Bapuji S Palki, INCRC/PowerTechnologies, 15-11-2009 Protection Application – An Overview Part 2A © ABB Group March 22, 2016 | Slide 1 © ABB Group March 22, 2016 | Slide 2 Layouts Typical Parts of a Power Plant Substation Busbar in Substation HV - Breaker Power plant Main Transformer Auxiliary Transformer Generator Breaker Excitation Transformer Excitation System Turbine valve Turbine - Generator Earthing System G Field Circuit Breaker Generator Protection Possible Faults Stator Earth Faults Rotor Earth Faults Stator Short Circuits Stator/Rotor Interturn faults External faults Generator Protection Abnormal Operating Condition overcurrent/overload unbalanced load overtemperature over- and undervoltage over- and underexcitation over- and underfrequency over-fluxing asynchronous running out of step generator motoring failures in the machine control system (i.e. AVR or governor failure) failures in the machine cooling system failures in the primary equipment (i.e. breaker head flashover) open phase • Following are the various protections recommended for the generator and generator transformer protection: Type of fault GENERATOR STATOR Short Circuits Asymmetry Stator overload Earth fault stator © ABB Group March 22, 2016 | Slide 6 ANSI Device Protection Functions No. 87G 87GT 21G 51 / 27 G 46G 51G 64G1 64G2 Generator differential Overall differential Minimum impedance (or alternatively Over current / under voltage) Negative sequence Overload 95% stator earth fault 100% stator earth fault Loss of excitation 40G Out of step Monitoring 98G 32G / 37G Blade fatigue Inter turn fault Mag. Circuits Higher voltage Accidental energisation Monitoring 81G 95G 99G 59G 27 / 50 G © ABB Group March 22, 2016 | Slide 7 60 G Loss of excitation Pole slip Low forward power / reverse power (double protection for large generators) Minimum frequency Over voltage or over current Overfluxing volt / Hz Over voltage Dead machine PT fuse failure GENERATOR ROTOR Rotor ground GENERATOR TRANSFORMER Short Circuits Ground fault Overhang UNIT AUXILIARY TRANSFORMER Short circuit Ground fault © ABB Group March 22, 2016 | Slide 8 64F Rotor earth fault 87GT 51GT 87T 51NGT 87NT 87HV Overall differential Overcurrent Transformer differential Earth fault over-current Restricted earth fault HV winding cum overhang differential 87 UAT 51 UAT 51 UAT 64 UAT Transformer differential Over-current Restricted over-current Restricted earth fault 50/51 Unit aux. transformer 64F Field winding ground-fault RAGRA (RXNB4) 1) Instruments © ABB Group March 22, 2016 | Slide 9 Protection and Monitoring REG 670 – Different applications REG 670 provides extensive protection and monitoring functionality 1ph U 3ph U The REG 670 provides protection functions and concepts for: Turbine (frequency, reverse power) Generator (Main1/Main2, Main/Back-up) Generator transformer/Step-up transformer Auxiliary/Station service transformer Excitation transformer 3ph I 1ph U G 1ph I 3ph I 1ph U REG 670 focus on the optimized integration and function to protect your generator IEC 61850 A Breakthrough for Substation Automation One world One technology One standard IEC 61850 “Combining the best properties in a new way...” © ABB Group March 22, 2016 | Slide 12 Power transformers in a power system 400 kV AC Transmission 130 kV Subtransmission Generation MV Distribution LV M © ABB Group March 22, 2016 | Slide 13 315MVA Transformer © ABB Group March 22, 2016 | Slide 14 Cooling Outer Ci rcui t H eat D i ssi pati on Pump opti onal I nner Ci rcui t Heat Producti on (Core and Wi ndi ngs) F an opti onal © ABB Group March 22, 2016 | Slide 15 Oi l i mmersed Tank In principle the larger the losses in the Inner Circuit the larger the size of the Outer Circuit (coolers or radiators) There is nevertheless