Connectivity to the ASCO Modbus

advertisement
Connectivity to the ASCO 5210 Digital Power Meter via Modbus
This design specification describes the Modbus
communications protocol as supported by the Power Meter
5210. It includes instructions on how to pass information
into and out of the device via the Modbus network. This
publication should be used by individuals wishing to
integrate either device into their facility by developing
software to communicate with either device. Additional
information can be found in Power Meter Operator’s
Manual 381333-368.
Modbus Protocol
Implementation Basics
The following rules define the Modbus slave
implementation of the devices:
 The devices operate as slaves only
(communication must be initiated by the master).
 The maximum number of bytes contained within one
packet of communications is 64.
 The maximum number of registered accessed with
one read is 29.
the network will act on the command, but it will not
issue any responses.
Function Code Field. This is a second byte of each
transmission and represents the commanded action to the
slave device (for queries from the master) or the action that
was taken by the slave device (for responses from the
slave). Codes between 1 and 127 are defined as Modbus
RTU functions. The function codes supported by the
Power Meter are detailed on pages 4-6 .
Data Field. The data field varies in length depending on
whether the message is a request or a response packet.
This field typically contains information required by the
slave device to perform the command specified in a
request packet or data being passed back by the slave
device in a response packet.
Error Check Field. The error check field consists of a
16 bit (2 byte) Cyclical Redundancy Check (CRC16). It
allows the receiving device to detect a packet that has been
corrupted with transmission errors. Refer to CRC-16
Algorithm on page 2 for details.
Packet Framing and Timing
Transmission Format
Although the Modbus protocol supports both ASCII and
RTU modes of transmission, only the RTU mode is
implemented. Within the RTU mode, the ASCO devices
support the following communication parameters:
 8 data bits
 no parity
 1 stop bit
Modbus RTU Packet Format
Every Modbus Packet consists of the following fields:




Device Address Field
Function Code Field
Data Field
Error Check Field
Because the Modbus RTU protocol does not define any
explicit packet synchronization bytes, synchronization is
accomplished implicitly with the use of silent intervals.
According to the Modbus RTU standard, all messages
must start with a silent interval of at least 3.5 character
times. This means that every byte within a packet must
precede the previous byte by fewer than 3.5 character
times based on the baud rate. And every new packet of
data must begin at least 3.5 character times or more after
the packet that had preceded it.
In summary, the three timing intervals associated with the
ASCO devices are as follows:
 Maximum time between two consecutive bytes
within a packet < 3.5 character times.
 Minimum time between two consecutive packets is
> 3.5 character times.
Device Address Field. This is the first byte of each
Modbus RTU transmission. The device address is a
number limited to the range of 0 - 247 and is
associated with a single device configured with a
matching address. Only the slave device whose
address matches the value in this field will respond to
the specified command. Device address 0 indicates a
broadcast command. This means that every slave on
 Maximum response time from a Master request to a
slave response is < 100 milliseconds.
ASCO Power Technologies, L.P., 50 Hanover Rd., Florham Park, NJ 07932 USA
1
381339-307 D
CRC-16 Algorithm
Procedure. The algorithm essentially treats the entire
data packet (less the start, stop, and, if used, parity bits) as
one continuous binary number. Since we are doing a 16-bit
CRC calculation, the binary number (entire packet) is
multiplied by 216 and then divided by the generator
polynomial. In the case of the Modbus protocol, the
generator polynomial is x16 + x15 + x2 + 1. The 16-bit
remainder of the division, which is the 16-bit CRC
checksum, is then appended to the end of the packet. The
resulting data packet including the 16-bit CRC checksum,
when divided by the same Generator Polynomial at the
receiver, will give a zero remainder if no transmission
errors have occurred.
1. Initially, load the 16-bit CRC register with the value
FFFF hex.
2. Exclusive OR the 16-bit CRC register with the first data
byte of the packet and store the result in the 16-bit CRC
register.
3. If the Least Significant Bit (LSB) of the 16-bit CRC
register is equal to one, then shift the 16-bit CRC
register to the right by one bit and then Exclusive OR
the result with the generator polynomial, A001 hex.
Otherwise, just shift the 16-bit CRC register to the right
by one bit.
4. Repeat step 3 until eight right shifts have been
performed.
The binary value of the Generator Polynomial is A001
hex. This is obtained by first dropping the mostsignificant-bit of the polynomial and then reversing the bit
order. This yields 1010000000000001 or A001h.
5. Exclusive OR the 16-bit CRC register with the next data
byte of the packet.
The steps for generating the 16-bit CRC checksum are as
follows:
7. The 16-bit CRC register contains the new checksum to
be appended to the end of the packet, Least Significant
Byte first.
6. Repeat steps 3-5 until all the bytes of the data packet
have been used in step 5.
CRC-16 Pseudocode. Below is the pseudocode for generating the 16-bit CRC checksum. XOR is the Exclusive-OR
function:
CRC16REG = FFFF hex
GENPOLY = A001 hex
FOR X = 1 to number of bytes in packet
BEGIN
XOR CRC16REG with the Xth data byte
FOR Y = 1 to 8
BEGIN
IF [(the least-significant-bit of CRC16REG) = 1] THEN
SHIFT CRC16REG one bit to the RIGHT
XOR CRC16REG with GENPOLY
OTHERWISE
SHIFT CRC16REG one bit to the RIGHT
END
NEXT Y
END
NEXT X
The resulting CRC16REG contains the 16-bit CRC checksum
CRC-16 C Programming Language Example. CRC16_checksum is a C language function that calculates and
returns the 16-bit CRC checksum of a string of characters. This is the brute force method as it consumes a lot of
processing power performing numerous bit shifts. A table look-up method based on this function would be more suitable
for embedded systems where processing power is at a premium. The following four parameters are passed as part of the
function
1. pointer to string
2. length of string (in bytes)
3. initial CRC value
4. desired Generator polynomial
Included to make this CRC-16 function generic for any generator polynomial
continued on next page
2
ASCO Power Technologies, L.P., 50 Hanover Rd., Florham Park, NJ 07932 USA
381339-307 D
The following C-language type definitions (typedef’s) are assumed:
1. typedef unsigned int uint;
2. typedef unsigned char uchar;
The function is defined as follows:
uint CRC16_checksum(uchar *Buffer, uint Length, uint CRC, uint Genpoly) {
uint index;
While (Length--) {
/* for each data byte in string */
CRC = CRC ^ (uint) *Buffer++;
/* exclusive OR data byte */
For (index = 0; index < 8; index++) {
/* for each of the 8 bits */
If ((CRC & 0x0001) == 1) CRC = (CRC >> 1) ^ Genpoly;
Else (CRC = CRC >> 1);
} /* for statement */
} /* while statement */
}
return(CRC);
An ASCO Example. Let’s assume the transmitting device desired to send the ASCII string “ASCO”. Using an ASCII
character look-up table, we have the following hexadecimal codes for each of the ASCO letters:
A = 0x65
S = 0x83
C = 0x67
O = 0x79
The transmitter would determine the 16-bit CRC checksum as follows (in C, both methods are equivalent):
CRC16_checksum(“ASCO”, 4, 0xFFFF, 0xA001) which returns CRC = 0xCD94
CRC16_checksum(“\x65\x83\x67\x79”, 4, 0xFFFF, 0xA001) which returns CRC = 0xCD94
Before sending the string, the transmitter would append the CRC checksum (in byte reverse order) to the string as follows:
“ASCO\x94\xCD” or the equivalent in hexadecimal notation “\x65\x83\x67\x79\x94\xCD”
If the receiving device received the string without any transmission errors, then doing the 16-bit CRC checksum on the
entire received string would yield (again, both methods are equivalent):
CRC16_checksum(“ASCO\x94\xCD”, 4, 0xFFFF, 0xA001) which returns CRC = 0x0000
CRC16_checksum(“\x65\x83\x67\x79\x94\xCD”, 4, 0xFFFF, 0xA001) which returns CRC = 0x0000
Since the CRC checksum is equal to zero, the transmission is deemed valid.
Had an error been induced during the transmission, such as the ASCII character ‘A’ being inadvertently changed to the
character ‘B’ (which is hexadecimal 0x66), the receiving device would determine the new checksum as:
CRC16_checksum(“BSCO\x94\xCD”, 4, 0xFFFF, 0xA001) which returns CRC = 0x3300
CRC16_checksum(“\x66\x83\x67\x79\x94\xCD”, 4, 0xFFFF, 0xA001) which returns CRC = 0x3300
Since the CRC is NON-ZERO (0x3300), the receiver would assume an error had occurred and discard the packet.
