technical specifications

advertisement
SPECIFICATIONS
DIVISION 15 – MECHANICAL
NEW ELEVATORS
BLOOMFIELD AVE STATION - NEWARK CITY SUBWAY
AT
BLOOMFIELD AVENUE
NEWARK, NJ
SECTION 15000
BASIC MECHANICAL REQUIREMENTS
PART 1 GENERAL
1.1
SUMMARY
A.
Section includes general requirements for all mechanical work, including any
plumbing, process piping, fire protection or HVAC systems applicable to this
project. The extent of mechanical work is as indicated on the Contract drawings
and individual specification sections, whether included in Division 15 –
Mechanical, or incorporated by reference.
B.
Schedule and stage mechanical work to follow the overall Contract phasing
plans. Furnish all labor, supervision, materials, tools and equipment necessary to
coordinate and install the mechanical work as indicated on Contract drawings, or
herein specified.
C.
Provide and install any plumbing, process piping, fire protection and HVAC
systems equipment and components thereof, including, but not limited to, the
following, where applicable to this project:
1.
Flexible pipe connectors, expansion joints and compensators, pipe loops,
offsets, and swing joints.
2.
Water meters, heat consumption meters, pressure gauges,
thermometers, static pressure gauges, and filter gauges.
3.
Pipe and equipment hangers and supports, equipment bases and
supports, vibration isolation, anchors, cutting, patching, pass through, fire
cutoff, smoke sealed and watertight sleeves, flashing, chases, and all
other mechanical equipment in association therewith.
4.
Electric motors furnished on equipment specified in Division 15.
5.
Nameplates, tags, stencils, pipe painting, pipe markers, and other means
of mechanical identification.
6.
Piping, equipment, and duct insulation.
7.
Pipe, pipe fittings, valves, and connections for sanitary sewer, domestic
water, storm water, natural gas, fuel oil, and process piping systems.
8.
Roof and floor drains, cleanouts, sillcocks and hose stations, wall and
yard hydrants, backflow preventers, water hammer arresters, sand and
grease interceptors, oil/water separators, thermostatic mixing valves, and
other plumbing specialties.
9.
Water closets, urinals, lavatories, sinks, service sinks, electric water
coolers, drinking fountains, showers, wash fountains, emergency eye/face
wash and shower stations, and other plumbing fixtures.
10.
Water heaters, heat exchangers, storage tanks, circulating pumps, sump
pumps, sewage ejectors, and other plumbing equipment.
11.
Packaged air conditioning units, air handling systems, coils, fans, filters,
and humidifiers.
NCS Bloomfield Avenue Station
New Elevators
15000 - 1
12.
13.
14.
15.
16.
D.
1.2
1.3
Ductwork, air turning devices, extractors, backdraft dampers, volume
control dampers, fire and smoke dampers, duct access doors, duct test
holes, air terminal units, VAV-boxes, reheat coils, diffusers, registers,
grilles, louvers, and hoods.
Thermostats and control systems.
Testing, adjusting and balancing.
Hangers, anchors, cutting, patching, pass through, fire cutoff, smoke
sealed and watertight sleeves, bases, chases, supports for fixtures, and
all other mechanical equipment in association therewith.
Temporary water, heating, cooling, and restroom facilities for construction
and all trades.
Install, connect, test and adjust, and leave the prescribed mechanical work ready
for safe and reliable operation; fit equipment and appurtenances to space
provided; and make all components readily accessible and serviceable.
DRAWINGS AND SPECIFICATIONS
A.
Drawings are generally diagrammatic and indicative of the work; follow as closely
as practicable. Neither the Drawings nor these Specifications are intended to
show or describe every small construction detail. Complete the work in such
manner that the various equipment and systems specified will function, operate
and perform in the true intent and meaning of these Specifications.
B.
Locations of equipment, fixtures, piping, etc. shown are only approximately
correct and are subject to modifications caused by structural conditions and
equipment of other trades. No extra charges are allowed for such modifications.
Obtain written approval for any changes contemplated before installation of the
work.
C.
Because of the small scale of Drawings, offsets that may be required to clear
structural work or existing conditions may not be shown. Provide necessary
offsets as required to complete the installation.
MECHANICAL SUBMITTALS
A.
Refer to the General Provisions for Construction for submittal definitions,
requirements, and procedures. Review of submittals is only for general
conformance with the overall design concept, and general compliance with the
standards and requirements specified herein.
B.
Submittal of Shop Drawings, Product Data, and Samples will only be accepted
when submitted by the Contractor. Data received directly from subcontractors
and material suppliers will not be processed.
C.
Perform field inspection of the existing mechanical systems prior to the initiation
of any work. Include all mechanical equipment that is relevant to the work
specified herein. Diagram and submit all findings to NJ TRANSIT.
NCS Bloomfield Avenue Station
New Elevators
15000 - 2
D.
1.4
Submit product data for specified materials and equipment, regardless of
whether specific manufacturers and models or only general design requirements
and reference standards are indicated. In addition, submit drawings of any other
materials or equipment requiring filing or coordination with other trades, as well
as any operating equipment specified elsewhere.
PERMITS, FEES, CODES AND STANDARDS
A.
Complete Work in conformance to the NJ Uniform Construction Code (NJUCC),
its adopted subcodes, and their referenced standards, whether or not specified
herein, including, but not limited to, the following:
1.
NJUCC Mechanical Subcode (2006 ICC International Mechanical Code).
a.
ASHRAE 55, Thermal Environmental Conditions for Human
Occupancy.
b.
ASHRAE 62, Ventilation for Acceptable Indoor Air Quality.
2.
NJUCC Fuel Gas Subcode (2006 ICC International Fuel Gas Code).
3.
NJUCC Plumbing Subcode (2006 NAPHCC National Standard Plumbing
Code).
4.
NJUCC Fire Protection Subcode (2006 ICC International Building Code,
NJ Edition).
a.
2006 ICC Fire Building Code.
b.
NFPA 13-2002, Installation of Sprinkler Systems.
c.
NFPA 14-2003, Standpipe and Hose Systems.
d.
NFPA 24-2002, Installation of Private Fire Service Mains.
e.
NFPA 30-2003, Flammable and Combustible Liquids Code.
5.
NJUCC Energy Conservation Subcode (ASHRAE/IES 90.1-2004).
6.
NJUCC Barrier Free Subcode (ICC/ANSI A117.1-2003).
7.
NJUCC Electrical Subcode (NFPA 70-2005, National Electrical Code).
8.
SMACNA - HVAC Duct Construction Standards - Metal and Flexible.
9.
ASME A13.1 - Scheme for the Identification of Piping Systems.
10.
NAIMA National Insulation Standards.
11.
Listing requirements of Underwriter’s Laboratories, ETL Testing
Laboratories, Factory Mutual, Warnock-Hersey, or other testing firm
acceptable to the authority having jurisdiction.
B.
Complete construction permit application form and applicable subcode forms as
required by the NJ Department of Community Affairs (NJDCA), Bureau of
Construction Project Review, State Buildings Unit. Submit forms to NJDCA
through NJ TRANSIT. NJ TRANSIT will pay for construction permit fees.
C.
Ensure all work is inspected and approved by the NJDCA. Request periodic
rough-in and final inspections as necessary in accordance with NJDCA
requirements.
D.
Do not request Acceptance for Substantial Completion for mechanical work until
final inspection has been made and Certificate of Approval or Occupancy has
been issued by the NJDCA.
NCS Bloomfield Avenue Station
New Elevators
15000 - 3
1.5
E.
Obtain markouts, permits and approvals from utility companies, and any other
authorities having jurisdiction. Pay any fees required by the utility company.
F.
Specific requirements of the NJUCC and its adopted subcodes supersede
conflicting requirements of other documents specified herein, except that the
Contract documents shall take precedence whenever they require materials,
workmanship, arrangements or construction of higher standard or larger size
than is required by codes and regulations.
TESTING LABORATORY CERTIFICATION
A.
1.6
1.7
1.8
Ensure that all mechanical equipment bears approval label from Underwriter’s
Laboratories, ETL/Intertek, Factory Mutual, Warnock-Hersey, or other testing firm
acceptable to the authority having jurisdiction where certification or listing is
furnished for the particular type of equipment.
QUALITY ASSURANCE
A.
Provide, at the appropriate time or as directed, the services of a competent,
factory-trained representative of the particular manufacturer of the equipment or
item involved, to inspect, adjust, and place in proper operating condition any and
all such items of manufacturer. No additional compensation will be allowed the
Contractor for such services.
B.
Demonstrate the proper functioning of all plumbing, fire protection and HVAC
systems equipment; and, equipment supplied by other trades included in the
mechanical work.
WARRANTY
A.
Refer to the General Provisions for Construction for procedures and submittal
requirements for warranties. Refer to individual equipment specifications for
warranty requirements.
B.
Compile and assemble the warranties specified into a separated set of vinyl
covered, 3-ring binders, tabulated and indexed for easy reference.
C.
Provide complete warranty information for each item to include product or
equipment to include date of beginning of warranty or bond; duration of warranty
or bond; and names, addresses and telephone numbers and procedures for filing
a claim and obtaining warranty services.
MANUFACTURER’S OPERATING INSTRUCTIONS
A.
Refer to the General Provisions for Construction for procedures and submittal
requirements for manufacturer’s installation, operating and maintenance
instructions. Refer to individual specification sections for equipment specific
requirements.
NCS Bloomfield Avenue Station
New Elevators
15000 - 4
1.9
1.10
B.
Provide, for each item of equipment or apparatus furnished, printed instruction
manuals obtained from the manufacturer covering the proper operation, care,
lubrication, cleaning, servicing, adjusting and parts manuals, of the items
involved, together with special safety instructions. Arrange for manufacturer's
representative to instruct NJ TRANSIT personnel, who will operate the
equipment, in all such details.
C.
Provide charts and diagrams giving the number, location and function of each
item, and including the following:
1.
Manufacturer;
2.
Product name;
3.
Model number;
4.
Serial number;
5.
Capacity;
6.
Operating and power characteristics;
7.
Labels of tested compliances; and,
8.
Similar essential data
D.
Locate nameplates in an accessible and easily visible location.
DELIVERY, STORAGE, AND HANDLING
A.
Deliver, store, protect, and handle Products to site under requirements of
General Provisions for Construction.
B.
Accept and store equipment and materials on site and inspect for damage,
unless off-site storage is authorized in writing. Protect from corrosion and
entrance of debris by storing above grade. Provide appropriate covering to
protect stored equipment and materials from damage and exposure to weather.
C.
Deliver products to project properly identified with names, model numbers, types,
grades, compliance labels, and similar information needed for distinct
identifications; adequately packaged; and protected to prevent damage during
shipment, storage and handling.
D.
Coordinate deliveries of materials and equipment to minimize construction site
congestion. Limit each shipment of materials and equipment to the items and
quantities needed for the smooth and efficient flow of installations.
PROJECT RECORD DOCUMENTS
A.
Submit under requirements of General Provisions for Construction.
B.
Mark “AS-BUILT” drawings and specifications to indicate revisions to all
equipment; approved substitutions and actual equipment and materials used;
actual equipment locations; mechanical circuitry; Change Orders; and, concealed
control system devices.
NCS Bloomfield Avenue Station
New Elevators
15000 - 5
C.
1.11
1.12
Mark “AS-BUILT” specifications to indicate approved substitutions; Change
Orders; actual equipment and materials used.
PROJECT CONDITIONS
A.
Verify that field measurements are as shown on Drawings.
B.
Verify routing and termination locations of piping and ductwork prior to rough-in.
C.
Piping and duct routing are shown on Drawings in approximate locations unless
dimensioned. Route as required to complete plumbing, fire protection or HVAC
system, as applicable.
SCHEDULING
A.
Schedule work to expedite collection of data to ensure completion of study for
final approval of distribution equipment shop drawings prior to release of
equipment for manufacturing.
PART 2 PRODUCTS
2.1
MATERIALS AND EQUIPMENT
A.
As specified in individual specification sections.
PART 3 EXECUTION
3.1
GENERAL REQUIREMENTS
A.
Coordinate work with all trades involved. Follow overall Contract phasing plans.
B.
Verify all dimensions by field measurements. Verify plumbing connections are as
shown on Drawings.
C.
Arrange for chases, slots, and openings to allow for mechanical installations.
D.
Coordinate the installation of required supporting devices and sleeves to be set
in poured-in-place concrete and other structural components, as they are
constructed.
E.
Sequence, coordinate and integrate installations of mechanical materials and
equipment for efficient flow of the work.
F.
Coordinate the cutting and patching of components to accommodate the
installation of mechanical equipment and materials. Perform patching using
trade most proficient in repairing the particular materials and/or surfaces
damaged.
NCS Bloomfield Avenue Station
New Elevators
15000 - 6
3.2
3.3
G.
Where mounting heights are not detailed or dimensioned, install mechanical
services and overhead equipment to provide the maximum headroom possible.
H.
Install mechanical equipment to facilitate maintenance and repair or replacement
of equipment components. As much as practical, connect equipment for ease of
disconnecting, with minimum of interference with other installations.
I.
Coordinate the installation of mechanical materials and equipment with structural
components and electrical systems.
J.
When two or more items of same material or equipment are required, provide
products of the same manufacturer. Product manufacturer uniformity does not
apply to raw materials, bulk materials, wire, conduit, fittings, sheet metal, steel
bar stock, welding rods, solder, fasteners, motors for dissimilar equipment units,
and similar items used in work, except as otherwise indicated.
K.
Provide products that are compatible within systems and other connected items.
COOPERATION WITH OTHER TRADES
A.
Cooperate with all other trades whose work might in any way affect Mechanical
installations, and arrange work within all practical limits so that there will be no
interference with the work of the various trades.
B.
Where the work is concealed, provide advance planning as necessary to prevent
projections beyond finished surfaces.
C.
Assume full responsibility for damage caused by Mechanical work to the work of
other trades during the execution of this Contract.
PIPING AND DUCTWORK LAYOUT
A.
Responsibility for accurate piping and ductwork layout and changes to the layout
rests with the Mechanical Contractor. Changes to the layout to accommodate
conditions arising during construction shall be made without additional
compensation.
1.
Run piping and ductwork straight and direct, neatly and evenly spaced,
forming right angles or parallel lines with building walls and other conduit.
2.
Keep horizontal piping runs high and close to walls, except where
concealed in construction.
3.
Install all piping and ductwork with necessary offsets as encountered to
suit structural and other building conditions. Minimize use of offsets, but
where necessary, keep close to underside of beams, joists and similar
construction.
4.
Conceal work in finished spaces where feasible, and where shown.
B.
Electrically lock out all mechanical equipment with tags until tested, and then lock
out again until completion of all construction activities and normal service begins.
NCS Bloomfield Avenue Station
New Elevators
15000 - 7
3.4
3.5
3.6
PAINTING
A.
Thoroughly clean all work and leave same in a neat and workmanlike condition
for the application of field painting.
B.
If factory finishes, including prime coats on equipment, are marred, worn, rusted,
or otherwise defaced, repaint same with two coats of enamel of matching color.
C.
Apply two coats of rust inhibiting enamel paint to all concealed supports
fabricated of ferrous metal that are not otherwise protected against corrosion.
D.
Unless otherwise noted, paint all uninsulated, exposed ductwork to match finish
of adjacent wall or structure. Refer to the requirements of Section 15075.
E.
Unless otherwise noted, paint all uninsulated ferrous metal piping in accordance
with the color-coding requirements indicated in Section 15075.
ELIMINATION OF NOISE AND VIBRATION
A.
Ensure all equipment and accessories operate without objectionable noise and
vibration.
B.
Should operation of any one or more of the systems produce noise or vibration
which is objectionable, make changes in equipment and do all work necessary to
eliminate the objectionable noise or vibration.
FINAL TESTS
A.
Prior to requesting Acceptance for Substantial Completion for mechanical work,
successfully perform all tests specified, deemed necessary to show proper
execution of the work, and/or required by code in the presence of the
Construction Manager, Engineer, and the appropriate NJDCA Subcode
Inspector. Submit scheduling of all testing procedures for approval in advance.
B.
Perform all tests and inspections of equipment, material, and wiring to determine
whether all provisions of these Specifications and Drawings have been fulfilled.
Test piping and ductwork for leakage and proper flow rates using suitable testing
instruments. Lubricate all rotating equipment and check direction of rotation of all
motors.
C.
Where equipment supplied by other trades includes connections to plumbing, fire
protection or HVAC systems, conduct testing that will prove proper functional
performance specifically by the trade responsible for that equipment.
NCS Bloomfield Avenue Station
New Elevators
15000 - 8
PART 4 COMPENSATION
4.1
MEASUREMENT AND PAYMENT
A.
Measurement: The work of this section shall not be measured.
B.
Payment: The cost of this section shall be included in the lump sum bid item
PLUMBING or HVAC SYSTEMS, as applicable to the equipment or system
served.
END OF SECTION
NCS Bloomfield Avenue Station
New Elevators
15000 - 9
SECTION 15060
HANGERS AND SUPPORTS
PART 1 GENERAL
1.1
1.2
SUMMARY
A.
Section Includes:
1.
Pipe hangers and supports.
2.
Hanger rods.
3.
Inserts.
4.
Flashing.
5.
Equipment curbs.
6.
Sleeves.
7.
Mechanical sleeve seals.
8.
Formed steel channel.
9.
Firestopping relating to mechanical work.
10.
Firestopping accessories.
11.
Equipment bases and supports.
B.
Related Sections:
1.
Section 03100 - Concrete Formwork: Execution requirements for
placement of inserts and sleeves in concrete forms specified by this
section.
2.
Section 03300 - Cast-in-Place Concrete: Execution requirements for
placement of concrete housekeeping pads specified by this section.
3.
Section 07270 - Firestopping: Product requirements for firestopping for
placement by this section.
4.
Section 07920 - Sealant and Caulking: Product requirements for sealant
materials for placement by this section.
5.
Section 09900 - Painting: Product and execution requirements for
painting specified by this section.
6.
Section 15070 - Mechanical Sound, Vibration, and Seismic Control:
Product and execution requirements for vibration isolators.
7.
Section 15140 - Domestic Water Piping: Execution requirements for
placement of hangers and supports specified by this section.
8.
Section 15150 - Sanitary Waste and Vent Piping: Execution requirements
for placement of hangers and supports specified by this section.
9.
