2023-08-30T22:30:22+03:00[Europe/Moscow] en true <p><strong>Source Range High Flux</strong></p>, <p><strong>Intermediate Range High Flux</strong></p>, <p><strong>Power Range Flux Low Setpoint</strong></p>, <p><strong>Power Range Flux High Setpoint</strong></p>, <p><strong>Power Range High Positive Rate</strong></p>, <p><strong>Power Range High Negative Rate</strong></p>, <p><strong>OTΔT</strong></p>, <p><strong>OPΔT</strong></p>, <p><strong>PZR Low Pressure</strong></p>, <p><strong>PZR High Pressure</strong></p>, <p><strong>PZR High Level</strong></p>, <p><strong>RCS Low Flow</strong></p>, <p><strong>RCP Under-voltage</strong></p>, <p><strong>RCP Under-frequency</strong></p>, <p><strong>SG Low Level</strong></p>, <p><strong>Turbine Trip</strong></p>, <p><strong>SI</strong></p>, <p><strong>General Warning</strong></p> flashcards
Trips

Trips

  • Source Range High Flux

    105 cps

    Startup Accident

  • Intermediate Range High Flux

    ~25%

    Startup Accident

  • Power Range Flux Low Setpoint

    25%

    Startup Accident

  • Power Range Flux High Setpoint

    109%

    Departure From Nucleate Boiling

  • Power Range High Positive Rate

    + 4% in 2 sec

    Rod Ejection

  • Power Range High Negative Rate

    - 4% in 2 sec

    Rod Drop

  • OTΔT

    110% ± penalties

    Departure From Nucleate Boiling

  • OPΔT

    110% - penalties

    Overpower

  • PZR Low Pressure

    1,940 psig

    Departure From Nucleate Boiling

  • PZR High Pressure

    2,385 psig

    RCS Integrity

  • PZR High Level

    92%

    RCS Integrity

  • RCS Low Flow

    89.9%

    Departure From Nucleate Boiling

  • RCP Under-voltage

    10,578 volts

    Departure From Nucleate Boiling

  • RCP Under-frequency

    57.2 Hz

    Departure From Nucleate Boiling

  • SG Low Level

    23.5%

    Loss of Heat Sink

  • Turbine Trip

    590 psig or 4 Valves

    Closed Loss of Heat Removal

  • SI

    2 trains

    LOCA or Steam Line Break

  • General Warning

    2/2

    Loss of Reactor Protection