a limit either due to the size of the coolers or to the impossibility of cooling a certain spot (hot-spot) in the Inner Circuit A pump to move the oil is often unnecessary. The generated heat will act as a siphon Types of Internal Faults © ABB Group March 22, 2016 | Slide 16 Earth faults Short-circuits Inter turn Faults Core Faults Tank Faults Reduced cooling Abnormal Conditions © ABB Group March 22, 2016 | Slide 17 Overload Over voltage Reduced system voltage Over excitation Overload Capability It is possible to overload power transformers Older transformers may withstand 140% continuously Overloading and loss of cooling causes overheating © ABB Group March 22, 2016 | Slide 18 Protective Relays Used ( Transformers > 5 MVA) Gas detector relay ( Buchholz) Over load protection Thermal relays Temperature monitoring relays Over current protection Ground fault protection Differential protection Interturn faults Pressure relay for tap changer Oil level monitor © ABB Group March 22, 2016 | Slide 19 Protective Relays Used ( Transformers < 5 MVA) Gas detector relay Overload protection Overcurrent protection Ground fault protection © ABB Group March 22, 2016 | Slide 20 Monitors Monitors are very important devices which detect faults and abnormal service conditions which may develop into fault. © ABB Group March 22, 2016 | Slide 21 Transformer Monitors Mechanical fault detectors Sudden gas pressure protection Buchholz protection Oil level monitoring Temperature Monitoring © ABB Group March 22, 2016 | Slide 22 The oil thermometer The winding thermometer Transformer protection with 670/650 series Introduction Transformer Protection 670/650 series Openness and flexibility Reliable Operation Complementary functionality Control Capabilities Communication Offering and application examples Technology Summary Relion® Summary © ABB Group November 2009 | Slide 23 670 series – optimized for generation and transmission applications provide versatile functionality, maximum flexibility and performance to meet the highest requirements of any application in generation and transmission protection systems. 650 series – your best choice for subtransmission applications provide “off-the-shelf”, ready to use solutions for transformer protection applications primarily in subtransmission networks. Fully compliant to the IEC 61850 standard Introduction Line Distance Protection 670/650 series Reliable Operation Complementary functionality Control Capabilities Communication Offering and application examples Technology Summary Relion® Summary © ABB Group November 2009 | Slide 24 Unrivalled compatibility for new and retrofit installations Designed for IEC 61850, implementing the core values of this standard Ensures open, future-proof and flexible system architectures, with state-of-the-art performance Interoperates with other IEC 61850 compliant IEDs © ABB Group March 22, 2016 | Slide 25 The reactor absorbs the capacitive power generated in long lines © ABB Group March 22, 2016 | Slide 26 Shunt Reactor © ABB Group March 22, 2016 | Slide 27 A B C A B C L R Lp Lp Ln © ABB Group March 22, 2016 | Slide 28 Lp General Shunt reactors are used in EHV systems to limit the over voltages due to capacitive VAR generation in Long Transmission Lines The shunt reactors are normally connected Through isolators to a line Through circuit breakers to a busbar © ABB Group March 22, 2016 | Slide 29 Through circuit breakers to the tertiary of a Interconnecting transformer Different locations of reactor © ABB Group March 22, 2016 | Slide 30 Internal Faults Faults occur in shunt reactors due to insulation breakdown, ageing of insulation, overheating due to over excitation, oil contamination and leakage Dry air-core reactors Phase-to-phase faults , resulting in high