MEMBERS. WHEN A TRAPEZE MEMBER IS NOT EXPLICITLY LISTED IN NFPA−13 (E.G. UNISTRUT),
DOCUMENTATION MUST BE PROVIDED THAT INDICATES ADEQUATE SECTION MODULUS AND OTHER PERTINENT PARAMETERS
ARE BEING MET.
CEILING SPACE
LIGHT COVE
9. SPRINKLERS:
9.1.
PROTECTION OF SPRINKLERS DURING PAINTING, AND REMOVAL THEREAFTER, SHALL BE BY DIVISION 9.
9.2.
UNLESS INDICATED OTHERWISE, ALL AUTOMATIC SPRINKLERS LOCATED WITHIN SUSPENDED TILE CEILINGS SHALL BE CHROME,
RECESSED TO MATCH EXISTING SPRINKLERS. UNLESS OTHERWISE NOTED, REMAINING EXPOSED SPRINKLERS SHALL BE
BRASS. SEE SPRINKLER LEGEND FOR SPRINKLER TYPE DETAILS.
9.3.
SPRINKLERS SHALL BE LOCATED IN THE CENTER OF TILE. SEE DETAIL 2/F100.
9.4.
HEAD GUARDS LISTED FOR USE WITH THE RESPECTIVE SPRINKLERS SHALL BE INSTALLED ANYWHERE EXPOSED SPRINKLERS
ARE LOCATED BELOW 7’−0" AFF.
9.5.
ELECTRICAL AND MECHANICAL ROOMS SHALL UTILIZE INTERMEDIATE TEMPERATURE RATED SPRINKLERS.
GRID CEILING
10. WATER SUPPLY DATA: CONTRACTOR SHALL BASE HYDRAULIC CALCULATIONS ON THE FOLLOWING WATER SUPPLY INFORMATION:
10.1. STATIC: 160 PSI
RESIDUAL: 150 PSI
FLOWING: 1186 GPM
10.2.
TEST CONDUCTED BY : WESTERN STATES FIRE PROTECTION
DATE: 06/04/10
10.3. EFFECTIVE POINT: WHERE 6 INCH UNDERGROUND CONNECTS TO 8 INCH UNDERGROUND MAIN. SEE SITE PLAN 1/F100.
10.4. HOSE ALLOWANCES SHALL BE TAKEN AT THIS SAME EFFECTIVE POINT.
12"
12"
12"
24"
48"
2x4 TILES
FIRE PROTECTION SYMBOLS LEGEND
LOCATE SPRINKLER AT CENTER OR 12 INCHES
FROM THE TWO ADJACENT GRID LINES
POST- INSTALLED
ANCHOR
6"
12"
University Hall
Fire Sprinkler System Upgrade
CONCRETE
FLOOR SLAB
RISER
VERTICAL PIPE
6"
EXISTING SPRINKLER PIPING
USER\PW: REED.ROISUM\M4500-3755 O:\PROJECTS\2010\10.01833\2.0 PROJECT EXECUTION\2.2 DESIGN - ENGINEERING\DRAWINGS\10.01833 F100.DWG 28 FEB 2011 - 3:52PM
XREFS:
12"
6"
NEW SPRINKLER PIPING
24"
CONCRETE
TEE
24"
UNDERGROUND WATER MAIN PIPING
CLIP
ANGLE
CAP
6"
ALL THREAD
ROD
POST- INSTALLED
ANCHOR
24"
24"
2x2
BLANK TILES
2x2
SCORED TILES
LOCATE SPRINKLER AT
CENTER OF TILE
PIPE BREAK
LOCATE SPRINKLER
6 INCHES FROM
TWO GRID LINES
OH1
ORDINARY HAZARD GROUP I AREA
OH2
ORDINARY HAZARD GROUP II AREA
1
FIRE DEPARTMENT CONNECTION
(FLUSH TYPE)
ALL THREAD
ROD
HANGER
RING
HANGER
RING
PIPE
PLAN NOTE
FIRE DEPARTMENT CONNECTION
(SIAMESE TYPE)
PIPE
BACKFLOW TEST OUTLET
UNDERGROUND GATE VALVE
HYDRANT
NOTE:
ALL ANCHORS AND HANGERS TO BE LISTED FOR
USE IN CONCRETE IN ACCORDANCE WITH NFPA 13,
2010 EDITION.
EXISTING REMOTE YARD FDC
CHECK VALVE
BUTTERFLY CONTROL VALVE
FLOW TEST INFO:
STATIC: 160 PSI
RESIDUAL: 150 PSI
FLOWING: 1186 GPM
CEILING HEIGHT ABOVE FINISHED FLOOR
EXISTING HYDRANT
ELEVATION = 92’−0"
EXISTING HYDRANT
EFFECTIVE POINT
DESIGN NOTES:
SEE TABLE BELOW FOR NUMBER
OH2
EXISTING 8 IN. UG
WATER MAIN
OF HANGERS REQUIRED
APPROX. 60 FT OF
EXISTING 6 IN. UG
WATER MAIN
EXISTING
GATE VALVE
ASTM F442 CPVC
BRANCHLINE *
FLOOR ELEVATION @
SPRINKLER CONTROLS = 72’−0"
EXISTING GATE VALVE
1. ALL AREAS WITH THIS SYMBOL:
SHALL BE DESIGNED
TO ORDINARY HAZARD GROUP II PARAMETERS AS PER
NFPA−13.
3955 CRAGWOOD DRIVE, COLORADO SPRINGS, COLORADO 80907
2’−6"
SEAL WITH
APPROVED FIRE
CAULKING (SEE
SPECIFICATIONS)
1.
OH1
EXISTING REMOTE YARD FDC
2. ALL AREAS WITH THIS SYMBOL:
SHALL BE DESIGNED
TO ORDINARY HAZARD GROUP I PARAMETERS AS PER
NFPA−13.
3. ALL AREAS WITH THIS SYMBOL: SP1 SHALL BE DESIGNED
TO FLOW 20 SPRINKLERS OR ENTIRE ROOM WITH
MINIMUM END HEAD PRESSURE OF 7 PSI. SPRINKLERS TO
BE 11.2K.
4. ALL REMAINING AREAS TO BE DESIGNED TO LIGHT
HAZARD PARAMETERS PER NFPA−13.
5. ALL HYDRAULIC CALCULATIONS SHALL INCLUDE A
MINIMUM 10 PSI SAFETY FACTOR.
6. IN ACCORDANCE WITH FM GLOBAL GUIDELINES, AREA
REDUCTIONS FOR QUICK RESPONSE SPRINKLERS, AND
"SMALL ROOM RULE", SHALL NOT BE USED.
MINIMUM ALLOWABLE HANGERS
PER LENGTH OF CPVC PIPE
PIPE SIZE
inches
1 Hanger
Pipe Length
2 Hangers
3 Hangers
1"
0’−0" TO 6’−0"
6’−1" TO 12’−0"
12’−1" TO 18’−0"
1¼"
0’−0" TO 6’−6"
6’−7" TO 13’−0"
13’−1" TO 19’−6"
1½"
0’−0" TO 7’−0"
7’−1" TO 14’−0"
14’−1" TO 21’−0"
2"
0’−0" TO 8’−0"
8’−1" TO 16’−0"
16’−1" TO 24’−0"
2½"
0’−0" TO 9’−0"
9’−1" TO 18’−0"
18’−1" TO 27’−0"
3"
0’−0" TO 10’−0"
10’−1" TO 20’−0"
20’−1" TO 30’−0"
c COPYRIGHT RTA, INC.
SHEET TITLE
SITE PLAN −
DETAILS − FIRE PRO
* NSF INTERNATIONAL APPROVED FOR USE WITH POTABLE WATER
RTA PROJECT NUMBER
UEI PROJECT NUMBER
10070.00
10.01833
DATE
NOTE:
THE MAXIMUM DISTANCE BETWEEN HANGERS FOR LISTED NONMETALLIC PIPE SHALL BE
MODIFIED AS SPECIFIED IN THE INDIVIDUAL PRODUCT LISTINGS.