Section 15160 - Storm Drainage Piping: Execution requirements for
placement of hangers and supports specified by this section.
REFERENCES
A.
ASTM International:
1.
ASTM E84 - Test Method for Surface Burning Characteristics of Building
Materials.
NCS Bloomfield Avenue Station
New Elevators
15060 - 1
2.
3.
4.
1.3
B.
American Welding Society:
1.
AWS D1.1 - Structural Welding Code - Steel.
C.
Manufacturers Standardization Society of the Valve and Fittings Industry:
1.
MSS SP 58 - Pipe Hangers and Supports - Materials, Design and
Manufacturer.
2.
MSS SP 69 - Pipe Hangers and Supports - Selection and Application.
3.
MSS SP 89 - Pipe Hangers and Supports - Fabrication and Installation
Practices.
D.
Underwriters Laboratories Inc.:
1.
UL - Fire Resistance Directory.
DEFINITIONS
A.
1.4
1.5
1.6
ASTM E119 - Method for Fire Tests of Building Construction and
Materials.
ASTM E814 - Test Method of Fire Tests of Through Penetration
Firestops.
ASTM F708 - Standard Practice for Design and Installation of Rigid Pipe
Hangers.
Firestopping (Through-Penetration Protection System): Sealing or stuffing
material or assembly placed in spaces between and penetrations through
building materials to arrest movement of fire, smoke, heat, and hot gases through
fire rated construction.
SYSTEM DESCRIPTION
A.
Firestopping Materials: ASTM E119; ASTM E814 to achieve fire ratings as noted
on Drawings for adjacent construction, but not less than 1 hour fire rating.
B.
Surface Burning: ASTM E84 with maximum flame spread/smoke developed
rating of 25/50.
C.
Firestop interruptions to fire rated assemblies, materials, and components.
PERFORMANCE REQUIREMENTS
A.
Firestopping: Conform to ASTM E119 for fire resistance ratings and ASTM E84
for surface burning characteristics.
B.
Firestopping: Provide certificate of compliance from authority having jurisdiction
indicating approval of materials used.
SUBMITTALS
A.
Submit in accordance with General Provisions for Construction.
NCS Bloomfield Avenue Station
New Elevators
15060 - 2
1.7
1.8
B.
Shop Drawings: Indicate system layout with location including critical dimensions,
sizes, and pipe hanger and support locations and detail of trapeze hangers.
C.
Product Data:
1.
Hangers and Supports: Submit manufacturers catalog data including load
capacity.
2.
Firestopping: Submit data on product characteristics, performance and
limitation criteria.
D.
Firestopping Schedule: Submit schedule of opening locations and sizes,
penetrating items, and required listed design numbers to seal openings to
maintain fire resistance rating of adjacent assembly.
E.
Design Data: Indicate load carrying capacity of trapeze, multiple pipe, and riser
support hangers. Indicate calculations used to determine load carrying capacity
of trapeze, multiple pipe, and riser support hangers. Submit sizing methods and
calculations sealed by a licensed professional engineer registered in the State of
New Jersey.
F.
Manufacturer's Installation Instructions:
1.
Hangers and Supports: Submit special procedures and assembly of
components.
2.
Firestopping: Submit preparation and installation instructions.
G.
Manufacturer's Certificate: Certify products meet or exceed specified
requirements.
H.
Engineering Judgments: For conditions not covered by UL listed designs, submit
judgments by licensed professional engineer suitable for presentation to authority
having jurisdiction for acceptance as meeting code fire protection requirements.
QUALITY ASSURANCE
A.
Perform Work in accordance with NJ Uniform Construction Code, and its adopted
subcodes, as indicated in Section 15010.
B.
Perform Work in accordance with AWS D1.1 for welding hanger and support
attachments to building structure.
QUALIFICATIONS
A.
Manufacturer: Company specializing in manufacturing Products specified in this
section with minimum three years documented experience.
B.
Installer: Company specializing in performing Work of this section with minimum
three years documented experience.
NCS Bloomfield Avenue Station
New Elevators
15060 - 3
1.9
1.10
1.11
DELIVERY, STORAGE, AND HANDLING
A.
Transport, handle, store, and protect products in accordance with the General
Provisions for Construction.
B.
Accept materials on site in original factory packaging, labeled with manufacturer's
identification.
C.
Protect from weather and construction traffic, dirt, water, chemical, and
mechanical damage, by storing in original packaging.
ENVIRONMENTAL REQUIREMENTS
A.
Maintain environmental conditions required for products installed or stored on
site in accordance with the General Provisions for Construction.
B.
Do not apply firestopping materials when temperature of substrate material and
ambient air is below 60 degrees F.
C.
Maintain this minimum temperature before, during, and for minimum 3 days after
installation of firestopping materials.
D.
Provide ventilation in areas to receive solvent cured materials.
FIELD MEASUREMENTS
A.
1.12
Verify field measurements prior to fabrication.
WARRANTY
A.
Provide product warranties and product bonds in accordance with the General
Provisions for Construction.
B.
Furnish five-year manufacturer’s warranty for pipe hangers and supports.
PART 2 PRODUCTS
2.1
PIPE HANGERS AND SUPPORTS
A.
Manufacturers:
1.
Carpenter & Paterson Inc.
2.
Creative Systems Inc.
3.
Flex-Weld, Inc.
4.
Globe Pipe Hanger Products Inc.
5.
Michigan Hanger Co.
6.
Superior Valve Co.
7.
Substitutions: Submit requests for substitution in accordance with the
General Provisions for Construction.
NCS Bloomfield Avenue Station
New Elevators
15060 - 4
B.
Plumbing Piping - DWV:
1.
Conform to MSS SP58; MSS SP69; and MSS SP89.
2.
Hangers for Pipe Sizes 1/2 to 1-1/2 inch: Malleable iron or carbon steel,
adjustable swivel, split ring.
3.
Hangers for Pipe Sizes 2 inches and Larger: Carbon steel, adjustable,
clevis.
4.
Multiple or Trapeze Hangers: Steel channels with welded spacers and
hanger rods.
5.
Wall Support for Pipe Sizes 3 inches and Smaller: Cast iron hook.
6.
Wall Support for Pipe Sizes 4 inches and Larger: Welded steel bracket
and wrought steel clamp.
7.
Vertical Support: Steel riser clamp.
8.
Floor Support: Cast iron adjustable pipe saddle, lock nut, nipple, floor
flange, and concrete pier or steel support.
9.
Copper Pipe Support: Copper-plated, carbon-steel adjustable, ring.
C.
Plumbing Piping - Water:
1.
Conform to MSS SP58; MSS SP69; and MSS SP89.
2.
Hangers for Pipe Sizes 1/2 to 1-1/2 inch: Malleable iron or carbon steel,
adjustable swivel, split ring.
3.
Hangers for Cold Pipe Sizes 2 inches and Larger: Carbon steel,
adjustable, clevis.
4.
Hangers for Hot Pipe Sizes 2 to 4 inches: Carbon steel, adjustable, clevis.
5.
Hangers for Hot Pipe Sizes 6 inches and Larger: Adjustable steel yoke,
cast iron roll, double hanger.
6.
Multiple or Trapeze Hangers: Steel channels with welded spacers and
hanger rods.
7.
Multiple or Trapeze Hangers for Hot Pipe Sizes 6 inches and Larger:
Steel channels with welded spacers and hanger rods, cast iron roll.
8.
Wall Support for Pipe Sizes 3 inches and Smaller: Cast iron hook.
9.
Wall Support for Pipe Sizes 4 inches and Larger: Welded steel bracket
and wrought steel clamp.
10.
Wall Support for Hot Pipe Sizes 6 inches and Larger: Welded steel
bracket and wrought steel clamp with adjustable steel yoke and cast iron
roll.
11.
Vertical Support: Steel riser clamp.
12.
Floor Support for Cold Pipe: Cast iron adjustable pipe saddle, lock nut,
nipple, floor flange, and concrete pier or steel support.
13.
Floor Support for Hot Pipe Sizes 4 inches and Smaller: Cast iron
adjustable pipe saddle, lock nut, nipple, floor flange, and concrete pier or
steel support.
14.
Floor Support for Hot Pipe Sizes 6 inches and Larger: Adjustable cast
iron roll and stand, steel screws, and concrete pier or steel support.
15.
Copper Pipe Support: Copper-plated, Carbon-steel ring.
D.
Refrigerant Piping:
1.
Conform to MSS SP58; MSS SP69; and MSS SP89.
NCS Bloomfield Avenue Station
New Elevators
15060 - 5
2.
3.
4.
5.
2.2
ACCESSORIES
A.
2.3
2.4
2.5
Hangers for Pipe Sizes 1/2 to 1-1/2 inch: Copper-plated malleable iron or
carbon steel, adjustable swivel, split ring.
Hangers for Pipe Sizes 2 inches and Larger: Copper-plated carbon steel,
adjustable, clevis.
Multiple or Trapeze Hangers: Steel channels with welded spacers and
hanger rods.
Vertical Support: Copper-plated steel riser clamp.
Hanger Rods: Mild steel threaded both ends, threaded on one end, or continuous
threaded.
INSERTS
A.
Manufacturers:
1.
B-Line Systems, Inc.
2.
Unistrut Corp.
3.
Kindorf Div., Thomas & Betts Corp.
4.
Substitutions: Submit requests for substitution in accordance with the
General Provisions for Construction.
B.
Spot Inserts: Galvanized steel or malleable iron, with threaded connection or
channel slot for hanger rods and insert nuts; lugs for attaching to forms; size
inserts to suit threaded hanger rods.
C.
Continuous Insert Channels: Minimum 12 gauge galvanized steel, with channel
slot for hanger rods and insert nuts; welded or punched anchors; anchor end
caps; size inserts to suit threaded hanger rods.
EXPANSION ANCHORS
A.
Manufacturers:
1.
Hilti Corp., “Kwik-Bolt” Model.
2.
ITW Ramset/Red Head, “Trubolt” Model.
3.
Molly Div., USM Corp., “Parabolt” Model.
4.
Substitutions: Submit requests for substitution in accordance with the
General Provisions for Construction.
B.
Anchors: Expanding wedge type with zinc-plated carbon steel stud, wedge, nut
and washer, sized for load intended.
FLASHING
A.
Metal Flashing: Minimum 26-gauge thick galvanized steel.
B.
Metal Counterflashing: Minimum 22-gauge thick galvanized steel.
C.
Lead Flashing:
NCS Bloomfield Avenue Station
New Elevators
15060 - 6
1.
2.
2.6
2.7
2.8
Waterproofing: 5 lb./sq. ft sheet lead.
Soundproofing: 1 lb./sq. ft sheet lead.
D.
Flexible Flashing: 47-mil thick sheet butyl; compatible with roofing.
E.
Caps: Steel, 22-gauge minimum; 16-gauge at fire resistant elements.
EQUIPMENT CURBS
A.
Manufacturers:
1.
Custom-Curb, Inc., Model CRC or CES.
2.
ThyCurb Div., ThyBar Corp., Model TC or TEMS.
3.
Roof Products and Systems Corp., Model RC or ER.
4.
The Pate Co., Model PC or ES.
5.
AES Industries, Inc., Model ARC or AES.
6.
Substitutions: Submit requests for substitution in accordance with the
General Provisions for Construction.
B.
Fabrication: Welded 18-gauge galvanized steel shell and base, mitered 3-inch
cant, variable step to match roof insulation, 1-1/2 inch thick insulation, factory
installed wood nailer.
SLEEVES
A.
Sleeves for Pipes Through Non-fire Rated Floors: 18-gauge thick galvanized
steel.
B.
Sleeves for Pipes Through Non-fire Rated Beams, Walls, Footings, and
Potentially Wet Floors: Steel pipe or 18-gauge thick galvanized steel.
C.
Sleeves for Round Ductwork: Galvanized steel.
D.
Sleeves for Rectangular Ductwork: Galvanized steel or wood.
E.
Sealant: Acrylic; refer to Section 07920.
MECHANICAL SLEEVE SEALS
A.
Manufacturers:
1.
Link-Seal Div., Thunderline Corp.
2.
CSD Sealing Systems.
3.
ProSet Systems, Inc.
4.
Substitutions: Submit requests for substitution in accordance with the
General Provisions for Construction.
B.
Product Description: Modular mechanical type, consisting of interlocking
synthetic rubber links shaped to continuously fill annular space between object
and sleeve, connected with bolts and pressure plates causing rubber sealing
NCS Bloomfield Avenue Station
New Elevators
15060 - 7
elements to expand when tightened, providing watertight seal and electrical
insulation.
2.9
2.10
FORMED STEEL CHANNEL
A.
Manufacturers:
1.
B-Line Systems/Cooper Industries.
2.
Kindorf/Thomas & Betts Corp.
3.
Unistrut Corp.
4.
Allied Tube and Conduit Corp., “Power-Strut.”
5.
GS Metals Corp., “Globe-Strut.”
6.
Versabar Corp.
7.
Substitutions: Submit requests for substitution in accordance with the
General Provisions for Construction.
B.
Product Description: ASTM A446/ASTM A525 zinc-coated or ASTM A570
painted steel for interior applications; ASTM A123 galvanized steel for exterior
applications, with holes 1-1/2 inches on center.
FIRESTOPPING
A.
Manufacturers:
1.
3M Corp., “Fire Barrier” CP 25WB or 2000N/S.
2.
Dow-Corning Corp., “Firestop RTV” 3-6548.
3.
Hilti Corp., “FS-One”.
4.
W.R. Grace & Co., “FlameSafe” FS-1900.
5.
Specified Technologies, Inc., “SpecSeal Triple S”.
6.
USG Corp., “FireCode”.
7.
AD Fire Protection Systems, “FireBarrier”.
8.
Substitutions: Submit requests for substitution in accordance with the
General Provisions for Construction.
B.
Product Description: Different types of products by multiple manufacturers are
acceptable as required to meet specified system description and performance
requirements; provide only one type for each similar application.
1.
Silicone Firestopping Elastomeric Firestopping: Single component
silicone elastomeric compound and compatible silicone sealant.
2.
Foam Firestopping Compounds: Two-component foam compound.
3.
Formulated Firestopping Compound of Incombustible Fibers: Formulated
compound mixed with incombustible non-asbestos fibers.
4.
Fiber Stuffing and Sealant Firestopping: Composite of mineral fiber
stuffing insulation with silicone elastomer for smoke stopping.
5.
Mechanical Firestopping Device with Fillers: Mechanical device with
incombustible fillers and silicone elastomer, covered with sheet stainless
steel jacket, joined with collars, penetration sealed with flanged stops.
6.
Intumescent Firestopping: Intumescent putty compound which expands
on exposure to surface heat gain.
7.
Firestop Pillows: Formed mineral fiber pillows.
NCS Bloomfield Avenue Station
New Elevators
15060 - 8
C.
2.11
Color: As selected from manufacturer’s full range of colors to match adjacent
finish.
FIRESTOPPING ACCESSORIES
A.
Primer: Type recommended by firestopping manufacturer for specific substrate
surfaces and suitable for required fire ratings.
B.
Dam Material: As recommended by firestopping product manufacturer. Use
mineral fiber where manufacturer’s instructions are silent.
C.
Installation Accessories: Provide clips, collars, fasteners, temporary stops or
dams, and other devices required to position and retain materials in place.
D.
General:
1.
Furnish NRTL listed products.
2.
Select products with rating not less than rating of wall or floor being
penetrated.
E.
Non-Rated Surfaces:
1.
Stamped steel, chrome plated, hinged, split ring escutcheons or floor
plates or ceiling plates for covering openings in occupied areas where
conduit is exposed.
2.
For exterior wall openings below grade, furnish modular mechanical type
seal consisting of interlocking synthetic rubber links shaped to
continuously fill annular space between conduit and cored opening or
water-stop type wall sleeve.
PART 3 EXECUTION
3.1
3.2
EXAMINATION
A.
Verify existing conditions before starting work.
B.
Verify openings are ready to receive sleeves.
C.
Verify openings are ready to receive firestopping.
PREPARATION
A.
Clean substrate surfaces of dirt, dust, grease, oil, loose material, or other matter
affecting bond of firestopping material.
B.
Remove incompatible materials affecting bond.
C.
Install backing or damming materials as required to arrest liquid material leakage.
D.
Do not use powder-actuated anchors.
NCS Bloomfield Avenue Station
New Elevators
15060 - 9
E.
3.3
3.4
Do not drill or cut structural members without written permission from the
Architect/Engineer.
INSTALLATION – ANCHORS AND INSERTS
A.
Anchors and Fasteners:
1.
Concrete Structural Elements: Use precast/preset inserts or expansion
anchors. Do not use powder-actuated fasteners.
2.
Steel Structural Elements: Use beam clamps, steel ramset fasteners, and
welded fasteners. Do not use spring steel clips and clamps.
3.
Concrete Surfaces: Use expansion anchors.
4.
Hollow Masonry, Plaster, and Gypsum Board Partitions: Use toggle bolts
or hollow wall fasteners.
5.
Solid Masonry Walls: Use expansion anchors or preset inserts.
6.
Sheet Metal: Provide sheet metal screws.
7.
Wood Elements: Provide wood screws.
B.
Inserts:
1.
Install inserts for placement in concrete forms.
2.
Install inserts for suspending hangers from reinforced concrete slabs and
sides of reinforced concrete beams.
3.
Provide hooked rod to concrete reinforcement section for inserts carrying
pipe over 4 inches.
4.
Where concrete slabs form finished ceiling, locate inserts flush with slab
surface.
5.
Where inserts are omitted, drill through concrete slab from below and
provide through-bolt with recessed square steel plate and nut recessed
into and grouted flush with slab.
INSTALLATION - PIPE HANGERS AND SUPPORTS
A.
Install in accordance with MSS SP 58; MSS SP 69; and MSS SP 89.
B.
Support horizontal piping as scheduled.
C.
Install hangers with minimum 1/2-inch space between finished covering and
adjacent work.
D.
Place hangers within 12 inches of each horizontal elbow.
E.
Use hangers with 1-1/2 inch minimum vertical adjustment.
F.
Support horizontal cast iron pipe adjacent to each hub, with 5 feet maximum
spacing between hangers.
G.
Support vertical piping as required by code.
H.
Where piping is installed in parallel and at same elevation, provide multiple pipe
or trapeze hangers.
NCS Bloomfield Avenue Station
New Elevators
15060 - 10
3.5
3.6
I.
