19 SOUTH TEJON ST., SUITE 300 COLORADO SPRINGS, CO. 80903 TELE.: 719−471−7566 FAX: 719−471−1174 www.rtaarchitects.com GENERAL NOTES PACK ANNULAR SPACE WITH MINERAL WOOL WALL ESCUTCHEON PIPE WALL ESCUTCHEON SKYLIGHT 5’−0" ROOF 2. THE ARCHITECTURAL BACKGROUND PROVIDED ON THESE SHEETS IS FOR GENERAL REFERENCE ONLY. CONTRACTOR SHALL VERIFY ALL BACKGROUNDS WITH ARCHITECTURAL SHEETS AND SITE VISIT. 3. SYSTEM DESIGN TO BE PER NFPA−13, 2010 EDITION AND THESE DRAWINGS AND SPECIFICATIONS. 4. CONTRACTOR SHALL OBTAIN SIGNED OWNER’S CERTIFICATE AS PER NFPA−13 AND SPECIFICATIONS. 5. REFER TO SPECIFICATIONS SECTION 21 1300 FOR ADDITIONAL INFORMATION REGARDING THE FIRE PROTECTION SYSTEM. 6. SEE PROJECT SPECIFICATIONS FOR SYSTEM TESTING REQUIREMENTS (HYDROSTATIC, TRIP TESTING ETC.). 9777 Pyramid Court, Suite 200 7. PIPING: 7.1. SPRINKLER CONTRACTOR SHALL COORDINATE LOCATION OF ALL PIPING AND SPRINKLERS WITH OTHER TRADES, HVAC SYSTEMS IN PARTICULAR. COORDINATION SHALL OCCUR DURING DESIGN AND LAYOUT, AS WELL AS IN THE FIELD. 7.2. SPRINKLER PIPING SHALL BE ROUGHED−IN PRIOR TO OR CONCURRENTLY WITH THE INSTALLATION OF MAJOR DUCTWORK. INSTALLATION OF SPRINKLERS BELOW OBSTRUCTING DUCTWORK MAY OCCUR LATER. 7.3. SIZING AND ACTUAL ROUTING OF ALL NEW SPRINKLER SYSTEM PIPING IS THE RESPONSIBILITY OF THE CONTRACTOR AND SUBJECT TO APPROVAL BY THE ENGINEER. 7.4. WET SYSTEM PIPING AND FITTINGS SHALL MEET THE REQUIREMENTS OF NFPA−13, EXCEPT THAT PRESS−FIT AND POZ−LOK SYSTEMS ARE NOT APPROVED FOR THIS PROJECT. 7.5. ALL PIPING 4 INCH AND LARGER TO BE SCHEDULE 40 STEEL; ALL PIPING 3 INCH AND SMALLER TO BE CPVC EXCEPT AS NOTED BELOW: 7.5.1. ALL EXPOSED PIPING TO BE SCHEDULE 40 STEEL. 7.5.2. ALL LOCATIONS NOT LISTED FOR CPVC SHALL BE SCHEDULE 40 STEEL. 7.5.3. WHERE SUNLIGHT, CHEMICALS, OR PHYSICAL ABUSE COULD BE EXPECTED, ONLY SCHEDULE 40 STEEL PIPE SHALL BE USED. 7.6. PIPING PENETRATIONS THROUGH RATED WALLS SHALL BE SEALED IN ACCORDANCE WITH SPECIFICATIONS (SEE ALSO DETAIL 3/F100). 