Control & Relay Protection Philosophy for 400KV AMRELI Sub Station

advertisement
GETCO / E / 4S - 087/ PP - 015 – 1A / R1 Dt.15.12.2011
Control & Relay Protection Philosophy for 400KV AMRELI Sub Station
A) Bus Bar Configuration
400kV System : Three Bus (Two Main and Transfer)
220kV System : Three Bus (Two Main and Transfer)
66KV System : Two Bus (One Main and Transfer)
Isolator system
400kV System: Four isolator configuration (Three Bus isolators and a Line isolator)
220kV System: Four isolator configuration (Three Bus isolators and a Line isolator)
66KV System: Three isolator configuration (Two Bus and a Line isolator)
B) Control Voltage
220V DC
C) Control & Relay panels
Existing Bays – Conventional Control & Relay Panels mounted in Control Room to be
retrofitted for SCADA compatibility.
New Bays – SCADA compatible Control & Protection Panels to be mounted in
Yard Kiosk
D) PLCC panels
PLCC Panels to be mounted in Control Room
PLCC BCU panel to be mounted in Control Room for interface between Control &
protection Panels and PLCC Panels, through GOOSE commands
E) Existing Protection system
400KV:–
1. Feeder:–
Distance Protection Relays – Main-I & Main-II (Distance) Protection Numerical Relay
with IEC 61850 Protocol
LBB Protection – Separate Static Relay
Over Voltage Protection
o Stage -1 – Electromechanical / Static Relay,
o Stage -2 – Electromechanical / Static Relay
2. ICT: –
Differential Protection Relay - Numerical (Non IEC- 61850) MiCOM P632
Directional O/C-E/F Protection Relay - Numerical Relay with IEC 61850 Protocol
REF Protection Relay - Electromechanical Relay
LBB Protection – Separate Static Relay
3. Bus Reactor: Differential protection Relay - Numerical Relay with IEC 61850 Protocol
Backup Impedance Protection Relay - Numerical Relay with IEC 61850 Protocol
REF protection - Electromechanical Relay
LBB Protection – Separate Static Relay
4. Bus Coupler: Directional O/C-E/F protection Relay - Numerical Relay with IEC 61850 Protocol
LBB Protection – Separate Static Relay
5. TBC:Non-Directional O/C-E/F protection Relay - Numerical Relay with IEC 61850 Protocol
LBB Protection – Separate Static Relay
Page 1 of 6
GETCO / E / 4S - 087/ PP - 015 – 1A / R1 Dt.15.12.2011
6. Bus Bar Protection –
ABB make Static scheme - RADSS
220KV:1. Feeder:–
Distance Protection Relays –Numerical Relay with IEC 61850 Protocol
Directional O/C-E/F protection Relay - Numerical Relay with IEC 61850 Protocol
LBB Protection – Separate Static Relay
2. ICT LV:–
Directional O/C-E/F Protection Relay - Numerical Relay with IEC 61850 Protocol
LBB Protection – Separate Static Relay
3. Transformer:Differential protection Relay - Numerical (Non IEC 61850) MiCOM P632
Directional O/C-E/F Protection Relay - Numerical Relay with IEC 61850 Protocol
REF protection Relay - Electromechanical Relay
LBB Protection – Separate Static Relay
4. Bus Coupler:Non-Directional O/C-E/F protection Relay - Numerical Relay with IEC 61850 Protocol
LBB Protection – Separate Static Relay
5. TBC:Directional O/C-E/F protection Relay - Numerical Relay with IEC 61850 Protocol
LBB Protection – Separate Static Relay
6. Bus Bar Protection –
ABB make Static scheme - RADSS
66KV:1. Feeder:–
O/C-E/F protection Relay - Electromechanical or Numerical (Non IEC 61850) Relays
2. Transformer LV: –
O/C-E/F protection Relay - Numerical (Non-IEC 61850) Relays
3. Station Transformer: O/C-E/F protection Relay - Numerical (Non-IEC 61850) Relays
Disturbance Recorder & Event Logger – Stand alone DR & EL Panels
F) Retrofitting in Existing C&R Panels
400KV :–
1. ICT:–
Differential protection Relay - Numerical (Non IEC- 61850) MiCOM P632
(To be converted in to IEC 61850 compatible protection relay).
