2024-05-02T21:23:22+03:00[Europe/Moscow] en true <p>Which UL Standard is required to be used by qualified electrical testing laboratories to</p><p>evaluate snap switches for electrical safety?</p><p></p><p>a.UL 20</p><p>b.UL 467</p><p>c.UL 498</p><p>d.UL 891</p>, <p>A motor circuit switch is generally required to be rated in ? .</p><p></p><p>a.amperes</p><p>b.horsepower</p><p>c.locked rotor amperes</p><p>d.voltage and short-circuit current</p>, <p>General-use dimmer switches shall be used to control ? unless listed for the control of</p><p>other loads and installed accordingly.</p><p></p><p>a.ceiling-suspended paddle fans</p><p>b.fluorescent luminaires</p><p>c.permanently installed incandescent luminaires</p><p>d.standard duplex or single receptacles</p>, <p>Where the white or gray conductor of a cable assembly is used as a switch loop for circuits of 50 volts or more, the switch loop must be permanently reidentified as an ungrounded conductor by ? .</p><p></p><p>a.an effective means of any color</p><p>b.marking tape, painting, or other effective means of a color other than white, gray, or</p><p>green</p><p>c.the use of gray or white paint</p><p>d.the use of gray or white tape</p>, <p>The white or gray conductor of a cable assembly, where used in switch loop wiring, is not permitted to be used as a ? .</p><p></p><p>a.return conductor from a switch to a switched outlet</p><p>b.supply side of single pole switch</p><p>c.supply side (point wire) of a 3-way switch</p><p>d.none of the above</p>, <p>A general-use snap switch used to supply a one-horsepower motor shall be permitted to</p><p>control a load of not greater than ? .</p><p></p><p>a.50% of the rating of the switch</p><p>b.80% of the ampere rating of the switch</p><p>c.100% of the rating of the switch</p><p>d.125% of the switch</p>, <p>Where switches or other devices are ganged in a four-gang box, and the voltage between adjacent switches exceeds 300 volts, which of the following is required?</p><p></p><p>a.Each switch requires its own device box.</p><p>b.Electrical tape is required around the device terminals.</p><p>c.Permanently installed barriers are required between adjacent devices.</p><p>d.Switches without screw terminals are required to be used.</p>, <p>Switches are required to be marked in accordance with which of the following?</p><p></p><p>a.Hospital grade when used at patient bed locations in a critical-care area</p><p>b.Ivory in color</p><p>c.To indicate the load they serve</p><p>d.Voltage and current ratings</p>, <p>Generally, multipole switches are permitted for use only on ? circuits unless listed and marked for other than single circuit use.</p><p></p><p>a.277 V</p><p>b.480 V</p><p>c.multiple circuits where clearly identified in the field</p><p>d.single</p>, <p>? are generally required to be grounded.</p><p></p><p>a.Dimmer switches</p><p>b.Fan controls and other similar switch controls</p><p>c.Snap switches</p><p>d.All of the above</p>, <p>Switch faceplates made of nonmetallic (insulating), noncombustible material must generally not be less than ? in thickness.</p><p></p><p>a.0.76 mm (0.030")</p><p>b.1.02 mm (0.040")</p><p>c.2.54 mm (0.100")</p>, <p>Where a snap switch is marked “CO/ALR,” it is suitable for use with which of the following</p><p>types of conductors?</p><p></p><p>a.Aluminum conductors</p><p>b.Copper conductor</p><p>c.Copper-clad aluminum conductors</p><p>d.All of the above</p>, <p>Snap switches with “push-in” terminal connection means are permitted for use with ? conductors.</p><p></p><p>a.aluminum</p><p>b.solid copper</p><p>c.stranded aluminum</p><p>d.stranded copper</p>, <p>Switches marked with an off position are required to ? .</p><p></p><p>a.be capable of being locked in the open position</p><p>b.completely disconnect all ungrounded conductors to the load they control</p><p>c.partially disconnect the load they control</p><p>d.none of the above</p>, <p>A general-use dimmer switch is required to be counted as ? where installed in a singlegang box on a circuit wired with 12 AWG copper conductors.</p><p></p><p>a.1 conductor (2.25 in.^3 total)</p><p>b.2 conductors (4.00 in.^3 total)</p><p>c.2 conductors (4.50 in.^3 total)</p><p>d.3 conductors (2.25 in.^3 total)</p>, <p>A 3-pole, general-use snap switch is generally permitted to be used to control ? .</p><p></p><p>a.multiple branch circuit where rated for the voltage applied</p><p>b.multiple circuits where marked “three-circuit”</p><p>c.3 circuits, all of different voltages</p><p>d.3 separate circuits where properly rated</p>, <p>What is the minimum size copper equipment grounding conductor required for a 20- ampere lighting circuit?</p><p></p><p>a.14 AWG</p><p>b.12 AWG</p><p>c.10 AWG</p><p>d.8 AWG</p>, <p>What is the minimum size equipment bonding jumper required to be connected from a grounding terminal on a switch for a neon tubing outline lighting circuit protected at 30 amperes?</p><p></p><p>a.14 AWG copper</p><p>b.12 AWG aluminum</p><p>c.12 AWG copper</p><p>d.10 AWG copper</p>, <p>? locations in a dwelling unit do not require a switch-controlled lighting outlet.</p><p></p><p>a.Attached garage</p><p>b.Bathroom</p><p>c.Clothes closet</p><p>d.Kitchen</p>, <p>Where an attic space contains equipment that requires servicing, such as an air conditioner, where is the switch for the required lighting outlet to be located?</p><p></p><p>a.At the air conditioner</p><p>b.At the usual point of entry to the attic</p><p>c.In the closet (where equipped with a pilot light)</p><p>d.In the garage</p>, <p>Where a neon transformer for a sign is installed in a soffit location, where is the switch controlled lighting outlet required to be located?</p><p></p><p>a.At or near the transformer(s)</p><p>b.At the stairway below the access panel</p><p>c.At the usual point of entry to the space</p><p>d.On the roof</p> flashcards