ASCO Power Technologies, L.P., 50 Hanover Rd., Florham Park, NJ 07932 USA
381339-307 D
3
Supported Function Codes for Power Meter
Function # 03 (03h) – Read Holding Registers
This function code allows the master to read one or more
consecutive data registers from the Power Meter. The data
registers are always 16 bit (two byte) values, transmitted
high order byte first. Refer to Register Map on page 09 for
details about the data register definitions of the Power
Meter.
The following example shows the format of a transmission
between a master requesting device and the responding
Power Meter (slave device) at address 24. The master
desires to read the four values of voltage, VA, VB, VC,
VAVE, beginning at Holding register location 40011 (which
is a “Data starting address” of 11decimal or 0A
hexadecimal).
Master Transmission
Packet Format
Slave address
Function code
Data starting address (high byte)
Data starting address (low byte)
Number of registers (high byte)
Number of registers (low byte)
CRC16 (low byte)
CRC16 (high byte)
Example (in hex)
18
03
00
0A
00
04
66
02
Slave Response
Packet Format
Slave address
Function code
Byte count
Data word #1 (high byte)
Data word #1 (low byte)
Data word #2 (high byte)
Data word #2 (low byte)
Data word #3 (high byte)
Data word #3 (low byte)
Data word #4 (high byte)
Data word #4 (low byte)
CRC16 (low byte)
CRC16 (high byte)
Example (in hex)
18
03
08
00
E6
00
E5
00
E7
00
E6
14
2E
The Power Meter supports the following Read Holding
Register addresses-decimal: 11-26, 31-46, 48, 51-64, 7184, 87-93, 96-125, 127-137, 213, 435-576, 578-697,699730. The Type of those Registers is defined as RO (Read
only).
Function # 06 (06h) – Preset Single Register
This function code allows the master device to modify the
contents of a single configuration register within the Power
Meter. The data registers are always 16 bit (two byte)
values, transmitted high order byte first. Refer to Register
Map on page 09 for details about the about the data
register definitions of the Power Meter.
4
The Power Meter currently supports the following Preset
Single register addresses. If a Function #06 command is
issued without one of these registers addresses, the Power
Meter will respond with an invalid address range
Exception Response (see Exception Responses on page 6).
40065
40066
40141
40142
40143
40144
40145
40146
40200
40201
40202
40203
40204
Address
(in hex
notation)
0040
0041
008C
008D
008E
008F
0090
0091
00C7
00C8
00C9
00CA
00CB
40205
40206
40207
00CC
00CD
00CE
40208
40209
40210
00CF
00D0
00D1
40211
40212
40214
40215
4032240325
4042240431
40433
40434
40698
40755
00D2
00D3
00D5
00D6
141-144
Nominal Voltage
Nominal Current
Power Meter Hours
Power Meter Minutes
Power Meter Year
Power Meter Month
Power Meter Date
Power Meter Day of Week
System type
Source mode
Potential transformer ratio (PTR)
Current transformer ratio (CTR)
Neutral current transformer ratio
(CT4R)
SCI comm. port (J5) protocol
SCI comm. port (J5) baud rate
SCI comm. port (J5) device
address
485 comm. Port (J1) protocol
485 comm. Port (J1) baud rate
485 comm. port (J1) device
address
Menu language selection
Demand Integration Period
Clear Demand
Clear Energies
Power Meter Name
1A5-1AE
Power Meter Location
Address
01B0
01B1
02B9
02F2
Description
Clear Min Max Parameters
CT installed
Date Format
Clear all Demands
The following example shows the format of a transmission
between a master device and the responding Power Meter
(slave device) at address 24. The master desires to set the
System Type (Holding register 40200) to a Single Phase –
3 Wire system (data value 02). See System Type on page
07 for details.
Master Transmission
Packet Format
Slave address
Function code
Data address (high byte)
Data address (low byte)
Data word (high byte)
Data word (low byte)
CRC16 (low byte)
CRC16 (high byte)
ASCO Power Technologies, L.P., 50 Hanover Rd., Florham Park, NJ 07932 USA
381339-307 D
Example (in hex)
18
06
00
C7
00
02
BB
FF
Slave Response
Packet Format
Slave address
Function code
Data starting address (high byte)
Data starting address (low byte)
Number of registers (high byte)
Number of registers (low byte)
CRC16 (low byte)
CRC16 (high byte)
Example (in hex)
18
06
00
C7
00
02
BB
FF
The following example shows the format of a transmission
between a master requesting device and the responding
Power Meter (slave device) at address 24. The master
desires to configure Power Meter name (Holding Registers
40322 – 40425) to “ASCOMAP ”.
The Power Meter supports the following Preset Single
Register addresses -decimal:65-66,141-146,200-212,214215 ,433,434,698,755.
Function # 16 (10h) – Preset Multiple Registers
This function code allows the master device to modify the
contents of consecutive configuration registers within the
Power Meter. The data registers are always 16 bit (two
byte) values, transmitted high order byte first. Refer to
Register Map on page 10 for details about the data register
definitions of the Power Meter.
The Power Meter currently supports the following Preset
Multiple register ranges. If a Function #16 command is
issued without one of these corresponding register ranges,
the Power Meter will respond with an invalid address
range Exception Response (see Exception Responses on
page 6).
Mutli write register e.g. 40200-212 only support entire range
write and not the intermediate range such as 200-203, 205207
The Power Meter supports the following Preset Multiple
Register addresses -decimal: 200-212,141-146, 322-325,
422-431.
Address
Start
End
40065
40066
40200
40211
40322
40325
40422
40431
Register
Count
2
12
4
10
Description
General Settings
General Settings
Power Meter Name
Power Meter Location
Master Transmission
Packet Format
Slave address
Function code
Data starting address (high byte)
Data starting address (low byte)
Number of registers (high byte)
Number of registers (low byte)
Byte count
Data word #1 (high byte)
Data word #1 (low byte)
Data word #2 (high byte)
Data word #2 (low byte)
Data word #3 (high byte)
Data word #3 (low byte)
Data word #4 (high byte)
Data word #4 (low byte)
CRC16 (low byte)
CRC16 (high byte)
Example (in hex)
18
10
01
41
00
04
08
41 “A”
53 ”S”
43 “C”
4F “O”
4D “M”
41 “A”
50 “P”
20 “ ”
16
69
Slave Response
Packet Format
Slave address
Function code
Data starting address (high byte)
Data starting address (low byte)
Number of registers (high byte)
Number of registers (low byte)
CRC16 (low byte)
CRC16 (high byte)
Example (in hex)
18
10
01
41
00
04
92
2B
Command String (in Hex)
ADDR 10 00 C7 00 02 04 ..data.. CRCLO CRCHI
ADDR 10 00 C7 00 0C 18 ..data.. CRCLO CRCHI
ADDR 10 00 E5 00 04 08 ..data.. CRCLO CRCHI
ADDR 10 01 45 00 0A 14 ..data.. CRCLO CRCHI
ASCO Power Technologies, L.P., 50 Hanover Rd., Florham Park, NJ 07932 USA
381339-307 D
5
Exception Responses
If the Modbus master device sends an unsupported
command, attempts to read an invalid holding register, or
attempts to write invalid data, the Power Meter (Modbus
slave) issues an exception response. The format for the
exception response is as follows:
1. SLAVE ADDRESS
2. FUNCTION CODE*
(With the most-significant-bit set to a 1)
3. ERROR CODE
4. CRC16 – low order byte
5. CRC16 – high order byte
* Note: The high order bit of the function code has
been set to one to indicate an exception response has
been generated.
The following table is a list of the exception codes
supported by the Power Meter.
Exception Response Error Codes
Error
code
01
02
03
Error
name
Illegal
function
Illegal
data
address
Illegal
data
value
Power Meter
implementation
The slave does not support the
function code contained in the master
query packet.
The slave does not support the Holding
Register address referenced in the
data field of the master query packet.
The slave does not support the data
referenced in the data field of the
master query packet.
The following example shows the format of a transmission between a master device and the responding
Power Meter (slave device) at address 24. The master
device attempts to write an invalid data value (04) to the
System Type holding register 40200. The Power Meter
slave device responds with Error code 03.
Master Transmission
Packet Format
Slave address
Function code
Data starting address (high byte)
Data starting address (low byte)
Data (high byte)
Data (low byte)
CRC16 (low byte)
CRC16 (high byte)
Example (in hex)
18
06
00
C7
00
04
3B
FD
Slave Response
Packet Format
Slave address
Function code
Error code
CRC16 (low byte)
CRC16 (high byte)
Example (in hex)
18
86
03
D3
A6
The following example shows the format of a transmission
between a master device and the responding Power Meter
(slave device) at address 24. The master device attempts
to write to an invalid address, 40216 (0x00D7). The Power
Meter slave device responds with Error code 02.
