2024-05-02T08:10:02+03:00[Europe/Moscow] en true <p>Considerations when judging electrical equipment include, but are not limited to, ? effects under normal conditions of use and also under abnormal conditions likely to arise</p><p>in service.</p><p></p><p>a. heating</p><p>b. intended</p><p>c. overcurrent</p><p>d. specific</p><p></p><p>NEC Reference</p>, <p>Listed or labeled equipment shall be ? and used in accordance with any instructions included in the listing or labeling.</p><p></p><p>a. built</p><p>b. installed</p><p>c. manufactured</p><p>d. setup</p><p></p><p>NEC Reference</p>, <p>Electrical equipment is required to be installed in a neat and workmanlike manner.</p><p></p><p>a. True</p><p>b. False</p><p></p><p>NEC Reference</p>, <p>Equipment must be acceptable to the authority having jurisdiction. An identifying label must always be attached to the equipment.</p><p></p><p>Select one:</p><p>True</p><p>False</p>, <p>Listed is defined, in part, as equipment, materials, or services included in a list published by an organization acceptable to ? .</p><p></p><p>a. IBEW/NECA</p><p>b.National Electrical Manufacturers Association (NEMA)</p><p>c.the authority having jurisdiction (AHJ)</p><p>d.the National Safety Council</p><p>e.Underwriters Laboratories (UL)</p>, <p>Equipment that is listed is published in a directory by an entity such as ? certifying that it has met established standards and is periodically reviewed to ensure standards compliance.</p><p>Select one:</p><p>a. NEMA</p><p>b. the manufacturer</p><p>c. the NEC</p><p>d. the testing laboratory</p>, <p>The NEC requirement that addresses installing equipment in a “neat and workmanlike manner” includes specific provisions for installations that are level, plumb, square, and adequately supported.</p><p></p><p>Select one:</p><p>True</p><p>False</p>, <p>Internal parts of electrical equipment, including busbars, wiring terminals, insulators, and other surfaces, shall not be damaged or contaminated by foreign materials such as ? .</p><p></p><p>a. abrasives</p><p>b. cleaners</p><p>c. corrosive residues</p><p>d. paint</p><p>e. plaster</p><p>f. all of the above</p><p></p><p>NEC Reference</p>, <p>NECA 1 defines the ? baseline of quality and workmanship for installing electrical products and systems.</p><p></p><p>a.benchmark</p><p>b.maximum</p><p>c.minimum</p><p>d.standard</p>, <p>The NECA 1 document describes what is meant by installing equipment in a “neat and workmanlike manner” as required in the NEC.</p><p></p><p>Select one:</p><p>True</p><p>False</p>, <p>NECA 1 indicates that if materials on a construction site are subject to water</p><p>accumulation, dirt, or dust, they must be protected by plastic wrapping and stored ? .</p><p></p><p>a.in jobsite portable metal containers</p><p>b.off-site in clean, dry, and heated warehouses</p><p>c.on a special poured concrete pad designed for such materials</p><p>d.on pallets or other means above the floor</p>, <p>According to NECA 1, a dry-type transformer, which has moisture sensitive insulation, must be stored in an area where the relative humidity is below ? at all times.</p><p></p><p>a.35%</p><p>b.75%</p><p>c.90%</p><p>d.100%</p>, <p>According to NECA 1, good workmanship shall be apparent in the installation of all electrical materials and equipment. Which fittings must be made up “tight” in accordance with the manufacturer’s and/or listing instructions?</p><p></p><p>I. Clamps</p><p>II. Connectors</p><p>III. Couplings</p><p>IV. Joints</p><p>V. Nuts</p><p>VI. Overcurrent devices</p><p>VII. Screws</p><p>VIII. Switches</p><p></p><p>a.I., II., III., IV., V., and VII</p><p>b.I., II., III., V., and VII.</p><p>c.I., V., VII., and VIII.</p><p>d.II., III., and IV.</p><p>e.IV., VI., and VIII.</p><p>f.All of the above</p>, <p>In accordance with NECA 1, all anchors must be of the type designed for the purpose and rated capable of adequately and safely securing the item to the base material. Corrosion from wet or damp locations, fumes, electrolytic action between dissimilar materials, etc. must be considered in accordance with NEC 300.6 for all installations.</p><p></p><p>Select one:</p><p>True</p><p>False</p>, <p>Per NECA 1, match all that apply to outlet boxes.</p><p></p><p>I. Before installing conductors, care must be taken to prevent entrance of foreign materials and all foreign matter must be cleared and removed.</p><p>II. Boxes for switches near doors shall be located on the opposite side of the hinge.</p><p>III. Covers larger than six feet square shall be hinged or sectionalized to facilitate removal and replacement.</p><p>IV. Hangers and supports shall be suitable for the type used.</p><p>V. It must be securely and rigidly attached or supported.</p><p>VI. When installed in concrete, it must occupy the middle third, when practical, and leave at least 3/4-inch concrete cover.</p><p></p><p>a.I., II., IV., and V.</p><p>b.I., II., V., and VI.</p><p>c.I., III., and V.</p><p>d.II., III., IV., and V.</p>, <p>Per NECA 1, match all that apply to junction and pull boxes.