A technical manual from the experts in Business-Critical Continuity™ Aerial Ultracab Cross-Connect Enclosures Description and Installation 631-201-009 (Version D, October 11, 2011) Business-Critical Continuity™, Emerson Network Power, and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co. NETSURE™, NetSpan™, NetReach™, NetXtend™, and NetPerform™ are trademarks of Emerson Network Power, Energy Systems, North America, Inc. All other trademarks are the property of their respective owners. The products covered by this instruction manual are manufactured and/or sold by Emerson Network Power, Energy Systems, North America, Inc. The information contained in this document is subject to change without notice and may not be suitable for all applications. While every precaution has been taken to ensure the accuracy and completeness of this document, Emerson Network Power, Energy Systems, North America, Inc. assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions. Refer to other local practices or building codes as applicable for the correct methods, tools, and materials to be used in performing procedures not specifically described in this document. This document is the property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. Copyright © 2011, Emerson Network Power, Energy Systems, North America, Inc. All rights reserved throughout the world. Emerson Network Power Aerial Distribution Products 631-201-009 Version D, October 11, 2011 TABLE OF CONTENTS 1. ABOUT THIS DOCUMENT 1 1.1 Purpose . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 1.2 Reason for Reissue . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 1.3 Information Not Provided in This Practice . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 2. DESCRIPTION 2 2.1 Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 2.2 Construction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 2.3 Terminal Blocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 2.4 Wire Pair Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 2.5 Feeder Pairs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 3. INSTALLATION 5 3.1 Choosing and Preparing a Location for the Enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . 5 3.2 Installing the Enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 4. JUMPER WIRING 7 4.1 Before You Begin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 4.2 Terminating Jumper Wires on CQF Blocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 4.3 Terminating Jumper Wires on RLS Blocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 4.4 Routing Wire . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 5. ACCESSORIES 10 5.2 Spool Shafts for Cross-Connect Jumper Wire . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 5.3 One-Pair Tester . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 5.4 Special Service Protective Cap . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 5.5 Label Kits for the Terminal Blocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Outside Plant Equipment Proprietary Information Page i of ii 631-201-009 Version D, October 11, 2011 Emerson Network Power Aerial Distribution Products This Page Intentionally Left Blank. Page ii of ii Proprietary Information Outside Plant Equipment Emerson Network Power Aerial Distribution Products 631-201-009 Version D, October 11, 2011 Part No. P71350 AERIAL ULTRACAB CROSS-CONNECT ENCLOSURES DESCRIPTION AND INSTALLATION 1. ABOUT THIS DOCUMENT 1.1 Purpose This practice provides instruction for installing the Aerial Ultracab Cross-Connect Enclosures. 1.2 Reason for Reissue Whenever this practice is reissued, the reason for reissue will be stated in this paragraph. • Update the installation instructions and illustrations. 1.3 Information Not Provided in This Practice Refer to other local practices or building codes as applicable for the correct methods, tools and materials to be used in performing procedures not specifically described in this document. If your enclosure is equipped with RLS terminal blocks, then refer to the following documents for specific information on wire termination on RLS50 blocks: • • 641-202-002, RLS50 Self-Strip Block Description and Installation and 641-202-009, RLS50 Self-Strip Block Feed-Thru Half-Tap Activator Kit Description and Installation Note: The information contained in this practice is subject to change without notice and may not be suitable for all applications. Outside Plant Equipment Proprietary Information Page 1 of 12 631-201-009 Version D, October 11, 2011 Emerson Network Power Aerial Distribution Products 2. DESCRIPTION 2.1 Application The Aerial Ultracab Cross-Connect Enclosures (Fig. 1 and Fig. 2) are pole-mounted, center-feed cross-connect/interface system equipped with quiet front CFQ terminal blocks or RLS self-strip terminal blocks. Fig. 1 : 400 Pair Aerial Ultracab Cross-Connect Enclosure Fig. 