Master Transmission
Packet Format
Slave address
Function code
Data starting address (high byte)
Data starting address (low byte)
Data (high byte)
Data (low byte)
CRC16 (low byte)
CRC16 (high byte)
Example (in hex)
18
06
00
D7
00
03
7B
FA
Slave Response
Packet Format
Slave address
Function code
Error code
CRC16 (low byte)
CRC16 (high byte)
6
ASCO Power Technologies, L.P., 50 Hanover Rd., Florham Park, NJ 07932 USA
381339-307 D
Example (in hex)
18
86
02
12
66
Configuration Register Details for Power Meter
Register Map for Power Meter
The following table describes the mapping of the registers within the Power Meter to Holding Registers defined in the Modbus
protocol.
Note:
The addresses in the format of 4xxxx follow the MODICON MODBUS protocol for point addressing.
The actual address sent is the Register Address shown in the map minus the value 40001.
Register
Type
Parameter
Name
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
VAN
VBN
VCN
VAVE
VAB
VBC
VCA
VLAVE
VLUNBAL
VUNBAL
IA
IB
IC
IAVE
IUNBAL
IN
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
kWA
kWB
kWC
kWT
kVARA
kVARB
kVARC
kVART
PfA
PfB
PfC
PfT
kVAA
kVAB
kVAC
kVAT
RO
Freq.
40051
RO
NormkWHIMP
Normal kWH Import (LO word)
40052
RO
NormkWHIMP
Normal kWH Import (HO word)
40054
RO
NormkWHEXP
Normal kWH Export (HO word)
Reg Number
40001-40010
40011
40012
40013
40014
40015
40016
40017
40018
40019
40020
40021
40022
40023
40024
40025
40026
40027-40030
40031
40032
40033
40034
40035
40036
40037
40038
40039
40040
40041
40042
40043
40044
40045
40046
40047
40048
40049-40050
Parameter
Description
Undefined
Phase A line to neutral voltage
Phase B line to neutral voltage
Phase C line to neutral voltage
Line to neutral average voltage
A-B line to line voltage
B-C line to line voltage
C-A line to line voltage
Line to line average voltage
Line to line voltage unbalance
Line to neutral voltage unbalance
Phase A current
Phase B current
Phase C current
Average current
Current unbalance
CT4 or neutral current
Undefined
Active Power phase A
Active Power phase B
Active Power phase C
Active Power total
Reactive Power phase A
Reactive Power phase B
Reactive Power phase C
Reactive Power total
Power Factor phase A
Power Factor phase B
Power Factor phase C
Power Factor total
volt-ampere Power phase A
volt-ampere Power phase B
volt-ampere Power phase C
volt-ampere Power total
Undefined
Frequency on phase VA
Undefined
40055
RO
NormkWHNET
Normal kWH Net (LO word)
40056
RO
NormkWHNET
Normal kWH Net (HO word)
40058
RO
NormkVarHIMP
Normal kVarH Import (HO word)
40059
RO
NormkVarHEXP
Normal kVarH Export (LO word)
40060
RO
NormkVarHEXP
Normal kVarH Export (HO word)
7
Data Range
Units
0 – 59,999
0 – 59,999
0 – 59,999
0 – 59,999
0 – 59,000
0 – 59,000
0 – 59,000
0 – 59,000
0 – 100%
0 – 100%
0 – 29,999 (55000)
0 – 29,999 (55000)
0 – 29,999 (55000)
0 – 29,999 (55000)
0 – 100%
0 – 29,999 (55000)
Volt
Volt
Volt
Volt
Volt
Volt
Volt
Volt
Implemented
in Firmware
Version
Amp.
843086-004
843086-004
843086-004
843086-004
843086-004
843086-004
843086-004
843086-004
843086-004
843086-004
843086-004
843086-004
843086-004
843086-004
843086-004
843086-004
-29,999 to +29,999
-29,999 to +29,999
-29,999 to +29,999
-29,999 to +29,999
-29,999 to +29,999
-29,999 to +29,999
-29,999 to +29,999
-29,999 to +29,999
(-.99 to +1.00) * 100
(-.99 to +1.00) * 100
(-.99 to +1.00) * 100
(-.99 to +1.00) * 100
0 – 29,999
0 – 29,999
0 – 29,999
0 – 29,999
kW
kW
kW
kW
kVAR
kVAR
kVAR
kVAR
Pf
Pf
Pf
Pf
kVA
kVA
kVA
kVA
843086-004
843086-004
843086-004
843086-004
843086-004
843086-004
843086-004
843086-004
843086-004
843086-004
843086-004
843086-004
843086-004
843086-004
843086-004
843086-004
(40.00 to 80.00) * 100
Hz x 100
843086-004
kWH
843086-004
kWH
843086-004
kWH
843086-004
kWH
843086-004
kWH
843086-004
kVARH
843086-004
kVARH
843086-004
kVARH
843086-004
-1,999,999,999 to +
1,999,999,999
-1,999,999,999 to +
1,999,999,999
-1,999,999,999 to +
1,999,999,999
ASCO Power Technologies, L.P., 50 Hanover Rd., Florham Park, NJ 07932 USA
1
Amp.
Amp.
Amp.
Amp.
381339-307 D
Reg Number
Register
Type
Parameter
Name
40061
RO
NormkVarHNET
Normal kVarH Net (LO word)
40062
RO
NormkVarHNET
Normal kVarH Net (HO word)
Parameter
Description
Data Range
-1,999,999,999 to +
1,999,999,999
40063
RO
NormkVAHNET
Normal kVAH Net (LO word)
-1,999,999,999 to +
1,999,999,999
40064
40065
40066
40067-40070
RO
RW
RW
NormkVAHNET
Nom_Volt
Nom_Amps
Normal kVAH Net (HO word)
Nominal Voltage
Nominal Current
Undefined
70-59999
1-55000
40071
RO
EmerkWHIMP
Emerg kWH Import (LO word)
-1,999,999,999 to +
1,999,999,999
40072
RO
EmerkWHIMP
Emerg kWH Import (HO word)
40073
RO
EmerkWHEXP
Emerg kWH Export (LO word)
40074
RO
EmerkWHEXP
Emerg kWH Export (HO word)
40075
RO
EmerkWHNET
Emerg kWH Net (LO word)
40076
RO
EmerkWHNET
Emerg kWH Net (HO word)
40077
RO
EmerkVarHIMP
Emerg kVarH Import (LO word)
40078
RO
EmerkVarHIMP
Emerg kVarH Import (HO word)
40079
RO
EmerkVarHEXP
Emerg kVarH Export (LO word)
40080
RO
EmerkVarHEXP
Emerg kVarH Export (HO word)
40081
RO
EmerkVarHNET
Emerg kVarH Net (LO word)
40082
RO
EmerkVarHNET
Emerg kVarH Net (HO word)
40083
RO
EmerkVAHNET
Emerg kVAH Net (LO word)
40084
40085-40086
40087
40088
40089
40090
40091
40092
40093
40094-40095
40096
40097
40098
40099
40100
40101
40102-40107
40108-40113
40114-40119
40120-40125
40126
40127
40128-40129
40130
40131
40132
RO
EmerkVAHNET
RO
RO
RO
RO
RO
RO
RO
kWT
kWT
kWT
kWT
IAVE
VLAVE
Freq.
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
SwitchPosition
kWT
kVART
kVAT
PfT
Freq.
V_String
SW_Date
SerialNumber
ModelNumber
RO
H_STATUS
RO
RO
RO
kWT
kWT
kWT
Emerg kVAH Net (HO word)
Undefined
Active Power (Watts) total
Instantaneous Watt Demand
Current Month Maximum Demand
Active Power (watts) Total
Average current
Line to line average voltage
Frequency on phase VA
Undefined
Main & auxiliary Switch positions
Active Power total
Reactive Power total
volt-ampere Power total
Power Factor total
Frequency on phase VA
Software Version string
Software build date string
Device serial number
Device model number
Undefined
Health status word
Undefined
Active Power (Watts) total
Instantaneous Watt demand
Current Month Maximum Demand
Current Month Maximum Watt
Demand Date
Current Month Maximum Watt
Demand Month
Current Month Maximum Watt
Demand Year
Current Month Maximum Watt
Demand Hour
8
40133
RO
40134
RO
40135
RO
40136
RO
-1,999,999,999 to +
1,999,999,999
-1,999,999,999 to +
1,999,999,999
-1,999,999,999 to +
1,999,999,999
-1,999,999,999 to +
1,999,999,999
-1,999,999,999 to +
1,999,999,999
-1,999,999,999 to +
1,999,999,999
-29,999 to +29,999
-29,999 to +29,999
-29,999 to +29,999
-29,999 to +29,999
0 – 29,999(55,000)
0 – 59,999
(40.00 to 80.00) * 100
0:normal 1:emergency
-29,999 to +29,999
-29,999 to +29,999
0 – 29,999
(-0.99 to +1.00) * 100
(40.00 to 80.00) * 100
12 ASCII characters
12 ASCII characters
12 ASCII characters
12 ASCII characters
Units
Implemented
in Firmware
Version
kVARH
843086-004
kVARH
843086-004
kVAH
843086-004
kVAH
Volt
Amp.