7.7. PAINTING OF PIPE TO BE BY DIVISION 9. NOTE: HOLES THROUGH WALLS SHALL BE A MINIMUM OF 1 IN. LARGER, AND MAXIMUM OF 2 IN. LARGER IN DIAMETER THAN THE OUTSIDE DIAMETER OF THE PIPE PASSING THRU THE RATED WALL. THIS SPACE SHALL BE FILLED WITH MINERAL WOOL AND SEALED WITH AN APPROVED LISTED FIRE CAULK OR SEALANT. ALL PENETRATIONS OF FIRE RATED WALLS AND ASSEMBLIES SHALL BE UL LISTED FOR THAT PURPOSE, FOR BOTH THE TYPE OF PIPE MATERIAL AND WALL OR CEILING/FLOOR CONSTRUCTION. LISTED ALTERNATE METHODS WILL BE ACCEPTED. GYP BOARD STEEL STUD CEILING SPACE THIS PROJECT INCLUDES THE DESIGN AND PROVISION OF A NEW WET−PIPE SPRINKLER SYSTEM THROUGHOUT THE UNSPRINKLERED PORTIONS OF THE BUILDING INDICATED ON THE FOLLOWING DRAWINGS. Englewood, CO 80112 Phone: 720.873.5700 Fax: 720.873.5701 Web: www.ulteig.com 8. HANGERS: 8.1. HANGERS, HANGER RODS, CLAMPS, AND INSERTS SHALL BE IN ACCORDANCE WITH NFPA−13, 2010 EDITION. 8.2. CPVC HANGERS SHALL BE IN ACCORDANCE WITH MANUFACTURER’S GUIDELINES. SEE DETAIL 4/F100. 8.3. TRAPEZE−STYLE HANGING ASSEMBLIES MAY BE USED, BUT ONLY WITH DOCUMENTATION ON THE SHOP DRAWINGS VALIDATING THE SIZING OF THE TRAPEZE MEMBERS. WHEN A TRAPEZE MEMBER IS NOT EXPLICITLY LISTED IN NFPA−13 (E.G. UNISTRUT), DOCUMENTATION MUST BE PROVIDED THAT INDICATES ADEQUATE SECTION MODULUS AND OTHER PERTINENT PARAMETERS ARE BEING MET. CEILING SPACE LIGHT COVE 9. SPRINKLERS: 9.1. PROTECTION OF SPRINKLERS DURING PAINTING, AND REMOVAL THEREAFTER, SHALL BE BY DIVISION 9. 9.2. UNLESS INDICATED OTHERWISE, ALL AUTOMATIC SPRINKLERS LOCATED WITHIN SUSPENDED TILE CEILINGS SHALL BE CHROME, RECESSED TO MATCH EXISTING SPRINKLERS. UNLESS OTHERWISE NOTED, REMAINING EXPOSED SPRINKLERS SHALL BE BRASS. SEE SPRINKLER LEGEND FOR SPRINKLER TYPE DETAILS. 9.3. SPRINKLERS SHALL BE LOCATED IN THE CENTER OF TILE. SEE DETAIL 2/F100. 9.4. HEAD GUARDS LISTED FOR USE WITH THE RESPECTIVE SPRINKLERS SHALL BE INSTALLED ANYWHERE EXPOSED SPRINKLERS ARE LOCATED BELOW 7’−0" AFF. 9.5. ELECTRICAL AND MECHANICAL ROOMS SHALL UTILIZE INTERMEDIATE TEMPERATURE RATED SPRINKLERS. GRID CEILING 10. WATER SUPPLY DATA: CONTRACTOR SHALL BASE HYDRAULIC CALCULATIONS ON THE FOLLOWING WATER SUPPLY INFORMATION: 10.1. STATIC: 160 PSI RESIDUAL: 150 PSI FLOWING: 1186 GPM 10.2. TEST CONDUCTED BY : WESTERN STATES FIRE PROTECTION DATE: 06/04/10 10.3. EFFECTIVE POINT: WHERE 6 INCH UNDERGROUND CONNECTS TO 8 INCH UNDERGROUND MAIN. SEE SITE PLAN 1/F100. 10.4. HOSE ALLOWANCES SHALL BE TAKEN AT THIS SAME EFFECTIVE POINT. 