B322 WATER PLANT PROGRAMMABLE LOGIC CONTROLLER REQUIREMENTS DOCUMENT PREPARED BY: ROBERT SPLINTER, MARK JOHNSON COMPUTER SCIENCE CORPORATION FOR: JUAN ETHERIDGE NATIONAL AERONAUTICS AND SPACE ADMINISTRATION JOHNSON SPACE CENTER 14 JUL 10 2101 NASA PARKWAY HOUSTON, TEXAS 77058 PLC REQUIREMENTS FOR B322 PLC July 14, 2010 Rev. A PURPOSE 1.1 This document is intended to describe the general operating guidelines and the interconnections required for the Programmable Logic Controller (PLC) that will be installed in B322 Johnson Space Center (JSC), Houston, Texas. 2 INCLUSIONS 2.1 The following items are included in this document Description of System Requirements for Operations Vendor Requirements Appendix A: Wirelists Appendix B: Water Tower Technical Data Appendix C: PLC and Existing I/O Configuration Page 2 of 8 PLC REQUIREMENTS FOR B322 PLC July 14, 2010 Rev. A 3 DESCRIPTION OF SYSTEM 3.1 The PLC shall provide controls to the four electric booster pumps and their associated control valves in the B322 Water Plant of JSC. It shall monitor the status of various water level switches and provide both automatic and manual start/stop commands to the system booster pumps and associated control valves. 3.2 The PLC shall provide on/off controls for local street lights located in the vicinity of B322. Details are provided in Section 4.2. 3.3 The PLC shall provide on/off controls for local water well pumps number 304 and 303. (new) 3.4 The PLC shall provide monitoring for the Johnson Space Center Site Pulse Gas Meter. 3.5 The PLC shall be a Allen-Bradley Logix5561, Model # 1756-L61, with a PanelView Plus 1500 touchscreen to communicate data and control the PLC. Included I/O shall be at least equivalent to the existing I/O. Additional information is included in Appendix C. 3.6 The PLC shall interface with Honeywell’s Enterprise Building Integrator (EBI), using MODBUS as the existing communication protocol. Two sets of twisted pair communication wires are provided. The PLC will also have Ethernet capability built in. 4 REQUIREMENTS FOR OPERATIONS 4.1 Domestic Water Booster Pump Operation 4.1.1 The PLC shall provide the controls and decision logic as required by this document. The logic shall be completely contained within the PLC. The PLC shall be operable in both automatic and manual override modes (operator manual operation). 4.1.2 The PLC shall monitor the points listed in Appendix A. The booster pump start levels are: TD1: 158.8ft TD2: 157.1ft TD3: 155.7ft Page 3 of 8 PLC REQUIREMENTS FOR B322 PLC July 14, 2010 Rev. A If the third booster pump remains on for sixty seconds, the PLC shall then issue the command to start the fourth pump. See Appendix B for more details. 4.1.3 When TD1 closes at 158.8 ft, it will signal the PLC to start a booster pump. The normal booster pump start sequence is: #1, #4, #2 and #5, but shall be configurable in the field by a trained operator. The PLC shall look for the following booster pump start criteria: A Pump which has electrical power A pump in AUTO A pump that is NOT running The associated control valve must be closed When it finds a pump that meets all the criteria, it will signal that booster pump to start and open the associated valve. If a booster pump is not available, it will move on to the next available pump. If a booster pump meets the above criteria, but does not start after 20 seconds, the PLC should turn off the failed unit, close the valve, and attempt to start the next available pump. In manual mode, the operator shall have full choice of which booster pump to start and valve to open, as long as the above criteria are satisfied. 4.1.4 A PanelView Plus 1500 touchscreen shall also be provided, and shall provide accurate, concise information to the operator as to the current status of the electric pumps and control valves. The display should provide adequate illumination under existing room lighting. See Appendix C for additional information. 4.1.5 The display shall also provide booster pump and valve selection capability to the operator. 4.1.6 Examples of Operation 4.1.6.1 For example, if Pump #1 was not in AUTO the PLC would recognize that and go to Pump #4. If Pump #4 met all the criteria, the PLC would signal it to start. If the level in the elevated storage tank continued to fall, TD2 would signal the PLC to start another pump at 157.1 ft. Again the PLC would follow the same sequence and criteria and start a second pump. When the level falls to 155.7 ft TD3 would signal the PLC to start a third pump. If TD3 remained energized for 60 seconds, it would signal to PLC to start another pump. This time the PLC does not consider if the pump is already running, it will simply signal Pump #5 to start. 