2 : 1800 Pair Aerial Ultracab Cross-Connect Enclosure 2.2 Construction Enclosures are manufactured of aluminum and mill-galvanized steel. All enclosures are powder coat painted with green or off-white finish. Enclosure dimensions are given in Table A. All enclosures are equipped with filtered vents for proper ventilation. Enclosure doors are secured by a three-point locking system and have closed-cell and bulb seal neoprene gasketing. Page 2 of 12 Proprietary Information Outside Plant Equipment Emerson Network Power Aerial Distribution Products 631-201-009 Version D, October 11, 2011 TABLE A - ENCLOSURE DIMENSIONS Enclosure Dimensions (inches) Pair Count Height Width Depth 100-400 33 16 14 500-900 45 24 14 1000-1200 45 32 14 1300-1800 62 33 14 1900-2700 62 46 14 2.3 Terminal Blocks The terminal block field is drop-down style and secured with hex head bolts. All blocks are hard-wired to a cable stub or harness behind the block face and are encapsulated for moisture resistance. Enclosures are equipped either with 50-pair CQF quiet-front screw-type binding post terminal blocks or with 50-pair RLS self-strip terminal blocks both shown in Fig. 3. The CQF terminal lugs are tin-plated for corrosion resistance and are captivated in the block to eliminate accidental detachment from the block housing. For information on RLS terminal blocks, see document 641-202-002, RLS50 Self-Strip Block Description and Installation. 50-pair CQF Block 50-pair RLS Block Fig. 3 : Terminal Blocks 2.4 Wire Pair Identification The feeder (in) and distribution (out) pairs are identified separately on the face of the enclosure blocks by color code. The binding posts or IDC clips are given terminal pair identification, starting with one and proceeding to the last pair number for that particular type of pair. Therefore, each has a feeder (in-green) pair Outside Plant Equipment Proprietary Information Page 3 of 12 631-201-009 Version D, October 11, 2011 Emerson Network Power Aerial Distribution Products number one and a distribution (out-blue) pair number one, etc. Terminal blocks are numbered horizontally (EXAMPLE: Row 1, pairs 1-5; row 2, pairs 6-10; on RLS: Row 1, pairs 1-10; etc.). 2.5 Feeder Pairs 100 - 400 pair enclosure 600 - 900 pair enclosure 1200 - 1800 pair enclosure distribution distribution feeder feeder distribution distribution distribution feeder feeder distribution distribution feeder distribution distribution feeder All standard pole-mounted cross-connect enclosures of 600 pairs and larger are configured for a feeder to distribution ratio of 1 to 2. Engineering design may dictate different counts. Feeder pairs are located in the left column for 100-pair to 400-pair enclosures; in the center column for 600-pair to 900-pair enclosures and in the two center columns for 1200-pair to 2700-pair enclosures. Refer to Fig. 4. 1900 - 2700 pair enclosure Fig. 4 : Layout of Terminal Blocks Page 4 of 12 Proprietary Information Outside Plant Equipment Emerson Network Power Aerial Distribution Products 631-201-009 Version D, October 11, 2011 3. INSTALLATION 3.1 Choosing and Preparing a Location for the Enclosure The pole-mounted cross-connect enclosures can be installed at any height. For ease of access, install the enclosure at working level per local practices. SAFETY SAFETY: In areas where damage could occur to enclosures mounted at ground level, such as alleys, mount the enclosure below aerial cables, with adequate clearance for bending the stub at a 90o angle to prepare the splice. A balcony may be installed for ease of access and to provide a safe working position for field technicians. 3.2 Installing the Enclosure DANGER Be sure the area above the hoisting operation is clear of power lines or obstructions. Also be sure to follow all local and company safety practices during lifting. Perform the following steps to install an Aerial Ultracab Cross-Connect Enclosure: Step 1: Drill a 11/16-inch hole through the pole for the top bracket (see Fig. 5). Fig. 5 : Top Pole-Mounting Bracket Outside Plant Equipment Proprietary Information Page 5 of 12 631-201-009 Version D, October 11, 2011 Emerson Network Power Aerial Distribution Products Step 2: Secure the top bracket to the pole with a 5/8-inch through bolt. Level the bracket before tightening the bolt. Step 3: Raise the unit using a block and tackle or winch line passed through a snatch block attached to the top of the sling. Guide the unit during the hoisting operation with a hand line fastened to the bottom pole-mounting bracket. Step 4: Place the enclosure on top of the pole-mounted bracket and verify that both brackets on the enclosure are properly engaged and sitting levelled on the pole bracket (see Fig. 6). Step 5: Secure the bottom pole mounting by drilling a 11/16-inch hole through the pole and using a 5/8-inch through bolt (see Fig. 7). Step 6: Attach the supplied stabilizer bars to the bottom of the enclosure using the supplied "U" clamps, do not tighten (see Fig. 7). Note: DOES NOT APPLY FOR 400 PAIR SIZE UNITS. Step 7: Attach the other end of the stabilizer bars to the pole using two 3/8-inch bolts per bar (see Fig. 7). Note: DOES NOT APPLY FOR 400 PAIR SIZE UNITS. Step 8: Tighten all mounting hardware. LIFTING BRACKETS POLE STABILIZER STABILIZER BARS BARS Fig. 6 : Lifting Brackets and Stabilizer Bars Page 6 of 12 Fig. 7 : Bottom Pole-Mounting Bracket Proprietary Information Outside Plant Equipment 631-205-105, MESA® SOLE Electronic Enclosure, Description and Emerson Network Power Aerial Distribution Products 631-201-009 Version D, October 11, 2011 4. JUMPER WIRING 4.1 Before You Begin Before running cross-connect jumper wire, craft personnel should become familiar with the numbering sequence used in the terminal as described in Paragraph 2.4 and Paragraph 2.5. Feeder and distribution fields are color-coded. Feeder cables are terminated in the green field and distribution cables are terminated in the blue field. Begin by terminating each 22 AWG "G" or 24 AWG "F" cross-connecting jumper wire pair as described in Section 4.2, Terminating Jumper Wires on CQF Blocks or Section 4.3, Terminating Jumper Wires on RLS Blocks. 4.2 Terminating Jumper Wires on CQF Blocks Perform the following steps to terminate a jumper wire pair on a CQF terminal block in the feeder field: Step 1: Pull enough jumper wire from the spool mounted on the housing door to reach the assigned feeder cable terminal binding post (see Fig. 8). Fig. 8 : Pulling Jumper Wire Step 2: Terminate the jumper wire on the terminal binding post as shown below (see Fig. 9). • Strip approximately 1/2-inch of insulation from the end of the jumper wire. Do not nick the conductor. • Loosen the screw on the binding post until the first washer rides out in front of the terminal silo. Outside Plant Equipment Proprietary Information Page 7 of 12 631-201-009 Version D, October 11, 2011 Emerson Network Power Aerial Distribution Products Step 3: Place the wire between the washers on the terminal binding post. Tighten securely, but do not over tighten (see Fig. 10). Fig. 9 : Jumper Wire Termination Fig. 10 : Placing Wire Between Washers on Binding Post Step 4: Continue on to Section 4.4, Routing Wire to route the wires. 4.3 Terminating Jumper Wires on RLS Blocks For specific information on terminating wire pairs on RLS blocks, see document 641-202-002, RLS50 Self-Strip Block Description and Installation. For information on dual wire termination to a pair, see document 641-202-009, RLS50 Self-Strip Block Feed-Thru Half-Tap Activator Kit Description and Installation. Once you have terminated a wire pair, continue on to Section 4.4, Routing Wire to route the wires. Page 8 of 12 Proprietary Information Outside Plant Equipment Emerson Network Power Aerial Distribution Products 631-201-009 Version D, October 11, 2011 4.4 Routing Wire Perform the following steps to route a jumper wire pair: Step 1: Route the wires horizontally between the activator rows to the wiring trough (see Fig. 11). Fig. 11 : Routing Wire Step 2: Place the wire behind the wire retainers at the sides or bottom of the terminal field, and make a finger loop in the wire to provide enough slack to trace the wires when necessary. Step 3: Route the cross-connecting jumper wire to the assigned distribution post or activator and cut to required length. Step 4: Terminate the jumper wire pair on the distribution field as you did on the feeder field. Outside Plant Equipment Proprietary Information Page 9 of 12 631-201-009 Version D, October 11, 2011 Emerson Network Power Aerial Distribution Products 5. ACCESSORIES 5.1 Table B lists ordering information for available accessories. TABLE B - ACCESSORIES Catalog Number Description P29869 spools shaft for cross-connect wire P33392 one-pair tester - CQF P69681 one-pair tester - RLS P38220 special service caps - CQF (package of 80) P53828 special service caps - RLS (package of 80) P44195 green (feeder) CQF block numbers 1-1500 P49940 green (feeder) CQF block numbers 1500-2700 P49941 blue (distribution) CQF block numbers 2701-3600 P44196 blue (distribution) CQF block numbers 1-2700 P64541 green (feeder) RLS block numbers 1-2100 P53350 blue (distribution) RLS block numbers 1-3600 P90370E off-white touch-up paint, 0.6 ounce bottle 5.2 Spool Shafts for Cross-Connect Jumper Wire G cross-connect spool holds 300 feet; F cross-connect spool holds 400 feet. Terminals have a spool shaft and retainer provided on the inside of the door (see Fig. 12). Page 10 of 12 Proprietary Information Outside Plant Equipment Emerson Network Power Aerial Distribution Products 631-201-009 Version D, October 11, 2011 5.3 One-Pair Tester Terminals have a one-pair tester secured to a mounting dish on the door of each terminal (see Fig. 13). Fig. 12 : Jumper Wire Spool Shaft Fig. 13 : One-Pair Tester, CQF Fig. 14 : Special Services Protective Cap 5.4 Special Service Protective Cap These are red plastic caps that fit over the silos surrounding the binding posts or activators (see Fig. 14). A package with eighty pairs of caps is furnished with each terminal. 