magnitude phase current Phase-to-earth faults ,, resulting in a low-magnitude earth-fault current, dependent upon the size of the system earthing. Turn-to-turn faults within the reactor bank, resulting in a very small change in phase current Oil-immersed reactors High current phase-to-phase and phase-to-earth faults. Turn-to-turn faults within the reactor winding. Miscellaneous failures such as loss of cooling or low oil © ABB Group March 22, 2016 | Slide 31 Abnormal Conditions Inrush currents Inrush currents flow in connection with energisation Inrush currents usually lower than 200% of rated current Transient overvoltages Temporary overvoltages © ABB Group March 22, 2016 | Slide 32 Shunt Reactor Protections © ABB Group March 22, 2016 | Slide 33 Differential protection Distance protection Phase over current protection Restricted earth fault protection Mechanical fault detectors Oil temperature and winding temperature protection Monitors Monitors are very important devices which detect faults and abnormal service conditions which may develop into fault. © ABB Group March 22, 2016 | Slide 34 Reactor Monitors Mechanical fault detectors Sudden gas pressure protection Buchholz protection Oil level monitoring Temperature Monitoring © ABB Group March 22, 2016 | Slide 35 The oil thermometer The winding thermometer Shunt reactor protection and control Introduction Transformer Protection 670/650 series Openness and flexibility Reliable Operation Complementary functionality Control Capabilities Communication Offering and application examples Technology Summary Relion® Summary © ABB Group November 2009 | Slide 36 Protection Phase segregated biased differential protection Low impedance restricted earth-fault High impedance differential protection Switching control for lines and buses © ABB Group March 22, 2016 | Slide 37 Capacitor Construction © ABB Group March 22, 2016 | Slide 38 Power Factor Correction Working Power (kW) Reactive Power (kVAR) KW is the Working Power component kVAR is the Non- Working Power or Reactive Power component to serve inductive loads, which require magnetizing current: Motors, Transformers, Lighting ballast KVA is the Total Power required to serve a load Capacitors supply the reactive power component Power Factor is a measurement of how efficiently power is being used. © ABB Group March 22, 2016 | Slide 39 Increased System Capacity Extra capacity for more KVA released system capacity Total Power (KVA) = Working Power (KW) Power Factor Power Factor Real Power kW Reactive Power kVAR Total Power kVA 60% 600 800 1000 70% 600 612 857 80% 600 450 750 90% 600 291 667 100% 600 Zero 600 By supplying reactive current (kVAR) close to the load, capacitors release system capacity on the entire system and reduce costs. © ABB Group March 22, 2016 | Slide 40 Voltage Stability A feeder circuit will have a voltage drop related to the impedance of the line and the power factor Adding capacitance will actually cause a voltage rise by supplying reactive current to the bus (less current = less voltage drop) © ABB Group March 22, 2016 | Slide 41 Products Capacitors – HV Products / Filter Capacitor Banks Improving the performance, quality and efficiency of electrical systems © ABB Group March 22, 2016 | Slide 42 Capacitor banks- General Normally used in MV networks to generate reactive power Series reactors are used to limit inrush current Harmonic filters for thyristor controlled reactors are also variation of capacitor banks having reactance tuned to capacitance Shunt Capacitors-General Shunt Capacitor Faults Terminal shunt faults Capacitor unit failures Capacitor unit over voltages Capacitor rack arc-over Abnormal Conditions Inrush currents Transient over voltages Temporary over voltages Out rush currents