Performance of the Tilecal cooling system Ana Henriques / Philippe Grenier / Gerolf Schlager (CERN) CERN ATLAS Week, February 2002 Index • Review - last ATLAS week • Influence of the ambient temperature – on the Cooling Unit – on non-isolated pipes • Cooling Pilot Project in B185 ATLAS week, February 2002 Gerolf Schlager (CERN) Review - last ATLAS week ATLAS week, February 2002 Gerolf Schlager (CERN) Cooling Unit in H8 return pipes output pipes control box fridge unit water tank ATLAS week, February 2002 Gerolf Schlager (CERN) Stability of the system during data taking Tout-Drawer <Mod2>=19.70.1 oC <Mod5>=19.60.1 oC Tin-Drawer <Mod2>=18.30.1 oC <Mod5>=18.40.1 oC T-Cooling=18.30.1 oC ATLAS week, February 2002 Gerolf Schlager (CERN) PMT gain variation versus temperature total energy deposited versus temperature in PMT#22 180 GeV electrons ΔE/E=0.21 %/°C 180 GeV pions ΔE/E=0.23 %/°C E/E = 0.2 % / oC(PMT) E/E = 0.1 % / oC(cooling) ATLAS week, February 2002 Gerolf Schlager (CERN) Influence of the ambient Temperature on the Cooling Unit ATLAS week, February 2002 Gerolf Schlager (CERN) Influence of the ambient Temperature T-cooling & T-room vs. Time August 20.0 24.5 T-room 19.0 23.5 T-room T-cooling 19.5 18.5 18.0 T-cooling=18.4±0.1ºC T-cooling 22.5 17.5 17.0 21.5 8.23.01 8.24.01 8.24.01 8.25.01 8.25.01 8.26.01 8.26.01 8.27.01 8.27.01 8.28.01 8.28.01 8.29.01 12:00 0:30 13:00 1:30 14:00 2:30 15:00 3:30 16:00 4:30 17:00 5:30 Time ATLAS week, February 2002 Gerolf Schlager (CERN) Influence of the ambient Temperature T-cooling vs. T-Room 18.6 September 01 0.093ºC / ºC (ambient) T-cooling 18.3 August 01 0.163ºC / ºC (ambient) 18.0 17.7 November 01 17.4 0.113ºC / ºC (ambient) 17.1 12 14 16 18 20 22 24 T-Room ATLAS week, February 2002 Gerolf Schlager (CERN) Improved Isolation 18.6 January 02 T-cooling T-out 18.3 0.027ºC / ºC (ambient) August 01 0.163ºC / ºC (ambient) 18.0 September 01 0.093ºC / ºC (ambient) 17.7 November 01 17.4 0.113ºC / ºC (ambient) 17.1 12 13 14 15 16 17 18 19 20 21 22 23 24 T-Room ATLAS week, February 2002 Gerolf Schlager (CERN) 25 Cooling water change per C(ambient) August September November January (improved Isolation) ATLAS week, February 2002 0.163C 0.093C 0.113C 0.027C Gerolf Schlager (CERN) Summary • For an ambient temperature change of 10°C we found a Cooling water change of 1.2 °C – This dependence is a problem during the calibration of the modules because they will be calibrated at different places and times – It does not affect the ATLAS detector because there will be no noticeable changes of the ambient temperature in the pit • We minimized this effect with improved isolation of the controller sensor – new values: ATLAS week, February 2002 0.3°C per 10°C(ambient) Gerolf Schlager (CERN) Effects of ambient temperature on nonisolated pipes ATLAS week, February 2002 Gerolf Schlager (CERN) ATLAS - Setup Temperature Gradient 5°C 10m • Temperature at “ “ should be as close as possible ATLAS week, February 2002 Cooling Water Gerolf Schlager (CERN) Mepla tube characteristics • • • • • 3 layer pipe (PE-Al-PE) Fast easy installation Bendable, stable Corrosion resistant Combines advantages of plastic and metal pipes • Foreseen for ATLAS • satisfy TIS requirements ATLAS week, February 2002 Gerolf Schlager (CERN) Non-isolated Mepla Tube Test • One isolated tube was replaced with a 10m nonisolated Mepla tube • Difference between Tin-Drawer and T-cooling was measured ambient effects on CU removed 10m Mepla tube Drawer 4 Isolated tube Drawer 1 T-cooling ATLAS week, February 2002 Tin-Drawer Gerolf Schlager (CERN) Isolated Tube January 0.40 Tin-Drawer – T-cooling T-in - T-out 0.01°C/ /ºC °C(ambient) 0.01ºC (ambient) 0.30 0.20 0.10 0.00 13.0 14.0 15.0 16.0 17.0 T-room ATLAS week, February 2002 Gerolf Schlager (CERN) 18.0 Non-isolated Mepla Tube January 0.40 Tin-Drawer – T-cooling T-in - T-out 0.30 0.04°C/ /ºC °C(ambient) 0.04ºC (ambient) 0.20 0.10 0.00 13.0 14.0 15.0 16.0 17.0 T-room ATLAS week, February 2002 Gerolf Schlager (CERN) 18.0 Summary Temperature pick-up per oC(ambient) • isolated tube non-isolated Mepla tube 0.01oC 0.04oC • Expected temp-gradient in pit 5°C => less than 0.2 °C temperature difference between lowest and highest module • Maximum change of PMT temperature 0.1°C ATLAS week, February 2002 Gerolf Schlager (CERN) Cooling Pilot Project in B185 ATLAS week, February 2002 Gerolf Schlager (CERN) Cooling Pilot Project Level 3 Level 2 HeatExchanger Level 1 Outlet ATLAS week, February 2002 Inlet • • • • • Real Size Test Bldg. 185 15m scaffolding Piping done Installation ready end of March • Tests until Sept.02 (finished before PRR) Gerolf Schlager (CERN)