high density metering - Engineered Process Systems

Power Monitoring Overview

GARY MORSE

Simple solutions for your power system

Schneider Electric Energy

Solutions:

Software

●POWERLOGIC Patents

●5000 Systems Installed

●200,000 devices shipped

●500 students trained per year at PowerLogic

University

●Power System Engineering group conducts system studies

●Advanced Systems group designs/builds custom solutions

Copyright © Schneider Electric 2008. All rights reserved.

2

What’s wrong with Electro-

Mechanical Metering

90 Year Old Technology

Requires Calibration

Does not respond to Harmonics

“Out of sight, Out of Mind”

No modern capabilities

No Communications

Copyright © Schneider Electric 2008. All rights reserved.

3

Copyright © Schneider Electric 2008. All rights reserved.

4

AC Analog Meter Technology

Calibrated to an Effective Change in the Magnetic Field Based on a Sinusoidal Wave Form

(Reading = Volts or Amperes)

N S

Peak Value

Effective Value

Copyright © Schneider Electric 2008. All rights reserved.

5

AC Digital Meter Technology

RMS VALUE CALCULATED FROM DIGITAL SAMPLES

TAKEN OVER THE SINE WAVE

Microprocessor

A/D Converter

Copyright © Schneider Electric 2008. All rights reserved.

6

Changing Technology

Copyright © Schneider Electric 2008. All rights reserved.

7

WHY MONITOR POWER?

TO MANAGE IT

●REDUCE ENERGY COST

●OPTIMIZE EQUIPMENT UTILIZATION

●IMPROVE POWER SYSTEM RELIABILITY

Copyright © Schneider Electric 2008. All rights reserved.

8

WHY MONITOR POWER?

REDUCE ENERGY COSTS

●DEMAND SIDE ENERGY MGMT

●LOWER DEMAND CHARGES

●ALLOCATE ENERGY COSTS BY

DEPARTMENT OR PRODUCTS

●IMPROVE SYSTEM POWER FACTOR

●UTILITY RATE STRUCTURE

Copyright © Schneider Electric 2008. All rights reserved.

9

UTILITY RATE

STRUCTURE

●INSURE THAT YOUR RATE

STRUCTURE COINCIDES WITH

USAGE

●CONSIDER AN INTERUPTABLE

RATE (DEMAND RESPONSE)

Copyright © Schneider Electric 2008. All rights reserved.

10

WHY MONITOR POWER?

OPTIMIZE EQUIPMENT

UTILIZATION

●EVALUATE CIRCUIT LOADING

●IMPROVE POWER SYSTEM PLANNING

●AVOID POTENTIAL EQUIP. DAMAGE

●AID SCHEDULING OF MAINTENANCE

Copyright © Schneider Electric 2008. All rights reserved.

11

WHY MONITOR POWER?

IMPROVE POWER SYSTEM

RELIABILITY

●EARLY DETECTION OF PROBLEMS

●REDUCTION OF DOWN-TIME INSURANCE

COSTS

●TROUBLE SHOOTING AND DIAGNOSTICS

●CONTROL OF CIRCUIT BREAKERS

●PWR. QUALITY AND HARMONICS ANALYSIS

Copyright © Schneider Electric 2008. All rights reserved.

12

POWER QUALITY

WHAT DOES IT MEAN?

●VOLTAGE DISTORTION????

●CURRRENT DISTORTION???

●HARMONICS????

●GROUNDING????

Copyright © Schneider Electric 2008. All rights reserved.

13

POWER QUALITY

IEEE RECOMMENDED PRACTICE FOR

MONITORING ELECTRIC POWER

QUALITY, FINAL DRAFT, APRIL 1994

DEFINITION:

“The concept of powering and grounding sensitive equipment in a manner that is suitable to its proper operation.”

Copyright © Schneider Electric 2008. All rights reserved.

14

POWER QUALITY

POWERING AND GROUNDING

7 CATEGORIES OF

ELECTROMAGNETIC PHENOMENA

NEED TO MINIMIZED

PROPER OPERATION

SENSITIVITY OF EQUIPMENT VARIES

WIDELY

IMPORTANCE OF CONTINUOUS

MONITORING

Copyright © Schneider Electric 2008. All rights reserved.

15

I.E.E.E. P1159 DEFINITIONS

CATEGORY DURATION

1. TRANSIENT <1 CYCLE

2. SHORT DURATION 1/2 CYCLE-1 MIN

3. LONG DURATION >1 MINUTE

4. VOLT IMBALANCE STEADY STATE

5. WAVE DISTORT. STEADY STATE

6. VOLT FLUCT. INTERMITTENT

7. FREQUENCY VAR. <10 SECONDS

Copyright © Schneider Electric 2008. All rights reserved.