843086-004
843086-004
843086-004
kWH
843086-004
kWH
843086-004
kWH
843086-004
kWH
843086-004
kWH
843086-004
kWH
843086-004
kVARH
843086-004
kVARH
843086-004
kVARH
843086-004
kVARH
843086-004
kVARH
843086-004
kVARH
843086-004
kVAH
843086-004
kVAH
843086-004
kW
kW
kW
843086-004
843086-011
843086-011
Amp.
Volt
Hz x 100
843086-004
843086-004
843086-004
kW
kVAR
kVA
Pf x 100
Hz x 100
0:Normal 1:Error
843086-004
843086-004
843086-004
843086-004
843086-004
843086-004
843086-004
843086-004
843086-004
843086-004
843086-004
-29,999 to +29,999
-29,999 to +29,999
-29,999 to +29,999
kW
kW
kW
843086-004
843086-011
843086-011
1-31
Date
843086-011
1-12
Month
843086-011
00-99
Year
843086-011
00-23
Hour
843086-011
ASCO Power Technologies, L.P., 50 Hanover Rd., Florham Park, NJ 07932 USA
381339-307 D
Reg Number
Register
Type
40137
RO
40138-40140
40141
40142
40143
40144
40145
40146
40147-40199
RW
RW
RW
RW
RW
RW
Parameter
Name
Parameter
Description
Current Month Maximum Watt
Demand Minute
Undefined
Power Meter Hours
Power Meter Minutes
Power Meter Year
Power Meter Month
Power Meter Date
Power Meter Day of week
Undefined
40200
RW
TYPESYSTEM
System Type
40201
RW
MODESOURCE
Source Mode
40202
40203
40204
RW
RW
RW
PTR
CTR
CT4R
40205
RW
PROTOCOLSCI
SCI comm. port (J5) protocol
40206
RW
BAUDSCI
SCI comm. port (J5) baud rate
40207
RW
ADDRSCI
SCI comm. port (J5) device address
40208
RW
PROTOCOL485
485 comm. port (J1) protocol
40209
RW
BAUD485
485 comm. port (J1) baud rate
40210
40211
40212
RW
RW
RW
ADDR485
TYPELANG
MIN
40213
RO
Subintl_Size
40214
WO
Clear_Demand
40215
40216-40321
40322-40325
40326-40421
40422-40431
40432
40433
WO
Clear_Energy
RW
PM-Name
RW
PM-Location
RW
485 comm. port (J1) device address
Language selection
Demand Integration period
Demand Subinterval Size(Fixed at
1 minute)
Reset Instantaneous and Current
Month maximum Demand registers
to 0
Clears Energy registers to 0
Undefined
Power Meter Name
Undefined
Power Meter Location
Undefined
Clear Min max parameters
40434
RW
CT installed
40435
40436
40437
40438
40439
40440
40441
40442
40443
40444
40445
40446
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
OTHER kWH Import (LO word)
OTHER kWH Import (HO word)
OTHER kWH Export (LO word)
OTHER kWH Export (HO word)
OTHER kWH Net (LO word)
OTHER kWH Net (HO word)
OTHER kVarH Import (LO word)
OTHER kVarH Import (HO word)
OTHER kVarH Export (LO word)
OTHER kVarH Export (HO word)
OTHER kVarH Net (LO word)
OTHER kVarH Net (HO word)
Potential Transformer Ratio
Current Transformer Ratio
4th Current Input Transformer Ratio
Data Range
00-59
0-23
0-59
0-99
1-12
1-31
0-6
0:3∅-4 w wye
1:3∅-3 w delta
2:1∅-3 w
3:1∅-2 w
0: normal
1: emergency
2: load
3: other (note 4)
120 to 28200 (note 5)
5 to 55000
OFF to 55000
1:ASCOBUS II
2:Modbus RTU
1:9600
2:19.2k
1 to 239
1:ASCOBUS II
2:Modbus RTU
1:9600
2:19.2k
3:38.4k
4:57.6k
1 to 239
0 to 8 (Note 1)
1 to 15
Units
Implemented
in Firmware
Version
Minute
843086-011
Hours
Minutes
Year
Month
Date
Day
843086-011
843086-011
843086-011
843086-011
843086-011
843086-011
843086-004
843086-004
843086-004
843086-004
843086-004
843086-004
843086-004
843086-004
843086-004
843086-004
Minutes
843086-004
843086-004
843086-011
(Write value 0x0000)
843086-011
(Write value 0xFFFF)
843086-004
8 ASCII chars
843086-004
20 ASCII chars
843086-004
(Write value 0xFFFF)
0:A-B-C
1:A
2:B
3:C
0 to + 1,999,999,999
843086-004
0 to + 1,999,999,999
0 to + 1,999,999,999
0 to + 1,999,999,999
0 to + 1,999,999,999
0 to + 1,999,999,999
ASCO Power Technologies, L.P., 50 Hanover Rd., Florham Park, NJ 07932 USA
381339-307 D
843086-004
kWH
kWH
kWH
kWH
kWH
kWH
kVARH
kVARH
kVARH
kVARH
kVARH
kVARH
843086-004
843086-004
843086-004
843086-004
843086-004
843086-004
843086-004
843086-004
843086-004
843086-004
843086-004
843086-004
9
Reg Number
Register
Type
40447
40448
RO
RO
40449
RO
40450
RO
40451
RO
40452
RO
40453
RO
40454
RO
40455
RO
40456
RO
40457
RO
40458
RO
40459
RO
40460
RO
40461
RO
40462
RO
40463
RO
40464
RO
40465
RO
40466
RO
40467
RO
40468
RO
40469
RO
40470
RO
40471
RO
40472
RO
40473
RO
40474
RO
40475
RO
40476
RO
40477
RO
40478
RO
40479
RO
10
Parameter
Name
Parameter
Description
OTHER kVAH Net (LO word)
OTHER kVAH Net (HO word)
% of Full scale Rated current in A
Phase
% of Full scale Rated current in B
Phase
% of Full scale Rated current in C
Phase
% of Full scale Rated Active Power
in A Phase
% of Full scale Rated Active Power
in B Phase
% of Full scale Active Power
current in C Phase
NORMAL Minimum Voltage on A
Phase
NORMAL Maximum Voltage on A
Phase
NORMAL Minimum Voltage on B
Phase
NORMAL Maximum Voltage on
B Phase
NORMAL Minimum Voltage on C
Phase
NORMAL Maximum Voltage on
C Phase
NORMAL Minimum L-N Average
Voltage
NORMAL Maximum L-N Average
Voltage
NORMAL Minimum Voltage on
AB Phase
NORMAL Maximum Voltage on
AB Phase
NORMAL Minimum Voltage on
BC Phase
NORMAL Maximum Voltage on
BC Phase
NORMAL Minimum Voltage on
CA Phase
NORMAL Maximum Voltage on
CA Phase
NORMAL Minimum L-L Average
Voltage
NORMAL Maximum L-L Average
Voltage
NORMAL Minimum Current in A
Phase
NORMAL Maximum Current in A
Phase
NORMAL Minimum Current in B
Phase
NORMAL Maximum Current in B
Phase
NORMAL Minimum Current in C
Phase
NORMAL Maximum Current in C
Phase
NORMAL Minimum Average
Current
NORMAL Maximum Average
Current
NORMAL Minimum Current in
Data Range
0 to + 1,999,999,999
Units
Implemented
in Firmware
Version
kVAH
kVAH
843086-004
843086-004
0 to 200
843086-004
0 to 200
843086-004
0 to 200
843086-004
0 to 200
843086-004
0 to 200
843086-004
0 to 200
843086-004
0 to 59999
Volt
843086-004
0 to 59999
Volt
843086-004
0 to 59999
Volt
843086-004
0 to 59999
Volt
843086-004
0 to 59999
Volt
843086-004
0 to 59999
Volt
843086-004
0 to 59999
Volt
843086-004
0 to 59999
Volt
843086-004
0 to 59999
Volt
843086-004
0 to 59999
Volt
843086-004
0 to 59999
Volt
843086-004
0 to 59999
Volt
843086-004
0 to 59999
Volt
843086-004
0 to 59999
Volt
843086-004
0 to 59999
Volt
843086-004
0 to 59999
Volt
843086-004
0 – 55,000
Amp.