</p><p></p><p>I. Before installing conductors, care must be taken to prevent entrance of foreign materials and all foreign matter must be cleared and removed.</p><p>II. Covers larger than six feet square shall be hinged or sectionalized to facilitate removal and replacement.</p><p>III. Hangers and supports shall be suitable for the type used.</p><p>IV. It must be located near the door on the opposite side of the hinge.</p><p>V. It must be securely and rigidly attached or supported.</p><p>VI. When installed in concrete, it must occupy the middle third, when practical, and leave at least 3/4-inch concrete cover.</p><p></p><p>a.I., II., and V.</p><p>b.I., III., V., and VI.</p><p>c.I., IV., V., and VI.</p><p>d.II., III., and V.</p><p>e.II., III., IV., and V.</p>, <p>In accordance with NECA 1, match all that may apply to raceways.</p><p></p><p>I. Before installing conductors, care must be taken to prevent entrance of foreign materials and all foreign matter must be cleared and removed.</p><p>II. Covers larger than six feet square shall be hinged or sectionalized to facilitate removal and replacement.</p><p>III. Hangers and supports shall be suitable for the type used.</p><p>IV. It must be located near the door on the opposite side of the hinge.</p><p>V. It must be securely and rigidly attached or supported.</p><p>VI. When installed in concrete, it must occupy the middle third, when practical, and leave at least 3/4-inch concrete cover.</p><p></p><p>a.I., II., and V.</p><p>b.I., III., IV., and V.</p><p>c.I., III., V., and VI.</p><p>d.I., IV., V., and VI.</p><p>e.II., III., IV., and V.</p>, <p>As indicated in NECA 1, what is the spacing of conduit support requirement of an exposed vertical run of 1 1/4 -inch rigid metal conduit (RMC)?</p><p></p><p>a.5'</p><p>b.7'</p><p>c.8'</p><p>d.10'</p>, <p>Do the spacing of conduit support requirements in NECA 1 differ from those in the NEC?</p><p></p><p>a.Yes</p><p>b.No</p>, <p>Electrical equipment shall be firmly secured to the surface on which it is mounted.</p><p></p><p>a. True</p><p>b. False</p><p></p><p>NEC Reference</p>, <p>In accordance with NECA 1, the mounting height of a telephone outlet is ? .</p><p></p><p>a.18"</p><p>b.24"</p><p>c.36"</p><p>d.42"</p>, <p>Per NECA 1, the mounting height of a fire alarm horn is ? .</p><p></p><p>a.42"</p><p>b.48"</p><p>c.80"</p><p>d.84"</p>, <p>Per NECA 1, the mounting height of a general use wall receptacle outlet is ? .</p><p></p><p>a.18"</p><p>b.24"</p><p>c.36"</p><p>d.42"</p>, <p>NECA 1 indicates that the mounting height of a wall lighting outlet is to be ? .</p><p></p><p>a.42"</p><p>b.48"</p><p>c.80"</p><p>d.84"</p>, <p>Listed is defined, in part, as equipment, materials, or services included in a list published by an organization acceptable to the authority having jurisdiction.</p><p></p><p>Select one:</p><p>True</p><p>False</p>, <p>Many of the products bearing the UL Mark incorporate ? bearing the UL Recognized Component Mark. That Mark ? provide evidence of listing or labeling which may be required by installation codes or standards.</p><p></p><p>a.components / does not</p><p>b.the company name / does</p><p>c.the trade name / does not</p><p>d.the trademark / does</p>, <p>The term ? is defined as “acceptable to the authority having jurisdiction.”</p><p></p><p>a.approved</p><p>b.compliant</p><p>c.labeled</p><p>d.listed</p>, <p>The NEC requires all material and equipment to be listed.</p><p></p><p>Select one:</p><p>True</p><p>False</p>, <p>The UL Listed Mark provides evidence of listing or labeling that may be required by installation codes or standards.</p><p></p><p>Select one:</p><p>True</p><p>False</p>, <p>Where the NEC does require listing, the equipment shall be installed and used in accordance with the ? the equipment.</p><p></p><p>a.industry standards for</p><p>b.instructions supplied with</p><p>c.specifications supplied to the testing lab by the manufacturer of</p><p>d.type and size of</p>, <p>UL's Field Evaluation Service covers on-site safety evaluations of installed products or systems conducted by UL technical staff. UL's Field Evaluation Product Mark can be applied to the product in the ? , if the product complies with the UL's requirements.</p><p></p><p>a.field</p><p>b.manufacturer's lab</p><p>c.UL lab</p><p>d.all of the above</p>, <p>With UL's Classification Service, UL determines that a manufacturer has demonstrated the ability to produce a product that complies with its requirements for the purpose of classification or evaluation regarding which of the following?</p><p></p><p>a.Field testing performance data</p><p>b.Manufacturer requirements for construction</p><p>c.Performance under specified conditions</p><p>d.Standards determined by council</p>, <p>A(n) ? marking is a European marking of conformity indicating that a product complies with the essential requirements of the applicable European laws or directives with respect to safety, health, environment, and consumer protection.</p><p></p><p>a.CE</p><p>b.CSA</p><p>c.EEA</p><p>d.UL</p> flashcards
Code Standards Lesson 4