16

SOURCES OF TRANSIENTS

● Outside Facility

● Lightning

● Capacitor Switching

● Line/Cable Switching

● Transformer Switching

● Current Limiting Fuse Operation

● Inside Facility

● Capacitance Switching

● Current Interruption (motors, etc.)

● Power Electronics Operation

● Electro-Static Discharge

Copyright © Schneider Electric 2008. All rights reserved.

17

4000

3000

2000

1000

0

-1000

-2000

5000

TRANSIENTS

Oscillatory Transient Phase A 4500 Volts

200nS per Data Point

Copyright © Schneider Electric 2008. All rights reserved.

18

TRANSIENTS

4600 Volt transient 2uS wide on Phase B

6000

5000

4000

3000

2000

1000

0

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37

-1000

200nS per Data Point

Copyright © Schneider Electric 2008. All rights reserved.

19

TRANSIENTS

GROUNDED WINDING CAUSED BY VOLTAGE SURGE

Copyright © Schneider Electric 2008. All rights reserved.

20

TRANSIENTS

WINDING DAMAGE CAUSED BY VOLTAGE SURGE

Copyright © Schneider Electric 2008. All rights reserved.

21

12 CYCLE WAVEFORM

VOLTAGE SAG A-N

400

300

200

100

0

-100

0

-200

100 200 300 400 500 600 700

-300

-400

Voltage A Phase

-500

-600

Set for 2 Cycle

Pre-trigger Current A-N

Captured Mid-day on (120/208 3 PH 400 amp) service for Office Building

800

Copyright © Schneider Electric 2008. All rights reserved.

22

Voltage Unbalance

●Voltage unbalance causes additional negative sequence currents to flow in induction motor.

●Resulting additional heating varies as cube of unbalance

● 3.5% Unbalance = 25% Heating

●Conventional motor protection does not adequately protect

●Monitoring, phase-loss protection necessary.

Copyright © Schneider Electric 2008. All rights reserved.

23

Case 5 - Unbalance at Tire Plant

500

490

480

470

460

450

440

430

Copyright © Schneider Electric 2008. All rights reserved.

24

Voltage Unbalance

ONE PHASE DAMAGE CAUSED BY UNEQUAL VOLTAGE

Copyright © Schneider Electric 2008. All rights reserved.

25

Xfr Loading Based On E-C Loss

North Transformer Loading

2500

Derated Capacity

2000

1500

1000

500

Actual Load

0

4/3/95

1:29

4/3/95

7:29

4/3/95

13:29

4/3/95

19:29

4/4/95

1:29

4/4/95

7:30

4/4/95

13:29

15-Minute Interval Ending Date/Time

4/4/95

19:30

4/5/95

1:30

4/5/95

7:29

4/5/95

13:30

Copyright © Schneider Electric 2008. All rights reserved.

26

Actual Neutral Waveform, Daily Profile

North Transformer Currents

1800

1600

1400

1200

1000

800

600

400

200

0

4/3/95

1:29

Average Phase Current

4/3/95

7:29

4/3/95

13:29

Neutral Current

4/3/95

19:29

4/4/95

1:29

4/4/95

7:30

4/4/95

13:29

15-Minute Interval Ending Date/Time

4/4/95

19:30

4/5/95

1:30

Copyright © Schneider Electric 2008. All rights reserved.

4/5/95

7:29

4/5/95

13:30

27

Measure the Cause - Not the Effect

Copyright © Schneider Electric 2008. All rights reserved.

125

120

115

110

105

100

0

Effective (rms) Voltages (06-28-94)(14:10:31)

50 100

Time (mS)

150 200

28

Features

PowerLogic Metering Overview

SEPAM

ION7300

PM800

ION6200

Enercept

HDM

Copyright © Schneider Electric 2008. All rights reserved.

Sub-Metering

ION7600

CM4000

CM3000

Power Quality

MicroLogic circuit breaker

Power Quality

29

CM-4250 Circuit Monitor

●0.04% Accuracy

●ANSI C12.20 Revenue Acc.

●True RMS to 255th Harmonic

●Sag/Swell Detection to 1/4 Hz

●Waveform Capture up to 512 samples/cycle, up to 64 sec

●100 ms RMS recording for up to 300 sec

●On-Board Custom Quantities for monitoring

Water, Air, Gas, and,Steam

●CM4000T is other meter in CM-4000 family

Copyright © Schneider Electric 2008. All rights reserved.