Capacitor Bank Protections Short -circuit protection (3I >>) Ground-fault protection (I ) Overload protection(3I/U >) Under current protection (I/U <) Unbalance protection (IN-N) Fusing Capacitor Fusing Internally Fused Fuse © ABB Group March 22, 2016 | Slide 48 Externally Fused Discharge Resistor Internal Strings Fuseless Conventional SPAJ 160 C : Unbalance , Overload and Under current functions Bapuji S Palki, INCRC/PowerTechnologies, 15-11-2009 Protection Application – An Overview Part 2B © ABB Group March 22, 2016 | Slide 50 © ABB Group March 22, 2016 | Slide 51 The Electric Utility Power Evacuation Substation Transmission Substation Switching Substation Distribution Substation © ABB Group March 22, 2016 | Slide 52 Transmission Line © ABB Group March 22, 2016 | Slide 53 Electrical faults in the power system Transmission lines 85% Busbar 12% Transformer/ Generator 3% 100% © ABB Group March 22, 2016 | Slide 54 Fault types © ABB Group March 22, 2016 | Slide 55 Transient faults are common on transmission lines, approximately 80-85% lightnings are the most common reason can also be caused by birds, falling trees, swinging lines etc. will disappear after a short dead interval Persistent faults can be caused by a broken conductor fallen down can be a tree falling on a line must be located and repaired before normal service Measuring principles © ABB Group March 22, 2016 | Slide 56 Overcurrent protection Differential protection Phase comparison Distance protection Directional- wave protection Overcurrent protection Are normally used in radial networks with system voltage below 70 kV where relatively long operating time is acceptable. On transmission lines directional or nondirectional over current relays are used as back-up protections. I> block © ABB Group March 22, 2016 | Slide 57 I> I> I> Pilot wire differential protection © ABB Group March 22, 2016 | Slide 58 Pilot wires can be in soil or on towers. The resistance in the wires will limit the use on longer lines. The use is mostly restricted to distances up to 10 km. Digital differential communication L1 L2 L3 DL1 DL2 DL3 © ABB Group March 22, 2016 | Slide 59 Digital communication with optical fibres or by multiplexed channels DL1 DL2 DL3 Phase comparison load I1 > > Phase comparison relays compare the angle difference between the two currents at both ends of the line. The measured time for zero crossing is transmitted to the other end. Normally a start criteria is added to the phase angle requirement. I2 I1 I2 e 1 e 2 e1 e - 2 I2 func- tion I1 I2 © ABB Group March 22, 2016 | Slide 60 The principle of distance protection ZK=Uk/Ik Uk Uk=0 metallic fault Zk A Z< © ABB Group March 22, 2016 | Slide 61 Ik B Fault resistance multi-phase faults consist only of arc resistance © ABB Group March 22, 2016 | Slide 62 L1 L1 L2 L2 L3 earth faults consist of arc and tower footing resistance Warrington´s formula Rarc = L3 28707 x L 1.4 I L= length of arc in meters I= the actual fault current in A Footing resistance Distance protection on short lines jX Quadrilateral characteristic improves sensitivity for higher RF/XF ratio It still has some limitations: RF XF © ABB Group March 22, 2016 | Slide 63 R the value of set RF/XF ratio is limited to 5 jX Distance protection on long lines Load impedance limits the reach in resistive direction High value of RF/XF ratio is generally not necessary Circular (mho) characteristic R © ABB Group March 22, 2016 | Slide 64 Has no strictly defined reach in resistive direction Needs limitations in resistive direction (blinder) The principle of distance protection t t3 t2 t1 l A B f 1 Z< C f 3 f 2 Z< Z< Z< t t3 t2 l © ABB Group March 22, 2016 | Slide 65 t1 The principle of distance protection Reach setting of zones R/ X Relation GFC (General