2. Bus Bar Protection: –
Existing ABB make static RADSS scheme is to be replaced with numerical IEC 61850
compatible Busbar protection scheme as per protection philosophy.
220KV:1. Transformer:Differential protection Relay - Numerical (Non IEC- 61850) MiCOM P632
(To be converted in to IEC 61850 compatible protection relay)
2. Bus Bar Protection –
Existing ABB make static RADSS scheme is to be replaced with numerical IEC 61850
compatible Busbar protection scheme as per protection philosophy.
Page 2 of 6
GETCO / E / 4S - 087/ PP - 015 – 1A / R1 Dt.15.12.2011
66KV :1. Feeder:–
O/C-E/F protection Relay shall be replaced with Numerical IEC 61850 compatible Bay
Control & Protection Relays as per protection philosophy.
2. Transformer LV: –
O/C-E/F protection Relay shall be replaced with Numerical IEC 61850 compatible Bay
Control & Protection Relays as per protection philosophy.
3. Station Transformer: Differential protection relay as per protection philosophy shall be provided
O/C-E/F protection Relay shall be replaced with Numerical IEC 61850 compatible Bay
Control & Protection Relays as per protection philosophy.
G)
Control & Protection for New Bays
It shall be as per Control & Protection philosophy tabulated as under.
H) Nos. of Bays & Bus Bar Protection
400 KV System
Line W/o Reactor Bay – 2 Nos.
ICT Bay – 2 Nos.
Bus Reactor Bay – 1 No.
TBC Bay – 1 No.
Bus Coupler Bay – 1 No.
New Line w/o Reactor Bays to be added – 6 Nos.
New Line with Reactor Bays to be added – 2 Nos.
New Bus Reactor Bay to be added – 1 No.
Bays to be connected to Bus Bar Protection - 16 Nos.
Total bays in the Sub Station will be – 16 Nos.
Bus Bar Protection
o Control Unit - 24 Bays
o Bay Units – 17 Nos. (16 +1 Spare) - 8 Nos to be provided in Control
Room Bus Bar Panel
- 9 Nos to be provided in C&P Panel in
Yard Kiosk
220 KV System
Feeder Bay – 4 Nos.
ICT LV Bays – 2 Nos.
220/66KV Transformer Bays – 3 Nos.
Bus Coupler Bay – 1 No.
TBC Bay – 1 No.
New Feeder Bays to be added – 2 Nos.
Bays to be connected to Bus Bar Protection - 13 Nos.
Future bays – 5 No.
Total bays in the Sub Station will be – 18 Nos.
Bus Bar Protection
o Control Unit - 24 Bays
o Bay Units – 14 Nos (13+1 Spare) - 12 Nos to be provided in Control Room
Bus Bar Panel
- 2 Nos to be provided in C&P Panel in
Yard Kiosk
66KV System
Feeder Bay – 4 Nos.
220/66KV Transformer LV Bays – 3 Nos
Page 3 of 6
GETCO / E / 4S - 087/ PP - 015 – 1A / R1 Dt.15.12.2011
66/11KV Transformer Bay – 1 No.
Total bays in the Sub Station – 8 Nos.
Control Philosophy – AMRELI Sub Station
System
400 KV Bay
Controlling Device to be Adopted
Bay Control Unit
Type of Controlling Device
BCU with IEC 61850 Protocol
220 KV Bay
Bay Control Unit
BCU with IEC 61850 Protocol
Bay Control & Protection Unit
BCPU with
Protocol
66 KV Bay
IEC
61850
Protection Philosophy – AMRELI Sub Station
A) Feeder Protection
400KV Feeders
400 KV Line W/o Reactor
1
2
3
400 KV Line with Reactor
1
2
3
4
Protection to be Adopted
Type of Relay
Two Distance Protection
Numerical Relay with IEC
[shall be of two different make 61850 Protocol
(i.e. from different
manufacturers) or of same make
with two different platforms with
same specifications]
-Main-I Protection &
-Main II Protection
Two Stage Over Voltage
Protection
- Stage I
- Separate Static Relay
- Stage II
- Integrated in Main I &
Main II Protection
Local Breaker Backup (LBB)
Integrated in Main I
Protection.
