BASIC FUNCTIONALITIES OF GRID OPERATION Dr M. S. R. Murty Power System Operation • • • • Efficiency Reliability Economy and Security Benefits of grid interconnection • Improving reliability • Reduced investment due to sharing of the generating resources • Improved load factor and increase in load diversity • Coordination of maintenance schedules Power System • Generation, Transmission and Distribution of electrical energy • Generation Sources: • Thermal: Conventional Steam, Diesel • Hydro, Nuclear, Gas Turbine , Renewable Typical Energy Scenario Hydro 15.96% Wind 1.99% Biomass 1.19% Solar thermal 0.40% Nuclear 5.06% Diesel 0.48% Gas 14.49% Coal 60.44% Power Plant Schemes Thermal, Hydro, Nuclear, Combined Cycle Simple Boiler scheme Governor Controls Guide vane position Hydro Turbine scheme Hydro Power P = 9.8 η Q H where P = power (kilowatts) η = plant efficiency Q = discharge flow rate (meter3 /s) H = head (meter) Nuclear : PWR Combined Cycle (Brayton & Rankine Cycles) EXHAUST GAS LOW PRESSURE STEAM (For Deaeration) AIR INLET FUEL INTERMEDIATE PRESSURE STEAM (To Intermediate Pressure Steam Turbine) COMBUSTOR HIGH PRESSURE STEAM (To High Pressure Steam Turbine) GENERATOR HEAT RECOVERY STEAM GENERATOR GENERATOR ELECTRIC POWER COMPRESSOR TURBINE ELECTRIC POWER GAS TURBINE STEAM TURBINE HIGH INTERMEDIATE PRESSURE PRESSURE STEAM STEAM CONDENSATE RETURN TO HRSG STEAM EXHAUST Combined Cycle Captive Power Plant AUX BOILERS NAPHTHA GAS OIL 4 x 125 TPH Refinery Fuel Oil 8 X 30 MW GAS TURBINE NAPHTHA GAS OIL 11 KV 8 X 125 TPH 33 KV HRSG 4 X 30 MW STEAM TURBINE TO REFINERY 11 KV TO GEB 132/220 kV 33 KV HP steam 42 Kg/cm2 Power Steam MP steam 17 Kg/cm2 INSTALLED CAPACITY PRESENT GENERATION EXPORT TO GEB CAPABILITY 360 MW 269 MW 80 MW 1500 TPH 979 TPH ------------ To Refinery Sample load curve Base Load and Peak Load Power plants • Base load: The unvarying load, which occurs almost the whole day on the power plant • Base power plants: (i) low operating cost (ii) capability of working continuously for the long periods (iii) requirement of few operating personnel and their repair should be economical and speedy. • Peak loads: Various peak demands of the load over and above the base load • Peak power plants: Capability of quick start, synchronization and taking up of system load and quick response to load variation. Base Load and Peak Load Power plants (contd.,) • • • • • • • Hydro : Well suited for both base load and peak load operations. The hydro-power plants should be employed for base load operation as far as possible because of their higher capital cost. However during the periods of draught, hydro-plants may be used as peak load plants. A steam power plant gives minimum cost of generation per unit when used as base load plant. However, in order to save fuel it may be used as peak load plant. Nuclear power plants are suitable only for base load operation at high load factors Gas turbine power plants are suitable for supplying peak loads Diesel power plants play a very little role in bulk power generation because of their uneconomical operation costs. Power Plant Control • Plant parameters are to be maintained by closed loop control • Boiler: Steam parameters like pressure, temperature, other process parameters like furnace pressure, drum level • Turbine- Generator : Power (MW), speed or frequency Boiler and Turbine Controls DESH SH1 Spray DRUM Q W W Fuel . Flux . . Air BOILER Master Pressure Control GOVERNOR Q Temperature Control 3 FW 150 at a 540ºC H T P I P T G Gas Drum Level control SH2 RH COND GENERATOR CONTROLS Hydro Generator Capability Curve Power System : One line diagram 25-bus power system Distribution System : Typical Load Despatch Centers: Functions • • • • • System operation and control Interregional transfer of power, covering contingency analysis and operational planning on real time basis Scheduling / re-scheduling of generation System restoration following grid disturbances Operation of regional pool account and regional reactive energy account. Load Dispatch centers OR System Control centers • Constantly monitor the power flows, frequency and voltage at each system point and the load on each network component. • Keep an eye on all the circuit-breakers in the grid • Receive all the necessary data in real time through extensive telecommunications network. • When a network component is switched off following a network incident (e.g. a lightening strike or a severed cable) or when maintenance work is being carried