Code Standards Lesson 11

da finale

  • Which UL Standard is required to be used by qualified electrical testing laboratories to

    evaluate snap switches for electrical safety?

    a.UL 20

    b.UL 467

    c.UL 498

    d.UL 891

    The correct answer is: UL 20

  • A motor circuit switch is generally required to be rated in ? .

    a.amperes

    b.horsepower

    c.locked rotor amperes

    d.voltage and short-circuit current

    The correct answer is: horsepower

  • General-use dimmer switches shall be used to control ? unless listed for the control of

    other loads and installed accordingly.

    a.ceiling-suspended paddle fans

    b.fluorescent luminaires

    c.permanently installed incandescent luminaires

    d.standard duplex or single receptacles

    The correct answer is: permanently installed incandescent luminaires

  • Where the white or gray conductor of a cable assembly is used as a switch loop for circuits of 50 volts or more, the switch loop must be permanently reidentified as an ungrounded conductor by ? .

    a.an effective means of any color

    b.marking tape, painting, or other effective means of a color other than white, gray, or

    green

    c.the use of gray or white paint

    d.the use of gray or white tape

    The correct answer is: marking tape, painting, or other effective means of a color other

    than white, gray, or green

  • The white or gray conductor of a cable assembly, where used in switch loop wiring, is not permitted to be used as a ? .

    a.return conductor from a switch to a switched outlet

    b.supply side of single pole switch

    c.supply side (point wire) of a 3-way switch

    d.none of the above

    The correct answer is: return conductor from a switch to a switched outlet

  • A general-use snap switch used to supply a one-horsepower motor shall be permitted to

    control a load of not greater than ? .

    a.50% of the rating of the switch

    b.80% of the ampere rating of the switch

    c.100% of the rating of the switch

    d.125% of the switch

    The correct answer is: 80% of the ampere rating of the switch

  • Where switches or other devices are ganged in a four-gang box, and the voltage between adjacent switches exceeds 300 volts, which of the following is required?

    a.Each switch requires its own device box.

    b.Electrical tape is required around the device terminals.

    c.Permanently installed barriers are required between adjacent devices.

    d.Switches without screw terminals are required to be used.

    The correct answer is: Permanently installed barriers are required between adjacent

    devices.