Protection and Bus Bar
protection
Two Distance Protection
Numerical Relay with IEC
[shall be of two different make 61850 Protocol
(i.e. from different
manufacturers) or of same make
with two different platforms with
same specifications]
- Main I Protection &
- Main II Protection
Two Stage Over Voltage
Protection
- Static Relay
- Stage I
- Integrated in Main I &
- Stage II
Main II Protection
Local Breaker Backup (LBB)
Integrated
in
Main
I
Protn.
Protection and
Main II
Protection
Reactor Differential Protection Numerical Relay with IEC
61850 Protocol
5 Reactor REF Protection
Numerical Relay with IEC
61850 Protocol
6 Backup Impedance Protection
Numerical Relay with IEC
61850 Protocol
Page 4 of 6
GETCO / E / 4S - 087/ PP - 015 – 1A / R1 Dt.15.12.2011
7 Buchholz Relay
8 Pressure Relief Device
9 Oil & Wdg. Temp. Alarm &
Tripping
10 Oil Level Low Alarm
400kV Bus Reactor
1 Reactor Differential Protection
Integrated in Reactor/ NGR.
Auxiliary relay in protection
panel.
Integrated
in
Reactor.
Auxiliary relay in protection
panel.
Integrated in Reactor/NGR.
Auxiliary relay in protection
panel.
Integrated in Reactor/NGR.
Auxiliary relay in protection
panel.
Numerical Relay with IEC
61850 Protocol
2 Restricted Earth Fault Protection Numerical Relay with IEC
61850 Protocol
3 Backup impedance protection
Numerical Relay with IEC
61850 Protocol
4 Buchholz Relay
Integrated
in
Auxiliary relay in
panel.
Integrated
in
Auxiliary relay in
panel.
Integrated
in
Auxiliary relay in
panel.
Integrated
in
Auxiliary relay in
panel.
Numerical Relay
61850 Protocol
5 Pressure Relief Device
6 Oil & Wdg Temp. Alarm &
Tripping
7 Oil Level Low Alarm
220 KV Feeders
E) Bus Bar Protection
400 KV Bus bar
220 KV Bus bar
Reactor.
protection
Reactor.
protection
Reactor.
protection
Reactor.
protection
1 Two Distance Protection
with IEC
[shall be of two different make
(i.e. from different
manufacturers) or of same make
with two different platforms with
same specifications]
-Main-I Protection &
-Main II Protection
2 Two Stage Over Voltage
Integrated in Main I &
Protection
Main II Protection
- Stage I
- Stage II
3 Local Breaker Backup (LBB)
Integrated in Main I
Protection.
Protection and Bus Bar
protection
1 Bus Differential Protection
(Single scheme)
16 Bays, Extendable up to 24
Bays (i. e. Control Unit - 24
Bays)
1 Bus Differential Protection
(Single scheme)
Numerical Relay with IEC
61850 Protocol
Numerical Relay with IEC
61850 Protocol
Page 5 of 6
GETCO / E / 4S - 087/ PP - 015 – 1A / R1 Dt.15.12.2011
13 Bays, Extendable up to 24
Bays (i. e. Control Unit - 24
Bays)
F) Disturbance Recorder & Event Loggers
Integrated feature of protective relays is used to provide the information about the Disturbance and
to log the events.
G) GPS based Time Synchronizing Equipment
400 KV Sub station is to be provided with IEC 61850 compatible Global Positioning System based
Time Synchronizing Equipment to synchronize all the protections.
Page 6 of 6