843086-004
0 – 55,000
Amp.
843086-004
0 – 55,000
Amp.
843086-004
0 – 55,000
Amp.
843086-004
0 – 55,000
Amp.
843086-004
0 – 55,000
Amp.
843086-004
0 – 55,000
Amp.
843086-004
0 – 55,000
Amp.
843086-004
0 – 55,000
Amp.
843086-004
ASCO Power Technologies, L.P., 50 Hanover Rd., Florham Park, NJ 07932 USA
381339-307 D
Reg Number
Register
Type
40480
RO
40481
RO
40482
RO
40483
RO
40484
RO
40485
RO
40486
RO
40487
RO
40488
RO
40489
RO
40490
RO
40491
RO
40492
RO
40493
RO
40494
RO
40495
RO
40496
RO
40497
RO
40498
RO
40499
RO
40500
RO
40501
RO
40502
RO
40503
RO
40504
RO
40505
RO
40506
RO
40507
RO
40508
RO
40509
RO
40510
RO
Parameter
Name
Parameter
Description
Neutral
NORMAL Maximum Current in
Neutral
NORMAL Minimum Active Power
on A Phase
NORMAL Maximum Active Power
on A Phase
NORMAL Minimum Active Power
on B Phase
NORMAL Maximum Active Power
on B Phase
NORMAL Minimum Active Power
on C Phase
NORMAL Maximum Active Power
on C Phase
NORMAL Minimum Total Active
Power
NORMAL Maximum Total Active
Power
NORMAL Minimum Reactive
Power on A Phase
NORMAL Maximum Reactive
Power on A Phase
NORMAL Minimum Reactive
Power on B Phase
NORMAL Maximum Reactive
Power on B Phase
NORMAL Minimum Reactive
Power on C Phase
NORMAL Maximum Reactive
Power on C Phase
NORMAL Minimum Total
Reactive Power
NORMAL Maximum Total
Reactive Power
NORMAL Minimum Apparent
Power on A Phase
NORMAL Maximum Apparent
Power on A Phase
NORMAL Minimum Apparent
Power on B Phase
NORMAL Maximum Apparent
Power on B Phase
NORMAL Minimum Apparent
Power on C Phase
NORMAL Maximum Apparent
Power on C Phase
NORMAL Minimum Total
Apparent Power
NORMAL Maximum Total
Apparent Power
NORMAL Minimum Power Factor
A Phase
NORMAL Maximum Power Factor
A Phase
NORMAL Minimum Power Factor
B Phase
NORMAL Maximum Power Factor
B Phase
NORMAL Minimum Power Factor
C Phase
NORMAL Maximum Power Factor
C Phase
Units
Implemented
in Firmware
Version
Amp.
843086-004
-32768 to +32768
kW
843086-004
-32768 to +32768
kW
843086-004
-32768 to +32768
kW
843086-004
-32768 to +32768
kW
843086-004
-32768 to +32768
kW
843086-004
-32768 to +32768
kW
843086-004
0 to 55000
kW
843086-004
0 to 55000
kW
843086-004
-32768 to +32768
kVAR
843086-004
-32768 to +32768
kVAR
843086-004
-32768 to +32768
kVAR
843086-004
-32768 to +32768
kVAR
843086-004
-32768 to +32768
kVAR
843086-004
-32768 to +32768
kVAR
843086-004
0 to 55000
kVAR
843086-004
0 to 55000
kVAR
843086-004
-32768 to +32768
kVA
843086-004
-32768 to +32768
kVA
843086-004
-32768 to +32768
kVA
843086-004
-32768 to +32768
kVA
843086-004
-32768 to +32768
kVA
843086-004
-32768 to +32768
kVA
843086-004
0 to 55000
kVA
843086-004
0 to 55000
kVA
843086-004
(-0.99 to +1.00) * 100
Pf x 100
843086-004
(-0.99 to +1.00) * 100
Pf x 100
843086-004
(-0.99 to +1.00) * 100
Pf x 100
843086-004
(-0.99 to +1.00) * 100
Pf x 100
843086-004
(-0.99 to +1.00) * 100
Pf x 100
843086-004
(-0.99 to +1.00) * 100
Pf x 100
843086-004
Data Range
0 – 55,000
ASCO Power Technologies, L.P., 50 Hanover Rd., Florham Park, NJ 07932 USA
381339-307 D
11
Reg Number
Register
Type
40511
RO
40512
RO
40513
RO
40514
RO
40515
RO
40516
RO
40517
RO
40518
RO
40519
RO
40520
RO
40521
RO
40522
RO
40523
RO
40524
RO
40525
RO
40526
RO
40527
RO
40528
RO
40529
RO
40530
RO
40531
RO
40532
RO
40533
RO
40534
RO
40535
RO
40536
RO
40537
RO
40538
RO
40539
RO
40540
RO
40541
RO
40542
RO
12
Parameter
Name
Parameter
Description
NORMAL Minimum Total Power
Factor
NORMAL Maximum Total Power
Factor
NORMAL Minimum System
Frequency
NORMAL Maximum System
Frequency
EMERG Minimum Voltage on A
Phase
EMERG Maximum Voltage on A
Phase
EMERG Minimum Voltage on B
Phase
EMERG Maximum Voltage on B
Phase
EMERG Minimum Voltage on C
Phase
EMERG Maximum Voltage on C
Phase
EMERG Minimum L-N Average
Voltage
EMERG Maximum L-N Average
Voltage
EMERG Minimum Voltage on AB
Phase
EMERG Maximum Voltage on AB
Phase
EMERG Minimum Voltage on BC
Phase
EMERG Maximum Voltage on BC
Phase
EMERG Minimum Voltage on CA
Phase
EMERG Maximum Voltage on CA
Phase
EMERG Minimum L-L Average
Voltage
EMERG Maximum L-L Average
Voltage
EMERG Minimum Current in A
Phase
EMERG Maximum Current in A
Phase
EMERG Minimum Current in B
Phase
EMERG Maximum Current in B
Phase
EMERG Minimum Current in C
Phase
EMERG Maximum Current in C
Phase
EMERG Minimum Average
Current
EMERG Maximum Average
Current
EMERG Minimum Current in
Neutral
EMERG Maximum Current in
Neutral
EMERG Minimum Active Power
on A Phase
EMERG Maximum Active Power
Data Range
Units
Implemented
in Firmware
Version
(-0.99 to +1.00) * 100
Pf x 100
843086-004
(-0.99 to +1.00) * 100
Pf x 100
843086-004
(40 to 100) * 100
Hz x 100
843086-004
(40 to 100) * 100
Hz x 100
843086-004
0 to 59999
Volt
843086-004
0 to 59999
Volt
843086-004
0 to 59999
Volt
843086-004
0 to 59999
Volt
843086-004
0 to 59999
Volt
843086-004
0 to 59999
Volt
843086-004
0 to 59999
Volt
843086-004
0 to 59999
Volt
843086-004
0 to 59999
Volt
843086-004
0 to 59999
Volt
843086-004
0 to 59999
Volt
843086-004
0 to 59999
Volt
843086-004
0 to 59999
Volt
843086-004
0 to 59999
Volt
843086-004
0 to 59999
Volt
843086-004
0 to 59999
Volt
843086-004
0 – 55,000
Amp.
843086-004
0 – 55,000
Amp.
843086-004
0 – 55,000
Amp.
843086-004
0 – 55,000
Amp.
843086-004
0 – 55,000
Amp.
843086-004
0 – 55,000
Amp.
843086-004
0 – 55,000
Amp.
843086-004
0 – 55,000
Amp.
843086-004
0 – 55,000
Amp.
843086-004
0 – 55,000
Amp.