  • Switches are required to be marked in accordance with which of the following?

    a.Hospital grade when used at patient bed locations in a critical-care area

    b.Ivory in color

    c.To indicate the load they serve

    d.Voltage and current ratings

    The correct answer is: Voltage and current ratings

  • Generally, multipole switches are permitted for use only on ? circuits unless listed and marked for other than single circuit use.

    a.277 V

    b.480 V

    c.multiple circuits where clearly identified in the field

    d.single

    The correct answer is: single

  • ? are generally required to be grounded.

    a.Dimmer switches

    b.Fan controls and other similar switch controls

    c.Snap switches

    d.All of the above

    The correct answer is: All of the above

  • Switch faceplates made of nonmetallic (insulating), noncombustible material must generally not be less than   ?   in thickness.a.0.76 mm (0.030")b.1.02 mm (0.040")c.2.54 mm (0.100")

    Switch faceplates made of nonmetallic (insulating), noncombustible material must generally not be less than ? in thickness.

    a.0.76 mm (0.030")

    b.1.02 mm (0.040")

    c.2.54 mm (0.100")

    The correct answer is: 2.54 mm (0.100")

  • Where a snap switch is marked “CO/ALR,” it is suitable for use with which of the following

    types of conductors?

    a.Aluminum conductors

    b.Copper conductor

    c.Copper-clad aluminum conductors

    d.All of the above

    The correct answer is: All of the above

  • Snap switches with “push-in” terminal connection means are permitted for use with ? conductors.

    a.aluminum

    b.solid copper

    c.stranded aluminum

    d.stranded copper

    The correct answer is: solid copper

  • Switches marked with an off position are required to ? .

    a.be capable of being locked in the open position

    b.completely disconnect all ungrounded conductors to the load they control

    c.partially disconnect the load they control

    d.none of the above

    The correct answer is: completely disconnect all ungrounded conductors to the load they

    control

  • A general-use dimmer switch is required to be counted as   ?   where installed in a singlegang box on a circuit wired with 12 AWG copper conductors.a.1 conductor (2.25 in.^3 total)b.2 conductors (4.00 in.^3 total)c.2 conductors (4.50 in.^3 total)d.3 conductors (2.25 in.^3 total)

    A general-use dimmer switch is required to be counted as ? where installed in a singlegang box on a circuit wired with 12 AWG copper conductors.

    a.1 conductor (2.25 in.^3 total)

    b.2 conductors (4.00 in.^3 total)

    c.2 conductors (4.50 in.^3 total)

    d.3 conductors (2.25 in.^3 total)

    The correct answer is: 2 conductors (4.50 in.^3 total)

  • A 3-pole, general-use snap switch is generally permitted to be used to control ? .

    a.multiple branch circuit where rated for the voltage applied

    b.multiple circuits where marked “three-circuit”

    c.3 circuits, all of different voltages

    d.3 separate circuits where properly rated

    The correct answer is: multiple circuits where marked “three-circuit”

  • What is the minimum size copper equipment grounding conductor required for a 20- ampere lighting circuit?

    a.14 AWG

    b.12 AWG

    c.10 AWG

    d.8 AWG

    The correct answer is: 12 AWG

  • What is the minimum size equipment bonding jumper required to be connected from a grounding terminal on a switch for a neon tubing outline lighting circuit protected at 30 amperes?

    a.14 AWG copper

    b.12 AWG aluminum

    c.12 AWG copper

    d.10 AWG copper

    The correct answer is: 10 AWG copper

  • ? locations in a dwelling unit do not require a switch-controlled lighting outlet.

    a.Attached garage

    b.Bathroom

    c.Clothes closet

    d.Kitchen

    The correct answer is: Clothes closet

  • Where an attic space contains equipment that requires servicing, such as an air conditioner, where is the switch for the required lighting outlet to be located?

    a.At the air conditioner

    b.At the usual point of entry to the attic

    c.In the closet (where equipped with a pilot light)

    d.In the garage

    The correct answer is: At the usual point of entry to the attic

  • Where a neon transformer for a sign is installed in a soffit location, where is the switch controlled lighting outlet required to be located?

    a.At or near the transformer(s)

    b.At the stairway below the access panel

    c.At the usual point of entry to the space

    d.On the roof

    The correct answer is: At or near the transformer(s)