02-28-11
REVISION
DRAWN BY:
0’
25’
50’
100’
CHECKED BY:
RAR
MAS
ISSUED FOR:
BID SET
SHEET NO.
F100
SPRINKLER LEGEND
SYMB.
MFR.
PLAN NOTES
THD TEMP.
SZ
RTG.
TYPE
ESCUT.
FINISH
VK302
5.6
QUICK
RECESSED PENDANT
1
2"
155°
CHROME
CHROME
VIKING
VK302
5.6
QUICK
RECESSED PENDANT
1
2"
200°
CHROME
CHROME
VIKING
VK462
5.6
QUICK
FLAT CONCEALED PENDANT − "MIRAGE"
1
2"
200°
BRASS
BRUSHED
BRASS
VIKING
VK300
5.6
QUICK
UPRIGHT
1
2"
200°
BRASS
N/A
VIKING
VK531
11.2
QUICK
UPRIGHT
3
155°
BRASS
N/A
VIKING
VK305
5.6
QUICK
HORIZONTAL SIDEWALL
1
2"
155°
BRASS
N/A
155°
CHROME
CHROME
4
"
VIKING
VK305
5.6
QUICK
RECESSED HORIZONTAL SIDEWALL
1
2"
VIKING
VK305
5.6
QUICK
RECESSED HORIZONTAL SIDEWALL
1
2"
200°
CHROME
CHROME
VIKING
VK606
8.0
QUICK
EXTENDED COVERAGE REC. HORIZ. SIDEWALL
3
155°
CHROME
CHROME
4"
13
#
1.
PROVIDE AND INSTALL HORIZONTAL SIDEWALL SPRINKLER UNDER OPEN GARAGE
DOOR.
2.
PROVIDE INTERMEDIATE OR HIGH TEMPERATURE RATED SPRINKLERS NEAR UNIT
HEATER BASED ON NFPA 13 GUIDELINES.
3.
PROVIDE AND INSTALL INTERMEDIATE TEMPERATURE RATED BRASS UPRIGHT
SPRINKLERS IN SKYLIGHTS. SEE 6/F100 FOR DETAILS.
4.
PROVIDE AND INSTALL INTERMEDIATE TEMPERATURE HORIZONTAL SIDEWALL
SPRINKLER POINTING DOWN THE SLOPE IN THE APPROXIMATE LOCATION SHOWN.
PIPING TO BE ROUTED AS HIGH AND TIGHT TO WALL AS POSSIBLE. ALL EXPOSED
PIPING TO BE SCHEDULE 40 STEEL IN THIS AREA.
5.
PROVIDE AND INSTALL INTERMEDIATE TEMPERATURE RATED CONCEALED
SPRINKLER WITH BRUSHED BRASS COVER PLATE IN DISPLAY CASE AS SHOWN.
6.
PROVIDE AND INSTALL INTERMEDIATE TEMPERATURE RATED RECESSED PENDANT
SPRINKLER IN APPROXIMATE LOCATION SHOWN. SPRINKLER PROTECTION NOT
REQUIRED IN SKYLIGHT.
7.
PROVIDE AND INSTALL EXTENDED COVERAGE RECESSED HORIZONTAL SIDEWALL
SPRINKLER IN APPROXIMATE LOCATION SHOWN. FINISH AND ESCUTCHEON FINISH
TO BE CHROME.
8.
NO WORK IN THIS AREA. EXISTING SPRINKLERS.
9.
PROVIDE AND INSTALL INTERMEDIATE TEMPERATURE HORIZONTAL SIDEWALL
SPRINKLER POINTING DOWN THE SLOPE IN THE APPROXIMATE LOCATION SHOWN.
ALL EXPOSED PIPING TO BE SCHEDULE 40 STEEL IN THIS AREA.
10. ROUTE LEVEL 2 FEED MAIN DOWN IN CHASE IN THIS APPROXIMATE LOCATION.
OH2
OH2
SP1
SP1
SPRNK
FINISH
VIKING
13
13
K
S.I.N.