Code Standards Lesson 4

  • Considerations when judging electrical equipment include, but are not limited to, ? effects under normal conditions of use and also under abnormal conditions likely to arise

    in service.

    a. heating

    b. intended

    c. overcurrent

    d. specific

    NEC Reference

    The correct answer is: heating

    The correct answer is: 110.3(A)(5)

  • Listed or labeled equipment shall be ? and used in accordance with any instructions included in the listing or labeling.

    a. built

    b. installed

    c. manufactured

    d. setup

    NEC Reference

    The correct answer is: installed

    The correct answer is: 110.3(B)

  • Electrical equipment is required to be installed in a neat and workmanlike manner.

    a. True

    b. False

    NEC Reference

    The correct answer is: True

    The correct answer is: 110.12

  • Equipment must be acceptable to the authority having jurisdiction. An identifying label must always be attached to the equipment.

    Select one:

    True

    False

    The correct answer is 'False'.

  • Listed is defined, in part, as equipment, materials, or services included in a list published by an organization acceptable to ? .

    a. IBEW/NECA

    b.National Electrical Manufacturers Association (NEMA)

    c.the authority having jurisdiction (AHJ)

    d.the National Safety Council

    e.Underwriters Laboratories (UL)

    The correct answer is: the authority having jurisdiction (AHJ)

  • Equipment that is listed is published in a directory by an entity such as ? certifying that it has met established standards and is periodically reviewed to ensure standards compliance.

    Select one:

    a. NEMA

    b. the manufacturer

    c. the NEC

    d. the testing laboratory

    The correct answer is: the testing laboratory

  • The NEC requirement that addresses installing equipment in a “neat and workmanlike manner” includes specific provisions for installations that are level, plumb, square, and adequately supported.