843086-004
-32768 to +32768
kW
843086-004
-32768 to +32768
kW
843086-004
ASCO Power Technologies, L.P., 50 Hanover Rd., Florham Park, NJ 07932 USA
381339-307 D
Reg Number
Register
Type
40543
RO
40544
RO
40545
RO
40546
RO
40547
RO
40548
RO
40549
RO
40550
RO
40551
RO
40552
RO
40553
RO
40554
RO
40555
RO
40556
RO
40557
RO
40558
RO
40559
RO
40560
RO
40561
RO
40562
RO
40563
RO
40564
RO
40565
RO
40566
RO
40567
RO
40568
RO
40569
RO
40570
RO
40571
RO
40572
RO
40573
RO
Parameter
Name
Parameter
Description
on A Phase
EMERG Minimum Active Power
on B Phase
EMERG Maximum Active Power
on B Phase
EMERG Minimum Active Power
on C Phase
EMERG Maximum Active Power
on C Phase
EMERG Minimum Total Active
Power
EMERG Maximum Total Active
Power
EMERG Minimum Reactive Power
on A Phase
EMERG Maximum Reactive Power
on A Phase
EMERG Minimum Reactive Power
on B Phase
EMERG Maximum Reactive Power
on B Phase
EMERG Minimum Reactive Power
on C Phase
EMERG Maximum Reactive Power
on C Phase
EMERG Minimum Total Reactive
Power
EMERG Maximum Total Reactive
Power
EMERG Minimum Apparent Power
on A Phase
EMERG Maximum Apparent
Power on A Phase
EMERG Minimum Apparent Power
on B Phase
EMERG Maximum Apparent
Power on B Phase
EMERG Minimum Apparent Power
on C Phase
EMERG Maximum Apparent
Power on C Phase
EMERG Minimum Total Apparent
Power
EMERG Maximum Total Apparent
Power
EMERG Minimum Power Factor A
Phase
EMERG Maximum Power Factor A
Phase
EMERG Minimum Power Factor B
Phase
EMERG Maximum Power Factor B
Phase
EMERG Minimum Power Factor C
Phase
EMERG Maximum Power Factor C
Phase
EMERG Minimum Total Power
Factor
EMERG Maximum Total Power
Factor
EMERG Minimum System
Frequency
Data Range
Units
Implemented
in Firmware
Version
-32768 to +32768
kW
843086-004
-32768 to +32768
kW
843086-004
-32768 to +32768
kW
843086-004
-32768 to +32768
kW
843086-004
0 to 55000
kW
843086-004
0 to 55000
kW
843086-004
-32768 to +32768
kVAR
843086-004
-32768 to +32768
kVAR
843086-004
-32768 to +32768
kVAR
843086-004
-32768 to +32768
kVAR
843086-004
-32768 to +32768
kVAR
843086-004
-32768 to +32768
kVAR
843086-004
0 to 55000
kVAR
843086-004
0 to 55000
kVAR
843086-004
-32768 to +32768
kVA
843086-004
-32768 to +32768
kVA
843086-004
-32768 to +32768
kVA
843086-004
-32768 to +32768
kVA
843086-004
-32768 to +32768
kVA
843086-004
-32768 to +32768
kVA
843086-004
0 to 55000
kVA
843086-004
0 to 55000
kVA
843086-004
(-0.99 to +1.00) * 100
Pf x 100
843086-004
(-0.99 to +1.00) * 100
Pf x 100
843086-004
(-0.99 to +1.00) * 100
Pf x 100
843086-004
(-0.99 to +1.00) * 100
Pf x 100
843086-004
(-0.99 to +1.00) * 100
Pf x 100
843086-004
(-0.99 to +1.00) * 100
Pf x 100
843086-004
(-0.99 to +1.00) * 100
Pf x 100
843086-004
(-0.99 to +1.00) * 100
Pf x 100
843086-004
(40 to 100) * 100
Hz x 100
843086-004
ASCO Power Technologies, L.P., 50 Hanover Rd., Florham Park, NJ 07932 USA
381339-307 D
13
Reg Number
Register
Type
40574
RO
40575
RO
40576
RO
40577
WO
40578
RO
14
Parameter
Name
Parameter
Description
40579
RO
40580
40581
40582
40583
40584
40585
40586
40587
RO
RO
RO
RO
RO
RO
RO
RO
EMERG Maximum System
Frequency
Resettable Engine Runtime counter
in Hours
Cumulative Engine Runtime
counter in Hours
Clear Resettable Engine Run time
counter
Expanded Health Status Register
(LO Word)
Expanded Health Status Register
(HO Word)
Phase A Voltage THD
Phase B Voltage THD
Phase C Voltage THD
Phase A Current THD
Phase B Current THD
Phase C Current THD
APAC Port Enable
APAC Address
40588
RO
APAC Baud rate
40589
RO
Heart Beat time
40590
RO
Transmit PDO1 Transmission Type
40591
40592
RO
RO
Transmit PDO1 Inhibit Time
Transmit PDO1 Event Time
40593
RO
Transmit PDO2 Transmission Type
40594
40595
RO
RO
Transmit PDO2 Inhibit Time
Transmit PDO2 Event Time
40596
RO
Transmit PDO3 Transmission Type
40597
40598
RO
RO
Transmit PDO3 Inhibit Time
Transmit PDO3 Event Time
40599
RO
Transmit PDO4 Transmission Type
Data Range
(40 to 100) * 100
Units
Implemented
in Firmware
Version
Hz x 100
843086-004
0 to 65535
Hour
843086-004
0 to 65535
Hour
843086-004
(Write value 0xFFFF)
843086-004
843086-004
0 to 31 (Note 2)
843086-004
0 to 100%
0 to 100%
0 to 100%
0 to 100%
0 to 100%
0 to 100%
1 – Enable; 2 – Disable
1 to 127
0 – 100Kbps; 1 –
250Kbps;
2 – 500Kbps; 3 –
1000Kbps;
0 to 60000
0 to 255
0 – OFF;
254 – Timed based on
Event Time & Inhibit
Timer
255 – Timed based on
Event Time, Inhibit
Timer & on change of
the mapped parameters
0 to 60000
0 to 60000
0 to 255 0 – OFF;
254 – Timed based on
Event Time & Inhibit
Timer; 255 – Timed
based on Event Time,
Inhibit Timer & on
change of the mapped
parameters
0 to 60000
0 to 60000
0 to 255 0 – OFF;
254 – Timed based on
Event Time & Inhibit
Timer; 255 – Timed
based on Event Time,
Inhibit Timer & on
change of the mapped
parameters
0 to 60000
0 to 60000
0 to 255 0 – OFF;
254 – Timed based on
Event Time & Inhibit
Timer; 255 – Timed
based on Event Time,
Inhibit Timer & on
change of the mapped
parameters
ASCO Power Technologies, L.P., 50 Hanover Rd., Florham Park, NJ 07932 USA
381339-307 D
843086-007
843086-007
843086-007
843086-007
843086-007
843086-007
843086-011
843086-011
843086-011
msec
843086-011
843086-011
msec
msec
843086-011
843086-011
843086-011
msec
msec
843086-011
843086-011
843086-011
msec
msec
843086-011
843086-011
843086-011
Reg Number
Register
Type
40600
40601
40602
RO
RO
RO
40603
RO
First Month Date (Date, Month)
40604
RO
First Month Year (Year, Hours)
40605
RO
40606
RO
40607
RO
Second Month Date (Date, Month)
40608
RO
Second Month Year (Year, Hours)
40609
RO
40610
RO
40611
RO
Third Month Date (Date, Month)
40612
RO
Third Month Year (Year, Hours)
40613
RO
40614
RO
40615
RO
Fourth Month Date (Date, Month)
40616
RO
Fourth Month Year (Year, Hours)
40617
RO
40618
RO
40619
RO
Fifth Month Date (Date, Month)
40620
RO
Fifth Month Year (Year, Hours)
40621
RO
40622
RO
40623
RO
Sixth Month Date (Date, Month)
40624
RO
Sixth Month Year (Year, Hours)
40625
RO
40626
RO
40627
RO
Seventh Month Date (Date, Month)
40628
RO
Seventh Month Year (Year, Hours)
40629
RO
40630
RO
40631
RO
Eighth Month Date (Date, Month)
40632
RO
Eighth Month Year (Year, Hours)
40633
RO
40634
RO
40635
RO
Ninth Month Date (Date, Month)
40636
RO
Ninth Month Year (Year, Hours)
Parameter
Name
KW
KW
KW
KW
KW
KW
KW
KW
KW
Parameter
Description
Transmit PDO4 Inhibit Time
Transmit PDO4 Event Time
First Month Max Demand
First Month Minutes (Minutes,
Seconds)
Second Month Max Demand
Second Month Minutes (Minutes,
Seconds)
Third Month Max Demand
Third Month Minutes (Minutes,
Seconds)
Fourth Month Max Demand
Fourth Month Minutes (Minutes,
Seconds)