4.2 Street Light Operation 4.2.1 The PLC shall also control and monitor the street lights located in the vicinity of B322. The on/off command is provided by Honeywell’s Enterprise Building Page 4 of 8 PLC REQUIREMENTS FOR B322 PLC July 14, 2010 Rev. A Integrator (EBI). The PLC will issue the command to the field devices through the single discrete output and monitor current usage. 4.2.2 The PLC shall provide status and amperage data back to: Honeywell via MODBUS and enable capability for Ethernet The operator, through the use of the display unit 4.3 Gas Meter Monitoring 4.3.1 The PLC shall monitor the pulse gas meter input, and accumulate gas usage data for output to: Honeywell via MODBUS and enable capability for Ethernet The operator, through the use of the display unit 5 VENDOR REQUIREMENTS The vendor shall provide, as a minimum, the following items: 1) An Allen Bradley PLC, with all associated components and standard accessories, as listed in Appendix C; 2) A display unit, with all associated components and standard accessories, as listed in Appendix C; 3) Detailed ladder logic diagrams, showing the relationships between inputs and outputs; 4) Two copies of the developed software on CD-ROM, along with two hardcopy printed versions, which are well-commented; 5) Any additional required software or hardware to enable JSC technicians and engineers access to the PLC hardware or software for future maintenance tasks or testing; 6) Training for JSC technicians and operators on the new PLC shall be in accordance with RFQ 09-860, Water Plant Upgrade, B319, Rev. 1. Page 5 of 8 PLC REQUIREMENTS FOR B322 PLC July 14, 2010 Rev. A APPENDIX A: Wirelist Discrete I/O: Microsoft Office Excel 2003 Worksheet Analog I/O: Microsoft Office Excel 2003 Worksheet Additional I/O: Microsoft Office Excel 2003 Worksheet Page 6 of 8 PLC REQUIREMENTS FOR B322 PLC July 14, 2010 Rev. A APPENDIX B: Water Tower Technical Data APPROX WATER VOLUME IN GAL WATER LEVEL (x1000). FEET HEAD ABOVE GROUND 240 163.6 Top of Tank 20.0 100.0 9.00 240 161.6 Probe high level P.T. 20.0 100.0 7.00 240 161.0 System overflows 18.9 93.0 6.50 239 160.8 High Alarm ON 18.4 90.0 6.30 CLOSE 238 160.5 1st boosting mode OFF 17.7 85.0 6.00 OPEN 235 160.0 High Alarm OFF 16.6 79.0 5.50 228 159.0 2nd boosting mode OFF 14.3 64.0 4.50 226 158.8 1st boosting mode ON 13.8 61.0 4.30 218 157.7 3rd boosting mode OFF 11.3 45.5 3.20 214 157.1 2nd boosting mode ON 10.1 38.0 2.67 CLOSE 202 155.7 3rd boosting mode ON 6.9 18.0 1.27 CLOSE 199 155.4 Low Alarm OFF 6.1 7.8 0.93 195 155.0 Low Alarm ON 5.0 6.4 0.44 190 154.6 Probe low level P.T. 4.0 0.0 0.00 OPERATION mA DC SIGNAL PERCENT OF TOTAL (%) FEET PROBE SUBMERGED IN WATER Page 7 of 8 FALLING RISING OPEN OPEN CLOSE OPEN OPEN CLOSE PLC REQUIREMENTS FOR B322 PLC July 14, 2010 Rev. A APPENDIX C: Existing I/O and PLC Configuration Tables MODICON I/O Model # Description # of Modules Total Points ADU 206 4-point, Voltage/Current Isolated Analog Input Module 4 16 DAP 208 8-point, 24-110 VDC/24-250 VAC Relay Output Module 5 40 DAU 204 4-point, 24 VDC Voltage/Current Analog Output Module 3 12 DEP 216 16-point, 24 VDC Discrete Input Module 2 32 DEP 218 16-point, 155 VAC Discrete Input Module 4 64 I/O Product Description MFR Model # Quantity Comments Logix5561 Processor Allen Bradley 1756-L61 1 Required Touchscreen Allen Bradley PanelView Plus 1500 1 Required 17 Slot ControlLogix Chassis Allen Bradley 1756-A17 TBD 85-265 VAC Redundant Power Supply Allen Bradley 1756-PAR2 TBD CLX Ethernet/IP 10/100 Bridge Module Allen Bradley 1756-ENBT 1 Required Analog Input – I/V 8 Pts Allen Bradley 1756-IF8 TBD Analog Input Analog Output – I/V 8Pts Allen Bradley 1756-OF8 TBD Analog Ouput 10-30 VAC Input 16 Pts Allen Bradley 1756-IA16 TBD Discrete Input, 120VAC 10-30 VAC Output 8 Pts Allen Bradley 1756-ON8 TBD Discrete Output 24VAC 4 Slot Rack Allen Bradley 1771-A1B TBD 16 Slot Rack Allen Bradley 1771-A4B TBD Power Supply Allen Bradley Advanced Interface Converter Allen Bradley A/B 700-HC54Z24-4 Relay with 700-HN103 Base Allen Bradley TBD 1761-NET-AIC 1 TBD PLC Components Page 8 of 8 Required