Fault Criterion) GFC ZL ZL Zb © ABB Group March 22, 2016 | Slide 66 PLCC equipment © ABB Group March 22, 2016 | Slide 67 Power Swing Blocking function X Power swing locus R t t = 40 ms © ABB Group March 22, 2016 | Slide 68 Series compensated system jX B´ A XC =70% 100% Xl =100% B F1 gape flashed Consideration for line distance protections B A 70% © ABB Group March 22, 2016 | Slide 69 R gape not flashed • Correct direction discrim-ination at voltage reversal (negative fault reactance) • variation in resulted line impedance Line distance protection with Relion® 670/650 series For maximum reliability of your power system Introduction Line Distance Protection 670/650 series Reliable Operation Complementary functionality Control Capabilities Full scheme distance protection with independent phase selection Power swing detection Wide range of scheme communication logics Five zone distance protection Communication Offering and application examples Technology Relion® Summary © ABB Group November 2009 Slide 70 Summary Phase to phase Phase to earth faults Fully compliant to the IEC 61850 standard Introduction Line Distance Protection 670/650 series Reliable Operation Complementary Unrivalled compatibility for new and retrofit installations Designed for IEC 61850, implementing the core values of this standard Ensures open, future-proof and flexible system architectures, with state-of-the-art performance Interoperates with other IEC 61850 compliant IEDs functionality Control Capabilities Communication Offering and application examples Technology Summary Relion® Summary © ABB Group November 2009 Slide 71 © ABB Group March 22, 2016 | Slide 72 Auto reclosing Cycle OH-lines High fault-rate (80-90%) Fast simultaneous Fault clearing © ABB Group March 22, 2016 | Slide 73 AUTORECLOSING CYCLE OH-lines Intermittent faults (80-90%) Successful AR-rate : High (80-90%) © ABB Group March 22, 2016 | Slide 74 Auto reclosing principles 95% of faults are transient type 3 Ph autoreclosing synchrocheck is used 1 Ph autoreclosing needs identification of faulty phase © ABB Group March 22, 2016 | Slide 75 Helps verify phase angles are not out of phase e.g: due to heavy power swing Phase identification is difficult for high resistance faults Single-pole Reclosing Single-Pole Reclosing A B C © ABB Group March 22, 2016 | Slide 76 A B C Artificial extinction of secondary arc by Fixed Four-reactor Scheme ABC ABC L R Lp Lp Lp Ln © ABB Group March 22, 2016 | Slide 77 Synchronism and Energizing check UBus ULine UBus FreqDiff < 50-300 mHz o PhaseDiff < 5-75 UDiff < 5-50% Ur UHigh > 50-120% Ur U Bus 1-ph U Line 3-ph (or 1-ph) ULow < 10-100% Ur SYNC-BLOCK © ABB Group March 22, 2016 | Slide 78 Fuse fail ULine © ABB Group March 22, 2016 | Slide 79 Need for Busbar protection In its absence fault clearance takes place in Zone-II of distance relay by remote end tripping This means slow and unselective tripping and wide spread black out Effect of delayed clearance © ABB Group March 22, 2016 | Slide 80 Greater damage at fault point Indirect shock to connected equipments like shafts of Generator and windings of transformer. Types of BB Protections High impedance Medium impedance Low impedance Blockable O/C relay ( For radial systems in distribution systems) © ABB Group March 22, 2016 | Slide 81 High impedance bus differential relay Basic features SETTING VR > IF ( RCT + 2 RL) VK > 2 VR RL A VR RCT B FOR VR TO BE ZERO FOR EXTERNAL FAULT nA = nB 1 + RA / ZA 1 + RB / ZB n = TURNS RATIO R = RCT + 2 RL Z = MAGNETIZING IMPEDANCE © ABB Group March 22, 2016 | Slide 82 Limitations of High impedance differential relay © ABB Group March 22, 2016 | Slide 83 Puts stringent requirements on CTs Need for dedicated CTs Identical CT ratios , magnetising impedances Aux CTs not