Fifth Month Max Demand
Fifth Month Minutes (Minutes,
Seconds)
Sixth Month Max Demand
Sixth Month Minutes (Minutes,
Seconds)
Seventh Month Max Demand
Seventh Month Minutes (Minutes,
Seconds)
Eighth Month Max Demand
Eighth Month Minutes (Minutes,
Seconds)
Ninth Month Max Demand
Data Range
0 to 60000
0 to 60000
-29,999 to +29,999
Date (1-31),Month (112)
Year (0-99), Hours (023)
0-59
-29,999 to +29,999
Date (1-31),Month (112)
Year (0-99), Hours (023)
0-59
-29,999 to +29,999
Date (1-31),Month (112)
Year (0-99), Hours (023)
0-59
-29,999 to +29,999
Date (1-31),Month (112)
Year (0-99), Hours (023)
0-59
-29,999 to +29,999
Date (1-31),Month (112)
Year (0-99), Hours (023)
0-59
-29,999 to +29,999
Date (1-31),Month (112)
Year (0-99), Hours (023)
0-59
-29,999 to +29,999
Date (1-31),Month (112)
Year (0-99), Hours (023)
0-59
-29,999 to +29,999
Date (1-31),Month (112)
Year (0-99), Hours (023)
0-59
-29,999 to +29,999
Date (1-31),Month (112)
Year (0-99), Hours (023)
ASCO Power Technologies, L.P., 50 Hanover Rd., Florham Park, NJ 07932 USA
381339-307 D
Units
msec
msec
kW
Date,
Month
Year, Hours
Minutes,
Seconds
kW
Date,
Month
Year, Hours
Minutes,
Seconds
kW
Date,
Month
Year, Hours
Minutes,
Seconds
kW
Date,
Month
Year, Hours
Minutes,
Seconds
kW
Date,
Month
Year, Hours
Implemented
in Firmware
Version
843086-011
843086-011
843086-011
843086-011
843086-011
843086-011
843086-011
843086-011
843086-011
843086-011
843086-011
843086-011
843086-011
843086-011
843086-011
843086-011
843086-011
843086-011
843086-011
843086-011
843086-011
Minutes,
Seconds
kW
Date,
Month
843086-011
Year, Hours
843086-011
843086-011
843086-011
Minutes,
Seconds
kW
Date,
Month
843086-011
Year, Hours
843086-011
Minutes,
Seconds
kW
Date,
Month
Year, Hours
843086-011
843086-011
843086-011
843086-011
843086-011
843086-011
Minutes,
Seconds
kW
Date,
Month
843086-011
Year, Hours
843086-011
843086-011
843086-011
15
Reg Number
Register
Type
40637
RO
40638
RO
40639
RO
Tenth Month Date (Date, Month)
40640
RO
Tenth Month Year (Year, Hours)
40641
RO
40642
RO
40643
RO
40644
RO
40645
RO
40646
RO
40647
RO
40648
RO
40649
RO
40650
RO
40651
RO
40652
RO
40653
RO
40654
RO
40655
RO
40656
RO
40657
RO
40658
RO
40659
RO
40660
RO
40661
RO
40662
RO
40663
RO
40664
RO
40665
RO
40666
RO
40667
RO
40668
RO
40669
RO
16
Parameter
Name
KW
KW
KW
KW
KW
KW
KW
KW
Parameter
Description
Ninth Month Minutes (Minutes,
Seconds)
Tenth Month Max Demand
Tenth Month Minutes (Minutes,
Seconds)
Eleventh Month Max Demand
Eleventh Month Date (Date,
Month)
Eleventh Month Year (Year,
Hours)
Eleventh Month Minutes (Minutes,
Seconds)
Twelveth Month Max Demand
Twelveth Month Date (Date,
Month)
Twelveth Month Year (Year,
Hours)
Twelveth Month Minutes
(Minutes, Seconds)
Thirteenth Month Max Demand
Thirteenth Month Date (Date,
Month)
Thirteenth Month Year (Year,
Hours)
Thirteenth Month Minutes
(Minutes, Seconds)
Data Range
0-59
-29,999 to +29,999
Date (1-31),Month (112)
Year (0-99), Hours (023)
0-59
-29,999 to +29,999
Date (1-31),Month (112)
Year (0-99), Hours (023)
0-59
-29,999 to +29,999
Date (1-31),Month (112)
Year (0-99), Hours (023)
0-59
-29,999 to +29,999
Date (1-31),Month (112)
Year (0-99), Hours (023)
0-59
Fourteenth Month Max Demand
Fourteenth Month Date (Date,
Month)
Fourteenth Month Year (Year,
Hours)
Fourteenth Month Minutes
(Minutes, Seconds)
-29,999 to +29,999
Date (1-31),Month (112)
Year (0-99), Hours (023)
Fifteenth Month Max Demand
Fifteenth Month Date (Date,
Month)
Fifteenth Month Year (Year,
Hours)
Fifteenth Month Minutes (Minutes,
Seconds)
-29,999 to +29,999
Date (1-31),Month (112)
Year (0-99), Hours (023)
Sixteenth Month Max Demand
Sixteenth Month Date (Date,
Month)
Sixteenth Month Year (Year,
Hours)
Sixteenth Month Minutes
(Minutes, Seconds)
-29,999 to +29,999
Date (1-31),Month (112)
Year (0-99), Hours (023)
Seventeenth Month Max Demand
Seventeenth Month Date (Date,
Month)
Seventeenth Month Year (Year,
Hours)
Seventeenth Month Minutes
(Minutes, Seconds)
-29,999 to +29,999
Date (1-31),Month (112)
Year (0-99), Hours (023)
0-59
0-59
0-59
0-59
ASCO Power Technologies, L.P., 50 Hanover Rd., Florham Park, NJ 07932 USA
381339-307 D
Units
Implemented
in Firmware
Version
Minutes,
Seconds
kW
Date,
Month
843086-011
Year, Hours
843086-011
Minutes,
Seconds
kW
Date,
Month
Year, Hours
Minutes,
Seconds
kW
Date,
Month
Year, Hours
Minutes,
Seconds
kW
Date,
Month
843086-011
843086-011
843086-011
843086-011
843086-011
843086-011
843086-011
843086-011
843086-011
843086-011
843086-011
843086-011
843086-011
Year, Hours
843086-011
Minutes,
Seconds
843086-011
kW
Date,
Month
843086-013
843086-013
Year, Hours
843086-013
Minutes,
Seconds
843086-013
kW
Date,
Month
843086-013
843086-013
Year, Hours
843086-013
Minutes,
Seconds
843086-013
kW
Date,
Month
843086-013
843086-013
Year, Hours
843086-013
Minutes,
Seconds
843086-013
kW
Date,
Month
843086-013
Year, Hours
843086-013
Minutes,
Seconds
843086-013
843086-013
Reg Number
Register
Type
Parameter
Name
40670
RO
KW
40671
RO
40672
RO
40673
RO
40674
RO
40675
RO
40676
RO
40677
RO
40678
RO
40679
RO
40680
RO
40681
RO
40682
RO
40683
RO
40684
RO
40685
RO
40686
RO
40687
RO
40688
RO
40689
RO
40690
RO
40691
RO
40692
RO
40693
RO
40694
RO
40695
RO
40696
RO
40697
RO
40698
RW
KW
KW
KW
KW
KW
KW
Parameter
Description
Data Range
Eighteenth Month Max Demand
Eighteenth Month Date (Date,
Month)
Eighteenth Month Year (Year,
Hours)
Eighteenth Month Minutes
(Minutes, Seconds)
-29,999 to +29,999
Date (1-31),Month (112)
Year (0-99), Hours (023)
Nineteenth Month Max Demand
Nineteenth Month Date (Date,
Month)
Nineteenth Month Year (Year,
Hours)
Nineteenth Month Minutes
(Minutes, Seconds)
-29,999 to +29,999
Date (1-31),Month (112)
Year (0-99), Hours (023)
Twentieth Month Max Demand
Twentieth Month Date (Date,
Month)
Twentieth Month Year (Year,
Hours)
Twentieth Month Minutes
(Minutes, Seconds)
-29,999 to +29,999
Date (1-31),Month (112)
Year (0-99), Hours (023)
Twenty First Month Max Demand
Twenty First Month Date (Date,
Month)
Twenty First Month Year (Year,
Hours)
Twenty First Month Minutes
(Minutes, Seconds)
-29,999 to +29,999
Date (1-31),Month (112)
Year (0-99), Hours (023)
Twenty Second Month Max
Demand
Twenty Second Month Date (Date,
Month)
Twenty Second Month Year (Year,
Hours)
Twenty Second Month Minutes
(Minutes, Seconds)
Twenty Third Month Max Demand
Twenty Third Month Date (Date,
Month)
Twenty Third Month Year (Year,
Hours)
Twenty Third Month Minutes
(Minutes, Seconds)
Twenty Fourth Month Max
Demand
Twenty Fourth Month Date (Date,
Month)
Twenty Fourth Month Year (Year,
Hours)
Twenty Fourth Month Minutes
