Conditioning of Moist Air a T2 T1 q 1.02m Properties of moist air Equations – Conservation of mass – Conservation of energy Change using bulk properties at inlet and outlet a h 2 h1 qm Classic moist air processes – Sensible heating and cooling – Cooling and dehumidifying h h w – Adiabatic humidifying W – Heating and humidifying – Adiabatic mixing Space conditioning m 32 m 32 m 13 – Sensible heat factor (SHF) m 13 m 12 m 12 – Cooling coil bypass (b) – Evaporative cooling – Economizer cycle 2 3 – Effect of fans 1 – Designing indoor RH a1 a1 a2 a2 a3 a3 h q hw w W m 2 1 Adiabatic mixing - Example – Two thousand cubic feet per minute (cfm) of air at 100 F db and 75 F wb (state 1) are mixed with 1000 cfm of air at 60 F db and 50 F wb (state 2). The process is adiabatic at a steady flow rate and at standard sea level pressure. Find the condition of the mixed streams. – Convert to SI: o C (o F 32) / 1.8 100o F 37.8o C 1 cfm 0.4719 Ls 75o F 23.9 o C 2000 cfm 944 L / s 60o F 15.6o C 1000 cfm 472 L / s 50o F 10o C Adiabatic mixing - Solution v1 0.9 m3 / kg a1 0.944 / 0.9 1.05 kg / s m v 2 0.825 m3 / kg a 2 0.472 / 0.825 0.57 kg / s m partial graphical method a2 m W2 W1 13.0 0.57 5.3 12.9 10.3 g / kg W3 W1 a3 m 1.62 T3 30o C fully graphical method a1 23 m a 3 12 m 3 38% Twb3 19.9o C 1 3 1.05 48.5 units 23 1.62 31.4 units 2 Typical air handling system 23°C Exhaust air Return air recirculation air energy recovery system -20°C Outdoor air economizer damper 22°C filter heating coil cooling coil Supply air 15°C - 35°C Sensible heat factor SHF q sensible heat trans fer q s s total heat trans fer q s q l q a (h z h 2 ) qs m a1 , T1 , W1 , h1 m 1 a ( h1 h z ) ql m q coil a 2 , T2 , W2 , h 2 m 2 w , Tw , h w m a1 m a2 m a m 1 2 z Sensible heat factor - Example – Conditioned air is supplied to a space at T=15C and Twb=14C at a flow rate of 0.5 kg/s. The sensible heat factor for the space is 0.70 and the space is to be maintained at 24C . Find the sensible and latent cooling loads for the space. 2 T 24o C SHF 0.7 If the cooling load is 6.6kW, what is m1 if state 1 is here? 1 1 0.5 kgs m T1 15o C Twb1 14 o C a ( h 2 h1 ) qm parallel 2 1 0.5(52.5 39.3) 6.6 kW (i.e., the supply air is heated and the space air is cooled) q s q SHF 6.60.7 4.6 kW q l q q s 2.0 kW Cooling coil bypass a 3 , T3 , W3 m a1 , T1 , W1 m 1 3 w , Tw , h w m T5 , 5 6 a 3 , T3 , W3 m a1 , T1 , W1 m 1 4 w , Tw , h w m 3 1 2 5 3 bypass factor 4 T4 = apparatus dew point b a 6 43 m a1 14 m T5 , 5 Evaporative cooling - 1 3 a 2 , T2 , W2 , h 2 m a1 , T1 , W1 , h1 m – Energy balance 1 a h1 m whw m ah2 m h1 h 2 w , hw m qs ql 2 negligible for water SHF 0.6 – Given air at outdoor conditions (1) and the SHF of the space we can use evaporative cooling to cool from state 1 to state 2 – The flow rate of air that is required to cool the space depends on cooling load 2 3 1 Is this a more favourable outdoor condition for evaporative cooling? Evaporative cooling - 2 – Low cost alternative to refrigerant systems Requires less energy for cooling Requires less capital investment – Cooling potential (Twb,design – Twb,outdoors) If the cooling potential is small, the air flow rates become very large and system is not economical because of fan and duct costs If cooling load is large, air flow rates become large – Evaporative systems are subject to mold and bacteria growth – Freezing may be a problem during swing seasons (spring/fall) in colder climates no potential OA design target good potential OA Economizer cycle – Using outdoor air to condition the indoor space – Can be used during “off-design” conditions to save energy (usually cooling) by increasing the amount of outside (ventilation) air (usually at night-time) – May be limited in amount of outdoor air if RH must be controlled to a specific value (often RH must remain below some maximum value) – must measure the enthalpy (T & ) to properly control 4 5 OA 1 2 3 Economizer cycle 4 4 OA – Known: 1 2 3 1. 2. 3. 4. 5. – Outdoor design conditions Indoor design conditions Loads -> SHF -> condition line Often T3,min -> state 3 -> ma3 Knowing the ventilation rate ma1, mix 1 and 4 to get 2 6. Cool (+bypass) from 2 to 3 Increase ventilation rate for “off-design” conditions of outdoor air want Td 8 C o 1 1 2 2 Td 3 Td 1 4 Effect of fans – Large HVAC systems have both a supply and exhaust air fan to keep the building at a desired P compared to outdoors. – All of the power is ultimately degraded to sensible energy in the airstream. – We will assume all of the energy rise occurs at the fan (most does) 4’ Power Q P 1000f m 4 5 Q volumetric air flow rate (L/s) P fan pressure rise (Pa) 3 f fan efficiency ( 60 to 80%) OA m motor efficiency ( 80 to 90%) 100% if motor is outside the airstream 1 2 3’ 4’ Effect of fans - summer 4 5 3 1 2 3’ Where are state points 3’ and 4’ ? 1 2 3’ Td 4’ 3 Exhaust fan increases the load on the cooling coil 4 Supply fan increases Td or reduces reheat Effect of fans - winter 6 qs ql 7 qh 5 1 Both fans reduce the heating coil load 4 5 6 7 2 1 3 2 3 4 Designing indoor RH - cooling – Given: qs - load calculation ql - load calculation T4 - comfort T3 - comfort, energy m1 - ventilation T1 - weather data/design conditions 1 - design conditions 4 qs ql qc 1 2 3 1 1 SHF qs qs ql Only state point 1 and the slope of the load line are specified The condition line is not fixed vertically T3 T4 T1 Humid climate – Assume condensation at the coil – We can now design 4 and control 4 it with the apparatus dew point 1 2 4 4 3 d T3 T4 2 1 1 d qs ql qc T1 3 Dry climate – Assume no condensation at the coil – We must use outdoor air to control the indoor humidity (4) – More difficult because we may not be able to control the outdoor air 1 flow rate over a large range 4 qs ql qc 2 3 w h fg m w q l / h fg ql m Since there is no condensation at the coil, this moisture must be removed by outdoor air w m 1 W4 W1 m 4 4 3 1 2 1 T3 T4 T1 Horizontal line for no condensation W4 w m W1 m1 Dry climate - 2 – If we can’t increase the outdoor air flow rate to reach the indoor design humidity, the indoor humidity will decrease – Usually ok to allow indoor RH to decrease in summer 1 – In this case the indoor humidity can be calculated as follows w h fg ql m 4 qs ql qc 2 3 w q l / h fg m Since there is no condensation at the coil, this moisture must be removed by outdoor air 4 w m 1 W4 W1 m W4 4 Solving for W4 W4 w m W1 m1 3 1 2 1 This locates state point 4 and determines 4 T3 T4 T1