Support riser piping independently of connected horizontal piping.
J.
Provide copper plated hangers and supports for copper piping.
K.
Design hangers for pipe movement without disengagement of supported pipe.
L.
Prime coat exposed steel hangers and supports. Refer to Section 09900.
Hangers and supports located in crawl spaces, pipe shafts, and suspended
ceiling spaces are not considered exposed.
M.
Provide clearance in hangers and from structure and other equipment for
installation of insulation. Refer to Section 15080.
INSTALLATION - EQUIPMENT BASES AND SUPPORTS
A.
Provide housekeeping pads of concrete, minimum 3-1/2 inches thick and
extending 6 inches beyond supported equipment. Refer to Section 03300.
B.
Using templates furnished with equipment, install anchor bolts, and accessories
for mounting and anchoring equipment.
C.
Construct supports of steel members or formed steel channel. Brace and fasten
with flanges bolted to structure.
D.
Provide rigid anchors for pipes after vibration isolation components are installed.
Refer to Section 15070.
INSTALLATION - FLASHING
A.
Provide flexible flashing and metal Counterflashing where piping and ductwork
penetrate weather or waterproofed walls, floors, and roofs.
B.
Flash vent and soil pipes projecting 3 inches minimum above finished roof
surface with lead worked 1 inch minimum into hub, 8 inches minimum clear on
sides with 24 x 24 inches sheet size. For pipes through outside walls, turn
flanges back into wall and caulk, metal counter-flash, and seal.
C.
Flash floor drains in floors with topping over finished areas with lead, 10 inches
clear on sides with minimum 36 x 36 inch sheet size. Fasten flashing to drain
clamp device.
D.
Seal floor drains, shower drains, and floor sinks watertight to adjacent materials.
E.
Provide acoustical lead flashing around ducts and pipes penetrating equipment
rooms for sound control.
F.
Provide curbs for mechanical roof installations 12 inches minimum high above
roofing surface. Flash and counter-flash with sheet metal; seal watertight. Attach
NCS Bloomfield Avenue Station
New Elevators
15060 - 11
counterflashing mechanical equipment and lap base flashing on roof curbs.
Flatten and solder joints.
G.
3.7
3.8
Adjust storm collars tight to pipe with bolts; caulk around top edge. Use storm
collars above roof jacks. Screw vertical flange section to face of curb.
INSTALLATION - SLEEVES
A.
Exterior watertight entries: Seal with mechanical sleeve seals.
B.
Set sleeves in position in forms. Provide reinforcing around sleeves.
C.
Size sleeves large enough to allow for movement due to expansion and
contraction. Provide for continuous insulation wrapping.
D.
Extend sleeves through floors minimum 1-inch above finished floor level. Caulk
sleeves.
E.
Where piping or ductwork penetrates floor, ceiling, or wall, close off space
between pipe or duct and adjacent work with firestopping insulation and caulk.
Provide close fitting metal collar or escutcheon covers at both sides of
penetration.
F.
Install chrome plated steel escutcheons at finished surfaces.
INSTALLATION - FIRESTOPPING
A.
Install material at fire rated construction perimeters and openings containing
penetrating sleeves, piping, ductwork, and other items, requiring firestopping.
B.
Apply primer where recommended by manufacturer for type of firestopping
material and substrate involved, and as required for compliance with required fire
ratings.
C.
Apply firestopping material in sufficient thickness to achieve required fire and
smoke rating, to uniform density and texture.
D.
Compress fibered material to maximum 40 percent of its uncompressed size.
E.
Place foamed material in layers to ensure homogenous density, filling cavities
and spaces. Place sealant to completely seal junctions with adjacent dissimilar
materials.
F.
Place intumescent coating in sufficient coats to achieve rating required.
G.
Remove dam material after firestopping material has cured.
H.
Fire Rated Surfaces:
NCS Bloomfield Avenue Station
New Elevators
15060 - 12
1.
2.
I.
3.9
Inspect installed firestopping for compliance with specifications and submitted
schedule.
CLEANING
A.
3.11
Non-Rated Surfaces:
1.
Seal opening through non-fire rated floor, wall, partition, ceiling, and roof
penetrations as follows:
a.
Install sleeve through opening and extending beyond minimum of
1 inch on both sides of building element.
b.
Size sleeve allowing minimum of 1-inch void between sleeve and
building element.
c.
Install type of firestopping material recommended by
manufacturer.
2.
Install escutcheons, floor plates or ceiling plates where pipe or conduit
penetrates non-fire rated surfaces in occupied spaces. Occupied spaces
include rooms with finished ceilings and where penetration occurs below
finished ceiling.
3.
Exterior wall openings below grade: Assemble rubber links of mechanical
sealing device to size of pipe and tighten in place, in accordance with
manufacturer's instructions.
4.
Interior partitions: Seal pipe penetrations at computer rooms,
telecommunication rooms, and/or data rooms. Apply sealant to both sides
of penetration to completely fill annular space between sleeve and
conduit.
FIELD QUALITY CONTROL
A.
3.10
Seal opening at floor, wall, partition, ceiling, and roof penetrations as
follows:
a.
Install sleeve through opening and extending beyond minimum of
1 inch on both sides of building element.
b.
Size sleeve allowing minimum of 1-inch void between sleeve and
building element.
c.
Pack void with backing material.
d.
Seal ends of sleeve with UL listed fire resistive silicone compound
to meet fire rating of structure penetrated.
Where pipe, duct, cable, conduit, wireway, and/or trough penetrates fire
rated surface, install firestopping product in accordance with
manufacturer's instructions.
Clean adjacent surfaces of firestopping materials.
PROTECTION OF FINISHED WORK
A.
Protect adjacent surfaces from damage by material installation.
NCS Bloomfield Avenue Station
New Elevators
15060 - 13
PART 4 COMPENSATION
4.1
MEASUREMENT AND PAYMENT
A.
Measurement: The work of this section shall not be measured.
B.
Payment: The cost of this section shall be included in the lump sum bid items
PLUMBING or HVAC SYSTEMS, as applicable to the system served.
END OF SECTION
NCS Bloomfield Avenue Station
New Elevators
15060 - 14
SECTION 15070
MECHANICAL SOUND, VIBRATION, AND SEISMIC CONTROL
PART 1 GENERAL
1.1
1.2
1.3
1.4
SUMMARY
A.
Section Includes:
1.
Vibration isolation.
2.
Seismic control.
B.
Related Sections:
1.
Section 15060 - Hangers and Supports: Product requirements for pipe
hangers and supports.
2.
Section 15120 - Piping Specialties: Product requirements for anchors and
piping expansion compensation.
3.
Section 15950 - Testing, Adjusting, and Balancing: Requirements for
sound and vibration measurements performed independent of this
section.
REFERENCES
A.
American Society of Heating, Refrigerating and Air Conditioning Engineers:
1.
ASHRAE Handbook - HVAC Applications.
B.
Sheet Metal and Air Conditioning Contractors’ National Association:
1.
SMACNA - HVAC Duct Construction Standard - Metal and Flexible.
C.
Federal Specifications and Standards:
1.
FS RR-W-410 - Wire Rope and Strand.
PERFORMANCE REQUIREMENTS
A.
Provide equipment vibration isolation and minimum static deflection in
accordance with the recommendations specified in Table 42 – Selection Guide
for Vibration Isolation, in the ASHRAE Handbook – HVAC Applications.
B.
Provide vibration isolation on motor driven equipment over 0.5 hp, plus
connected piping and ductwork.
SUBMITTALS
A.
Submit in accordance with General Provisions for Construction.
B.
Product Data: Submit schedule of vibration isolator type with location and load on
each. Submit catalog information indicating, materials, dimensional data,
performance.
NCS Bloomfield Avenue Station
New Elevators
15070 - 1
1.5
1.6
1.7
C.
Manufacturer's Installation Instructions: Submit special procedures and setting
dimensions. Indicate installation requirements maintaining integrity of sound
isolation.
D.
Manufacturer's Certificate: Certify isolators meet or exceed specified
requirements.
CLOSEOUT SUBMITTALS
A.
Submit in accordance with General Provisions for Construction.
B.
Project Record Documents: Record actual locations of hangers including
attachment points.
QUALIFICATIONS
A.
Manufacturer: Company specializing in manufacturing products specified in this
section with minimum three years documented experience.
B.
Installer: Company specializing in performing Work of this section with minimum
three years documented experience and approved by manufacturer.
FIELD MEASUREMENTS
A.
Verify field measurements prior to fabrication.
PART 2 PRODUCTS
2.1
VIBRATION ISOLATORS
A.
Manufacturers:
1.
Mason Industries, Inc.
2.
Aeroflex, Inc., Isolator Products Group (VMC/Korfund).
3.
Isolation Technologies, Inc.
4.
Taylor Devices, Inc.
5.
Vibration Isolation, Inc.
6.
Substitutions: Refer to requirements of General Provisions for
Construction.
B.
Open Spring Isolators:
1.
Spring Isolators:
a.
For Exterior and Humid Areas: Furnish hot dipped galvanized
housings and neoprene coated springs.
b.
Code: Color code springs for load carrying capacity.
2.
Springs: Minimum horizontal stiffness equal to 75 percent vertical
stiffness, with working deflection between 0.3 and 0.6 of maximum
deflection.
NCS Bloomfield Avenue Station
New Elevators
15070 - 2
3.
4.
Spring Mounts: Furnish with leveling devices, minimum 0.25 inch thick
neoprene sound pads, and zinc chromate plated hardware.
Sound Pads: Size for minimum deflection of 0.05 inch; meet requirements
for neoprene pad isolators.
C.
Restrained Spring Isolators:
1.
Spring Isolators:
a.
For Exterior and Humid Areas: Furnish hot dipped galvanized
housings and neoprene coated springs.
b.
Code: Color code springs for load carrying capacity.
2.
Springs: Minimum horizontal stiffness equal to 75 percent vertical
stiffness, with working deflection between 0.3 and 0.6 of maximum
deflection.
3.
Spring Mounts: Furnish with leveling devices, minimum 0.25 inch thick
neoprene sound pads, and zinc chromate plated hardware.
4.
Sound Pads: Size for minimum deflection of 0.05 inch; meet requirements
for neoprene pad isolators.
5.
Restraint: Furnish mounting frame and limit stops.
D.
Closed Spring Isolators:
1.
Spring Isolators:
a.
For Exterior and Humid Areas: Furnish hot dipped galvanized
housings and neoprene coated springs.
b.
Code: Color code springs for load carrying capacity.
2.
Type: Closed spring mount with top and bottom housing separated with
neoprene rubber stabilizers.
3.
Springs: Minimum horizontal stiffness equal to 75 percent vertical
stiffness, with working deflection between 0.3 and 0.6 of maximum
deflection.
4.
Housings: Incorporate neoprene isolation pad meeting requirements for
neoprene pad isolators, and neoprene side stabilizers with minimum 0.25
inch clearance.
E.
Restrained Closed Spring Isolators:
1.
Spring Isolators:
a.
For Exterior and Humid Areas: Furnish hot dipped galvanized
housings and neoprene coated springs.
b.
Code: Color code springs for load carrying capacity.
2.
Type: Closed spring mount with top and bottom housing separated with
neoprene rubber stabilizers.
3.
Springs: Minimum horizontal stiffness equal to 75 percent vertical
stiffness, with working deflection between 0.3 and 0.6 of maximum
deflection.
4.
Housings: Incorporate neoprene isolation pad meeting requirements for
neoprene pad isolators, and neoprene side stabilizers with minimum 0.25
inch clearance and limit stops.
F.
Spring Hanger:
1.
Spring Isolators:
NCS Bloomfield Avenue Station
New Elevators
15070 - 3
a.
2.
3.
4.
For Exterior and Humid Areas: Furnish hot dipped galvanized
housings and neoprene coated springs.
b.
Code: Color code springs for load carrying capacity.
Springs: Minimum horizontal stiffness equal to 75 percent vertical
stiffness, with working deflection between 0.3 and 0.6 of maximum
deflection.
Housings: Incorporate neoprene isolation pad meeting requirements for
neoprene pad isolators.
Misalignment: Capable of 20 degree hanger rod misalignment.
G.
Neoprene Pad Isolators:
1.
Rubber or neoprene-waffle pads.
a.
30 durometer.
b.
Minimum 1/2-inch thick.
c.
Maximum loading 40 psi.
d.
Height of ribs: not to exceed 0.7 times width.
2.
Configuration: 1/2-inch thick waffle pads bonded each side of 1/4-inch
thick steel plate.
H.
Rubber Mount or Hanger: Molded rubber designed for 0.5 inches deflection with
threaded insert.
I.
Glass Fiber Pads: Neoprene jacketed pre-compressed molded glass fiber.
J.
Seismic Snubbers:
1.
Type: Non-directional and double acting unit consisting of interlocking
steel members restrained by neoprene elements.
2.
Neoprene Elements: Replaceable, minimum 0.75-inch thick.
3.
Capacity: 4 times load assigned to mount groupings at 0.40-inch
deflection.
4.
Attachment Points and Fasteners: Capable of withstanding 3 times rated
load capacity of seismic snubber.
K.
Seismic Wire Bracing:
1.
Type: FS RR-W-410; Galvanized steel wire, 7x19 strand core.
2.
Fasteners: U-bolt clips, minimum two (2) per cable connection.
PART 3 EXECUTION
3.1
EXAMINATION
A.
3.2
Verify equipment, ductwork and piping is installed before work in this section is
started.
EXISTING WORK
A.
Provide access to existing piping and ductwork and other installations remaining
active and requiring access.
NCS Bloomfield Avenue Station
New Elevators
15070 - 4
B.
3.3
3.4
Extend existing piping and ductwork installations using materials and methods
compatible with existing mechanical installations.
INSTALLATION
A.
Attach ductwork to acoustic louvers with flexible duct connections. Refer to
Section 15820.
B.
Install isolation for motor driven equipment.
C.
Adjust equipment level.
D.
Install spring hangers without binding.
E.
On closed spring isolators, adjust so side stabilizers are clear under normal
operating conditions.
F.
Prior to making piping connections to equipment with operating weights
substantially different from installed weights, block up equipment with temporary
shims to final height. When full load is applied, adjust isolators to load to allow
shim removal.
G.
Provide pairs of horizontal limit springs on hanger supported, horizontally
mounted equipment.
H.
Provide resiliently mounted equipment, piping, and ductwork with seismic
snubbers. Provide each inertia base with minimum of four seismic snubbers
located close to isolators. Snub equipment designated for post disaster use to
0.05 inch maximum clearance. Provide other snubbers with clearance between
0.15 inch and 0.25 inch.
I.
Support piping connections to isolated equipment resiliently to nearest flexible
pipe connector or as follows:
1.
Up to 4 inch Diameter: First three points of support.
2.
5 to 8 inch Diameter: First four points of support.
3.
10 inch Diameter and Over: First six points of support.
4.
Select three hangers closest to vibration source for minimum 1.0 inch
static deflection or static deflection of isolated equipment. Select
remaining isolators for minimum 1.0 inch static deflection or 1/2 static
deflection of isolated equipment.
FIELD QUALITY CONTROL
A.
Inspect isolated equipment after installation and submit report. Include static
deflections.
NCS Bloomfield Avenue Station
New Elevators
15070 - 5
PART 4 COMPENSATION
4.1
MEASUREMENT AND PAYMENT
A.
Measurement: The work of this section shall not be measured.
B.
Payment: The cost of this section shall be included in the lump sum bid items
PLUMBING or HVAC SYSTEMS, as applicable to the system served.
END OF SECTION
NCS Bloomfield Avenue Station
New Elevators
15070 - 6
SECTION 15075
MECHANICAL IDENTIFICATION
PART 1 GENERAL
1.1
SUMMARY
A.
1.2
REFERENCES
A.
1.3
1.4
1.5
Section Includes:
1.
Nameplates.
2.
Tags.
3.
Stencils.
4.
Pipe markers.
5.
Ceiling tacks.
6.
Lockout devices.
American Society of Mechanical Engineers:
1.
ASME A13.1 - Scheme for the Identification of Piping Systems.
SUBMITTALS
A.
Submit in accordance with General Provisions for Construction.
B.
Product Data: Submit manufacturers catalog literature for each product required.
C.
Shop Drawings: Submit list of wording, symbols, letter size, and color coding for
mechanical identification and valve chart and schedule, including valve tag
number, location, function, and valve manufacturer's name and model number.
D.
Manufacturer's Installation Instructions: Indicate installation instructions, special
procedures, and installation.
E.
Manufacturer's Certificate: Certify products meet or exceed specified
requirements.
CLOSEOUT SUBMITTALS
A.
Submit in accordance with General Provisions for Construction.
B.
Project Record Documents: Record actual locations of tagged valves; include
valve tag numbers.
QUALITY ASSURANCE
A.
Conform to ASME A13.1 for color scheme for identification of piping systems and
accessories.
NCS Bloomfield Avenue Station
New Elevators
15075 - 1
1.6
1.7
QUALIFICATIONS
A.
Manufacturer: Company specializing in manufacturing products specified in this
section with minimum three years documented experience.
B.
Installer: Company specializing in performing Work of this section with minimum
three years documented experience.
FIELD MEASUREMENTS
A.
Verify field measurements prior to fabrication.
PART 2 PRODUCTS
2.1
2.2
NAMEPLATES
A.
Manufacturers:
1.
Seton Identification Products Co.
2.
Brady Corp.
3.
EMED Co., Inc.
4.
Carlton Industries, Inc.
5.
Marking Systems, Inc.
6.
Substitutions: Submit requests for substitution in accordance with the
General Provisions for Construction.
B.
Product Description: Laminated three-layer plastic with engraved black letters on
white contrasting background color; minimum 1/8-inch thick.
C.
Letter Size:
1.
1/8-inch high letters for identifying individual equipment and loads.
2.
1/4-inch high letters for identifying grouped equipment and loads.
TAGS
A.
Manufacturers:
1.
Seton Identification Products Co.
2.
Brady Corp.
3.
EMED Co., Inc.
4.
Carlton Industries, Inc.
5.
Marking Systems, Inc.
6.
Substitutions: Submit requests for substitution in accordance with the
General Provisions for Construction.
B.
Plastic Tags: Laminated three-layer plastic with engraved black letters on light
contrasting background color. Tag size minimum 1-1/2 inches diameter.
C.