RSPNS
NO. FCTR
INSPECTOR’S
TEST OUTLET
1
11. NOT USED.
12. NO SPRINKLER PROTECTION REQUIRED BELOW NON−COMBUSTIBLE EXTERIOR
OVERHANG.
13
19 SOUTH TEJON ST., SUITE 300
COLORADO SPRINGS, CO. 80903
TELE.: 719−471−7566 FAX: 719−471−1174
www.rtaarchitects.com
9777 Pyramid Court, Suite 200
Englewood, CO 80112
Phone: 720.873.5700
Fax: 720.873.5701
Web: www.ulteig.com
13. CPVC PIPING NOT ALLOWED IN OR ABOVE THIS ROOM.
2
14. COORDINATE CROSS MAIN ROUTING WITH EXISTING CONDITIONS.
13
15. PROVIDE AND INSTALL CONCEALED SPRINKLER WITH BRUSHED BRASS COVER
PLATE AS SHOWN.
13
16. NO SPRINKLER PROTECTION REQUIRED WITHIN CEILING POCKET.
13
SP1
13
13
13
OH2
OH1
1
OH2
OH1
SP1
OH1
OH1
OH1
OH2
13
13
13
OH1
14
OH2
OH2
DESIGN NOTES:
OH2
OH2
1. ALL AREAS WITH THIS SYMBOL:
SHALL BE DESIGNED
TO ORDINARY HAZARD GROUP II PARAMETERS AS PER
NFPA−13.
EXISTING HOSE
CONNECTION
OH1
2. ALL AREAS WITH THIS SYMBOL:
SHALL BE DESIGNED
TO ORDINARY HAZARD GROUP I PARAMETERS AS PER
NFPA−13.
3
3
OH1
University Hall
Fire Sprinkler System Upgrade
3. ALL AREAS WITH THIS SYMBOL: SP1 SHALL BE DESIGNED
TO FLOW 20 SPRINKLERS OR ENTIRE ROOM WITH
MINIMUM END HEAD PRESSURE OF 7 PSI. SPRINKLERS TO
BE 11.2K.
OH2
4. ALL REMAINING AREAS TO BE DESIGNED TO LIGHT
HAZARD PARAMETERS PER NFPA−13.
5. ALL HYDRAULIC CALCULATIONS SHALL INCLUDE A
MINIMUM 10 PSI SAFETY FACTOR.
16
USER\PW: REED.ROISUM\M4500-3755 O:\PROJECTS\2010\10.01833\2.0 PROJECT EXECUTION\2.2 DESIGN - ENGINEERING\DRAWINGS\10.01833 F110.DWG 28 FEB 2011 - 3:47PM
XREFS:
6. IN ACCORDANCE WITH FM GLOBAL GUIDELINES, AREA
REDUCTIONS FOR QUICK RESPONSE SPRINKLERS, AND
"SMALL ROOM RULE", SHALL NOT BE USED.
16
remove
head??
3
3
OH2
OH2
12
3
3955 CRAGWOOD DRIVE, COLORADO SPRINGS, COLORADO 80907
3
16
9
16
OH1
14
15
THIS LEVEL
FEED MAIN
LEVEL 2
FEED MAIN
LEVEL 2
FEED MAIN
16
16
LEVEL 2
FEED MAIN
16
c COPYRIGHT RTA, INC.
12
5
4
10
4
4
4
12
7
7
SHEET TITLE
PARTIAL MAIN LEVEL
7
DN TO LEVEL 2
FLOOR PLAN
16
FIRE PROTECTION
5
RTA PROJECT NUMBER
UEI PROJECT NUMBER
10070.00
10.01833
DATE
16
02-28-11
6
REVISION
12
LEVEL 2
FEED MAIN
12
5
16
DRAWN BY:
12
CHECKED BY:
OH2
RAR
MAS
OH2
UNIVERSITY HALL BUILDING
ISSUED FOR:
BID SET
0’
KEY PLAN
N.T.S.
4’
8’
16’
SHEET NO.
NORTH
SEE 1/F120 FOR CONTINUATION
F110
SPRINKLER LEGEND
SYMB.