30

ECC21

Comms

●Optional Ethernet Comms Card at

10MBaud or 100MBaud

●Connect using UTP or Fiber to Ethernet port

●UTP can be 10/100BaseT

●Fiber-optic port 100 Base FX

●RS485 Modbus master port supports 31

Additional devices

●On-Board Web Server Provides 10

HTML pages

● Setup and view summary data

● Power Quality Summary

● Energy Summary

●E-mail on alarm

Copyright © Schneider Electric 2008. All rights reserved.

31

I/O Options

Analog & Digital

I/O Modules

I/O Extender

Module

●Up to 25 digital/analog I/O points

●1 Digital Output Standard (KYZ)

●Up to 2 I/O Cards (IOC44) with:

●4 Digital inputs with 1ms time stamps

●3-10 Amp relays, 1 Solid state output

●I/O Extender Module (IOX) supports up to 8 analog & digital I/O modules

●Analog Inputs/Outputs 0-5Vdc or

Copyright © Schneider Electric 2008. All rights reserved.

4-20mA

●Digital Inputs 120 & 240 Vac or 3 to 32

Vdc

●Digital Outputs 120 & 240 Vac or 60 &

200 Vdc

32

Disturbance Direction Detection

Utility

AVAILABLE WITH

CM-4000 OR CM-3350

Copyright © Schneider Electric 2008. All rights reserved.

Loads

33

Disturbance Direction Detection

Copyright © Schneider Electric 2008. All rights reserved.

34

CM-3000

●CM-3250 STANDARD (1 SEC) AND HIGH

SPEED (100 MSEC) ALARMS WITH

WAVEFORM CAPTURE

●CM-3350 DISTURBANCE INCLUDING

SAG/SWELL DETECTION

●REQUIRES SEPARATE DISPLAY - EASY

INSTALL

●WILL ACCEPT ECC-21 AND IOC-44

Copyright © Schneider Electric 2008. All rights reserved.

35

CM-3000

●8 MB MEMORY

●ACC. I, V, .075% READ + .025% F.S.

●128 SAMPLES/CYCLE - 63 HARM.

●100 ms LOGS FOR V,I,P,PF

●LOG MIN/MAX/AVG

●NO PT’S <600V / CONTRL PWR TO 300V

Copyright © Schneider Electric 2008. All rights reserved.

36

POWER METER 800 Series

 Performance Specifications:

 Accurate through 63rd Harmonic

 Current/Voltage: +/- 0.075%

 Power/Energy: +/- 0.15% of Reading

 Metering Range: 2-200%

 Operating Temperature Range: -25 ° to +70 °C Meter, 0° to 55°C Display

 Certified Revenue Accurate per ANSI C12.20.

Meets IEC 60687 Class 0.5S

 RS-485 Multipoint Communications. (2-wire)

 Voltage Input Direct Connect up to 600V

 Control Power 100-415 Vac/100-300Vdc

Copyright © Schneider Electric 2008. All rights reserved.

37

POWER METER 800 SERIES

 Three Meters Available

● PM820

● Advanced Metering

● 80kb of memory

● Custom logging and alarming

● PM850

● 800kb of memory

● Trending and Forecasting

● Waveform Capture

● PM870

● Sag/Swell Detection with Waveform Capture

● EN50160 Power Quality evaluation

Copyright © Schneider Electric 2008. All rights reserved.

38

Features - Input & Output Modules

●Available with Digital and Analog

I/O to monitor:

●Equipment status

●Critical Alarm status

●Sync with Utility demand intervals

●Standard with 2 Digital I/O

●1 KY / Alarm Digital output

●1 Digital input

●I/O option modules

●PM8M26 - 2 dig. out & 6 dig. In

●PM8M2222 - 2 dig. out,2 dig. In & 2 analog out, 2 analog in

Copyright © Schneider Electric 2008. All rights reserved.

39

PM8ECC

●LIKE THE ECC21, HAS ON-

BOARD WEB PAGES, E-MAIL

ON ALARM

●FIELD INSTALLABLE, PM-8’S

ONLY

Copyright © Schneider Electric 2008. All rights reserved.

40

POWERLOGIC ®

Power Meter Draw-out

Retrofit Kit

Copyright © Schneider Electric 2008. All rights reserved.