12" 12" 12" 24" 48" 2x4 TILES FIRE PROTECTION SYMBOLS LEGEND LOCATE SPRINKLER AT CENTER OR 12 INCHES FROM THE TWO ADJACENT GRID LINES POST- INSTALLED ANCHOR 6" 12" University Hall Fire Sprinkler System Upgrade CONCRETE FLOOR SLAB RISER VERTICAL PIPE 6" EXISTING SPRINKLER PIPING USER\PW: REED.ROISUM\M4500-3755 O:\PROJECTS\2010\10.01833\2.0 PROJECT EXECUTION\2.2 DESIGN - ENGINEERING\DRAWINGS\10.01833 F100.DWG 28 FEB 2011 - 3:52PM XREFS: 12" 6" NEW SPRINKLER PIPING 24" CONCRETE TEE 24" UNDERGROUND WATER MAIN PIPING CLIP ANGLE CAP 6" ALL THREAD ROD POST- INSTALLED ANCHOR 24" 24" 2x2 BLANK TILES 2x2 SCORED TILES LOCATE SPRINKLER AT CENTER OF TILE PIPE BREAK LOCATE SPRINKLER 6 INCHES FROM TWO GRID LINES OH1 ORDINARY HAZARD GROUP I AREA OH2 ORDINARY HAZARD GROUP II AREA 1 FIRE DEPARTMENT CONNECTION (FLUSH TYPE) ALL THREAD ROD HANGER RING HANGER RING PIPE PLAN NOTE FIRE DEPARTMENT CONNECTION (SIAMESE TYPE) PIPE BACKFLOW TEST OUTLET UNDERGROUND GATE VALVE HYDRANT NOTE: ALL ANCHORS AND HANGERS TO BE LISTED FOR USE IN CONCRETE IN ACCORDANCE WITH NFPA 13, 2010 EDITION. EXISTING REMOTE YARD FDC CHECK VALVE BUTTERFLY CONTROL VALVE FLOW TEST INFO: STATIC: 160 PSI RESIDUAL: 150 PSI FLOWING: 1186 GPM CEILING HEIGHT ABOVE FINISHED FLOOR EXISTING HYDRANT ELEVATION = 92’−0" EXISTING HYDRANT EFFECTIVE POINT DESIGN NOTES: SEE TABLE BELOW FOR NUMBER OH2 EXISTING 8 IN. UG WATER MAIN OF HANGERS REQUIRED APPROX. 60 FT OF EXISTING 6 IN. UG WATER MAIN EXISTING GATE VALVE ASTM F442 CPVC BRANCHLINE * FLOOR ELEVATION @ SPRINKLER CONTROLS = 72’−0" EXISTING GATE VALVE 1. ALL AREAS WITH THIS SYMBOL: SHALL BE DESIGNED TO ORDINARY HAZARD GROUP II PARAMETERS AS PER NFPA−13. 3955 CRAGWOOD DRIVE, COLORADO SPRINGS, COLORADO 80907 2’−6" SEAL WITH APPROVED FIRE CAULKING (SEE SPECIFICATIONS) 1. OH1 EXISTING REMOTE YARD FDC 2. ALL AREAS WITH THIS SYMBOL: SHALL BE DESIGNED TO ORDINARY HAZARD GROUP I PARAMETERS AS PER NFPA−13. 3. ALL AREAS WITH THIS SYMBOL: SP1 SHALL BE DESIGNED TO FLOW 20 SPRINKLERS OR ENTIRE ROOM WITH MINIMUM END HEAD PRESSURE OF 7 PSI. SPRINKLERS TO BE 11.2K. 4. ALL REMAINING AREAS TO BE DESIGNED TO LIGHT HAZARD PARAMETERS PER NFPA−13. 5. ALL HYDRAULIC CALCULATIONS SHALL INCLUDE A MINIMUM 10 PSI SAFETY FACTOR. 