out, dispatchers can activate or deactivate certain network components remotely. • Coordination of planning of maintenance of generating machines of various generating companies • Planning for maintaining proper voltages through review of reactive compensation requirement through system studies and monitoring of installed capacitors Transmision criteria • Transmission System shall be capable of withstanding the following contingency outages : • Outage of a 132 kV / 220 kV /400 kV line • Outage of single Interconnecting transformer • Outage of one pole of HVDC Bipole line • Without necessitating load shedding or rescheduling of generation during Steady State Operation • All the Generating Units may operate within their reactive capability curves and the network voltage profile shall also be maintained within voltage limits specified. • The transmission system shall be capable of withstanding the loss of most severe single system infeed without loss of stability. Abnormalities • Loss of supply • Prolonged operation of the system frequency below and above specified limits. • Unacceptable high or low voltage • System instability • Unacceptable overloading of transmission system elements. Power System Controls • Generation Controls - Real Power-Frequency ( P-f) control - Reactive Power- Voltage (Q-V) Control • Network Controls - Breaker, Transformer taps Controls, Series/Shunt Compensators & FACTS Controllers • Load Controls • System Wide/Dispatching Controls - Energy Management System (EMS) - Distribution Automation System (DAS) Time Scales: Power system operation • Regulation -- seconds to a few minutes -similar to variations in customer demand • Load-following -- tens of minutes to a few hours -- usage follows predictable patterns • Scheduling and commitment of generating units -- one to several days Time Scales: Power system operation Real time control of Generation • System voltage, frequency and stability • System frequency is controlled through adjustment of the mechanical power of the generators using speed governor feedback and area generation control (AGC) • Dynamic stability enhancement: adjustment of the generator’s excitation voltage via the power system stabilizer (PSS) loop • And transmission level FACTS devices Power System Operation: Time frame • Load control: under severe stability conditions such as under-frequency load shedding • Traditionally load is viewed as a variable uncontrolled demand, and the generation must constantly adjust to reliably meet the demand. System Security • The ability of a power system in normal operation to undergo a likely disturbance without entering an emergency or a restorative state. • The objective of security control is to keep the power system in the normal state. Need for frequency regulation • Wide variation in frequency causes damage to electrical equipment in industries, agriculture etc., • Power plant equipment like turbines, generators and auxiliaries get damaged • Turbine last stage blades are susceptible to damage due to low frequency operation • Product quality like in rolling mills is severely affected by frequency fluctuation • Power system security is severely affected at low frequencies Security Assessment / Control Normal SECURE Restorative Control INSECURE EMERGENCY RESTORATIVE Emergency Control A Typical Architecture of an Energy Management System Grid Code Grid Code • Grid code is a technical document containing the rules governing the operation, maintenance and development of the transmission system • The grid code is intended to establish the reciprocal obligations of all participants who are part of the transmission system operator. • The grid code specifies a minimum of technical, design and operational plant criteria • Planning code: provides for the supply of information for planning and development studies. • The connection conditions specifies a minimum of technical, design and operational plant criteria • Operating code contains details for high level operational procedures for example demand control, operational planning and data provision. • Marketing Code: Energy trading, Ancillary services SUMMARY • Maintaining system security, reliability, quality, stability and ensuring economic operation are the major operating concerns. • On line monitoring, operation and control of the modern day power systems is performed by computer aided monitoring & dispatching systems (SCADA / EMS) • Distribution systems are monitored by Distribution Automation (DA) systems.