2
SEE SITE PLAN 1/F100
FOR CONTINUATION
1
EXISTING 6 IN. UG
WATER MAIN
ROUTE FEED MAIN
UP TO LEVEL 2
MFR.
S.I.N.
K
RSPNS
NO. FCTR
THD TEMP.
SZ
RTG.
TYPE
ESCUT.
FINISH
SPRNK
FINISH
VIKING
VK302
5.6
QUICK
RECESSED PENDANT
1
2"
155°
CHROME
CHROME
VIKING
VK302
5.6
QUICK
RECESSED PENDANT
1
2"
200°
CHROME
CHROME
VIKING
VK462
5.6
QUICK
FLAT CONCEALED PENDANT − "MIRAGE"
1
2"
200°
BRASS
BRUSHED
BRASS
VIKING
VK300
5.6
QUICK
UPRIGHT
1
2"
200°
BRASS
N/A
3
VIKING
VK531
11.2
QUICK
UPRIGHT
155°
BRASS
N/A
VIKING
VK305
5.6
QUICK
HORIZONTAL SIDEWALL
1
2"
155°
BRASS
N/A
VIKING
VK305
5.6
QUICK
RECESSED HORIZONTAL SIDEWALL
1
2"
155°
CHROME
CHROME
VIKING
VK305
5.6
QUICK
RECESSED HORIZONTAL SIDEWALL
1
2"
200°
CHROME
CHROME
3
155°
CHROME
CHROME
VIKING
VK606
8.0
QUICK
EXTENDED COVERAGE REC. HORIZ. SIDEWALL
ALL ROOMS WITHIN THIS PORTION
OF THE FLOOR PROVIDED WITH
EXISTING SPRINKLER PROTECTION.
PLAN NOTES
4
"
4"
19 SOUTH TEJON ST., SUITE 300
COLORADO SPRINGS, CO. 80903
TELE.: 719−471−7566 FAX: 719−471−1174
www.rtaarchitects.com
#
1.
SPRINKLER CONTROLS. SEE DETAIL 2/F200.
2.
PROVIDE AND INSTALL (2) NEW SPARE HEAD CABINETS. ONE 12
HEAD SPARE CABINET TO HOLD THE REQUIRED SPARE
SPRINKLERS AND ONE (6) HEAD CABINET TO HOUSE SPARE
COVER PLATES AS SPECIFIED.
3.
PROVIDE HORIZONTAL SIDEWALL SPRINKLER IN ELEVATOR PIT
LOCATED NO MORE THAN 2 FT UP FROM PIT FLOOR. PROVIDE
FLOW SWITCH WITH VALVE ABOVE CEILING, OUTSIDE ELEVATOR
SHAFT. ROUTE TEST/DRAIN PIPING TO EXTERIOR WALL AND
OUT. PROVIDE SPLASH BLOCK AT EXTERIOR.
4.
NO SPRINKLERS OR SPRINKLER PIPING ALLOWED IN ELEVATOR
EQUIPMENT ROOM.
5.
PROVIDE AND INSTALL INTERMEDIATE TEMPERATURE RATED
CONCEALED SPRINKLER WITH BRUSHED BRASS COVER PLATE
IN DISPLAY CASE AS SHOWN.
6.
LEVEL 2 FLOOR CONTROLS LOCATED ABOVE CEILING. SEE
3/F200 FOR DETAILS.
7.
ROUTE DRAIN PIPING TO EXTERIOR WALL IN APPROXIMATE
LOCATION SHOWN. PROVIDE SPLASH BLOCK AT EXTERIOR.
8.
NO WORK IN THIS AREA. EXISTING SPRINKLERS.
9.
FEED MAIN FROM LEVEL 1. ROUTE MAIN ABOVE CEILING TO
FLOOR CONTROLS LOCATION SHOWN.
9777 Pyramid Court, Suite 200
Englewood, CO 80112
Phone: 720.873.5700
Fax: 720.873.5701
Web: www.ulteig.com
10. FEED MAIN UP FROM LEVEL 2.
0’
4’
8’
16’
11. LEVEL 1 FLOOR CONTROLS. SEE 4/F200 FOR DETAILS.
12. NO SPRINKLER PROTECTION REQUIRED BELOW
NON−COMBUSTIBLE EXTERIOR OVERHANG.