6. IN ACCORDANCE WITH FM GLOBAL GUIDELINES, AREA REDUCTIONS FOR QUICK RESPONSE SPRINKLERS, AND "SMALL ROOM RULE", SHALL NOT BE USED. MINIMUM ALLOWABLE HANGERS PER LENGTH OF CPVC PIPE PIPE SIZE inches 1 Hanger Pipe Length 2 Hangers 3 Hangers 1" 0’−0" TO 6’−0" 6’−1" TO 12’−0" 12’−1" TO 18’−0" 1¼" 0’−0" TO 6’−6" 6’−7" TO 13’−0" 13’−1" TO 19’−6" 1½" 0’−0" TO 7’−0" 7’−1" TO 14’−0" 14’−1" TO 21’−0" 2" 0’−0" TO 8’−0" 8’−1" TO 16’−0" 16’−1" TO 24’−0" 2½" 0’−0" TO 9’−0" 9’−1" TO 18’−0" 18’−1" TO 27’−0" 3" 0’−0" TO 10’−0" 10’−1" TO 20’−0" 20’−1" TO 30’−0" c COPYRIGHT RTA, INC. SHEET TITLE SITE PLAN − DETAILS − FIRE PRO * NSF INTERNATIONAL APPROVED FOR USE WITH POTABLE WATER RTA PROJECT NUMBER UEI PROJECT NUMBER 10070.00 10.01833 DATE NOTE: THE MAXIMUM DISTANCE BETWEEN HANGERS FOR LISTED NONMETALLIC PIPE SHALL BE MODIFIED AS SPECIFIED IN THE INDIVIDUAL PRODUCT LISTINGS. 02-28-11 REVISION DRAWN BY: 0’ 25’ 50’ 100’ CHECKED BY: RAR MAS ISSUED FOR: BID SET SHEET NO. F100 SPRINKLER LEGEND SYMB. MFR. PLAN NOTES THD TEMP. SZ RTG. TYPE ESCUT. FINISH VK302 5.6 QUICK RECESSED PENDANT 1 2" 155° CHROME CHROME VIKING VK302 5.6 QUICK RECESSED PENDANT 1 2" 200° CHROME CHROME VIKING VK462 5.6 QUICK FLAT CONCEALED PENDANT − "MIRAGE" 1 2" 200° BRASS BRUSHED BRASS VIKING VK300 5.6 QUICK UPRIGHT 1 2" 200° BRASS N/A VIKING VK531 11.2 QUICK UPRIGHT 3 155° BRASS N/A VIKING VK305 5.6 QUICK HORIZONTAL SIDEWALL 1 2" 155° BRASS N/A 155° CHROME CHROME 4 " VIKING VK305 5.6 QUICK RECESSED HORIZONTAL SIDEWALL 1 2" VIKING VK305 5.6 QUICK RECESSED HORIZONTAL SIDEWALL 1 2" 200° CHROME CHROME VIKING VK606 8.0 QUICK EXTENDED COVERAGE REC. HORIZ. SIDEWALL 3 155° CHROME CHROME 4" 13 # 1. PROVIDE AND INSTALL HORIZONTAL SIDEWALL SPRINKLER UNDER OPEN GARAGE DOOR. 2. PROVIDE INTERMEDIATE OR HIGH TEMPERATURE RATED SPRINKLERS NEAR UNIT HEATER BASED ON NFPA 13 GUIDELINES. 3. PROVIDE AND INSTALL INTERMEDIATE TEMPERATURE RATED BRASS UPRIGHT SPRINKLERS IN SKYLIGHTS. SEE 6/F100 FOR DETAILS. 4. PROVIDE AND INSTALL INTERMEDIATE TEMPERATURE HORIZONTAL SIDEWALL SPRINKLER POINTING DOWN THE SLOPE IN THE APPROXIMATE LOCATION SHOWN. PIPING TO BE ROUTED AS HIGH AND TIGHT TO WALL AS POSSIBLE. ALL EXPOSED PIPING TO BE SCHEDULE 40 STEEL IN THIS AREA. 5. PROVIDE AND INSTALL INTERMEDIATE TEMPERATURE RATED CONCEALED SPRINKLER WITH BRUSHED BRASS COVER PLATE IN DISPLAY CASE AS SHOWN. 6. PROVIDE AND INSTALL INTERMEDIATE TEMPERATURE RATED RECESSED PENDANT SPRINKLER IN APPROXIMATE LOCATION SHOWN. SPRINKLER PROTECTION NOT REQUIRED IN SKYLIGHT. 