Metal Tags: Brass with stamped letters; tag size minimum 1-1/2 inches diameter
square with finished edges.
NCS Bloomfield Avenue Station
New Elevators
15075 - 2
2.3
2.4
D.
Information Tags: Clear plastic with printed "Danger," "Caution," or "Warning"
and message; size 3-1/4 x 5-5/8 inches with grommet and self-locking nylon ties.
E.
Tag Chart: Typewritten letter size list of applied tags and location in anodized
aluminum frame plastic laminated.
STENCILS
A.
Manufacturers:
1.
Seton Identification Products Co.
2.
Brady Corp.
3.
EMED Co., Inc.
4.
Carlton Industries, Inc.
5.
Marking Systems, Inc.
6.
Substitutions: Submit requests for substitution in accordance with the
General Provisions for Construction.
B.
Stencils: With clean cut symbols and letters of following size:
1.
Up to 2 inches Outside Diameter of Insulation or Pipe: 1/2 inch high
letters.
2.
2-1/2 to 6 inches Outside Diameter of Insulation or Pipe: 1-inch high
letters.
3.
Over 6 inches Outside Diameter of Insulation or Pipe: 1-3/4 inches inches
high letters.
4.
Ductwork and Equipment: 1-3/4 inches inches high letters.
C.
Stencil Paint: As specified in Section 09900, semi-gloss enamel, colors and
lettering size conforming to ASME A13.1.
PIPE MARKERS
A.
Manufacturers:
1.
Seton Identification Products Co.
2.
Brady Corp.
3.
EMED Co., Inc.
4.
Carlton Industries, Inc.
5.
Marking Systems, Inc.
6.
Substitutions: Submit requests for substitution in accordance with the
General Provisions for Construction.
B.
Color and Lettering: Conform to ASME A13.1.
C.
Plastic Pipe Markers: Factory fabricated, flexible, semi-rigid plastic, preformed to
fit around pipe or pipe covering. Larger sizes may have maximum sheet size with
spring fastener.
D.
Plastic Tape Pipe Markers: Flexible, vinyl film tape with pressure sensitive
adhesive backing and printed markings.
NCS Bloomfield Avenue Station
New Elevators
15075 - 3
E.
2.5
2.6
Plastic Underground Pipe Markers: Bright colored continuously printed plastic
ribbon tape, minimum 6 inches wide x 4 mils thick, manufactured for direct burial
service. Provide 2-inch wide metallic detection tape for plastic and cement
piping.
CEILING TACKS
A.
Manufacturers:
1.
Seton Identification Products Co.
2.
Brady Corp.
3.
EMED Co., Inc.
4.
Carlton Industries, Inc.
5.
Marking Systems, Inc.
6.
Substitutions: Submit requests for substitution in accordance with the
General Provisions for Construction.
B.
Description: Steel with 3/4 inch diameter color-coded head.
C.
Color code as follows:
1.
HVAC equipment: Yellow.
2.
Fire dampers/smoke dampers: Red.
3.
Plumbing valves: Green.
4.
Heating/cooling valves: Blue.
5.
Compressed air valves: White.
LOCKOUT DEVICES
A.
Manufacturers:
1.
Seton Identification Products Co.
2.
Brady Corp.
3.
EMED Co., Inc.
4.
Carlton Industries, Inc.
5.
Marking Systems, Inc.
6.
Substitutions: Submit requests for substitution in accordance with the
General Provisions for Construction.
B.
Lockout Hasps: Anodized aluminum Reinforced nylon hasp with erasable label
surface; size minimum 7-1/4 x 3 inches.
C.
Valve Lockout Devices: Nylon Steel Plastic device preventing access to valve
operator, accepting lock shackle.
PART 3 EXECUTION
3.1
PREPARATION
A.
Degrease and clean surfaces to receive adhesive for identification materials.
NCS Bloomfield Avenue Station
New Elevators
15075 - 4
B.
3.2
Prepare surfaces in accordance with Section 09900 for stencil painting.
INSTALLATION
A.
Apply stencil painting in accordance with Section 09900.
B.
Install identifying devices after completion of coverings and painting.
C.
Install plastic nameplates with corrosive-resistant mechanical fasteners, or
adhesive.
D.
Install tags using corrosion resistant chain. Number tags consecutively by
location.
E.
Install underground plastic pipe markers 6 to 8 inches below finished grade,
directly above buried pipe.
F.
Identify air handling units, pumps, heat transfer equipment, tanks, and water
treatment devices with plastic nameplates stencil painting. Identify in-line pumps
and other small devices with tags.
G.
Identify control panels and major control components outside panels with plastic
nameplates.
H.
Identify valves in main and branch piping with tags.
I.
Identify air terminal units and radiator valves with numbered tags.
J.
Tag automatic controls, instruments, and relays. Key to control schematic.
K.
Identify piping, concealed or exposed, with plastic pipe markers plastic tape pipe
markers stenciled painting. Use tags on piping 3/4 inch diameter and smaller.
Identify service, flow direction, and pressure. Install in clear view and align with
axis of piping. Locate identification not to exceed 20 feet on straight runs
including risers and drops, adjacent to each valve and tee, at each side of
penetration of structure or enclosure, and at each obstruction.
L.
Identify ductwork with plastic nameplates stenciled painting. Identify with air
handling unit identification number and area served. Locate identification at air
handling unit, at each side of penetration of structure or enclosure, and at each
obstruction.
M.
Provide ceiling tacks to locate valves or dampers above T-bar type panel
ceilings. Locate in corner of panel closest to equipment.
NCS Bloomfield Avenue Station
New Elevators
15075 - 5
PART 4 COMPENSATION
4.1
MEASUREMENT AND PAYMENT
A.
Measurement: The work of this section shall not be measured.
B.
Payment: The cost of this section shall be included in the lump sum bid items
PLUMBING or HVAC SYSTEMS, as applicable to the system served.
END OF SECTION
NCS Bloomfield Avenue Station
New Elevators
15075 - 6
SECTION 15080
MECHANICAL INSULATION
PART 1 GENERAL
1.1
1.2
SUMMARY
A.
Section Includes:
1.
Ductwork insulation.
2.
Duct liner.
3.
Insulation jackets.
4.
Equipment insulation
5.
Breeching insulation.
6.
Piping system insulation.
7.
Insulation accessories including vapor retarders, jackets, and
accessories.
B.
Related Sections:
1.
Section 15060 - Hangers and Supports: Product and Execution
requirements for inserts at hanger locations.
2.
Section 15075 - Mechanical Identification: Product requirements for
mechanical identification.
3.
Section 15770 – Heat Trace Equipment: Electric heat tracing.
REFERENCES
A.
ASTM International:
1.
ASTM A167 - Standard Specification for Stainless and Heat-Resisting
Chromium-Nickel Steel Plate, Sheet, and Strip.
2.
ASTM B209 - Standard Specification for Aluminum and Aluminum-Alloy
Sheet and Plate.
3.
ASTM C177 - Standard Test Method for Steady-State Heat Flux
Measurements and Thermal Transmission Properties by Means of the
Guarded-Hot-Plate Apparatus.
4.
ASTM C195 - Standard Specification for Mineral Fiber Thermal Insulating
Cement.
5.
ASTM C449/C449M - Standard Specification for Mineral Fiber HydraulicSetting Thermal Insulating and Finishing Cement.
6.
ASTM C518 - Standard Test Method for Steady-State Heat Flux
Measurements and Thermal Transmission Properties by Means of the
Heat Flow Meter Apparatus.
7.
ASTM C533 - Standard Specification for Calcium Silicate Block and Pipe
Thermal Insulation.
8.
ASTM C534 - Standard Specification for Preformed Flexible Elastomeric
Cellular Thermal Insulation in Sheet and Tubular Form.
9.
ASTM C547 - Standard Specification for Mineral Fiber Pipe Insulation.
NCS Bloomfield Avenue Station
New Elevators
15080 - 1
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
25.
26.
B.
1.3
ASTM C552 - Standard Specification for Cellular Glass Thermal
Insulation.
ASTM C553 - Standard Specification for Mineral Fiber Blanket Thermal
Insulation for Commercial and Industrial Applications.
ASTM C591 - Standard Specification for Unfaced Preformed Rigid
Cellular Polyisocyanurate Thermal Insulation.
ASTM C592 - Standard Specification for Mineral Fiber Blanket Insulation
and Blanket-Type Pipe Insulation (Metal-Mesh Covered) (Industrial Type).
ASTM C610 - Standard Specification for Molded Expanded Perlite Block
and Pipe Thermal Insulation.
ASTM C612 - Standard Specification for Mineral Fiber Block and Board
Thermal Insulation.
ASTM C795 - Standard Specification for Thermal Insulation for Use in
Contact with Austenitic Stainless Steel.
ASTM C921 - Standard Practice for Determining the Properties of
Jacketing Materials for Thermal Insulation.
ASTM C1071 - Standard Specification for Thermal and Acoustical
Insulation (Glass Fiber, Duct Lining Material).
ASTM C1126 - Standard Specification for Faced or Unfaced Rigid
Cellular Phenolic Thermal Insulation.
ASTM C1136 - Standard Specification for Flexible, Low Permeance
Vapor Retarders for Thermal Insulation.
ASTM C1290 - Standard Specification for Flexible Fibrous Glass Blanket
Insulation Used to Externally Insulate HVAC Ducts.
ASTM D1784 - Standard Specification for Rigid Poly (Vinyl Chloride)
(PVC) Compounds and Chlorinated Poly (Vinyl Chloride) (CPVC)
Compounds.
ASTM E84 - Standard Test Method for Surface Burning Characteristics of
Building Materials.
ASTM E96 - Standard Test Methods for Water Vapor Transmission of
Materials.
ASTM E162 - Standard Test Method for Surface Flammability of Materials
Using a Radiant Heat Energy Source.
ASTM G21 - Standard Practice for Determining Resistance of Synthetic
Polymeric Materials to Fungi.
Sheet Metal and Air Conditioning Contractors’:
1.
SMACNA - HVAC Duct Construction Standard - Metal and Flexible.
SUBMITTALS
A.
Submit in accordance with General Provisions for Construction.
B.
Product Data: Submit product description, thermal characteristics and list of
materials and thickness for each service, and location.
C.
Manufacturer's Installation Instructions: Submit manufacturers published
literature indicating proper installation procedures.
NCS Bloomfield Avenue Station
New Elevators
15080 - 2
D.
1.4
1.5
1.6
1.7
Manufacturer's Certificate: Certify products meet or exceed specified
requirements.
QUALIFICATIONS
A.
Manufacturer: Company specializing in manufacturing products specified in this
section with minimum three years documented experience.
B.
Applicator: Company specializing in performing Work of this section with
minimum three years documented experience.
DELIVERY, STORAGE, AND HANDLING
A.
Deliver, store, protect, and handle Products to site under requirements of
General Provisions for Construction.
B.
Accept materials on site in original factory packaging, labeled with manufacturer's
identification, including product density and thickness.
C.
Protect insulation from weather and construction traffic, dirt, water, chemical, and
mechanical damage, by storing in original wrapping.
ENVIRONMENTAL REQUIREMENTS
A.
Install insulation only when ambient temperature and humidity conditions are
within range recommended by manufacturer.
B.
Maintain temperature during and after installation for minimum period of 24
hours.
FIELD MEASUREMENTS
A.
Verify field measurements prior to fabrication.
PART 2 PRODUCTS
2.1
GLASS FIBER, RIGID
A.
Manufacturers:
1.
Owens-Corning Fiberglas Corp., Type SSL-II.
2.
Knauf Fiber Glass, “1000°.”
3.
Johns-Manville Corp., “Micro-Lok.”
4.
Substitutions: Submit requests for substitution in accordance with the
General Provisions for Construction.
B.
Insulation: ASTM C547; rigid, noncombustible.
1.
‘K’ factor: ASTM C177 or ASTM C518, 0.23 at 75 degrees F.
2.
Maximum Service Temperature: 850 degrees F.
NCS Bloomfield Avenue Station
New Elevators
15080 - 3
3.
4.
2.2
2.3
Maximum Water Vapor Transmission: ASTM E96, 0.02 perm.
Maximum Moisture Absorption: <0.2 percent by volume.
C.
Vapor Retarder Jacket: ASTM C1136 flexible, Type II.
D.
Facing: 1-inch galvanized steel hexagonal wire mesh stitched on one face of
insulation.
E.
Vapor Retarder Lap Adhesive:
1.
Manufacturers:
a.
Foster Products Div., Specialty Construction Brands, Inc., “Drion”
Model 85-75.
b.
Substitutions: Submit requests for substitution in accordance with
the General Provisions for Construction.
2.
Fast-setting, water-resistant contact cement, compatible with insulation.
F.
Insulating Cement/Mastic:
1.
Manufacturers:
a.
Foster Products Div., Specialty Construction Brands, Inc., “Sealfas
G-P-M” Model 35-00.
b.
Substitutions: Submit requests for substitution in accordance with
the General Provisions for Construction.
2.
ASTM C195; hydraulic setting on mineral wool.
CELLULAR GLASS
A.
Manufacturers:
1.
Pittsburgh Corning, Inc., “FoamGlas.”
2.
Cell-U-Foam Corp.
3.
Substitutions: Submit requests for substitution in accordance with the
General Provisions for Construction.
B.
Insulation: ASTM C552, Type II - pipe and tubing insulation, Class 2 - Jacketed.
1.
‘K’ Factor: ASTM C177 or ASTM C518, 0.29 at 75 degrees F.
2.
Maximum Service Temperature: 900 degrees F.
3.
Maximum Water Vapor Transmission: ASTM E96, 0.00 perm.
4.
Maximum Moisture Absorption: ASTM C240, 0.2 percent by volume.
5.
Density: 7.5 lb/cu ft.
EXPANDED PERLITE
A.
Manufacturers:
1.
Industrial Insulation Group LLC, “Sproule WR-1200.”
2.
Substitutions: Submit requests for substitution in accordance with the
General Provisions for Construction.
B.
Molded expanded perlite block and pipe insulation: ASTM C610, pipe insulation
for use on surfaces up to 1200 degree F.
1.
‘K’ Factor: ASTM C177 or ASTM C518, 0.53 at 400 degrees F.
NCS Bloomfield Avenue Station
New Elevators
15080 - 4
2.
3.
2.4
2.5
2.6
Maximum Service Temperature: 1,200 degrees F.
Density: 12.0 lb/cu ft.
HYDROUS CALCIUM SILICATE
A.
Manufacturers:
1.
Industrial Insulation Group LLC, “Thermo 12 Gold.”
2.
Substitutions: Submit requests for substitution in accordance with the
General Provisions for Construction.
B.
Calcium Silicate Block and Pipe Thermal Insulation: ASTM C533, Type I.
1.
‘K’ Factor: ASTM C177 or ASTM C518, 0.50 at 400 degrees F.
2.
Maximum Service Temperature: 1,200 degrees F.
3.
Density: 14.5 lb/cu ft.
C.
Tie Wire: 0.048-inch stainless steel with twisted ends on maximum 12-inch
centers.
D.
Mineral Fiber Hydraulic-Setting Thermal Insulating and Finishing Cement:
1.
Manufacturers:
a.
Industrial Insulation Group LLC, “CalCoat 127.”
b.
Insulco Div., MFS, Inc., “Smoothkote.”
c.
Ramco Insulation, Inc., “Ramcote 1200.”
d.
Substitutions: Submit requests for substitution in accordance with
the General Provisions for Construction.
2.
ASTM C449/C449M.
EXPANDED POLYSTYRENE
A.
Manufacturers:
1.
Dow Chemical Co., “Styrofoam.”
2.
Dyplast Products, LLC, “EPS.”
3.
Substitutions: Submit requests for substitution in accordance with the
General Provisions for Construction.
B.
Unfaced Preformed Rigid Cellular Polystyrene Thermal Insulation: ASTM C591,
Type III, compressive strength 50 psi.
1.
‘K’ Factor: ASTM C177 or ASTM C518, 0.259 at 75 degrees F.
2.
Maximum Service Temperature: 165 degrees F.
3.
Maximum Water Vapor Transmission: ASTM E96, 1.50 perm.
4.
Maximum Moisture Absorption: ASTM D2842, 1.0 percent by volume.
5.
Density: 1.60 lb/cu ft.
POLYETHYLENE
A.
Manufacturers:
1.
Nomaco K-Flex, “therma-cel SSL.”
2.
Nomaco K-Flex, “NomaLock.”
NCS Bloomfield Avenue Station
New Elevators
15080 - 5
3.
B.
2.7
2.8
2.9
Substitutions: Submit requests for substitution in accordance with the
General Provisions for Construction.
Preformed flexible closed cell polyethylene insulation: ASTM C1427; Tubular
form.
1.
‘K’ Factor: ASTM C177 or ASTM C518, 0.25 at 75 degrees F.
2.
Maximum Service Temperature: 200 degrees F.
3.
Maximum Water Vapor Transmission: ASTM E96, 0.05 perm.
4.
Maximum Moisture Absorption: ASTM C209, 0.0 percent by volume.
5.
Density: 1.5 lb/cu ft.
CELLULAR POLYISOCYANURATE
A.
Manufacturers:
1.
Dow Chemical Co., “Trymer 2000XP.”
2.
Dyplast Products, LLC, “ISO-C1.”
3.
Substitutions: Submit requests for substitution in accordance with the
General Provisions for Construction.
B.
ASTM C591, Unfaced preformed rigid cellular polyisocyanurate thermal
insulation, Type III.
1.
‘K’ Factor: ASTM C177 or ASTM C518, 0.19 at 75 degrees F.
2.
Maximum Service Temperature: 300 degrees F.
3.
Maximum Water Vapor Transmission: ASTM E96, 4.0 perm.
4.
Maximum Moisture Absorption: ASTM D2842, 1.16 percent by volume.
5.
Density: 2.0 lb/cu ft.
6.
Compressive Strength: 50 psi.
CELLULAR PHENOLIC FOAM
A.
Manufacturers:
1.
Kingspan Corp., “Kooltherm.”
2.
Substitutions: Submit requests for substitution in accordance with the
General Provisions for Construction.
B.
Faced or unfaced rigid cellular phenolic pipe and board thermal insulation, ASTM
C1126, Type II and Type III.
1.
‘K’ Factor: ASTM C177 or ASTM C518, 0.125 at 50 degrees F.
2.