    Select one:

    True

    False

    The correct answer is 'False'.

  • Internal parts of electrical equipment, including busbars, wiring terminals, insulators, and other surfaces, shall not be damaged or contaminated by foreign materials such as ? .

    a. abrasives

    b. cleaners

    c. corrosive residues

    d. paint

    e. plaster

    f. all of the above

    NEC Reference

    The correct answer is: all of the above

    The correct answer is: 110.12(B)

  • NECA 1 defines the ? baseline of quality and workmanship for installing electrical products and systems.

    a.benchmark

    b.maximum

    c.minimum

    d.standard

    The correct answer is: minimum

  • The NECA 1 document describes what is meant by installing equipment in a “neat and workmanlike manner” as required in the NEC.

    Select one:

    True

    False

    The correct answer is 'True'.

  • NECA 1 indicates that if materials on a construction site are subject to water

    accumulation, dirt, or dust, they must be protected by plastic wrapping and stored ? .

    a.in jobsite portable metal containers

    b.off-site in clean, dry, and heated warehouses

    c.on a special poured concrete pad designed for such materials

    d.on pallets or other means above the floor

    The correct answer is: on pallets or other means above the floor

  • According to NECA 1, a dry-type transformer, which has moisture sensitive insulation, must be stored in an area where the relative humidity is below ? at all times.

    a.35%

    b.75%

    c.90%

    d.100%

    The correct answer is: 75%

  • According to NECA 1, good workmanship shall be apparent in the installation of all electrical materials and equipment. Which fittings must be made up “tight” in accordance with the manufacturer’s and/or listing instructions?

    I. Clamps

    II. Connectors

    III. Couplings

    IV. Joints

    V. Nuts

    VI. Overcurrent devices

    VII. Screws

    VIII. Switches

    a.I., II., III., IV., V., and VII

    b.I., II., III., V., and VII.

    c.I., V., VII., and VIII.

    d.II., III., and IV.

    e.IV., VI., and VIII.

    f.All of the above

    The correct answer is: I., II., III., V., and VII.

  • In accordance with NECA 1, all anchors must be of the type designed for the purpose and rated capable of adequately and safely securing the item to the base material. Corrosion from wet or damp locations, fumes, electrolytic action between dissimilar materials, etc. must be considered in accordance with NEC 300.6 for all installations.

    Select one:

    True

    False

    The correct answer is 'True'.

  • Per NECA 1, match all that apply to outlet boxes.

    I. Before installing conductors, care must be taken to prevent entrance of foreign materials and all foreign matter must be cleared and removed.

    II. Boxes for switches near doors shall be located on the opposite side of the hinge.

    III. Covers larger than six feet square shall be hinged or sectionalized to facilitate removal and replacement.

    IV. Hangers and supports shall be suitable for the type used.

    V. It must be securely and rigidly attached or supported.

    VI. When installed in concrete, it must occupy the middle third, when practical, and leave at least 3/4-inch concrete cover.

    a.I., II., IV., and V.

    b.I., II., V., and VI.

    c.I., III., and V.

    d.II., III., IV., and V.

    The correct answer is: I., II., IV., and V.

  • Per NECA 1, match all that apply to junction and pull boxes.

    I. Before installing conductors, care must be taken to prevent entrance of foreign materials and all foreign matter must be cleared and removed.

    II. Covers larger than six feet square shall be hinged or sectionalized to facilitate removal and replacement.

    III. Hangers and supports shall be suitable for the type used.

    IV. It must be located near the door on the opposite side of the hinge.

    V. It must be securely and rigidly attached or supported.

    VI. When installed in concrete, it must occupy the middle third, when practical, and leave at least 3/4-inch concrete cover.

    a.I., II., and V.

    b.I., III., V., and VI.

    c.I., IV., V., and VI.

    d.II., III., and V.

    e.II., III., IV., and V.

    The correct answer is: II., III., and V.

  • In accordance with NECA 1, match all that may apply to raceways.