5.5 Label Kits for the Terminal Blocks These are available in green or blue colored labels. The green label kits are used for pair counts in the feeder fields. The blue label kits are for pair counts in the distribution field. Specify numbers required. Outside Plant Equipment Proprietary Information Page 11 of 12 631-201-009 Version D, October 11, 2011 Emerson Network Power Aerial Distribution Products NOTES Emerson Network Power / 4350 Weaver Parkway / Warrenville, Illinois 60555 / (630) 579-5000 / FAX (630) 579-5050 © 2011 Emerson Network Power, Energy Systems, North America, Inc. All rights reserved. Any unauthorized reproduction or transmission without the prior consent of Emerson Network Power is prohibited. www.EmersonNetworkPower.com/EnergySystems Specifications subject to change without notice. Emerson Network Power, Energy Systems, North America, Inc. disclaims any responsibility or liability for the use of the information contained in this practice. Page 12 of 12 NetPerform™ Optimization Services At Emerson Network Power, we understand the importance of reliable equipment – it’s critical to both your business and your bottom line. That is why we offer a wide array of services to meet all of your network infrastructure needs. Technical Support Email Phone DCpower.TAC@Emerson.com OSP.TAC@Emerson.com 1.800.800.5260 Answers technical product and system questions; determines status of warranties and contractual agreements for repair. Services - Design, Deployment & Optimization Email ES.Services@Emerson.com Phone 1.800.800.1280, option 7 FreedomCare Secure.EmersonNetworkPower.com Provides quotes and bid responses, order placement and scheduling for design, and deployment and optimization services. Download service & maintenance reports online. Spare Parts Email Phone DCpower.Spares@Emerson.com OSP.Spares@Emerson.com 1.800.800.1280, option 5 Pricing and PO processing of spare parts, including but not limited to breakers, cables, fuses, rectifier fans, misc. breaker and fuse panels, enclosure fans, doors & switches, etc. DC Power Depot Repair Email DCpower.Repair@Emerson.com Phone 1.800.800.1280, option 6 Creates and processes RMAs, determines lead times and pricing, provides repair shipping information and status. DC Power Product Training Email Phone DCpower.Training@Emerson.com Requests for quotes, order placement and scheduling. 1.800.800.1280, option 8 For More Information To learn more about service offerings from Emerson Network Power, please contact your sales representative, call 1-800-800-1280 option 7, email ES.Services@Emerson.com or visit www.EmersonNetworkPower.com/EnergySystems. Emerson (NYSE: EMR), based in St. Louis, Missouri (USA), is a global leader in bringing technology and engineering together to provide innovative solutions for customers in industrial, commercial, and consumer markets through its network power, process management, industrial automation, climate technologies, and tools and storage businesses. For more information, visit: Emerson.com. Emerson Network Power, a business of Emerson (NYSE:EMR), is the global leader in enabling Business-Critical Continuity™ from grid to chip for telecommunication networks, data centers, health care and industrial facilities. Emerson Network Power provides innovative solutions and expertise in areas including AC and DC power, precision cooling, embedded computing and power, integrated racks and enclosures, power switching and controls, infrastructure management, and connectivity. All solutions are supported globally by local Emerson Network Power service technicians. For more information on Emerson Network Power’s full suite of solutions specifically supporting the communications network infrastructure, including NetSpan™, NetReach™ and NetXtend™ outside plant enclosures and equipment, NetSure™ DC power systems, and NetPerform™ Optimization, Design & Deployment services, visit: EmersonNetworkPower.com/EnergySystems. . Learn more about Emerson Network Power products and services at: EmersonNetworkPower.com. Emerson Network Power Energy Systems, North America 4350 Weaver Parkway, Warrenville, IL 60555 Toll Free: 800-800-1280 (USA and Canada) Telephone: 440-246-6999 Fax: 440-246-4876 Web: EmersonNetworkPower.com/EnergySystems EnergyNet: Secure.EmersonNetworkPower.com Emerson Network Power. The global leader in enabling Business-Critical Continuity™ . AC Power Connectivity DC Power EmersonNetworkPower.com Embedded Computing Embedded Power Outside Plant Power Switching & Controls Racks & Integrated Cabinets Services Infrastructure Management & Monitoring Precision Cooling Surge Protection