Maximum Service Temperature: 250 degrees F.
3.
Maximum Water Vapor Transmission: ASTM E96, 0.05 perm.
4.
Maximum Moisture Absorption: ASTM C209, 0.0 percent by volume.
5.
Density: 2.2 lb/cu ft.
ELASTOMERIC CELLULAR FOAM
A.
Manufacturers:
1.
Armacell LLC, “AP Armaflex.”
2.
Nomaco K-Flex, “Insul-Tube.”
3.
Aeroflex USA, Inc., “Aerocel EPDM.”
NCS Bloomfield Avenue Station
New Elevators
15080 - 6
4.
B.
2.10
2.11
Substitutions: Submit requests for substitution in accordance with the
General Provisions for Construction.
Preformed flexible elastomeric cellular thermal insulation in sheet and tubular
form: ASTM C534; Type I, Tubular form.
1.
‘K’ Factor: ASTM C177 or ASTM C518, 0.27 at 75 degrees F.
2.
Maximum Service Temperature: 220 degrees F.
3.
Maximum Water Vapor Transmission: ASTM E96, 0.10 perm.
4.
Maximum Moisture Absorption: ASTM C209, 0.2 percent by volume.
5.
Density: 3.0 to 6.0 lb/cu ft.
POLYETHYLENE/ELASTOMERIC CELLULAR FOAM INSULATION ADHESIVE
A.
Manufacturers:
1.
Armacell LLC, “Armaflex” Type 520.
2.
Nomaco K-Flex, Type R-320.
3.
Aeroflex USA, Inc., “Aeroseal.”
4.
Substitutions: Submit requests for substitution in accordance with the
General Provisions for Construction.
B.
Air-dried, contact adhesive, compatible with insulation.
PIPE INSULATION AND EQUIPMENT JACKETS
A.
PVC Jacket:
1.
Manufacturers:
a.
Johns-Manville Corp., “Zeston 300.”
b.
Proto PVC Corp., “LoSmoke.”
c.
Speedline Corp., “Smoke Safe.”
d.
Substitutions: Submit requests for substitution in accordance with
the General Provisions for Construction.
2.
Product Description: ASTM D1784, One piece molded type fitting covers
and sheet material, off-white color.
3.
Thickness: 15 mil.
4.
Connections: Brush on welding adhesive or pressure sensitive color
matching vinyl tape.
B.
Aluminum Pipe Jacket:
1.
Manufacturers:
a.
Pabco/Childers Metals, ITW Insulation Systems.
b.
Substitutions: Submit requests for substitution in accordance with
the General Provisions for Construction.
2.
ASTM B209, half-hard temper aluminum with integral bonded moisture
retarder.
3.
Thickness: 0.020-inch thick sheet.
4.
Finish: Embossed.
5.
Joining: Longitudinal slip joints and 2-inch laps.
6.
Fittings: 0.024-inch thick die shaped fitting covers with factory attached
protective liner.
NCS Bloomfield Avenue Station
New Elevators
15080 - 7
7.
2.12
Metal Jacket Bands: ½- inch wide; 0.020-inch thick aluminum.
C.
Stainless Steel Pipe Jacket:
1.
Manufacturers:
a.
Pabco/Childers Metals, ITW Insulation Systems.
b.
Substitutions: Submit requests for substitution in accordance with
the General Provisions for Construction.
2.
ASTM A240, Type 304 stainless steel with integral bonded moisture
retarder.
3.
Thickness: 0.016-inch thick.
4.
Finish: Corrugated.
5.
Fittings: 0.016-inch thick die shaped fitting covers with factory attached
protective liner.
6.
Metal Jacket Bands: ½- inch wide; 0.015-inch thick stainless steel.
D.
Canvas Equipment Jacket:
1.
UL listed.
2.
Fabric: 6 oz/sq yd, plain weave cotton.
3.
Fire retardant lagging adhesive. Composite of insulation, jacket and
lagging adhesive having flame spread index not greater than 25 and
smoke developed index not greater than 50 when tested to ASTM E84.
E.
Covering Adhesive Mastic:
1.
Manufacturers:
a.
Foster Products Div., Specialty Construction Brands, Inc., Model
30-07.
b.
Substitutions: Submit requests for substitution in accordance with
the General Provisions for Construction.
2.
Compatible with insulation.
F.
Lagging Adhesive:
1.
Manufacturers:
a.
Foster Products Div., Specialty Construction Brands, Inc.,
“Insulfas” Model 30-30.
b.
Substitutions: Submit requests for substitution in accordance with
the General Provisions for Construction.
2.
Quick-setting, water based fiberglass reinforced lagging adhesive,
compatible with insulation.
GLASS FIBER DUCT INSULATION, FLEXIBLE
A.
Manufacturers:
1.
Owens-Corning Fiberglas Corp., “SOFTR.”
2.
Knauf Fiber Glass, “Friendly Feel.”
3.
Johns-Manville Corp., “Micro-Lite.”
4.
Substitutions: Submit requests for substitution in accordance with the
General Provisions for Construction.
NCS Bloomfield Avenue Station
New Elevators
15080 - 8
B.
2.13
2.14
Insulation: ASTM C553, flexible glass fiber duct wrap insulation, Type 150, with
FSK jacket.
1.
‘K’ Factor: ASTM C177 or ASTM C518, 0.25 at 75 degrees F.
2.
Maximum Service Temperature: 250 degrees F.
3.
Maximum Water Vapor Transmission: ASTM E96, 0.02 perm.
4.
Maximum Moisture Absorption: ASTM C1104, <5.0 percent by volume.
5.
Density: 1.5 lb/cu ft.
GLASS FIBER DUCT INSULATION, RIGID
A.
Manufacturers:
1.
Owens-Corning Fiberglas Corp., “700 Series.”
2.
Knauf Fiber Glass, “Insulation Board.”
3.
Johns-Manville Corp., “Spin-Glas Board.”
4.
Substitutions: Submit requests for substitution in accordance with the
General Provisions for Construction.
B.
Insulation: ASTM C553, rigid glass fiber duct board insulation, with FSK jacket.
1.
‘K’ Factor: ASTM C177 or ASTM C518, 0.24 at 75 degrees F.
2.
Maximum Service Temperature: 150 degrees F.
3.
Maximum Water Vapor Transmission: ASTM E96, 0.02 perm.
4.
Maximum Moisture Absorption: ASTM C1104, <5.0 percent by volume.
5.
Density: 3.0 lb/cu ft.
GLASS FIBER DUCT LINER
A.
Manufacturers:
1.
Owens-Corning Fiberglas Corp., “Fiberglas Duct Liner Board” or “QuietR.”
2.
Knauf Fiber Glass, “Duct Liner E-M.”
3.
Johns-Manville Corp., “Linacoustic RC” or “LinaTex.”
4.
Substitutions: Submit requests for substitution in accordance with the
General Provisions for Construction.
B.
Insulation: ASTM C1071 glass fiber duct lining material.
1.
‘K’ Factor: ASTM C177 or ASTM C518, 0.24 at 75 degrees F.
2.
Maximum Service Temperature: 250 degrees F.
3.
Maximum Air Velocity: 6,000 fpm.
4.
Maximum Moisture Absorption: ASTM C1104, 3.0 percent by volume.
5.
Density: 3.0 lb/cu ft.
6.
Sound Absorption:
1-½”
2”_
a.
125 Hz:
0.16
0.24
b.
250 Hz:
0.39
0.79
c.
500 Hz:
0.91
1.13
d.
1,000 Hz:
1.01
1.13
e.
2,000 Hz:
1.01
1.04
f.
4,000 Hz
1.01
1.05
g.
NRC:
0.85
1.00
C.
Adhesive:
NCS Bloomfield Avenue Station
New Elevators
15080 - 9
1.
2.
D.
2.15
Manufacturers:
a.
RCD Corp., “No. 5 Ductliner.”
b.
Foster Products Div., Specialty Construction Brands, Inc., Model
82-00.
c.
McGill AirSeal LLC, “Uni-Grab”
d.
Substitutions: Submit requests for substitution in accordance with
the General Provisions for Construction.
Waterproof, ASTM E162 fire-retardant type.
Liner Fasteners:
1.
Manufacturers:
a.
Carlisle-Hardcast, Inc., “Grip-Ons” or Weld-Ons.”
b.
Gripnail Corp., “Gripnail” or “Power-Point.”
c.
Cain Mfg. Co., Inc., “Pincher” or “Pointer.”
d.
Substitutions: Submit requests for substitution in accordance with
the General Provisions for Construction.
2.
Galvanized steel, impact applied or welded, with integral round head.
GLASS FIBER ROUND DUCT LINER
A.
Manufacturers:
1.
Owens-Corning Fiberglas Corp., “Quiet Zone Spiral Duct Liner.”
2.
Knauf Fiber Glass, “.”
3.
Johns-Manville Corp., “Spiracoustic Plus.”
4.
Substitutions: Submit requests for substitution in accordance with the
General Provisions for Construction.
B.
Insulation: ASTM C1071 glass fiber duct lining material, Type II. Round,
preformed in cylindrical sections with ASTM G21 impregnated surface coat.
1.
‘K’ Factor: ASTM C177 or ASTM C518, 0.23 at 75 degrees F.
2.
Maximum Service Temperature: 250 degrees F.
3.
Maximum Air Velocity: 6,000 fpm.
4.
Maximum Moisture Absorption: ASTM C1104, 3.0 percent by volume.
5.
Density: 3.0 lb/cu ft.
6.
Sound Absorption:
1”_
1-½”
a.
125 Hz:
0.08
0.12
b.
250 Hz:
0.19
0.33
c.
500 Hz:
0.69
0.92
d.
1,000 Hz:
0.94
1.04
e.
2,000 Hz:
0.99
1.03
f.
4,000 Hz
0.98
1.02
g.
NRC:
0.70
0.85
NCS Bloomfield Avenue Station
New Elevators
15080 - 10
PART 3 EXECUTION
3.1
3.2
EXAMINATION
A.
Verify piping, equipment and ductwork has been tested before applying insulation
materials.
B.
Verify surfaces are clean and dry, with foreign material removed.
PIPE INSULATION INSTALLATION
A.
Exposed Piping: Locate insulation and cover seams in least visible locations.
B.
Insulated pipes conveying fluids below ambient temperature: Insulate entire
system including fittings, valves, unions, flanges, strainers, flexible connections,
pump bodies, and expansion joints.
C.
Glass fiber insulated pipes conveying fluids below ambient temperature:
1.
Furnish factory-applied or field-applied vapor retarder jackets. Secure
factory-applied jackets with pressure sensitive adhesive self-sealing
longitudinal laps and butt strips. Secure field-applied jackets with outward
clinch expanding staples and seal staple penetrations with vapor retarder
mastic.
2.
Insulate fittings, joints, and valves with molded insulation of like material
and thickness as adjacent pipe. Finish with glass cloth and vapor retarder
adhesive or PVC fitting covers.
D.
For hot piping conveying fluids over 140 degrees F, insulate flanges and unions
at equipment.
E.
Man made mineral fiber insulated pipes conveying fluids above ambient
temperature:
1.
Furnish factory-applied or field-applied standard jackets. Secure with
outward clinch expanding staples or pressure sensitive adhesive system
on standard factory-applied jacket and butt strips or both.
2.
Insulate fittings, joints, and valves with insulation of like material and
thickness as adjoining pipe. Finish with glass cloth and adhesive or PVC
fitting covers.
F.
Inserts and Shields:
1.
Application: Piping or Equipment 2 inches diameter or larger.
2.
Shields: Galvanized steel between pipe hangers or pipe hanger rolls and
inserts.
3.
Insert location: Between support shield and piping and under finish jacket.
4.
Insert configuration: Minimum 6 inches long, of thickness and contour
matching adjoining insulation; may be factory fabricated.
5.
Insert material: Compression resistant insulating material suitable for
planned temperature range and service.
NCS Bloomfield Avenue Station
New Elevators
15080 - 11
3.3
G.
Continue insulation through penetrations of building assemblies or portions of
assemblies having fire resistance rating of one hour or less. Provide intumescent
firestopping when continuing insulation through assembly. Finish at supports,
protrusions, and interruptions. Refer to Section 07840 for penetrations of
assemblies with fire resistance rating greater than one hour.
H.
Pipe Exposed in Mechanical Equipment Rooms or Finished Spaces
1.
Less than 10 feet above finished floor: Finish with aluminum or stainless
steel jacket.
2.
10 feet or more above finished floor: Finish with canvas jacket sized for
finish painting or PVC jacket and fitting covers.
I.
Exterior Applications: Provide vapor retarder jacket. Insulate fittings, joints, and
valves with insulation of like material and thickness as adjoining pipe, and finish
with glass mesh reinforced vapor retarder cement. Cover with aluminum or
stainless steel jacket with seams located at 3 or 9 o’clock position on side of
horizontal piping with overlap facing down to shed water or on bottom side of
horizontal equipment.
J.
Buried Piping: Insulate only where insulation manufacturer recommends
insulation product may be installed in trench, tunnel or direct buried. Install
factory fabricated assembly with inner all-purpose service jacket with self-sealing
lap, and asphalt impregnated open mesh glass fabric, with 1 mil thick aluminum
foil sandwiched between three layers of bituminous compound; outer surface
faced with polyester film.
K.
Heat Traced Piping: Insulate fittings, joints, and valves with insulation of like
material, thickness, and finish as adjoining pipe. Size insulation large enough to
enclose pipe and heat tracer. Cover with aluminum or stainless steel jacket with
seams located at 3 or 9 o’clock position on side of horizontal piping with overlap
facing down to shed water.
EQUIPMENT INSULATION INSTALLATION
A.
Factory Insulated Equipment: Do not insulate.
B.
Exposed Equipment: Locate insulation and cover seams in least visible locations.
C.
Apply insulation close to equipment by grooving, scoring, and beveling insulation.
Fasten insulation to equipment with studs, pins, clips, adhesive, wires, or bands.
D.
Fill joints, cracks, seams, and depressions with bedding compound to form
smooth surface. On cold equipment, use vapor retarder cement.
E.
Insulated equipment containing fluids below ambient temperature: Insulate entire
system.
NCS Bloomfield Avenue Station
New Elevators
15080 - 12
3.4
F.
Glass fiber insulated equipment containing fluids below ambient temperature:
Provide vapor retarder jackets, factory-applied or field-applied. Finish with glasscloth and vapor barrier adhesive.
G.
For hot equipment containing fluids over 140 degrees F, insulate flanges and
unions with removable sections and jackets.
H.
Glass fiber insulated equipment containing fluids above ambient temperature:
Provide standard jackets, with or without vapor retarder, factory-applied or fieldapplied. Finish with glass cloth and adhesive.
I.
Finish insulation at supports, protrusions, and interruptions.
J.
Equipment in Mechanical Equipment Rooms or Finished Spaces: Finish with
aluminum jacket or stainless steel jacket.
K.
Nameplates and ASME Stamps: Bevel and seal insulation around; do not
insulate over.
L.
Equipment Requiring Access for Maintenance, Repair, or Cleaning: Install
insulation for easy removal and replacement without damage.
DUCTWORK INSULATION INSTALLATION
A.
Insulated ductwork conveying air below ambient temperature:
1.
Provide insulation with vapor retarder jackets.
2.
Finish with tape and vapor retarder jacket.
3.
Continue insulation through walls, sleeves, hangers, and other duct
penetrations.
4.
Insulate entire system including fittings, joints, flanges, fire dampers,
flexible connections, and expansion joints.
B.
Insulated ductwork conveying air above ambient temperature:
1.
Provide with or without standard vapor retarder jacket.
2.
Insulate fittings and joints. Where service access is required, bevel and
seal ends of insulation.
C.
Ductwork Exposed in Mechanical Equipment Rooms or Finished Spaces:
1.
Less than 10 feet above finished floor: Finish with aluminum or stainless
steel jacket.
2.
10 feet or more above finished floor: Finish with canvas jacket sized for
finish painting.
D.
Exterior Applications: Provide insulation with vapor retarder jacket. Cover with
caulked aluminum or stainless jacket with seams located on bottom side of
horizontal duct section.
E.
External Duct Insulation Application:
NCS Bloomfield Avenue Station
New Elevators
15080 - 13
1.
2.
3.
4.
5.
F.
3.5
Secure insulation with vapor retarder with wires and seal jacket joints with
vapor retarder adhesive or tape to match jacket.
Secure insulation without vapor retarder with staples, tape, or wires.
Install without sag on underside of ductwork. Use adhesive or mechanical
fasteners where necessary to prevent sagging. Lift ductwork off trapeze
hangers and insert spacers.
Seal vapor retarder penetrations by mechanical fasteners with vapor
retarder adhesive.
Stop and point insulation around access doors and damper operators to
allow operation without disturbing wrapping.
Duct and Plenum Liner Application:
1.
Adhere insulation with adhesive for minimum 90 percent coverage.
2.
Secure insulation with mechanical liner fasteners. Refer to SMACNA
Standards for spacing.
3.
Seal and smooth joints. Seal and coat transverse joints.
4.
Seal liner surface penetrations with adhesive.
5.
Duct dimensions indicated are net inside dimensions required for airflow.
Increase duct size to allow for insulation thickness.
PIPE INSULATION SCHEDULES
A.
Plumbing Systems:
1.
Domestic Hot/Cold Water Supply:
a.
Man Made Mineral Fiber Insulation:
1)
Pipe Size Range: All sizes.
2)
Thickness: 1 inch.
b.
Cellular Glass Insulation:
1)
Pipe Size Range: All sizes.
2)
Thickness: 1 inch.
c.
Expanded Perlite Insulation:
1)
Pipe Size Range: All sizes.
2)
Thickness: 1 inch.
d.
Cellular Phenolic Foam Insulation:
1)
Pipe Size Range: All sizes.
2)
Thickness: 1 inch.
e.
Cellular Elastomeric Foam Insulation:
1)
Pipe Size Range: All sizes.
2)
Thickness: 1 inch.
2.
Domestic Hot Water Re-circulation:
a.
Man Made Mineral Fiber Insulation:
1)
Pipe Size Range: All sizes.
2)
Thickness: 1 inch.
b.
Expanded Polyethylene Insulation:
1)
Pipe Size Range: All sizes.
2)
Thickness: 1 inch.
c.
Cellular Phenolic Foam Insulation:
1)
Pipe Size Range: All sizes.