13. CPVC PIPING NOT ALLOWED IN OR ABOVE THIS ROOM.
DESIGN NOTES:
OH2
1. ALL AREAS WITH THIS SYMBOL:
SHALL BE DESIGNED
TO ORDINARY HAZARD GROUP II PARAMETERS AS PER
NFPA−13.
OH1
2. ALL AREAS WITH THIS SYMBOL:
SHALL BE DESIGNED
TO ORDINARY HAZARD GROUP I PARAMETERS AS PER
NFPA−13.
FEED MAIN UP
FROM LEVEL 3
(LOWER LEVEL)
4. ALL REMAINING AREAS TO BE DESIGNED TO LIGHT
HAZARD PARAMETERS PER NFPA−13.
ALL ROOMS WITHIN THIS PORTION
OF THE FLOOR PROVIDED WITH
EXISTING SPRINKLER PROTECTION.
5. ALL HYDRAULIC CALCULATIONS SHALL INCLUDE A
MINIMUM 10 PSI SAFETY FACTOR.
University Hall
Fire Sprinkler System Upgrade
6. IN ACCORDANCE WITH FM GLOBAL GUIDELINES, AREA
REDUCTIONS FOR QUICK RESPONSE SPRINKLERS, AND
"SMALL ROOM RULE", SHALL NOT BE USED.
USER\PW: REED.ROISUM\M4500-3755 O:\PROJECTS\2010\10.01833\2.0 PROJECT EXECUTION\2.2 DESIGN - ENGINEERING\DRAWINGS\10.01833 F120.DWG 28 FEB 2011 - 3:42PM
XREFS:
SEE 1/F110 FOR
CONTINUATION
FEED MAIN UP TO LEVEL 1
(MAIN/GARDEN LEVEL)
5
0’
4’
8’
16’
5
8
LEVEL 2
FEED MAIN
5
12
OH2
OH2
8
3955 CRAGWOOD DRIVE, COLORADO SPRINGS, COLORADO 80907
3. ALL AREAS WITH THIS SYMBOL: SP1 SHALL BE DESIGNED
TO FLOW 20 SPRINKLERS OR ENTIRE ROOM WITH
MINIMUM END HEAD PRESSURE OF 7 PSI. SPRINKLERS TO
BE 11.2K.
13
8
OH1
OH2
OH1
4
13
3
c COPYRIGHT RTA, INC.
SHEET TITLE
ALL ROOMS WITHIN THIS PORTION
OF THE FLOOR PROVIDED WITH
EXISTING SPRINKLER PROTECTION.
PARTIAL FLOOR PLANS
FIRE PROTECTION
SPRINKLERED
FROM ABOVE
7
LEVEL 1
FEED MAIN
11
10
RTA PROJECT NUMBER
UEI PROJECT NUMBER
10070.00
10.01833
DATE
02-28-11
DN FROM LEVEL 1
REVISION
9
LEVEL 2
FEED MAIN
6
DRAWN BY:
7
CHECKED BY:
RAR
MAS
UNIVERSITY HALL BUILDING
ISSUED FOR:
BID SET
KEY PLAN
N.T.S.
SHEET NO.
NORTH
0’
4’
8’
16’
0’
4’
8’
16’
F120
19 SOUTH TEJON ST., SUITE 300
COLORADO SPRINGS, CO. 80903
TELE.: 719−471−7566 FAX: 719−471−1174
www.rtaarchitects.com
1
2
3
4
5
6
7
8
9777 Pyramid Court, Suite 200
Englewood, CO 80112
Phone: 720.873.5700
Fax: 720.873.5701
Web: www.ulteig.com
8’
16’