acceptable Inability to cope with increasing fault levels RADSS medium impedance relay IR1 T MD n MD Ud3 dR D2 US © ABB Group March 22, 2016 | Slide 84 D1 REB500 - Numerical Busbar and Breaker Failure Protection ABB Network Partner AG REB 500 C E Distributed installation ABB Network Partner AG REB 500 ABB Network Partner AG C E Bay Unit Central Unit REB 500 ABB Network Partner AG REB 500 C E Bay Unit C E Bay Unit REB 500 C E Bay Unit E © ABB Group March 22, 2016 | Slide 85 ABB Network Partner AG E Advantages of medium/ Low impedance relays Free from any need for Identical CT ratios or matched CTs Other relays can be included in the same CT core Increasing fault levels have no impact © ABB Group March 22, 2016 | Slide 86 1000/5 200/5 500/5 5A 3.5 A 5/1 500 A 200 A 700 A 5/0.5 5/0.2 0.7 A 0.2 A Diff. relay RADSS IN SINGLE BUS © ABB Group March 22, 2016 | Slide 87 5A 0.5 A REQUIREMENTS ON THE ISOLATOR AUXILIARY CONTACTS Isolator Aux. Contact ‘a’ should close before the primary contact a b closes and Aux contact’ b’ closes after the primary contact opens. O C Throw-over relay 0% Main contact Aux. Contact a Aux. Contact b © ABB Group March 22, 2016 | Slide 88 100% DOUBLE BUSBAR SYSTEM WITH TRANSFER BUS BUS - A BUS - B AUX. BUS © ABB Group March 22, 2016 | Slide 89 1½- BREAKER SYSTEM RADSS - A L1 L3 L5 L2 L4 L6 BUS - A BUS - B RADSS - B © ABB Group March 22, 2016 | Slide 90 Busbar Protection REB670 © ABB Group April 2009 Slide 91 © ABB Group March 22, 2016 | Slide 92 History - Circuit breaker development Example: 420 kV Air Blast …around 1960 © ABB Group March 22, 2016 | Slide 93 Oil Minimum SF6 Gas …around 1980 …today’s technology Interrupters Interrupter design © ABB Group March 22, 2016 | Slide 94 + Relay back-up RELAY SYSTEM CHANNEL 52 50 - 52a 52 52a RELAY SYSTEM CHANNEL + © ABB Group March 22, 2016 | Slide 95 Breaker back-up 5 1 6 2 Z< 7 8 3 4 For uncleared fault shown CB’s to be tripped are 1, 3, 4 & 6 © ABB Group March 22, 2016 | Slide 96 Classical CBFP Breaker Failure Protection I> I> I> I> + if trip from relay © ABB Group March 22, 2016 | Slide 97 t trip © ABB Group March 22, 2016 | Slide 98 Introduction Majority faults are earth faults Earth fault protection depends on type of earthing © ABB Group March 22, 2016 | Slide 99 Effectively earthed Reactance earthed High resistance earthed Resonance earthed Measurement of earth fault current © ABB Group March 22, 2016 | Slide 100 Measurement of zero sequence voltage L1 L2 L3 U0> Earth fault protection in solidly earthed systems IDMT earth fault relays are used to detect earth faults in effectively earthed system © ABB Group March 22, 2016 | Slide 102 Directional Earth Fault Relay © ABB Group March 22, 2016 | Slide 103 Directional earth fault relays are used Can use communication link Inrush current stabilization may be required for sensitive settings Directional earth fault relay for High resistance earthed system Directional earth fault relay used when in feed of capacitive current from an object is higher than 60% of required sensitivity Measures active component of fault current © ABB Group March 22, 2016 | Slide 104 Earth fault in resonance earthed network A B C ΣI01 C0 ΣI02 L RL U0 Ief R0 Earth fault in isolated network A B C ΣI01 C0 U0 ΣI02 Ief R0 Directional earth fault relay © ABB Group March 22, 2016 | Slide 107 Restricted earth fault relay © ABB Group March 22, 2016 | Slide 108 © ABB Group March 22, 2016 | Slide 109 What is Substation Automation ? A combination of: © ABB Group March 22, 2016 | Slide 110 Protection Monitoring Control Communication What is Substation Automation ? Substitution for conventional control panels Substitution for other sub systems A more efficient way of controlling your substation © ABB Group March 22, 2016 | Slide 