41

Voltage leads

ENERCEPT

Split Core CT’s

Copyright © Schneider Electric 2008. All rights reserved.

RS 485 Modbus

42

Enercept Meter

● Self Contained “All in One” metering concept

●CTs are included, No PTs up to 480 v

●Metering and comms circuits in one CT housing and pod

●Control power from voltage input

● Split core CTs; easy to install

● 2-wire Modbus port is standard

● 1% meter system accuracy

● UL Listed

● Two models - Basic and Enhanced

●Basic: Energy and Power

●Enhanced: Adds Demand, Voltage, Current, PF, etc

Copyright © Schneider Electric 2008. All rights reserved.

43

HIGH DENSITY METERING

High Density Metering (HDM) Solutions

Copyright © Schneider Electric 2008. All rights reserved.

44

HIGH DENSITY METERING

●AVAILABLE IN 1, 4, 8 METER

CONFIGURATION OR 16

●EACH CONFIGURATION CAN

HAVE FEWER METERS.

SPACES COVERED BY PLATES

●CAN BE ORDERED WITH

OPTIONAL EGX FOR ETHERNET

CONNECTION

●REQUIRES 5A SEC. CT’S NOT

INCLUDED WITH HDM.

Copyright © Schneider Electric 2008. All rights reserved.

45

HIGH DENSITY METERING

EGX mounting space

UL489 CB

Shorting Blocks

Copyright © Schneider Electric 2008. All rights reserved.

Factory installed wiring harnesses

46

HDM 4-Meter Enclosures

●NEMA 1 & NEMA 3R * versions

●Applications

●1-phase or 3-phase

●120/208V, 240V, 277/480V, 480V

DELTA, 347/600V * , 600V *

●Includes voltage disconnect switch

●Minimal wall space required

●30.6”h x 7.2”w x 7.4”d

●UL 508a & UL 50 certified

Copyright © Schneider Electric 2008. All rights reserved.

47

ETHERNET NETWORK

SYSTEM MANAGER

SOFTWARE

PLANT WIDE ETHERNET NETWORK

PM-8 WITH PM8ECC

MODBUS/TCP

PROTOCOL

60.03

Kilo

M ega

AM MET ER ( A)

VOL TM ETER, L- L (V)

VOL TM ET ER, L -N (V)

[CT :5 ]

[PT : 120 ]

[Sys . T ype ]

WATT MET ER ( W)

VARM ET ER ( VAr )

VA METER (VA)

POWER FACTOR M ET ER

[Dm d . In t. ]

[W H/Pul se]

[Ad d re ss]

[Ba ud Ra te ]

FREQUENCY METER ( Hz)

DEM AND AMMET ER ( A)

DEMAND POWER ( W)

[No rm . F r eq.]

[R ese t]

[R ese t]

DEM AND POWER (VA)

WATT HOUR M ET ER

VARHOUR M ET ER

[R ese t]

[R ese t]

[R ese t]

THD, CURRENT (%)

T HD, VOLT AGE ( %)

K-FACTOR

[R st . M in / M ax]

[Se t Pa ssw or d ]

[A cc ep t]

3- PHASE

A (A-B)

B (B-C)

C (C-A)

N

PHASE

[En te r]

SELECT

METER

[Va lue ]

METERS

M IN

M AX

AL ARM

[Set up ]

MODE

SQUAR E D

Pow er Logic

CIRCUIT MONITOR

60.03

Kilo

M ega

AM MET ER ( A)

VOL TM ETER, L- L (V)

VOL TM ET ER, L -N (V)

[CT :5 ]

[PT : 120 ]

[Sys . T ype ]

WATT MET ER ( W)

VARM ET ER ( VAr )

VA METER (VA)

POWER FACTOR M ET ER

[Dm d . In t. ]

[W H/Pul se]

[Ad d re ss]

[Ba ud Ra te ]

FREQUENCY METER ( Hz)

DEM AND AMMET ER ( A)

DEMAND POWER ( W)

[No rm . F r eq.]

[R ese t]

[R ese t]

DEM AND POWER (VA)

WATT HOUR M ET ER

VARHOUR M ET ER

[R ese t]

[R ese t]

[R ese t]

THD, CURRENT (%)

T HD, VOLT AGE ( %)

K-FACTOR

[R st . M in / M ax]

[Se t Pa ssw or d ]

[A cc ep t]

3- PHASE

A (A-B)

B (B-C)

C (C-A)

N

PHASE

[En te r]

SELECT

METER

[Va lue ]

METERS

M IN

M AX

AL ARM

[Set up ]

MODE

SQUAR E D

Pow er Logic

CIRCUIT MONITOR

RS-485 19.2k Sub-Networks

Copyright © Schneider Electric 2008. All rights reserved.