2)
Thickness: 1 inch
NCS Bloomfield Avenue Station
New Elevators
15080 - 14
3.6
DUCTWORK INSULATION SCHEDULES
A.
Exhaust Ducts Within 10 feet of Exterior Openings:
1.
Flexible Glass Fiber Ductwork Insulation: Minimum 1-inch thick.
2.
Rigid Glass Fiber Ductwork Insulation: Minimum 1-inch thick.
B.
Outside Air Intake Ducts:
1.
Flexible Glass Fiber Ductwork Insulation: Minimum 1-inch thick.
2.
Rigid Glass Fiber Ductwork Insulation: Minimum 1-inch thick.
C.
Supply Ducts:
1.
Flexible Glass Fiber Ductwork Insulation: Minimum 1-inch thick.
2.
Rigid Glass Fiber Ductwork Insulation: Minimum 1-inch thick.
3.
Flexible Glass Fiber Duct Liner Insulation: Minimum 1-inch thick.
4.
Rigid Glass Fiber Duct Liner Insulation: Minimum 1-inch thick.
D.
Return and Relief Ducts in Mechanical Rooms:
1.
Flexible Glass Fiber Ductwork Insulation: Minimum 1-inch thick.
2.
Rigid Glass Fiber Ductwork Insulation: Minimum 1-inch thick.
E.
Ducts Exposed to Outdoors:
1.
Flexible Glass Fiber Ductwork Insulation: Minimum 2-inches thick.
2.
Rigid Glass Fiber Ductwork Insulation: Minimum 2-inches thick.
PART 4 COMPENSATION
4.1
MEASUREMENT AND PAYMENT
A.
Measurement: The work of this section shall not be measured.
B.
Payment: The cost of this section shall be included in the lump sum bid items
PLUMBING or HVAC SYSTEMS, as applicable to the system served.
END OF SECTION
NCS Bloomfield Avenue Station
New Elevators
15080 - 15
SECTION 15125
PIPING EXPANSION COMPENSATION
PART 1 GENERAL
1.1
1.2
SUMMARY
A.
Section Includes:
1.
Flexible pipe connectors.
2.
Expansion joints.
3.
Expansion compensators.
B.
Related Sections:
1.
Section 15060 - Hangers and Supports: Product and installation
requirements for piping hangers and supports.
2.
Section 15070 - Mechanical Sound, Vibration, Seismic Control: Product
and installation requirements for vibration isolators used in piping
systems.
REFERENCES
A.
1.3
1.4
American Welding Society:
1.
AWS D1.1 - Structural Welding Code - Steel.
DESIGN REQUIREMENTS
A.
Provide structural work and equipment required for expansion and contraction of
piping. Verify anchors, guides, and expansion joints provide and adequately
protect system.
B.
Expansion Compensation Design Criteria:
1.
Installation Temperature: 50 degrees F.
2.
Domestic Hot Water: 140 degrees F.
3.
Safety Factor: 30 percent.
SUBMITTALS
A.
Submit in accordance with General Provisions for Construction.
B.
Shop Drawings: Indicate layout of piping systems, including flexible connectors,
expansion joints, expansion compensators, loops, offsets and swing joints.
C.
Product Data:
1.
Flexible Pipe Connectors: Indicate maximum temperature and pressure
rating, face-to-face length, live length, hose wall thickness, hose
NCS Bloomfield Avenue Station
New Elevators
15125 - 1
2.
1.5
1.6
1.7
convolutions per foot and per assembly, fundamental frequency of
assembly, braid structure, and total number of wires in braid.
Expansion Joints: Indicate maximum temperature and pressure rating,
and maximum expansion compensation.
D.
Manufacturer's Installation Instructions: Submit special procedures.
E.
Manufacturer's Certificate: Certify products meet or exceed specified
requirements.
F.
Welders’ Certificate: Include welders’ certification of compliance with AWS D1.1.
G.
Manufacturer’s Field Reports: Indicate results of inspection by manufacturer’s
representative.
CLOSEOUT SUBMITTALS
A.
Submit in accordance with General Provisions for Construction.
B.
Project Record Documents: Record actual locations of flexible pipe connectors,
expansion joints, anchors, and guides.
C.
Operation and Maintenance Data: Submit adjustment instructions.
QUALIFICATIONS
A.
Manufacturer: Company specializing in manufacturing products specified in this
section with minimum ten years documented experience.
B.
Installer: Company specializing in performing Work of this section with minimum
three years documented experience.
DELIVERY, STORAGE, AND HANDLING
A.
Deliver, store, protect, and handle Products to site under requirements of
General Provisions for Construction.
B.
Accept expansion joints on site in factory packing with shipping bars and
positioning devices intact. Inspect for damage.
C.
Protect equipment from exposure by leaving factory coverings, pipe end
protection, and packaging in place until installation.
PART 2 PRODUCTS
2.1
FLEXIBLE PIPE CONNECTORS
A.
Steel Piping:
NCS Bloomfield Avenue Station
New Elevators
15125 - 2
1.
2.
3.
4.
5.
6.
7.
B.
2.2
Manufacturers:
a.
Flex-Hose Co., Inc., “Pumpsaver” Model SMP or SMN.
b.
The Metraflex Co., Model SLP or SST.
c.
Proco Products, Inc., Model FF-6201 or TT-6201.
d.
Flex-Weld, Inc., “Keflex” Model KSSPC-MPT or KSSPC-FLG.
e.
Vibration Mountings and Controls, Inc., Model MFE or NE.
f.
Mason Industries, Inc., Model BSS-RF or BSS-MN.
g.
Substitutions: Submit requests for substitution in accordance with
the General Provisions for Construction.
Inner Hose: Stainless Steel.
Exterior Sleeve: Double-braided stainless steel.
Pressure Rating: 150 psig at 70 degrees F.
Joint: As specified for pipe joints.
Size: Use pipe-sized units.
Maximum offset: 1/2 inch on each side of installed center line.
Copper Piping:
1.
Manufacturers:
a.
Flex-Hose Co., Inc., “Pumpsaver” Model BSW or BSN.
b.
The Metraflex Co., Model BBT or BBS.
c.
Proco Products, Inc., Model SEB-6201 or TTB-6201.
d.
Vibration Mountings and Controls, Inc., Model MFE or NE.
e.
Mason Industries, Inc., Model BBF-RF or BBF-MN.
f.
Substitutions: Submit requests for substitution in accordance with
the General Provisions for Construction.
2.
Inner Hose: Bronze
3.
Exterior Sleeve: Braided bronze.
4.
Pressure Rating: 150 psig at 70 degrees F.
5.
Joint: As specified for pipe joints.
6.
Size: Use pipe-sized units.
7.
Maximum offset: 1/2 inch on each side of installed center line.
EXPANSION JOINTS AND COMPENSATORS
A.
Stainless Steel Bellows Type:
1.
Manufacturers:
a.
Flex-Hose Co., Inc., “Bellowsflex” Model BF/150.
b.
The Metraflex Co., Model MN.
c.
Proco Products, Inc., Model FF-6801.
d.
Flex-Weld, Inc., “Keflex” Series 308.
e.
Substitutions: Submit requests for substitution in accordance with
the General Provisions for Construction.
2.
Working Pressure: 200 psig WOG
3.
Maximum Temperature: 250 degrees F.
4.
Maximum Compression: 1-1/2 inch.
5.
Maximum Extension: 1/4 inch.
6.
Joint: As specified for pipe joints.
7.
Size: Use pipe sized units.
8.
Application: Steel piping 3 inch and smaller.
NCS Bloomfield Avenue Station
New Elevators
15125 - 3
B.
Spherical Flexible Compensator:
1.
Manufacturers:
a.
Flex-Hose Co., Inc., “Flexzorber” Model NNS or NND.
b.
The Metraflex Co., “MetraSphere” Model R or “DoubleSphere”
Model O.
c.
Proco Products, Inc., Model 240 or 242.
d.
Vibration Mountings and Controls, Inc., “Quiet-Sphere” Model
VMS or VMT.
e.
Mason Industries, Inc., “Mason-Flex” Model MNFC or MNTNC.
f.
Mercer Rubber Co., “Invincible” Model 450 or 452.
g.
Red Valve Co., Inc., “Redflex” Model J-1.
h.
Substitutions: Submit requests for substitution in accordance with
the General Provisions for Construction.
2.
Body: Neoprene and nylon.
3.
Working Pressure: 150 psi
4.
Maximum Temperature: 250 degrees F.
5.
Maximum Compression: 1/2 inch.
6.
Maximum Elongation: 3/8 inch.
7.
Maximum Offset: 1/2 inch.
8.
Maximum Angular Movement: 15 degrees.
9.
Joint: Galvanized.
10.
Size: Use pipe sized units.
11.
Application: Steel piping 2 inch and larger.
C.
Sliding Sleeve Expansion Compensator:
1.
Manufacturers:
a.
Flex-Hose Co., Inc., “Flexpress” Model FP/150.
b.
The Metraflex Co., Model HP.
c.
Flex-Weld, Inc., “Keflex” Series 311.
d.
Substitutions: Submit requests for substitution in accordance with
the General Provisions for Construction.
2.
Working Pressure: 125 psi.
3.
Maximum Temperature: 250 degrees F.
4.
Joint: As specified for pipe joints.
5.
Size: Use pipe sized units.
6.
Application: Copper piping 2 inch and over.
D.
Loop-Type Expansion Compensator:
1.
Manufacturers:
a.
Flex-Hose Co., Inc., “Tri-Flex Loop” Model TFL4SMN, TFL4SMP
or TFL4BSW.
b.
The Metraflex Co., “Metraloop” Model MLT, MLS or MLF.
c.
Flex-Weld, Inc., “Keflex.”
d.
Substitutions: Submit requests for substitution in accordance with
the General Provisions for Construction.
2.
Working Pressure: 125 psi.
3.
Maximum Temperature: 250 degrees F.
4.
Joint: As specified for pipe joints.
NCS Bloomfield Avenue Station
New Elevators
15125 - 4
5.
6.
2.3
Size: Use pipe sized units.
Application: Copper or steel piping 2 inch and smaller.
ACCESSORIES
A.
Pipe Alignment Guides: Two piece welded steel with enamel paint, bolted, with
spider to fit standard pipe, frame with four mounting holes, clearance for
minimum 1 inch thick insulation, minimum 3 inch travel.
PART 3 EXECUTION
3.1
3.2
INSTALLATION
A.
Install Work in accordance with manufacturer’s instructions.
B.
Install flexible pipe connectors on pipes connected to equipment supported by
vibration isolation. Refer to Section 15070. Provide line size flexible connectors.
C.
Install flexible connectors at right angles to displacement. Install one end
immediately adjacent to isolated equipment and anchor other end. Install in
horizontal plane unless indicated otherwise.
D.
Rigidly anchor pipe to building structure. Provide pipe guides to direct movement
only along axis of pipe. Erect piping so strain and weight is not on cast
connections or apparatus.
E.
Provide support and anchors for controlling expansion and contraction of piping.
Provide loops, pipe offsets, and swing joints, or expansion joints where required
and as indicated on Drawings. Refer to Section 15060 for pipe hanger installation
requirements.
F.
Provide grooved piping systems with minimum one joint per inch pipe diameter
instead of flexible connector supported by vibration isolation. Grooved piping
systems need not be anchored.
G.
Provide expansion loops as indicated on Drawings.
MANUFACTURER'S FIELD SERVICES
A.
Furnish inspection services by flexible pipe manufacturer's representative for final
installation and certify installation is in accordance with manufacturer's
recommendations and connectors are performing satisfactorily.
NCS Bloomfield Avenue Station
New Elevators
15125 - 5
PART 4 COMPENSATION
4.1
MEASUREMENT AND PAYMENT
A.
Measurement: The work of this section shall not be measured.
B.
Payment: The cost of this section shall be included in the lump sum bid items
PLUMBING or HVAC SYSTEMS, as applicable to the system served.
END OF SECTION
NCS Bloomfield Avenue Station
New Elevators
15125 - 6
SECTION 15440
PLUMBING PUMPS
PART 1 GENERAL
1.1
1.2
1.3
1.4
SUMMARY
A.
Section Includes:
1.
Oil sensing submersible elevator sump pump.
2.
Pump accessories and appurtenances.
B.
Related Sections:
1.
Section 15150 – Sanitary Waste and Vent Piping.
2.
Section 16150 – Wiring Connections.
REFERENCES
A.
ASTM International:
1.
ASTM A53/A53M – Standard Specification for Pipe, Steel, Black and HotDipped, Zinc-Coated, Welded and Seamless.
B.
National Fire Protection Association:
1.
NFPA 70 – National Electrical Code
C.
Underwriter’s Laboratories:
1.
UL 508 – Industrial Control Equipment.
2.
UL 778 – Motor-Operated Water Pumps.
SUBMITTALS
A.
Submit in accordance with General Provisions for Construction.
B.
Shop Drawings: Submit installation details for pumps, piping, controls and
accessories including wiring schematics.
C.
Product Data: Submit data for specified Products.
D.
Manufacturer’s Certificates: Submit Statement of Compliance, supporting data,
from material suppliers attesting that pumps provided meet or exceed
performance criteria and conform to specification requirements.
CLOSEOUT SUBMITTALS
A.
Submit in accordance with General Provisions for Construction.
NCS Bloomfield Avenue Station
New Elevators
15440 - 1
B.
1.5
1.6
QUALIFICATIONS
A.
Manufacturer: company specializing in manufacturing Products specified in this
section with minimum three years documented experience.
B.
Installer: Company specializing in performing work of this section with minimum
three years documented experience and approved by manufacturer.
PRE-INSTALLATION MEETINGS
A.
1.7
1.8
1.9
A.
Transport, handle, store, and protect products in accordance with the General
Provisions for Construction.
B.
Prepare pumps and accessories for shipment to prevent entry of foreign matter
into product body.
C.
Store products in areas protected from weather, moisture, or possible damage;
do not store products directly on ground; handle products to prevent damage to
interior or exterior surfaces.
ENVIRONMENTAL REQUIREMENTS
A.
Maintain environmental conditions required for products installed or stored on
site in accordance with the General Provisions for Construction.
B.
Conduct operations not to interfere with, interrupt, damage, destroy, or endanger
integrity of surface or subsurface structures or utilities, and landscape in
immediate or adjacent areas.
COORDINATION
Coordinate work with utilities within construction area.
MAINTENANCE MATERIALS
A.
1.11
Convene minimum one week prior to commencing work of this section.
DELIVERY, STORAGE AND HANDLING
A.
1.10
Operation and Maintenance Data: Submit installation instructions, servicing
requirements, assembly views, lubrication instructions, and replacement parts
list.
Furnish special tools required for equipment maintenance.
FIELD MEASUREMENTS
A.
Verify field measurements prior to fabrication.
NCS Bloomfield Avenue Station
New Elevators
15440 - 2
PART 2 PRODUCTS
2.1
PUMPS
A.
Manufacturers:
1.
Stancor, Inc., Model SE-40, or approved equal.
2.
Substitutions: Submit requests for substitution in accordance with the
General Provisions for Construction.
B.
Description: UL 778; Submersible oil-sensing pump with stainless steel/
polycarbonate housing, vortex type non-clog impeller, float switch activation,
remote control panel, and control cabling.
1.
Capacity:
a.
50 GPM at 5 feet TDH design point.
b.
45 GPM at 10 feet TDH secondary point.
c.
22 feet TDH shutoff head.
C.
Motor: 115 volt, 1 phase, 60 Hz, 0.4 hp, 3600 rpm maximum; non-overloading
throughout entire range of pump curve.
D.
Oil Sensor: Self-cleaning, hermetically sealed stainless steel probe capable of
distinguishing between oil contaminated effluent and wastewater.
E.
Control Panel: UL 508; NEMA 4X weathertight polycarbonate enclosure with
solid state monitoring circuitry, LED type indicator lights, water tight alarm horn,
alarm silencing and reset switches, pin-type control cable receptacle, internal
terminal strip, and single point power connection cord/plug.
1.
Indicator Lights:
a.
Power.
b.
Pump operating.
c.
Oil detection.
d.
High liquid level.
e.
Motor overload.
2.
Float Switches: Sealed float-type mercury switches in shock-resistant
solid polyurethane, with heavy neoprene-jacketed weighted cords.
a.
Pump activation.
b.
High liquid level alert.
3.
Pump Operation:
a.
On rise of liquid level, pump activation float switch energizes
pump.
b.
If liquid level drops below oil sensor probe, pump shuts off.
c.
If high-level liquid alarm float switch remains activated 30 seconds
after pump energizes, audible alarm is sounded.
d.
If oil sensor probe detects presence of oil, audible alarm is
sounded, and pumps are locked out of operation until system is
manually reset.
NCS Bloomfield Avenue Station
New Elevators
15440 - 3
2.2
2.3
2.4
PUMP DISCHARGE PIPING
A.
Refer to Section 15150.
B.
Provide check valve with hydraulically sealed, quick disconnect, discharge flange
and ball valve with stem extension in pump discharge line.
C.
Pump discharge check valve shall be provided with a weep-back ¼” hole drilled
through it’s flapper face to provide for back flow into sump to prevent freezing of
pump discharge piping.
ALARM DIAL OUT ANNUNCIATOR
A.
Provide Sensaphone Model 800, or approved equal at In-Bound elevator
machine room, or approved equal.
B.
Connect to NJ Transit provided phone line.
APPURTENANCES
A.
Fasteners and Hardware: Stainless steel.
PART 3 EXECUTION
3.1
3.2
3.3
EXAMINATION
A.
Verify existing conditions before starting work.
B.
Verify connections, size, and location are as indicated on Drawings.
C.
Verify electrical power is of correct voltage and operating characteristics.
INSTALLATION
A.
Install pumps in elevator sumps in accordance with manufacturer's instructions.
B.
Provide necessary piping, fittings, and valves as indicated on Drawings.
ALARM DIAL OUT SYSTEM SETUP
A.
Demonstration and Training:
1.
Furnish two (2) hours of instruction for up to (8) NJ Transit staff, to be
conducted at project site with manufacturer's representative. Coordinate
training schedule with Construction Manager, Engineer and manufacturer.
Provide minimum of ten (10) days notice prior to proposed
commencement of training.
2.
Instruct NJ Transit staff on how to program, test and maintain the alarm
remote monitoring automatic dialer:
NCS Bloomfield Avenue Station
New Elevators
15440 - 4
a.
b.
c.