(Minutes, Seconds)
Date Format
0-59
0-59
0-59
0-59
-29,999 to +29,999
Date (1-31),Month (112)
Year (0-99), Hours (023)
0-59
-29,999 to +29,999
Date (1-31),Month (112)
Year (0-99), Hours (023)
0-59
-29,999 to +29,999
Date (1-31),Month (112)
Year (0-99), Hours (023)
0-59
0 to 2
ASCO Power Technologies, L.P., 50 Hanover Rd., Florham Park, NJ 07932 USA
381339-307 D
Units
Implemented
in Firmware
Version
kW
Date,
Month
843086-013
Year, Hours
843086-013
Minutes,
Seconds
843086-013
kW
Date,
Month
843086-013
843086-013
843086-013
Year, Hours
843086-013
Minutes,
Seconds
843086-013
kW
Date,
Month
843086-013
843086-013
Year, Hours
843086-013
Minutes,
Seconds
843086-013
kW
Date,
Month
843086-013
Year, Hours
843086-013
Minutes,
Seconds
843086-013
kW
843086-013
Date,
Month
843086-013
Year, Hours
843086-013
Minutes,
Seconds
843086-013
843086-013
kW
Date,
Month
843086-013
Year, Hours
843086-013
Minutes,
Seconds
843086-013
kW
843086-013
Date,
Month
843086-013
Year, Hours
843086-013
Minutes,
Seconds
0 – US
Format
1 – EU
Format
2 – ISO
Format
843086-013
843086-013
843086--013
17
Reg Number
Register
Type
Parameter
Name
Parameter
Description
40699
40700
40701
40702
40703
40704
RO
RO
RO
RO
RO
RO
KW
40705
RO
Last 60 Mins Max Demand
Last 60 Mins Max Demand Date
Last 60 Mins Max Demand Month
Last 60 Mins Max Demand Year
Last 60 Mins Max Demand Hours
Last 60 Mins Max Demand Minutes
Last 60 Mins Max Demand
Seconds
40706
RO
40707
40708
40709
40710
40711
RO
RO
RO
RO
RO
40712
RO
40713
RO
40714
Last 60 Mins Max Demand Day
KW
RO
40715
40716
40717
40718
40719
40720
RO
RO
RO
RO
RO
RO
40721
RO
Last 24 Hours Max Demand
Last 24 Hours Max Demand Date
Last 24 Hours Max Demand Month
Last 24 Hours Max Demand Year
Last 24 Hours Max Demand Hours
Last 24 Hours Max Demand
Minutes
Last 24 Hours Max Demand
Seconds
Last 24 Hours Max Demand Day
KW
Last 30 Days Max Demand
Last 30 Days Max Demand Date
Last 30 Days Max Demand Month
Last 30 Days Max Demand Year
Last 30 Days Max Demand Hours
Last 30 Days Max Demand Minutes
Last 30 Days Max Demand
Seconds
40722
RO
18
40723
40724
RO
RO
40725
RO
40726
RO
40727
RO
40728
RO
40729
RO
Last 30 Days Max Demand Day
KW
Last 12 Months Max Demand
Last 12 Months Max Demand Date
Last 12 Months Max Demand
Month
Last 12 Months Max Demand Year
Last 12 Months Max Demand
Hours
Last 12 Months Max Demand
Minutes
Last 12 Months Max Demand
Seconds.
Data Range
Units
Implemented
in Firmware
Version
-29,999 to +29,999
Date (1-31)
Month (1-12)
Year (0-99)
Hours (0-23)
0-59
kW
Date
Month
Year
Hours
Minutes
843086-013
843086-013
0-59
Seconds
843086-013
0–6
0 – Sunday;
1 – Monday;
2 – Tuesday;
3 – Wednesday;
4 – Thursday;
5 – Friday;
6 – Saturday
-29,999 to +29,999
Date (1-31)
Month (1-12)
Year (0-99)
Hours (0-23)
843086-013
843086-013
843086-013
843086-013
kW
Date
Month
Year
Hours
843086-013
843086-013
843086-0132
843086-013
843086-013
0-59
Minutes
843086-013
0-59
Seconds
843086-013
0–6
0 – Sunday;
1 – Monday;
2 – Tuesday;
3 – Wednesday;
4 – Thursday;
5 – Friday;
6 – Saturday
843086-013
-29,999 to +29,999
Date (1-31)
Month (1-12)
Year (0-99),
Hours (0-23)
0-59
kW
Date
Month
Year
Hours
Minutes
843086-013
843086-013
843086-013
843086-013
843086-013
843086-013
0-59
Seconds
843086-013
0–6
0 – Sunday;
1 – Monday;
2 – Tuesday;
3 – Wednesday;
4 – Thursday;
5 – Friday;
6 – Saturday
-29,999 to +29,999
Date (1-31)
Month (1-12)
843086-013
kW
Date
Month
843086-013
843086-013
843086-013
Year (0-99),
Year
843086-013
Hours (0-23)
Hours
843086-013
0-59
Minutes
843086-013
0-59
Seconds
843086-013
ASCO Power Technologies, L.P., 50 Hanover Rd., Florham Park, NJ 07932 USA
381339-307 D
Reg Number
40730
Register
Type
RO
40731-40754
40755
Parameter
Name
Parameter
Description
Last 12 Months Max Demand Day
Data Range
Units
0–6
0 – Sunday;
1 – Monday;
2 – Tuesday;
3 – Wednesday;
4 – Thursday;
5 – Friday;
6 – Saturday
Implemented
in Firmware
Version
843086-013
Undefined
WO
Clear all Demands
(Write value 0x0000)
ASCO Power Technologies, L.P., 50 Hanover Rd., Florham Park, NJ 07932 USA
381339-307 D
Clear
Demand
843086-013
19
Note 3- Unexpected Interrupt Details:
Note 1 - Languages
Data
0
1
2
3
4
5
6
7
8
Language
English
Spanish
Italian
French
German
Portuguese
Russian
Korean
Chinese
Note 2- Bit Position in Health Register
Value
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
Functionality
EEPROM
DC Test
AC Test
RTC Test
LCD Test
Left Key Status
Right Key Status
Up Key Status
Down Key Status
ESC Key Status
Enter Key Status
Phase A ADC
Phase B ADC
Phase C ADC
Phase N ADC
RS485 Test
APAC1 Test
APAC2 Test
Digital Inputs Test
PLL Test
AC Good Test
LED Test
Calibration Status
Defaults loaded to all
structures in database
Defaults loaded to
Config structure in
database
Runtime ADC error
Unexpected Interrupt
value(note 10)
Not Used
Not Used
Description
Value
1
2
3
4
5
6
6
8
9
10
11
12
13
14
15
Description
SPI2 end-transfer/overrun
SCI1 or SCI2 error interrupt
SCC interrupt A
MibADC end event conversion
SW interrupt(SSI)
HET interrupt 2
HECC1 interrupt B
SCC interrupt B
MibADC end groupt 1 conversion
DMA interrupt 1
GIO interrupt B
MibADC end group 2 conversion
SCI3 error interrupt
HECC2 interrupt A
HECC2 interrupt B
Note 4- Source Mode – Holding Register no. 40201
The source mode register defines the source bus to which
the Power Meter is connected. The Energy register display
window changes according to the bus defined. The user
can specify a normal bus connection, an emergency bus
connection, a connection to the load side of the bus or no
specific designation.
0 - Normal
1 - Failed
Binary
value
0 (00h)
1 (01h)
2 (02h)
Label
Description
NORMAL
EMERGENCY
LOAD
3 (03h)
OTHER
Normal power bus
Emergency power bus
Load power bus
Any power bus with no
designation on the Energy
registers
When the LOAD selection is chosen, the Power Meter uses
the N/E INPUT status input to determine ATS switch
position. Two sets of Energy registers are used; Normal
energy registers & Emergency energy registers.
0-Normal
1 to 15-Failed
Note 5- Potential Transformer Ratio –
Register no. 40202
This register defines the full-scale voltage input value for
the three phases of voltage. This is based on the ratio of the
external voltage transformers (PTs) connected between the
Power Meter and the power bus.
Range
120 to 28,200
The value of 28,200 is the ratio 235:1 (120 * 235 =
28,200). Note that if external voltage transformers are not
required and subsequently not used, the ratio should be set
to 120, which is 1:1.
20
ASCO Power Technologies, L.P., 50 Hanover Rd., Florham Park, NJ 07932 USA
1
381339-307 D
Download