400 Series 440 Surge Protective Device Submittal Specification General Specifications Maximum Continuous Operating Voltage Short Circuit Current Rating (SCCR) Maximum Surge Current Rating Operating Frequency Range EMI/RFI Noise Rejection UL1449 Location Type UL1449 Nominal Discharge Current (In) Status Indication (Standard) 120VAC 150%, all others 115% 200kAIC 50/100/150kA Per Mode, 100/200/300kA Per Phase 47-63Hz 40dB Max (Type 1), 60dB Max (Type 2) Type 1 / Type 2 20kA Green/Red LED, Audible Alarm, Alarm Test/Silence Feature, & Relay Alarm Contacts N-G Indication, Surge LED, Surge Counter, ATDS ANSI/UL 1449 Third Edition Type 1 or Type 2; cUL CE, IEC61643-11 Class I/II NEMA Type 4X Optional: NEMA 12, 4 (Steel) Standard Non-Metallic Enclosure- 3.8 lbs (1.8 kg); Optional NEMA 12 or 4 Enclosure- 12.7 lbs (7.8 kg) 10 Year Replacement Status Indication (Optional) Certifications IEC Class Standard Enclosure Weights Warranty ANSI/UL 1449 Third Edition, Type 1 VPR’s Source Configuration SA, YA YC YD DB / DF / DG Model Number Configurator L-N 800V 1200V 1500V N/A _4 _4 _0 _ _ _ _ _A _N _ _J _1 _S Configuration & Voltage SA Single Phase, 3W+G (L1, L2, N, G) YA Three Phase WYE, 4W+G (L1, L2, L3, N, G) Three Phase WYE, 4W+G (L1, L2, L3, N, G) Three Phase WYE, 4W+G (L1, L2, L3, N, G) YC YD DB DF DG Three Phase Delta, 3W+G (L1, L2, L3, G) Three Phase Delta, 3W+G (L1, L2, L3, G) Three Phase Delta, 3W+G (L1, L2, L3, G) 120/240 VAC 120/208 VAC, 127/220 VAC 05 10 15 277/480 VAC, 254/440 VAC A L C T 220 VAC, 230 VAC, 240 VAC 480 VAC S Standard X Consult Factory for additional source configurations, Surge Ratings, Monitoring Options, Enclosure Ratings, Etc. 9.6” [244] For a unit with the RJ-45 Ethernet port accessible on the front cover, change the enclosure rating from NEMA 4X (440xxxxxxxTJxx) to NEMA 1 (440xxxxxxxTCxx) Enclosure Type NEMA 12 Steel NEMA 4 Steel * Model Number 440xxxxxxALxx 440xxxxxxAGxx 10” x 8” x 4” [254] x [203] x [102] Monitoring Option Red & Green LEDs, Relay Alarm Contacts & Audible Alarm * Steel enclosure units require the “A” monitoring option. “A” option plus N-G LEDs & Surge LED “A” option plus N-G LEDs & Surge Counter Advanced Transient Detection System See publication SL-70109, TS-70109 CUL Approvals For all applications requiring CUL approvals, change the SPD model number from a UL Type 1 (440xxxxxxxx1x) to a UL Type 2 (440xxxxxxxx2x) NEMA 4X Enclosure (“J”) External Ethernet Port Option N-G 800V 1200V 1500V N/A Replace the “J” in the standard model number (11th digit) with an “L” or “G” as shown below for an optional steel enclosure. Dimensional Information 600 VAC L-L 1200V 2000V 2500V 2000V / 2000V / 3000V Optional Steel Enclosures NEMA 4 or NEMA 12 Additional Accessories Surge Rating 50kA Per Mode 100kA Per Phase 100kA Per Mode 200kA Per Phase 150kA Per Mode 300kA Per Phase 346/600 VAC L-G 800V 1200V 1500V 1200V / 1800V / 2000V ½” NPT FLEXIBLE CONDUIT Advanced Transient Detection System A Web-Based Power Quality Monitor Integrated within a Surge Protection Device 4.9” [124] 100 Emerson Parkway 4.0” Binghamton, NY 13905 [102] P (607) 721 8840 P (800) 288 6169 F (607) 722 8713 E contactsurge@emerson.com ½” NPT FLEXIBLE CONDUIT (24”) AND CONNECTOR ASSEMBLY INCLUDED Real-Time Measurements Event Logging with Time/Date Stamp Embedded Web Page Ethernet, MODBUS, RS-485 Communications SPD Health Status - % Protection remaining LCD Display 2.1” [53] 1.7” [44] SS-70108 Rev 2 1-15