3.4
3.5
Review procedures for troubleshooting and maintaining equipment
Demonstrate Programming of alarm messages and phone
numbers to be dialed out to
Review Information in User's Manual
B.
Initial Programming of dialer with messages and phone numbers:
1.
Alarm outgoing messages for high water and oil detected as follows:
a.
" Newark Light Rail, Bloomfield Station, Out bound elevator has
been shut down due to oil detected in pit sump pump"
b.
" Newark Light Rail, Bloomfield Station, In bound elevator has
been shut down due to oil detected in pit sump pump"
c.
" Newark Light Rail, Bloomfield Station, Out bound elevator pit
sump pit has a high water level alarm condition"
d.
"Newark Light Rail, Bloomfield Station, In bound elevator pit sump
pit has a high water level alarm condition"
C.
Phone numbers to be dialed out to at NJ Transit Response Center:
1.
(973) 491-8779
2.
(973) 491-8778
D.
Test all function of dialer by running false alarms at each pump for each type of
alarm and confirm that responses are received by dialer
E.
Warrant equipment and installation for 1 year parts and labor
FIELD QUALITY CONTROL
A.
Upon completion of installation, examine, adjust and test each unit for proper
operation under direction of manufacturer's representative.
B.
Check and adjust liquid level control and alarm settings.
C.
Test each pump with clean water through minimum of four complete cycles of lift
station including high-level and low-level conditions to demonstrate correct pump
operation, control settings, alarm settings, freedom from pump vibration, noise
and overheating. Provide water as required for testing purposes.
D.
Demonstrate with each pump provision for pump removal, service and
replacement.
MANUFACTURER’S FIELD SERVICES
A.
Provide services of manufacturer's representative for period of not less than 2
man days to inspect installations, and conduct performance testing and training.
NCS Bloomfield Avenue Station
New Elevators
15440 - 5
PART 4 COMPENSATION
4.1
MEASUREMENT AND PAYMENT
A.
Measurement: The work of this section shall not be measured.
B.
Payment: The cost of this section shall be included in the lump sum bid item
PLUMBING.
END OF SECTION
NCS Bloomfield Avenue Station
New Elevators
15440 - 6
SECTION 15739
SPLIT SYSTEM AIR CONDITIONING UNITS
PART 1 GENERAL
1.1
1.2
1.3
SUMMARY
A.
Section Includes:
1.
Air handling unit.
2.
Condensing unit.
B.
Related Sections:
1.
Section 15070 - Mechanical Sound, Vibration, and Seismic Control:
Vibration isolators.
2.
Section 15150 – Sanitary Waste and Vent Piping: Execution requirements
for connection to condensate drainage piping specified by this section.
3.
Section 15940 - Sequence of Operation: Sequences of operation applying
to units in this section.
4.
Section 16150 - Wiring Connections: Electrical connection to units.
REFERENCES
A.
Air-Conditioning and Refrigeration Institute:
1.
ARI 210/240 - Unitary Air-Conditioning and Air-Source Heat Pump
Equipment.
2.
ARI 270 - Sound Rating of Outdoor Unitary Equipment.
B.
American Society of Heating, Refrigerating and Air-Conditioning Engineers:
1.
ASHRAE 90.1 - Energy Standard for Buildings Except Low-Rise
Residential Buildings.
C.
National Electrical Manufacturers Association:
1.
NEMA MG 1 - Motors and Generators.
SUBMITTALS
A.
Submit in accordance with General Provisions for Construction.
B.
Product Data: Submit data indicating:
1.
Cooling and heating capacities.
2.
Dimensions.
3.
Weights.
4.
Rough-in connections and connection requirements.
5.
Duct connections.
6.
Electrical requirements with electrical characteristics and connection
requirements.
7.
Controls.
NCS Bloomfield Avenue Station
New Elevators
15739 - 1
8.
1.4
1.5
1.6
Accessories.
C.
Manufacturer's Installation Instructions: Submit assembly, support details,
connection requirements, and include start-up instructions.
D.
Manufacturer's Certificate: Certify Products meet or exceed specified
requirements.
E.
Manufacturer’s Field Reports: Submit start-up report for each unit.
CLOSEOUT SUBMITTALS
A.
Submit in accordance with General Provisions for Construction.
B.
Project Record Documents: Record actual locations of controls installed remotely
from units.
C.
Operation and Maintenance Data: Submit manufacturer's descriptive literature,
operating instructions, installation instructions, and maintenance and repair data.
QUALITY ASSURANCE
A.
Performance Requirements:
1.
Energy Efficiency Rating (EER): Not less than prescribed by ASHRAE
90.1 when used in combination with compressors and evaporator coils
when tested in accordance with ARI 210/240.
2.
Seasonal Energy Efficiency Rating (SEER): Overall minimum system
efficiency of 13.0.
B.
Cooling Capacity: Rate in accordance with ARI 210/240.
C.
Sound Rating: Measure in accordance with ARI 270.
D.
Ensure that equipment bears approval label from Underwriter’s Laboratories,
ETL/Intertek, Factory Mutual, Warnock-Hersey, or other testing firm acceptable
to the authority having jurisdiction where certification or listing is furnished for the
particular type of equipment.
QUALIFICATIONS
A.
Manufacturer: Company specializing in manufacturing products specified in this
section with minimum five years documented experience.
B.
Installer: Company specializing in performing Work of this section with minimum
five years documented experience and approved by manufacturer.
NCS Bloomfield Avenue Station
New Elevators
15739 - 2
1.7
1.8
1.9
DELIVERY, STORAGE, AND HANDLING
A.
Deliver, store, protect, and handle Products to site under requirements of
General Provisions for Construction.
B.
Provide dry air holding charge in the indoor section.
C.
Pre-charge outdoor unit with R-410a refrigerant for 70 feet of refrigerant tubing.
D.
Accept units and components on site in factory protective containers, with factory
shipping skids and lifting lugs. Inspect for damage.
E.
Comply with manufacturer's installation instruction for rigging, unloading and
transporting units.
F.
Protect units from weather and construction traffic by storing in dry, roofed
location.
COORDINATION
A.
Coordinate installation of condensing units with platform steel and concrete
housekeeping pads.
B.
Coordinate installation of air handling units with building structure.
WARRANTY
A.
1.10
Furnish five-year manufacturer’s warranty for compressors.
MAINTENANCE SERVICE
A.
Furnish service and maintenance of equipment for one year from Date of
Substantial Completion. Include maintenance items as shown in manufacturer's
operating and maintenance data, including filter replacements, fan belt
replacement, and controls checkout and adjustments.
B.
Furnish 24-hour emergency service on breakdowns and malfunctions for this
maintenance period. Furnish capability of response time within 4 hours.
PART 2 PRODUCTS
2.1
SPLIT SYSTEM AIR CONDITIONING UNITS
A.
Product Description: Variable speed inverter compressor type split system heat
pump with wall mounted indoor air handling unit; factory wired wall mounted
controller; horizontal discharge, single phase outdoor unit; and all refrigeration
circuits, controls, accessories, and specialties.
NCS Bloomfield Avenue Station
New Elevators
15739 - 3
2.2
INDOOR UNITS (AC-1, AC-2, AC-3)
A.
Manufacturers:
1.
Mitsubishi Electric, Inc., “Mr. Slim” Model PKA-A24FA, or approved equal.
2.
Substitutions: Submit requests for substitution in accordance with the
General Provisions for Construction.
B.
Description: Factory assembled, wired and tested high wall fan coil unit with
control/power wiring, refrigeration piping, control circuit board, fan motor, and
integral wall mounting bracket.
C.
Cabinet: Fabricated of high strength white molded plastic, with front panel filter
access, factory applied insulation, and wall mounting plate.
1.
Wall mounted by means of a, The cabinet shall be formed from. Cabinet
color shall be white –24,000 Munsell 3.4Y 7.7/08.
2.
Contained within the unit shall be all factory. Insulation: Factory applied to
each surface to insulate entire cabinet, with edges protected from
erosion.
3.
The unit in conjunction with the wired, wall mounted controller shall have
a self-diagnostic function, 3-minute time delay mechanism, an auto restart
function, and a test run switch. Indoor unit and refrigerant pipes shall be
purged with dry nitrogen before shipment from the factory.
D.
Evaporator Fan: Two-speed, high performance, double inlet, forward curve,
direct drive sirocco fan; statically and dynamically balanced, with permanently
lubricated motor.
E.
Vane: There shall be a motorized horizontal vane to automatically direct air flow
in a horizontal and downward direction for uniform air distribution. The horizontal
vane shall significantly decrease downward air resistance for lower noise levels,
and shall close the outlet port when operation is stopped. There shall also be a
set of vertical vanes to provide horizontal swing airflow movement selected by
remote control.
F.
Evaporator Coil: Multi-angled heat exchanger of non-ferrous construction, with
pre-coated, low-resistance aluminum strake fins on copper tubing; PhosCopper
or silver alloy brazed tube joints pressure tested at the factory; condensate pan
with internal trap; and auxiliary drip pan and drain under the coil.
G.
Refrigeration System: Single refrigeration circuits controlled by factory installed
piston type refrigerant metering device.
H.
Air Filters: Return air shall be filtered by means of an easily removable washable
filter.
I.
Electrical Characteristics: 208 volts, single phase, 60 Hz.
NCS Bloomfield Avenue Station
New Elevators
15739 - 4
2.3
CONDENSING UNIT
A.
Manufacturers:
1.
Mitsubishi Electric, Inc., Model PUZ-A24NHA-BS, or approved equal.
2.
Substitutions: Submit requests for substitution in accordance with the
General Provisions for Construction.
B.
General: Factory assembled, piped, and wired and tested air-cooled condensing
unit, fully compatible with the indoor unit controls and capacity, consisting of
casing, compressor, condenser, coils, condenser fan and motor, condensate
pump and unit controls and interface board.
1.
Minimum Operating Temperature: 0°F ambient without supplemental low
ambient controls.
2.
Maximum Operating Height Difference: 100 feet between indoor and
outdoor units.
3.
Factory Rated Refrigerant Tubing Length: Pre-charged for a maximum
distance of 70 feet.
4.
Maximum Refrigerant Tubing Length: 165 feet without the need for line
size changes, traps or additional oil.
C.
Unit Casing: Galvanized steel with electrostatically applied, thermally fused
acrylic or polyester powder coating and munsell 3Y 7.8/1.1 finish; and ABS
plastic fan grille.
D.
Compressor: DC rotary compressor with variable speed inverter drive to
dynamically match the room load; intermittently applied compressor motor
current to prevent liquid accumulation in the compressor during the off cycle;
accumulator; and high pressure safety switch. Mount to avoid transmission of
vibration.
E.
Condenser Coil: The L shaped condenser coil shall be of copper tubing with flat
aluminum fins to reduce debris build up. The coil shall be protected with an
integral metal guard. Refrigerant flow from the condenser shall be controlled by
means of linear expansion valve (LEV) metering orifice. The LEV shall be control
by a microprocessor controlled step motor.
F.
Electrical Characteristics: 208 volts, single phase, 60 Hz.
G.
Controls: Furnish operating and safety controls including high and low pressure
cutouts, control transformer, and magnetic contactors for compressor and
condenser fan motors. Activate outdoor unit via pulse signal 24 volts DC control
signal from microprocessor located in the indoor unit. Provide pulse amplitude
modulation circuit to utilize 98% of input power supply.
H.
Condenser Fans and Drives: Horizontal discharge airflow fan mounted in front of
the coil, with raised guard to prevent contact with moving parts and permanently
lubricated motor bearings.
I.
Condensing Unit Accessories:
NCS Bloomfield Avenue Station
New Elevators
15739 - 5
1.
2.
3.
4.
5.
2.4
Low ambient cooling control to -20 degrees F.
Time delay relay.
Anti-short cycle timer.
Disconnect switch.
PVC coated steel wire condenser guard.
J.
Refrigeration specialties: Furnish the following:
1.
Mixed phase line service valve.
2.
Suction line service valve with gauge port.
3.
Compressor suction/discharge service gauge ports with Schrader fittings.
4.
Charge of compressor oil.
5.
Holding charge of refrigerant.
6.
Accumulator.
7.
Pressure relief device.
K.
Refrigerant: Furnish charge of refrigerant R-410A.
L.
Capacity: As scheduled on Drawings.
CONTROLS
A.
Description: Wall mounted microprocessor-based system with liquid crystal
display, controlling space temperature, optimum fan speed, and self-diagnostic
checks, with 67°F to 87°F temperature control range. Interconnect indoor and
outdoor unit microprocessors with single, non-polar, two-wire cable with no
splices. Include the following functions:
1.
Automatic restart after power failure at the same operating conditions as
at failure;
2.
Timer function providing minimum 24-hour timer cycle for system
automatic Start/Stop;
3.
Return-air temperature sensor with high discharge temperature
shutdown;
4.
Indoor coil freeze protection.
5.
Integral setback control;
6.
Automatic airsweep control.
7.
Fan Only and Dehumidification modes providing room air circulation when
no cooling is required;
8.
Continuous diagnostic checks of unit operation indicating malfunctions via
error messages displayed at the control panel;
9.
User-selectable high, medium, low, or automatic fan speed control during
all operating modes;
10.
Compressor short cycle delay.
B.
Unit Controls:
1.
On/Off button.
2.
Increase/Decrease Set Temperature buttons.
3.
Heat/Auto/Cool/Dry/Fan mode selector.
4.
Timer Menu button.
5.
Timer On/Off button,
NCS Bloomfield Avenue Station
New Elevators
15739 - 6
6.
7.
8.
9.
10.
11.
12.
C.
Set Time buttons.
Fan Speed selector.
Vane Position selector.
Louver Swing button.
Ventilation button.
Test Run button.
Check Mode button.
Display Parameters:
1.
Set Temperature.
2.
Room Temperature.
3.
Pipe Temperatures (liquid, discharge, indoor and outdoor).
4.
Compressor Operating Conditions (running current, frequency, input
voltage, on/off status, and operating time)
5.
LEV opening pulses, sub cooling and discharge super heat.
PART 3 EXECUTION
3.1
3.2
3.3
EXAMINATION
A.
Verify existing conditions before starting work.
B.
Verify concrete pad for condensing unit is ready for unit installation.
INSTALLATION - INDOOR UNIT
A.
Install indoor unit on wall as indicated on Drawings in accordance with
manufacturer’s instructions.
B.
Install condensate piping from pump to building drainage system.
C.
Install components furnished loose for field mounting.
D.
Install connection to electrical power wiring in accordance with Division 16.
Provide disconnecting means in accordance with code.
INSTALLATION - CONDENSING UNIT
A.
Install condensing units suspended from platform steel on vibration isolators.
Refer to Section 15070.
B.
Install refrigerant piping from unit to condensing unit. Install refrigerant specialties
furnished with unit.
C.
Evacuate refrigerant piping and install initial charge of refrigerant.
D.
Install electrical devices furnished loose for field mounting.
NCS Bloomfield Avenue Station
New Elevators
15739 - 7
3.4
E.
Install control wiring between air handling unit, condensing unit, and field
installed accessories.
F.
Install connection to electrical power wiring in accordance with Division 16.
Provide disconnecting means in accordance with code.
MANUFACTURER'S FIELD SERVICES
A.
3.5
3.6
3.7
Furnish initial start-up and shutdown during first year of operation, including
routine servicing and checkout.
CLEANING
A.
Vacuum clean coils and inside of unit cabinet.
B.
Install new filters in units at Substantial Completion.
DEMONSTRATION
A.
Demonstrate air handling unit operation and maintenance.
B.
Demonstrate starting, maintenance, and operation of condensing unit including
low ambient temperature operation.
C.
Furnish services of manufacturer's technical representative for one 8-hour day to
instruct Owner's personnel in operation and maintenance of units. Schedule
training with Construction Manager, and provide at least 7 days notice in
advance of training date.
PROTECTION OF FINISHED WORK
A.
Do not operate units until ductwork is clean, filters are in place, bearings
lubricated, and fan has been test run under observation.
PART 4 COMPENSATION
4.1
MEASUREMENT AND PAYMENT
A.
Measurement: The work of this section shall not be measured.
B.
Payment: The cost of this section shall be included in the lump sum bid item
HVAC SYSTEMS.
END OF SECTION
NCS Bloomfield Avenue Station
New Elevators
15739 - 8
SECTION 15760
TERMINAL HEATING UNITS
PART 1 GENERAL
1.1
1.2
1.3
1.4
SUMMARY
A.
Section Includes:
1.
Electric unit heaters.
2.
Electric radiant heaters.
B.
Related Sections:
1.
Section 16150 - Wiring Connections: Execution requirements for electric
connection to units specified by this section.
2.
Section 16225 - Motors: Product requirements for motors for placement
by this section.
SUBMITTALS
A.
Submit in accordance with General Provisions for Construction.
B.
Shop Drawings: Indicate installation of ceiling hung infrared electric heaters.
C.
Product data: Provide manufacturer's standard data for unit size, finish, and
performance data.
D.
Manufacturer's Installation Instructions: Submit assembly, support details, and
connection requirements.
CLOSEOUT SUBMITTALS
A.
Submit in accordance with General Provisions for Construction.
B.
Project Record Documents: Record actual locations of heaters on project record
documents.
C.
Operation and Maintenance Data: Submit manufacturers descriptive literature,
operating instructions, installation instructions, maintenance and repair data, and
parts listings.
QUALIFICATIONS
A.
Manufacturer: Company specializing in manufacturing products specified in this
section with minimum three years documented experience.
B.
Installer: Company specializing in performing Work of this section with minimum
three years documented experience.
NCS Bloomfield Avenue Station
New Elevators
15760 - 1
1.5
1.6
DELIVERY, STORAGE, AND HANDLING
A.
Deliver, store, protect, and handle Products to site under requirements of
General Provisions for Construction.
B.
Accept units on site in factory packing. Inspect for damage. Store under roof.
FIELD MEASUREMENTS
A.
Verify field measurements prior to fabrication.
PART 2 PRODUCTS
2.1
2.2
ELECTRIC RADIANT HEATERS
A.
Manufacturers:
1.
TPI Corp., “Mul-T-Mount” Model, or approved equal.
2.
Substitutions: Submit requests for substitution in accordance with the
General Provisions for Construction.
B.