7. PROVIDE AND INSTALL EXTENDED COVERAGE RECESSED HORIZONTAL SIDEWALL SPRINKLER IN APPROXIMATE LOCATION SHOWN. FINISH AND ESCUTCHEON FINISH TO BE CHROME. 8. NO WORK IN THIS AREA. EXISTING SPRINKLERS. 9. PROVIDE AND INSTALL INTERMEDIATE TEMPERATURE HORIZONTAL SIDEWALL SPRINKLER POINTING DOWN THE SLOPE IN THE APPROXIMATE LOCATION SHOWN. ALL EXPOSED PIPING TO BE SCHEDULE 40 STEEL IN THIS AREA. 10. ROUTE LEVEL 2 FEED MAIN DOWN IN CHASE IN THIS APPROXIMATE LOCATION. OH2 OH2 SP1 SP1 SPRNK FINISH VIKING 13 13 K S.I.N. RSPNS NO. FCTR INSPECTOR’S TEST OUTLET 1 11. NOT USED. 12. NO SPRINKLER PROTECTION REQUIRED BELOW NON−COMBUSTIBLE EXTERIOR OVERHANG. 13 19 SOUTH TEJON ST., SUITE 300 COLORADO SPRINGS, CO. 80903 TELE.: 719−471−7566 FAX: 719−471−1174 www.rtaarchitects.com 9777 Pyramid Court, Suite 200 Englewood, CO 80112 Phone: 720.873.5700 Fax: 720.873.5701 Web: www.ulteig.com 13. CPVC PIPING NOT ALLOWED IN OR ABOVE THIS ROOM. 2 14. COORDINATE CROSS MAIN ROUTING WITH EXISTING CONDITIONS. 13 15. PROVIDE AND INSTALL CONCEALED SPRINKLER WITH BRUSHED BRASS COVER PLATE AS SHOWN. 13 16. NO SPRINKLER PROTECTION REQUIRED WITHIN CEILING POCKET. 13 SP1 13 13 13 OH2 OH1 1 OH2 OH1 SP1 OH1 OH1 OH1 OH2 13 13 13 OH1 14 OH2 OH2 DESIGN NOTES: OH2 OH2 1. ALL AREAS WITH THIS SYMBOL: SHALL BE DESIGNED TO ORDINARY HAZARD GROUP II PARAMETERS AS PER NFPA−13. EXISTING HOSE CONNECTION OH1 2. ALL AREAS WITH THIS SYMBOL: SHALL BE DESIGNED TO ORDINARY HAZARD GROUP I PARAMETERS AS PER NFPA−13. 3 3 OH1 University Hall Fire Sprinkler System Upgrade 3. ALL AREAS WITH THIS SYMBOL: SP1 SHALL BE DESIGNED TO FLOW 20 SPRINKLERS OR ENTIRE ROOM WITH MINIMUM END HEAD PRESSURE OF 7 PSI. SPRINKLERS TO BE 11.2K. OH2 4. ALL REMAINING AREAS TO BE DESIGNED TO LIGHT HAZARD PARAMETERS PER NFPA−13. 5. ALL HYDRAULIC CALCULATIONS SHALL INCLUDE A MINIMUM 10 PSI SAFETY FACTOR. 16 USER\PW: REED.ROISUM\M4500-3755 O:\PROJECTS\2010\10.01833\2.0 PROJECT EXECUTION\2.2 DESIGN - ENGINEERING\DRAWINGS\10.01833 F110.DWG 28 FEB 2011 - 3:47PM XREFS: 6. IN ACCORDANCE WITH FM GLOBAL GUIDELINES, AREA REDUCTIONS FOR QUICK RESPONSE SPRINKLERS, AND "SMALL ROOM RULE", SHALL NOT BE USED. 16 remove head?? 3 3 OH2 OH2 12 3 3955 CRAGWOOD DRIVE, COLORADO SPRINGS, COLORADO 80907 3 16 9 16 OH1 14 15 THIS LEVEL FEED MAIN LEVEL 2 FEED MAIN LEVEL 2 FEED MAIN 16 16 LEVEL 2 FEED MAIN 16 c COPYRIGHT RTA, INC. 