111 8 The conventional way Control Board Telecontrol RTU Alarming Synchronization Busbar Protection MARSHALING RACK Local ControlTELE- © ABB Group March 22, 2016 | Slide 112 Interlocking ALARMING Measuring NISATION Bay BUSBAR Protection PROTECTION System Engineering Tool The New Way Station Monitoring System Station HMI Gateway Station Clock Communication only during engineering IED Tool Station bus Bay Control Web Client Object Protection Control & Protection Multi Object Protection IEDs Process bus Merging Unit © ABB Group March 22, 2016 | Slide 113 Merging Unit Multi Bay Control Conventional Control & Protection Fault Recording Station Level ABB 225kV LIGNE ABOBO 1 125VDC Distributuion Battery A =D04+R01 125VDC Distributuion Battery B Bay Protection ABB 225kV LIGNE ABOBO 1 125VDC Distributuion Battery A Busbar Protection ABB =D04+R01 ABB =D04+R01 225kV LIGNE ABOBO 1 125VDC Distributuion Battery A 125VDC Distributuion Battery B 125VDC Distributuion Battery B Event Recording =D04+R01 ABB 225kV LIGNE ABOBO 1 125VDC Distributuion Battery A =D04+R01 125VDC Distributuion Battery B ABB RTU 200IN 1 IN 2 IN 3 IN 4 IN 5 IN 6 IN 7 IN 8 OUT 1 056 citcadnI 056 citcadnI 056 citcadnI Network Partner 9114 24351678ABB 10 11 13 15 162REL316*4 =W1 =W2 12345678-Q1 9111 12 13 14 15 160eriosn V 4.2b FERMER cABB Network Partner 912REL316*4 2435678111 10 13 14 15 16 REB500 ABB Network Partner ON/OFF BAY CONTROL RELAY REC316*4 LOCAL CONTROL RTU 200IN 1 IN 2 IN 3 IN 4 IN 5 IN 6 IN 7 IN 8 OUT ON/OFF 38 Indactic650 650 Indactic METERING ABB RTU 200IN 1 IN 2 IN 3 IN 4 IN 5 IN 6 IN 7 IN 8 OUT ON/OFF Indactic650 650 Indactic LINE PROTECTION RELAY REL316*4 ABB BUSBAR PROTECTION REB500 ABB 225kV LIGNE ABOBO 1 ABB Bay Level 225kV LIGNE ABOBO 1 125VDC Distributuion Battery A 125VDC Distributuion Battery B SCADA RTU For each function a dedicated device and separate Panel Control Panel ABB =D04+R01 ABB =W1 =W2 -Q1 SEL -Q2 SEL -Q0 SEL TESTE LAMPE Extensive station wide cabling OUVRIRFERMER ABB ESC EXE Local Control DISTANCE LOC Process Level Marshalling Extensive bay cabling GIS or AIS Switchgear -Q2 -Q0 -Q1 -Q9 -Q8 Substitution of Conventional Technology Bay Control/Protection Cubicles Fällanden Steuerung / Schutz Fällanden Steuerung / Schutz MicroSCADA =AD17-KB2 =AD17-KB2 Feldsteuergerät REC216 mit Messung und Synchrocheck Feldsteuergerät REC216 mit Messung und Synchrocheck Interbay bus Ethernet Switches d gi ta l LEITUNGSHAUPTSCHUTZ REL316*4 I 0 I 0 STUFENVERL. WE-BLOCK LEITUNGSHAUPTSCHUTZ REL316*4 I 0 I 0 STUFENVERL. WE-BLOCK PRÜFSTECKER Reset AUS I 0 di gi tal SCHUTZ EIN/AUS PRÜFSTECKER Reset AUS I 0 SCHUTZ EIN/AUS -Q2 -Q1 COM 581 ABB Power Automation AG COM581 NCC / RCC Communication Converter -Q0 Marshalling -Q9 C Control Cubicle Relays for control / logic Transducers, Meters Switches, Lamps Annunciators, Terminals -Q8 Protection Cubicle SER / Fault Recorder SCADA RTU NCC / RCC Modern Substation Automation (SA) Bay Control/Protection Cubicles Fällanden Steuerung / Schutz Fällanden Steuerung / Schutz =AD17-KB2 MicroSCADA =AD17-KB2 220VDC SPANNUNG SYS 1 220VDC SPANNUNG SYS 2 220VDC SPANNUNG SYS 1 220VDC SPANNUNG SYS 2 Feldsteuergerät REC216 mit Messung und Synchrocheck I 0 VERRIEGELUNG Feldsteuergerät REC216 mit Messung und Synchrocheck Interbay bus Ethernet Switches I d gi ta l 0 VERRIEGELUNG LEITUNGSHAUPTSCHUTZ REL316*4 I I 0 0 STUFENVERL. WE-BLOCK LEITUNGSHAUPTSCHUTZ REL316*4 I I 0 -Q2 -Q1 0 AUS AUS RESERVESCHUTZ I -X1 SYNCHRONISIERUNG HAND AUS 0 I AUS 0 SCHUTZ EIN/AUS 2 x 220/24V DC/DC SPANNUNGSVERSORGUNG 2 x 220/24V DC/DC SPANNUNGSVERSORGUNG -Q0 -Q8 ABB Power Automation AG COM581 NCC / RCC Communication Converter C E Marshalling -Q9 COM 581 SCHUTZ EIN/AUS RESERVESCHUTZ -X1 SYNCHRONISIERUNG HAND di gi tal SCHUTZ EIN/AUS I 0 SCHUTZ EIN/AUS SAMMELSCHIENENSCHUTZ REB500 SAMMELSCHIENENSCHUTZ REB500 I 0 PRÜFSTECKER Reset STUFENVERL. WE-BLOCK PRÜFSTECKER Reset Still extensive bay cabling Modern SA Architecture Station Level Network Control Center NCC ABB Network Partner AG C -Q2 -Q0 -Q1 -Q9 -Q8 Features and Benefits Basic Functionality E Bay Level Process Level COM581 Implementation of Intelligent Technology Intelligent Primary Equipment MicroSCADA Interbay bus Ethernet Switches M M -Q2 di gi tal -Q2 -Q1 -Q51 -Q0 Drive control & monitoring circuitry PISA A PISA A PISA B -Q8 -Q9 -Q8 i it l COM 581 ABB Power Automation AG COM581 Communication Converter NCC / RCC C -Q0 -T1 -Q9 LOCAL SET REMOTEOPERATION PISA Feeder Marshalling -Q1 t d gi tal M ? Sampling AD-Conversion Signal Processing Signal Filtering Process Bus Station Level Intelligent SA Architecture Network Control Center NCC C Basic Functionality E Bay Level M M M ? LOCAL SET REMOTEOPERATION -Q2 -Q0 -Q1 -Q51 PISA A PISA B PISA A PISA Process Level COM581 -T1 -Q9 -Q8 FEATURES AND BENEFITS ABB Network Partner AG Functional Structure of Modern SA Station Level Functions Allocation Network Control Center NCC ABB Network Partner AG C E Bay Level Process Level COM581 Scalable System Extensions SCADA Remote Communication Fault evaluation Monitoring Events and alarms Supervision & Control Data Exchange Monitoring GIS or AIS Switchgear Instrument Transformers Power Transformers Surge Arresters -Q2 -Q0 -Q1 -Q9 -Q8 Intelligent Substation Automation Functional Structure Station Level Network Control Center NCC ABB Network Partner AG COM581 C E Bay Level Scalable System Extensions SCADA Remote Communication Fault evaluation Monitoring Events and alarms Supervision & Control Data Exchange M M Monitoring M ? LOCAL SET REMOTEOPERATION -Q2 -Q0 -Q1 -Q51 PISA A PISA B PISA A PISA Process Level Functions Allocation -T1 -Q9 -Q8 Intelligent or “smart” AIS / GIS Switchgear Data acquisition Sensors & Actuators Power Transformers Surge Arrestors Intelligent SA: Control, Protection and Sensors ABB Actuator for isolator & earthing switch control PISA PISA PISA PISA Line Protection 1 I Abgangsschutz M M Bay Controller Feldleitgerät M Switches Actuator for circuit breaker control ? LOCAL SET REMOTE OPERATION PISA A Line Protection 2 II Abgangsschutz PISA A PISA B Busbar Protection Sensors for current & voltage measurement Process Bus Interbay bus 1 Interbay bus 2 Monitoring via IEDs for Protection Advanced analysis tools Alarm Classes Automatic printing Summary report GPS User friendly visualization Universal Time synchronization CONCISE / FAST Distance to Fault Mo 12. 11. 96 GMT 17:02.43.305 Ayer Rajah & Labrador Feeder One Sequence of Events ABB Network Partner AG IED Parameter # Of trips C E ABB Network Partner AG REL 316*4 ABB Network Partner AG REL 316*4 ABB Network Partner AG 1 9 1 9 2 10 2 10 1 9 3 11 3 11 2 10 4 12 4 12 3 11 5 13 5 13 4 12 6 14 6 14 5 13 7 15 7 15 6 14 8 16 8 16 7 15 8 16 C C E E REL 316*4 C E Station level supervision Single Line Diagram: Diagnostic: Fault Recording and Evaluation Automatic fault location printout Remote Control via Network Control Centre (NCC) The goal of the IEC 61850 standard Interoperability The ability for IED’s from one or several manufacturer to exchange information and use the information for the their own functions. Free Configuration The standard shall support different philosophies and allow a free allocation of functions e.g. it will work equally well for centralized (RTU like) or decentralized (SCS like) systems. Long Term Stability The standard shall be future proof, i.e. it must be able to follow the progress in communication technology as well as evolving system requirements. © ABB Group March 22, 2016 | Slide 127 © ABB Group March 22, 2016 | Slide 128