Assembly: UL listed and labeled, 20-gauge stainless steel housing and
adjustable mounting brackets, with gold anodized aluminum reflectors,
distribution pattern as scheduled on Drawings.
C.
Heating Elements: 96 percent efficiency moisture and thermal shock resistant
clear quartz lamps, with coiled tungsten filament located in halogen filled sealed
quartz envelope, porcelain end caps, and high temperature pigtail leads.
D.
Control: On-demand pushbutton control with timed shutoff and thermostatic
interlock.
E.
Electrical Characteristics: As scheduled on Drawings.
ELECTRIC CABINET HEATERS
A.
Manufacturers:
1.
Q-Mark Div., Marley Electric Heating Co., Type LFK.
2.
Substitutions: Submit requests for substitution in accordance with the
General Provisions for Construction.
B.
Assembly: UL listed and labeled assembly with terminal box and cover, and builtin controls, suitable for recessed or surface mounting.
C.
Heating Elements: Steel finned metal sheath element.
D.
Cabinet: Heavy-gauge steel with easily removed front panel with integral air
outlet and inlet grilles.
NCS Bloomfield Avenue Station
New Elevators
15760 - 2
E.
Fan: Direct-drive propeller type, statically and dynamically balanced, with fan
guard.
F.
Motor: Permanently lubricated, sleeve bearings for horizontal models; ball
bearings for vertical models.
G.
Control: Separate fan speed switch and thermostat heat selector switch, factory
wired. Furnish thermal overload.
H.
Electrical Characteristics: As scheduled on Drawings.
PART 3 EXECUTION
3.1
3.2
3.3
EXAMINATION
A.
For recessed units, verify recess dimensions are correct size.
B.
Verify wall construction is ready for installation.
C.
Verify ductwork is ready for installation.
D.
Verify concealed blocking and supports are in place and connections are
correctly located.
EXAMINATION
A.
Verify that field conditions are acceptable and are ready to receive work.
B.
Verify that required utilities are available, in proper location, and ready for use.
INSTALLATION
A.
Install in accordance with manufacturer's instructions. Furnish copy of
manufacturer's wiring diagram submittal. Install electrical wiring in accordance
with Section 16150.
B.
Support heaters from structure using construction details shown on Contract
drawings
C.
Locate each unit in position indicated.
D.
Install units with sufficient clearance from adjacent construction, piping, ductwork,
and other obstructions to allow access for service and maintenance.
E.
Install devices furnished by manufacturer but not factory-mounted.
F.
Cabinet Unit Heaters: Install at locations as indicated on Drawings. Coordinate to
assure correct recess size for recessed units.
NCS Bloomfield Avenue Station
New Elevators
15760 - 3
G.
3.4
Infrared Heaters: Support from building structure, with hangers anchored to
building, at height indicated on Drawings, maintaining required clearances to
combustible surfaces.
CLEANING
A.
After construction is completed, including painting, clean exposed surfaces of
units. Vacuum clean coils and inside of heater cabinets.
B.
Touch-up marred or scratched surfaces of factory-finished cabinets, using finish
materials furnished by manufacturer.
PART 4 COMPENSATION
4.1
MEASUREMENT AND PAYMENT
A.
Measurement: The work of this section shall not be measured.
B.
Payment: The cost of this section shall be included in the lump sum bid item
HVAC SYSTEMS.
END OF SECTION
NCS Bloomfield Avenue Station
New Elevators
15760 - 4
SECTION 15940
SEQUENCE OF OPERATION
PART 1 GENERAL
1.1
SUMMARY
A.
Section includes sequence of operation for:
1.
Air conditioning units.
2.
Cabinet electric wall heaters.
3.
Radiant electric unit heaters.
4.
Exhaust fans.
B.
Related Sections:
1.
2.
3.
1.2
1.3
Section 15739 - Split System Air Conditioning Units.
Section 15760 - Terminal Heating Units.
Section 15950 - Testing, Adjusting and Balancing.
SUBMITTALS
A.
Submit in accordance with General Provisions for Construction.
B.
Shop Drawings: Indicate mechanical system controlled and control system
components.
1.
Label with settings, adjustable range of control and limits. Submit written
description of control sequence.
2.
Submit flow diagrams for each control system, graphically depicting
control logic.
CLOSEOUT SUBMITTALS
A.
Submit in accordance with General Provisions for Construction.
B.
Project Record Documents: Record actual locations of components and set
points of controls, including changes to sequences made after submission of
shop drawings.
PART 2 PRODUCTS
Not Used.
NCS Bloomfield Avenue Station
New Elevators
15940 - 1
PART 3 EXECUTION
3.1
SPLIT SYSTEM COMMUNICATIONS ROOM AIR CONDITIONING UNIT
A.
3.2
Microprocessor based unit-mounted thermostat set at 72 degrees F to maintain
constant space temperature. Refer to Section 15739.
CABINET ELECTRIC WALL HEATERS
A.
Single temperature thermostat mounted in cabinet return air set at temperature
scheduled on Drawings; maintains constant space temperature by cycling unit
fan motor and electric heating elements. Integral thermostat continues fan
operation until element temperature falls below 100 degrees F.
PART 4 COMPENSATION
4.1
MEASUREMENT AND PAYMENT
A.
Measurement: The work of this section shall not be measured.
B.
Payment: The cost of this section shall be included in the lump sum bid item
HVAC SYSTEMS.
END OF SECTION
NCS Bloomfield Avenue Station
New Elevators
15940 - 2
SECTION 15950
TESTING, ADJUSTING, AND BALANCING
PART 1 GENERAL
1.1
1.2
1.3
SUMMARY
A.
Section Includes:
1.
Testing adjusting, and balancing of air systems.
2.
Measurement of final operating condition of HVAC systems.
3.
Sound measurement of equipment operating conditions.
4.
Vibration measurement of equipment operating conditions.
B.
Related Sections:
1.
Section 15940 - Sequence of Operation: Sequences of operation for
HVAC equipment.
REFERENCES
A.
Associated Air Balance Council:
1.
AABC MN-1 - National Standards for Testing and Balancing Heating,
Ventilating, and Air Conditioning Systems.
B.
American Society of Heating, Refrigerating and Air-Conditioning Engineers:
1.
ASHRAE 111 - Practices for Measurement, Testing, Adjusting and
Balancing of Building Heating, Ventilation, Air-Conditioning and
Refrigeration Systems.
C.
Natural Environmental Balancing Bureau:
1.
NEBB - Procedural Standards for Testing, Adjusting, and Balancing of
Environmental Systems.
SUBMITTALS
A.
Submit in accordance with General Provisions for Construction.
B.
Prior to commencing Work, submit proof of latest calibration date of each
instrument.
C.
Test Reports: Indicate data on AABC MN-1 National Standards for Total System
Balance forms, forms prepared following ASHRAE 111, or NEBB Report forms.
D.
Field Reports: Indicate deficiencies preventing proper testing, adjusting, and
balancing of systems and equipment to achieve specified performance.
NCS Bloomfield Avenue Station
New Elevators
15950 - 1
1.4
1.5
1.6
1.7
E.
Prior to commencing Work, submit report forms or outlines indicating adjusting,
balancing, and equipment data required. Include detailed procedures, agenda,
and sample report forms.
F.
Submit draft copies of report for review prior to final acceptance of Project.
G.
Furnish reports in soft cover, letter size, 3-ring binder manuals, complete with
table of contents page and indexing tabs, with cover identification at front and
side. Include set of reduced drawings with air outlets and equipment identified to
correspond with data sheets, and indicating thermostat locations.
CLOSEOUT SUBMITTALS
A.
Submit in accordance with General Provisions for Construction.
B.
Project Record Documents: Record actual locations of flow measuring stations,
balancing valves and rough settings.
C.
Operation and Maintenance Data: Furnish final copy of testing, adjusting, and
balancing report inclusion in operating and maintenance manuals.
QUALITY ASSURANCE
A.
Perform Work in accordance with AABC MN-1 National Standards for Field
Measurement and Instrumentation, Total System Balance; ASHRAE 111; or
NEBB Procedural Standards for Testing, Balancing and Adjusting of
Environmental Systems.
B.
Maintain one copy of each document on site.
C.
Prior to commencing Work, calibrate each instrument to be used. Upon
completing Work, recalibrate each instrument to assure reliability.
QUALIFICATIONS
A.
Agency: Company specializing in testing, adjusting, and balancing of systems
specified in this section with minimum three years documented experience.
B.
Perform Work under supervision of AABC Certified Test and Balance Engineer;
NEBB Certified Testing, Balancing and Adjusting Supervisor; or registered
professional engineer experienced in performance of this Work and licensed in
State of New Jersey.
PRE-INSTALLATION MEETINGS
A.
Convene minimum one week prior to commencing work of this section.
NCS Bloomfield Avenue Station
New Elevators
15950 - 2
1.8
SEQUENCING
A.
1.9
Sequence balancing between completion of systems tested and Date of
Substantial Completion.
SCHEDULING
A.
Schedule and provide assistance in final adjustment and test of life safety, smoke
evacuation, and/or smoke control systems with NJDCA Subcode Inspector.
PART 2 PRODUCTS
Not Used.
PART 3 EXECUTION
3.1
EXAMINATION
A.
3.2
3.3
Verify systems are complete and operable before commencing work. Verify the
following:
1.
Systems are started and operating in safe and normal condition.
2.
Temperature control systems are installed complete and operable.
3.
Proper thermal overload protection is in place for electrical equipment.
4.
Final filters are clean and in place. If required, install temporary media in
addition to final filters.
5.
Duct systems are clean of debris.
6.
Fans are rotating correctly.
7.
Fire and volume dampers are in place and open.
8.
Air coil fins are cleaned and combed.
9.
Access doors are closed and duct end caps are in place.
10.
Air outlets are installed and connected.
11.
Duct system leakage is minimized.
PREPARATION
A.
Furnish instruments required for testing, adjusting, and balancing operations.
B.
Make instruments available to Architect/Engineer to facilitate spot checks during
testing.
INSTALLATION TOLERANCES
A.
Air Handling Systems: Adjust to within plus or minus 10 percent of design.
B.
Air Outlets and Inlets: Adjust total to within plus 10 percent and minus 5 percent
of design to space. Adjust outlets and inlets in space to within plus or minus 10
percent of design.
NCS Bloomfield Avenue Station
New Elevators
15950 - 3
3.4
3.5
ADJUSTING
A.
Verify recorded data represents actual measured or observed conditions.
B.
Permanently mark settings of valves, dampers, and other adjustment devices
allowing settings to be restored. Set and lock memory stops.
C.
After adjustment, take measurements to verify balance has not been disrupted. If
disrupted, verify correcting adjustments have been made.
D.
Report defects and deficiencies noted during performance of services, preventing
system balance.
E.
Leave systems in proper working order, replacing belt guards, closing access
doors, closing doors to electrical switch boxes, and restoring thermostats to
specified settings.
F.
At final inspection, recheck random selections of data recorded in report.
Recheck points or areas as selected and witnessed by Construction Manager.
G.
Check and adjust systems approximately six months after final acceptance and
submit report.
AIR SYSTEM PROCEDURE
A.
Adjust air handling and distribution systems to obtain required or design supply,
return, and exhaust air quantities.
B.
Make air quantity measurements in main ducts by Pitot tube traverse of entire
cross sectional area of duct.
C.
Measure air quantities at air inlets and outlets.
D.
Adjust distribution system to obtain uniform space temperatures free from
objectionable drafts.
E.
Use volume control devices to regulate air quantities only to extent adjustments
do not create objectionable air motion or sound levels. Effect volume control by
using volume dampers located in ducts.
F.
Vary total system air quantities by adjustment of fan speeds. Provide sheave
drive changes to vary fan speed. Vary branch air quantities by damper
regulation.
G.
Provide system schematic with required and actual air quantities recorded at
each outlet or inlet.
NCS Bloomfield Avenue Station
New Elevators
15950 - 4
3.6
H.
Measure static air pressure conditions on air supply units, including filter and coil
pressure drops, and total pressure across fan. Make allowances for 50 percent
loading of filters.
I.
Adjust outside air automatic dampers, outside air, return air, and exhaust
dampers for design conditions.
J.
Measure temperature conditions across outside air, return air, and exhaust
dampers to check leakage.
SCHEDULES
A.
Equipment Requiring Testing, Adjusting, and Balancing:
1.
Air Cooled Refrigerant Condensers.
2.
Packaged Heating/Cooling Units.
3.
Packaged Terminal Air Conditioning Units.
4.
Fans.
5.
Air Filters.
6.
Air Inlets and Outlets.
B.
Report Forms
1.
Title Page:
a.
Name of Testing, Adjusting, and Balancing Agency
b.
Address of Testing, Adjusting, and Balancing Agency
c.
Telephone and facsimile numbers of Testing, Adjusting, and
Balancing Agency
d.
Project name
e.
Project location
f.
Project Architect
g.
Project Engineer
h.
Project Contractor
i.
Project altitude
j.
Report date
2.
Summary Comments:
a.
Design versus final performance
b.
Notable characteristics of system
c.
Description of systems operation sequence
d.
Summary of outdoor and exhaust flows to indicate building
pressurization
e.
Nomenclature used throughout report
f.
Test conditions
3.
Instrument List:
a.
Instrument
b.
Manufacturer
c.
Model number
d.
Serial number
e.
Range
f.
Calibration date
4.
Electric Motors:
NCS Bloomfield Avenue Station
New Elevators
15950 - 5
5.
6.
7.
8.
a.
Manufacturer
b.
Model/Frame
c.
HP/BHP and kW
d.
Phase, voltage, amperage; nameplate, actual, no load
e.
RPM
f.
Service factor
g.
Starter size, rating, heater elements
h.
Sheave Make/Size/Bore
V-Belt Drive:
a.
Identification/location
b.
Required driven RPM
c.
Driven sheave, diameter and RPM
d.
Belt, size and quantity
e.
Motor sheave diameter and RPM
f.
Center to center distance, maximum, minimum, and actual
Air Cooled Condenser:
a.
Identification/number
b.
Location
c.
Manufacturer
d.
Model number
e.
Serial number
f.
Entering DB air temperature, design and actual
g.
Leaving DB air temperature, design and actual
h.
Number of compressors
Cooling Coil Data:
a.
Identification/number
b.
Location
c.
Service
d.
Manufacturer
e.
Air flow, design and actual
f.
Entering air DB temperature, design and actual
g.
Entering air WB temperature, design and actual
h.
Leaving air DB temperature, design and actual
i.
Leaving air WB temperature, design and actual
j.
Saturated suction temperature, design and actual
k.
Air pressure drop, design and actual
Electric Duct Heater:
a.
Manufacturer
b.
Identification/number
c.
Location
d.
Model number
e.
Design kW
f.
Number of stages
g.
Phase, voltage, amperage
h.
Test voltage (each phase)
i.
Test amperage (each phase)
j.
Air flow, specified and actual
k.
Temperature rise, specified and actual
NCS Bloomfield Avenue Station
New Elevators
15950 - 6
9.
10.
11.
12.
Air Moving Equipment:
a.
Location
b.
Manufacturer
c.
Model number
d.
Serial number
e.
Arrangement/Class/Discharge
f.
Air flow, specified and actual
g.
Return air flow, specified and actual
h.
Outside air flow, specified and actual
i.
Total static pressure (total external), specified and actual
j.
Inlet pressure
k.
Discharge pressure
l.
Sheave Make/Size/Bore
m.
Number of Belts/Make/Size
n.
Fan RPM
Return Air/Outside Air Data:
a.
Identification/location
b.
Design air flow
c.
Actual air flow
d.
Design return air flow
e.
Actual return air flow
f.
Design outside air flow
g.
Actual outside air flow
h.
Return air temperature
i.
Outside air temperature
j.
Required mixed air temperature
k.
Actual mixed air temperature
l.
Design outside/return air ratio
m.
Actual outside/return air ratio
Exhaust Fan Data:
a.
Location
b.
Manufacturer
c.
Model number
d.
Serial number
e.
Air flow, specified and actual
f.
Total static pressure (total external), specified and actual
g.
Inlet pressure
h.
Discharge pressure
i.
Sheave Make/Size/Bore
j.
Number of Belts/Make/Size
k.
Fan RPM
Duct Traverse:
a.
System zone/branch
b.
Duct size
c.
Area
d.
Design velocity
e.
Design air flow
f.
Test velocity
NCS Bloomfield Avenue Station
New Elevators
15950 - 7
13.
14.
15.
16.
g.
Test air flow
h.
Duct static pressure
i.
Air temperature
j.
Air correction factor
Duct Leak Test:
a.
Description of ductwork under test
b.
Duct design operating pressure
c.
Duct design test static pressure
d.
Duct capacity, air flow
e.
Maximum allowable leakage duct capacity times leak factor
f.
Test apparatus
1)
Blower
2)
Orifice, tube size
3)
Orifice size
4)
Calibrated
g.
Test static pressure
h.
Test orifice differential pressure
i.
Leakage
Air Distribution Test Sheet:
a.
Air terminal number
b.
Room number/location
c.
Terminal type
d.
Terminal size
e.
Area factor
f.
Design velocity
g.
Design air flow
h.
Test (final) velocity
i.
Test (final) air flow
j.
Percent of design air flow
Sound Level Report:
a.
Location
b.
Octave bands - equipment off
c.
Octave bands - equipment on
d.
RC level - equipment on
Vibration Test:
a.
Location of points:
1)
Fan bearing, drive end
2)
Fan bearing, opposite end
3)
Motor bearing, center (when applicable)
4)
Motor bearing, drive end
5)
Motor bearing, opposite end
6)
Casing (bottom or top)
7)
Casing (side)
8)
Duct after flexible connection (discharge)
9)
Duct after flexible connection (suction)
b.
Test readings:
1)
Horizontal, velocity and displacement
2)
Vertical, velocity and displacement
NCS Bloomfield Avenue Station
New Elevators
15950 - 8
c.
d.
e.
3)
Axial, velocity and displacement
Normally acceptable readings, velocity and acceleration
Unusual conditions at time of test
Vibration source (when non-complying)
PART 4 COMPENSATION
4.1
MEASUREMENT AND PAYMENT
A.
Measurement: The work of this section shall not be measured.
B.
Payment: The cost of this section shall be included in the allowance for
TESTING, ADJUSTING AND BALANCING.
END OF SECTION
NCS Bloomfield Avenue Station
New Elevators
15950 - 9
Download