12 5 4 10 4 4 4 12 7 7 SHEET TITLE PARTIAL MAIN LEVEL 7 DN TO LEVEL 2 FLOOR PLAN 16 FIRE PROTECTION 5 RTA PROJECT NUMBER UEI PROJECT NUMBER 10070.00 10.01833 DATE 16 02-28-11 6 REVISION 12 LEVEL 2 FEED MAIN 12 5 16 DRAWN BY: 12 CHECKED BY: OH2 RAR MAS OH2 UNIVERSITY HALL BUILDING ISSUED FOR: BID SET 0’ KEY PLAN N.T.S. 4’ 8’ 16’ SHEET NO. NORTH SEE 1/F120 FOR CONTINUATION F110 SPRINKLER LEGEND SYMB. 2 SEE SITE PLAN 1/F100 FOR CONTINUATION 1 EXISTING 6 IN. UG WATER MAIN ROUTE FEED MAIN UP TO LEVEL 2 MFR. S.I.N. K RSPNS NO. FCTR THD TEMP. SZ RTG. TYPE ESCUT. FINISH SPRNK FINISH VIKING VK302 5.6 QUICK RECESSED PENDANT 1 2" 155° CHROME CHROME VIKING VK302 5.6 QUICK RECESSED PENDANT 1 2" 200° CHROME CHROME VIKING VK462 5.6 QUICK FLAT CONCEALED PENDANT − "MIRAGE" 1 2" 200° BRASS BRUSHED BRASS VIKING VK300 5.6 QUICK UPRIGHT 1 2" 200° BRASS N/A 3 VIKING VK531 11.2 QUICK UPRIGHT 155° BRASS N/A VIKING VK305 5.6 QUICK HORIZONTAL SIDEWALL 1 2" 155° BRASS N/A VIKING VK305 5.6 QUICK RECESSED HORIZONTAL SIDEWALL 1 2" 155° CHROME CHROME VIKING VK305 5.6 QUICK RECESSED HORIZONTAL SIDEWALL 1 2" 200° CHROME CHROME 3 155° CHROME CHROME VIKING VK606 8.0 QUICK EXTENDED COVERAGE REC. HORIZ. SIDEWALL ALL ROOMS WITHIN THIS PORTION OF THE FLOOR PROVIDED WITH EXISTING SPRINKLER PROTECTION. PLAN NOTES 4 " 4" 19 SOUTH TEJON ST., SUITE 300 COLORADO SPRINGS, CO. 80903 TELE.: 719−471−7566 FAX: 719−471−1174 www.rtaarchitects.com # 1. SPRINKLER CONTROLS. SEE DETAIL 2/F200. 2. PROVIDE AND INSTALL (2) NEW SPARE HEAD CABINETS. ONE 12 HEAD SPARE CABINET TO HOLD THE REQUIRED SPARE SPRINKLERS AND ONE (6) HEAD CABINET TO HOUSE SPARE COVER PLATES AS SPECIFIED. 3. PROVIDE HORIZONTAL SIDEWALL SPRINKLER IN ELEVATOR PIT LOCATED NO MORE THAN 2 FT UP FROM PIT FLOOR. PROVIDE FLOW SWITCH WITH VALVE ABOVE CEILING, OUTSIDE ELEVATOR SHAFT. ROUTE TEST/DRAIN PIPING TO EXTERIOR WALL AND OUT. PROVIDE SPLASH BLOCK AT EXTERIOR. 4. NO SPRINKLERS OR SPRINKLER PIPING ALLOWED IN ELEVATOR EQUIPMENT ROOM. 5. PROVIDE AND INSTALL INTERMEDIATE TEMPERATURE RATED CONCEALED SPRINKLER WITH BRUSHED BRASS COVER PLATE IN DISPLAY CASE AS SHOWN. 6. LEVEL 2 FLOOR CONTROLS LOCATED ABOVE CEILING. SEE 3/F200 FOR DETAILS. 7. ROUTE DRAIN PIPING TO EXTERIOR WALL IN APPROXIMATE LOCATION SHOWN. PROVIDE SPLASH BLOCK AT EXTERIOR. 8. NO WORK IN THIS AREA. EXISTING SPRINKLERS. 