Rectifier R48-3200 The reliable and efficient R48-3200 rectifier reduces

advertisement
DC Power for
Business-Critical Continuity™
Rectifier
R48-3200
Key Features
n3200 watt rectifier
designed for -48V DC
power applications
nOptimized depth –
reduced footprint allows
installation in short-depth
racks and cabinets
nDSP (Digital Signaling
Processor) means fewer
components, optimized
operation and active load
sharing for increased
reliability
The reliable and efficient R48-3200 rectifier reduces
power consumption, lowering operating cost.
Description
The 3200 watt rectifier (R48-3200) is designed to convert standard AC supply voltages into stable nominal -48V DC voltage that is adjustable to application needs.
The R48-3200 is a constant power rectifier designed with the latest patented
switch-mode technology using DSP (Digital Signaling Processor) functionality for
efficient operation.
For a higher load capacity, rectifiers can be connected in parallel, and intelligent
control can be added with the help of a separate controller.
nCompliant with global
standards – delivers quality,
performance and reliability no
matter what the application
or location demands
nHigh efficiency, up to 92%,
reduces power consumption
for lower operating costs
nHot pluggable – facilitates
future extensions
nWide input voltage range –
operates in the most
demanding environments
where input voltage changes
nWide temperature operating
range (-40°C / -40°F to +75°C /
167°F) meets the harshest
climatic environment
requirements
2012.09
1
Rectifier R48-3200
Psophometric Noise (system)
Temperature Derating
Control and Monitoring
Rectifier Alarm and Signaling
Visual Indications
Environmental
Temperature Range, Operating
Temperature Range, Storage
Relative Humidity
Altitude
45 50
55
120
70
80
60
40
20
0
-40
-20
0
20
40
60
80
100
Temperature (°C)
Output Power vs. Input Voltage
at Temp <45°C
See diagram
67A
0 to 67A
92%
<1 mV
<32 dBrnc
(See diagram)
65
100
-42 to -58 V DC
3200W@Vout >48VDC
85
120
176
290
100
80
60
40
20
0
0
50
100
150
200
250
300
350
Input Voltage (VAC)
Alarm and status reported via CAN bus to system controller
Green LED:
Normal Operation
Yellow LED:
Alarm
Red LED:
Failure
Flashing Red LED:
Fan Failure
Safety
-40 to +75°C, -40 to +167°F
-40 to +75°C, -40 to +167°F
0 to 95%
2000 m, 6560 ft at full power
ETSI EN 300 386 class B, FCC CFR 47 Part 15 class B,
Telcordia GR-1089-CORE class B
IEC 60950, EN 60950, UL 60950
Mechanics
Dimensions (H x W x D)
Weight
132 x 85.3 x 287mm / 5.2 x 3.36 x 11.3 inches
3.5kg / 7.7Ibs
Other Parts
Controller Units
See separate ACU/ACU+ and SCU/SCU+ datasheets
EMC
Output Power vs. Temperature
264V ≥ Vin ≥ 176VAC
% of max output power
DC Output
Output Voltage, Adjustment Range
Output Power
Output Power, Derated for Input
Voltage
Output Current
Output Current Limit Set Point
Efficiency
200 to 250 V AC
85 to 290 V AC
45 to 55 Hz
20A
0.99
<5% from 50 to 100% of rated load
Output voltage vs. Output current,
max. output power 3200 W
Output Voltage (V)
AC Input
Input Voltage, Nominal
Input Voltage, Permitted Variation
Line Frequency
Max Input Current
Power Factor
THD (Total Harmonic Distortion)
Diagrams
% of max output power
Technical Specifications
70
60
50
40
30
20
10
0
0
55A
10 15 20
25 30 35 40
45
50 55
67A
60 65 70
75
Output Current (A)
Ordering Information
Model Number
1R483200XXX
Description
Rectifier 48V, 3200W
EmersonNetworkPower.com/EnergySystems (North America)
EmersonNetworkPower.eu/EnergySystems (EMEA)
© Emerson Network Power Energy Systems North America 2012.
Business-Critical Continuity™, Emerson Network Power™, the Emerson Network Power logo, Emerson® and Consider it Solved are service marks and trademarks of Emerson Electric Co.
EnergyMaster™, eSure™, NetPerform™, NetReach™, NetSpan™, NetSure® and NetXtend™ are trademarks of Emerson Network Power Energy Systems North America.
2
2012.09