PM6 with EGX-100

MODBUS/TCP

48

ETHERNET GATEWAY

●EGX-100

● 10/100BASE T/TX UTP/STP ETHERNET

● SINGLE SERIAL PORT CONFIGURABLE

TO RS485 OR RS-232

● SERIAL PROTOCOLS: MODBUS RTU,

MODBUS ASCII, POWERLOGIC (SYMAX),

JBUS

● REQUIRES SEPARATE CONTROL POWER:

24VDC OR POE (IEE802.3AF)

● IT FUNCTIONS: SNMP, FDR BASIC (DUPLICATE

IP ADDRESS DETECTION), SUPPORTS 32

CONCURENT MODBUS TCP CONNECTIONS

● PROVIDES MODBUS SERIAL MASTER DEVICES

TO ACCESS MODBUS TCP DEVICES

Copyright © Schneider Electric 2008. All rights reserved.

49

ETHERNET GATEWAY

●EGX-300 SAME FEATURES AS

EGX100 +

● 512 MB MEMORY

● ON-BOARD WEB SERVER FOR REAL TIME DATA

● USE STANDARD WEB PAGES OR LOAD

CUSTOMIZED

● ON-BOARD LOGGING OF 26 DIFFERENT

QUANTITIES. CAN BE UPLOADED TO PC USING

FTP OR E-MAIL

● CAN SUPPORT UP TO 64 DEVICES. CAN

SUPPORT 32 SERIAL DEVICES CONNECTED

● CAN SUPPORT REAL-TIME DATA & LOGGING

FOR OTHER DEVICES ON THE NETWORK.

Copyright © Schneider Electric 2008. All rights reserved.

50

SMS V4.0

Copyright © Schneider Electric 2008. All rights reserved.

51

System Manager Software V4.0

Distributed power monitoring system .

Leverages Windows Vista, Windows XP, or

Windows Server 2003

Modular architecture supports multiple devices and custom software applications

Improved data acquisition and data sharing utilizing open database (ODBC)

Flexible architecture-1 PowerLogic PC with additional WEB clients

Real time power system viewing

Copyright © Schneider Electric 2008. All rights reserved.

52

System Manager V4.0

- The Architecture

THE SOFTWARE RESIDES ON A PC USING WINDOWS XP

OR VISTA FOR SMSDL AND SMSSE AND ON A PC USING

WINDOWS SERVER 2003 FOR SMSPE

SOFTWARE PC

DEPENDING ON THE

LICENSE, ADDITIONAL

CLIENTS CAN ACCESS

INFORMATION USING

INTERNET EXPLORER

MAIN MENU

METERS

ETHERNET

SWITCH

480

461

155220

Copyright © Schneider Electric 2008. All rights reserved.

53

VIRTUAL METER

Copyright © Schneider Electric 2008. All rights reserved.

54

Copyright © Schneider Electric 2008. All rights reserved.

55

ALARMS

Copyright © Schneider Electric 2008. All rights reserved.

56

DATA LOGGING & TRENDING

Copyright © Schneider Electric 2008. All rights reserved.

57

GFX4.0

●GRAPHICAL PRESENTATION OF REAL-TIME DATA

Copyright © Schneider Electric 2008. All rights reserved.

58

Technical Support Center

Copyright © Schneider Electric 2008. All rights reserved.

615 287-3400

59

Copyright © Schneider Electric 2008. All rights reserved.

POWERLOGIC

University

Training Program Benefits

Users gain maximum benefit from their system

Tech support reduced as customers become proficient

Customers taught power quality, energy management problem solving

Customers learn new products as they are released

60

WRAP UP & SUMMARY

VOLTS LN A= 275

B= 275 C= 275

Mode Select

SQUARE D D

SQUARE

Power

Power Meter

Logic

®

PM600’s

● EXPANDED OUR METERING

HARDWARE

● ENHANCED SOFTWARE OPTIONS

● NEW COMMUNICATIONS OPTIONS

● ENLARGED ENGINEERING

SERVICES

ENERCEPT

SQUARE D’s

PM800’s

CONTINUED COMMITMENT

TO THE POWER MONITORING MARKET

CM-3000

CM-4000

EGX-400

Copyright © Schneider Electric 2008. All rights reserved.

PORTABLE CM

SMSPE