9. FEED MAIN FROM LEVEL 1. ROUTE MAIN ABOVE CEILING TO FLOOR CONTROLS LOCATION SHOWN. 9777 Pyramid Court, Suite 200 Englewood, CO 80112 Phone: 720.873.5700 Fax: 720.873.5701 Web: www.ulteig.com 10. FEED MAIN UP FROM LEVEL 2. 0’ 4’ 8’ 16’ 11. LEVEL 1 FLOOR CONTROLS. SEE 4/F200 FOR DETAILS. 12. NO SPRINKLER PROTECTION REQUIRED BELOW NON−COMBUSTIBLE EXTERIOR OVERHANG. 13. CPVC PIPING NOT ALLOWED IN OR ABOVE THIS ROOM. DESIGN NOTES: OH2 1. ALL AREAS WITH THIS SYMBOL: SHALL BE DESIGNED TO ORDINARY HAZARD GROUP II PARAMETERS AS PER NFPA−13. OH1 2. ALL AREAS WITH THIS SYMBOL: SHALL BE DESIGNED TO ORDINARY HAZARD GROUP I PARAMETERS AS PER NFPA−13. FEED MAIN UP FROM LEVEL 3 (LOWER LEVEL) 4. ALL REMAINING AREAS TO BE DESIGNED TO LIGHT HAZARD PARAMETERS PER NFPA−13. ALL ROOMS WITHIN THIS PORTION OF THE FLOOR PROVIDED WITH EXISTING SPRINKLER PROTECTION. 5. ALL HYDRAULIC CALCULATIONS SHALL INCLUDE A MINIMUM 10 PSI SAFETY FACTOR. University Hall Fire Sprinkler System Upgrade 6. IN ACCORDANCE WITH FM GLOBAL GUIDELINES, AREA REDUCTIONS FOR QUICK RESPONSE SPRINKLERS, AND "SMALL ROOM RULE", SHALL NOT BE USED. USER\PW: REED.ROISUM\M4500-3755 O:\PROJECTS\2010\10.01833\2.0 PROJECT EXECUTION\2.2 DESIGN - ENGINEERING\DRAWINGS\10.01833 F120.DWG 28 FEB 2011 - 3:42PM XREFS: SEE 1/F110 FOR CONTINUATION FEED MAIN UP TO LEVEL 1 (MAIN/GARDEN LEVEL) 5 0’ 4’ 8’ 16’ 5 8 LEVEL 2 FEED MAIN 5 12 OH2 OH2 8 3955 CRAGWOOD DRIVE, COLORADO SPRINGS, COLORADO 80907 3. ALL AREAS WITH THIS SYMBOL: SP1 SHALL BE DESIGNED TO FLOW 20 SPRINKLERS OR ENTIRE ROOM WITH MINIMUM END HEAD PRESSURE OF 7 PSI. SPRINKLERS TO BE 11.2K. 13 8 OH1 OH2 OH1 4 13 3 c COPYRIGHT RTA, INC. SHEET TITLE ALL ROOMS WITHIN THIS PORTION OF THE FLOOR PROVIDED WITH EXISTING SPRINKLER PROTECTION. PARTIAL FLOOR PLANS FIRE PROTECTION SPRINKLERED FROM ABOVE 7 LEVEL 1 FEED MAIN 11 10 RTA PROJECT NUMBER UEI PROJECT NUMBER 10070.00 10.01833 DATE 02-28-11 DN FROM LEVEL 1 REVISION 9 LEVEL 2 FEED MAIN 6 DRAWN BY: 7 CHECKED BY: RAR MAS UNIVERSITY HALL BUILDING ISSUED FOR: BID SET KEY PLAN N.T.S. SHEET NO. NORTH 0’ 4’ 8’ 16’ 0’ 4’ 8’ 16’ F120 19 SOUTH TEJON ST., SUITE 300 COLORADO SPRINGS, CO. 80903 TELE.: 719−471−7566 FAX: 719−471−1174 www.rtaarchitects.com 1 2 3 4 5 6 7 8 9777 Pyramid Court, Suite 200 Englewood, CO 80112 Phone: 720.873.5700 Fax: 720.873.5701 Web: www.ulteig.com 8’ 16’ 9 11 9 11 10 9 1 5 6 8 13 5 7 13 7 4 4 1 4 1 EXISTING 6 IN. UNDERGROUND WATER LEAD−IN. 1 1 BUTTERFLY VALVE WITH TAMPER SWITCH. 