    I. Before installing conductors, care must be taken to prevent entrance of foreign materials and all foreign matter must be cleared and removed.

    II. Covers larger than six feet square shall be hinged or sectionalized to facilitate removal and replacement.

    III. Hangers and supports shall be suitable for the type used.

    IV. It must be located near the door on the opposite side of the hinge.

    V. It must be securely and rigidly attached or supported.

    VI. When installed in concrete, it must occupy the middle third, when practical, and leave at least 3/4-inch concrete cover.

    a.I., II., and V.

    b.I., III., IV., and V.

    c.I., III., V., and VI.

    d.I., IV., V., and VI.

    e.II., III., IV., and V.

    The correct answer is: I., III., V., and VI.

  • As indicated in NECA 1, what is the spacing of conduit support requirement of an exposed vertical run of 1 1/4 -inch rigid metal conduit (RMC)?

    a.5'

    b.7'

    c.8'

    d.10'

    The correct answer is: 8'

  • Do the spacing of conduit support requirements in NECA 1 differ from those in the NEC?

    a.Yes

    b.No

    The correct answer is: Yes

  • Electrical equipment shall be firmly secured to the surface on which it is mounted.

    a. True

    b. False

    NEC Reference

    The correct answer is: True

    The correct answer is: 110.13(A)

  • In accordance with NECA 1, the mounting height of a telephone outlet is ? .

    a.18"

    b.24"

    c.36"

    d.42"

    The correct answer is: 18"

  • Per NECA 1, the mounting height of a fire alarm horn is ? .

    a.42"

    b.48"

    c.80"

    d.84"

    The correct answer is: 80"

  • Per NECA 1, the mounting height of a general use wall receptacle outlet is ? .

    a.18"

    b.24"

    c.36"

    d.42"

    The correct answer is: 18"

  • NECA 1 indicates that the mounting height of a wall lighting outlet is to be ? .

    a.42"

    b.48"

    c.80"

    d.84"

    The correct answer is: 84"

  • Listed is defined, in part, as equipment, materials, or services included in a list published by an organization acceptable to the authority having jurisdiction.

    Select one:

    True

    False

    The correct answer is 'True'.

  • Many of the products bearing the UL Mark incorporate ? bearing the UL Recognized Component Mark. That Mark ? provide evidence of listing or labeling which may be required by installation codes or standards.

    a.components / does not

    b.the company name / does

    c.the trade name / does not

    d.the trademark / does

    The correct answer is: components / does not

  • The term ? is defined as “acceptable to the authority having jurisdiction.”

    a.approved

    b.compliant

    c.labeled

    d.listed

    The correct answer is: approved

  • The NEC requires all material and equipment to be listed.

    Select one:

    True

    False

    The correct answer is 'False'.

  • The UL Listed Mark provides evidence of listing or labeling that may be required by installation codes or standards.

    Select one:

    True

    False

    The correct answer is 'True'.

  • Where the NEC does require listing, the equipment shall be installed and used in accordance with the ? the equipment.

    a.industry standards for

    b.instructions supplied with

    c.specifications supplied to the testing lab by the manufacturer of

    d.type and size of

    The correct answer is: instructions supplied with

  • UL's Field Evaluation Service covers on-site safety evaluations of installed products or systems conducted by UL technical staff. UL's Field Evaluation Product Mark can be applied to the product in the ? , if the product complies with the UL's requirements.

    a.field

    b.manufacturer's lab

    c.UL lab

    d.all of the above

    The correct answer is: field

  • With UL's Classification Service, UL determines that a manufacturer has demonstrated the ability to produce a product that complies with its requirements for the purpose of classification or evaluation regarding which of the following?

    a.Field testing performance data

    b.Manufacturer requirements for construction

    c.Performance under specified conditions

    d.Standards determined by council

    The correct answer is: Performance under specified conditions

  • A(n) ? marking is a European marking of conformity indicating that a product complies with the essential requirements of the applicable European laws or directives with respect to safety, health, environment, and consumer protection.

    a.CE

    b.CSA

    c.EEA

    d.UL

    The correct answer is: CE