9
11
9
11
10
9
1
5
6
8
13
5
7
13
7
4
4
1
4
1 EXISTING 6 IN. UNDERGROUND WATER LEAD−IN.
1
1 BUTTERFLY VALVE WITH TAMPER SWITCH.
3 FLOOR CONTROL VALVE ASSEMBLY INCLUDING:
XREFS:
3a
FLOW SWITCH
3b
PRESSURE RELIEF VALVE
3c
PRESSURE GAUGE WITH 3−WAY VALVE
3d
3d
5
13
6
3 EXISTING 4 IN. 2000SS AMES BACKFLOW ASSEMBLY
12
5
2
5
4
2 EXISTING 4 IN. MAIN.
13
3
2 CHECK VALVE
3b
3
USER\PW: REED.ROISUM\M4500-3755 O:\PROJECTS\2010\10.01833\2.0 PROJECT EXECUTION\2.2 DESIGN - ENGINEERING\DRAWINGS\10.01833 F200.DWG 28 FEB 2011 - 3:57PM
12
3c
2
3d
2
4
3a
8
6
10
5
1
4
1
2
4
4 EXISTING MAIN DRAIN
4
5
5 EXISTING FLOW SWITCH
6
6 EXISTING PRESSURE GAUGE
7 EXISTING SYSTEM BUTTERFLY CONTROL VALVE
3
DRAIN TO OUTSIDE WALL
4
3
8 EXISTING WET SYSTEM
4 TO LEVEL 2 SPRINKLER SYSTEM
9 EXISTING FDC PIPING
5 TO LEVEL 1 SPRINKLER SYSTEM
10 EXISTING FDC CHECK VALVE
6 FEED MAIN FROM BELOW
11 EXISTING STANDPIPE PIPING
3
12 NEW BUTTERFLY VALVE WITH TAMPER SWITCH
3d
6
13 NEW WET SYSTEM
3d
6
1.
PROVIDE AND INSTALL (2) NEW SPARE HEAD
CABINETS ON WALL NEAR SPRINKLER CONTROLS.
ONE 12 HEAD SPARE CABINET TO HOLD THE
REQUIRED SPARE SPRINKLERS AND ONE (6) HEAD
CABINET TO HOUSE SPARE COVER PLATES AS
SPECIFIED.
11
11
9
9
3955 CRAGWOOD DRIVE, COLORADO SPRINGS, COLORADO 80907
4’
University Hall
Fire Sprinkler System Upgrade
0’
10
1
4
1
10
1
3a
3c
8
3d
4
7
ABOVE CEILING SPACE
2
2
3d
6
8
3
1
5
5
3b
2
4
4
ABOVE CEILING SPACE
1 EXISTING 6 IN. UNDERGROUND WATER LEAD−IN.
3
5
LIGHT FIXTURE (TYP.)
5
4
2 EXISTING 4 IN. MAIN.
3 EXISTING 4 IN. 2000SS AMES BACKFLOW ASSEMBLY
CEILING
5
4 EXISTING MAIN DRAIN
6
2
4
5 EXISTING FLOW SWITCH
6
6 EXISTING PRESSURE GAUGE
1 BUTTERFLY VALVE WITH TAMPER SWITCH.
7 EXISTING SYSTEM BUTTERFLY CONTROL VALVE
3
2 CHECK VALVE
4
8 EXISTING WET SYSTEM
3 FLOOR CONTROL VALVE ASSEMBLY INCLUDING:
3d
3a
FLOW SWITCH
3b
PRESSURE RELIEF VALVE
3c
PRESSURE GAUGE WITH 3−WAY VALVE
3d
DRAIN TO OUTSIDE WALL
9 EXISTING FDC PIPING
10 EXISTING FDC CHECK VALVE
11 EXISTING STANDPIPE PIPING
LIGHT FIXTURE (TYP.)
3
c COPYRIGHT RTA, INC.
SHEET TITLE
DETAILS − FIRE PRO
3d
4 TO LEVEL 2 SPRINKLER SYSTEM
5 FEED MAIN
RTA PROJECT NUMBER
UEI PROJECT NUMBER
10070.00
10.01833
DATE
02-28-11
OFFICE 208
REVISION
OFFICE 208
0’
1’
2’
4’
3d
DRAWN BY:
CHECKED BY:
RAR
MAS
ISSUED FOR:
BID SET
SHEET NO.
F200