3 FLOOR CONTROL VALVE ASSEMBLY INCLUDING: XREFS: 3a FLOW SWITCH 3b PRESSURE RELIEF VALVE 3c PRESSURE GAUGE WITH 3−WAY VALVE 3d 3d 5 13 6 3 EXISTING 4 IN. 2000SS AMES BACKFLOW ASSEMBLY 12 5 2 5 4 2 EXISTING 4 IN. MAIN. 13 3 2 CHECK VALVE 3b 3 USER\PW: REED.ROISUM\M4500-3755 O:\PROJECTS\2010\10.01833\2.0 PROJECT EXECUTION\2.2 DESIGN - ENGINEERING\DRAWINGS\10.01833 F200.DWG 28 FEB 2011 - 3:57PM 12 3c 2 3d 2 4 3a 8 6 10 5 1 4 1 2 4 4 EXISTING MAIN DRAIN 4 5 5 EXISTING FLOW SWITCH 6 6 EXISTING PRESSURE GAUGE 7 EXISTING SYSTEM BUTTERFLY CONTROL VALVE 3 DRAIN TO OUTSIDE WALL 4 3 8 EXISTING WET SYSTEM 4 TO LEVEL 2 SPRINKLER SYSTEM 9 EXISTING FDC PIPING 5 TO LEVEL 1 SPRINKLER SYSTEM 10 EXISTING FDC CHECK VALVE 6 FEED MAIN FROM BELOW 11 EXISTING STANDPIPE PIPING 3 12 NEW BUTTERFLY VALVE WITH TAMPER SWITCH 3d 6 13 NEW WET SYSTEM 3d 6 1. PROVIDE AND INSTALL (2) NEW SPARE HEAD CABINETS ON WALL NEAR SPRINKLER CONTROLS. ONE 12 HEAD SPARE CABINET TO HOLD THE REQUIRED SPARE SPRINKLERS AND ONE (6) HEAD CABINET TO HOUSE SPARE COVER PLATES AS SPECIFIED. 11 11 9 9 3955 CRAGWOOD DRIVE, COLORADO SPRINGS, COLORADO 80907 4’ University Hall Fire Sprinkler System Upgrade 0’ 10 1 4 1 10 1 3a 3c 8 3d 4 7 ABOVE CEILING SPACE 2 2 3d 6 8 3 1 5 5 3b 2 4 4 ABOVE CEILING SPACE 1 EXISTING 6 IN. UNDERGROUND WATER LEAD−IN. 3 5 LIGHT FIXTURE (TYP.) 5 4 2 EXISTING 4 IN. MAIN. 3 EXISTING 4 IN. 2000SS AMES BACKFLOW ASSEMBLY CEILING 5 4 EXISTING MAIN DRAIN 6 2 4 5 EXISTING FLOW SWITCH 6 6 EXISTING PRESSURE GAUGE 1 BUTTERFLY VALVE WITH TAMPER SWITCH. 7 EXISTING SYSTEM BUTTERFLY CONTROL VALVE 3 2 CHECK VALVE 4 8 EXISTING WET SYSTEM 3 FLOOR CONTROL VALVE ASSEMBLY INCLUDING: 3d 3a FLOW SWITCH 3b PRESSURE RELIEF VALVE 3c PRESSURE GAUGE WITH 3−WAY VALVE 3d DRAIN TO OUTSIDE WALL 9 EXISTING FDC PIPING 10 EXISTING FDC CHECK VALVE 11 EXISTING STANDPIPE PIPING LIGHT FIXTURE (TYP.) 3 c COPYRIGHT RTA, INC. SHEET TITLE DETAILS − FIRE PRO 3d 4 TO LEVEL 2 SPRINKLER SYSTEM 5 FEED MAIN RTA PROJECT NUMBER UEI PROJECT NUMBER 10070.00 10.01833 DATE 02-28-11 OFFICE 208 REVISION OFFICE 208 0’ 1’ 2’ 4’ 3d DRAWN BY: CHECKED BY: RAR MAS ISSUED FOR: BID SET SHEET NO. F200