FPASA BULLETIN SF 14 FIRE SAFETY FOR COMPUTER INSTALLATIONS Electronic computer and data processing equipment are essential and commonplace tools for business, industry, government and research groups. People quickly become dependant on the equipment. A minor problem which causes a computer to “go down” can temporarily immobilise an institution until the fault is rectified. This usually only taken a few minutes. A serious fire, however, might disable an installation for days, resulting in enormous losses. Some computer fires London, UK. -Electrical fault ignited paper element in air conditioning duct. Berkshire, UK. -Short circuit in refrigeration unit of air conditioning system. Newcastle, UK. -Short circuit inside the computer cabinet. Detectors alerted the brigade who were unable to extinguish the fire with extinguishers due to its advanced state – a fixed gaseous system would have extinguished the fire before their arrival. Durban. -Fire started in offices and spread to involve computer suite not separated by fire resisting construction. Smoke detectors connected to fire station activated but too late to save the suite. Computer tapes in strong room survived the fire. Port Elizabeth. -Two months downtime. Heat and smoke from a small fire immobilised a large computer centre. Records Fire protection considerations for software and data has to be made for computer suites and also for servers, personal computers etc. found in offices. 4/2000 The records are stored on: hard magnetic discs flexible magnetic discs magnetic tapes paper products (punch cards) photographic material electronic hardware compact discs Important and duplicate records should be stored in a separate room of at least two hour fire resistance. Refer also to SABS 0141, Code of practice for the processing, testing and storage of silver-gelatine microfilm for archival purposes. Computer records are damaged by fire in a number of ways: A sustained ambient temperature of 80°C, can cause damage to functioning computer equipment temperature above 40°C will damage magnetic tapes and flexible discs but damages incurred between 40°C and 50°C can generally be reconditioned flexible discs deteriorate rapidly above 66°C paper products may become damaged when the ambient temperature increases above 170°C microfilm damage will occur at temperatures above 90°C in the presence of steam or at 260°C in dry heat contamination with smoke and corrosive gases Build to protect Computers and electronic equipment are valuable and should be located in a detached building or in an area segregated from other parts of the building. Segregation is achieved by enclosing the room with at least one hour fire resistant walls and ceilings. When the building has a medium fire load, eg: a factory, the minimum fire resistance should be two hours with four hours fire resistance when the building has a high fire load, eg: a warehouse. Other rooms required to accommodate programmes, maintenance staff, paper supplies and recorded data, should be separated from the computer room and combustible materials kept to a minimum – metal furniture with fire retardant upholstery is recommended. Minimum amounts of paper should be allowed in the computer room. Construction details for computer rooms are outlined in BS 6266 and NFPA 75 and include reference to: restriction of the combustibility of the floor space and ceiling fire-stopping of openings into the room correct electrical installation according to standards air circulation through each cabinet (air filters used in the air conditioning system should neither burn freely nor emit large volumes of smoke if attacked by flames) separate electrical power supplies, distribution boards etc. housed in cut-off rooms fire dampers which close automatically under emergency conditions fitted to air conditioning ducting 4/2000 Fire detection is delayed when the air conditioning system transports smoke away from smouldering computer equipment during the initial phase of the fire when the smoke is highly diluted Fire Protection Statistics show that most fires involving computer hardware start in the computer cabinets. A typical fire is of the smouldering variety caused by overheating of overloaded or faulty electrical components. If the smouldering fire goes undetected, or if the electrical power is not shut down, the heat of the electrical component can ignite combustible material in the vicinity. The fire then spreads, fanned by the computer’s cooling equipment. Fire protection should include: Portable fire-fighting equipment – carbon dioxide extinguishers should be provided near the computer installation. Hose-reels or water type extinguishers should be considered for protecting paper storage areas. Hose-reels outside the computer room are advantageous in fighting external fire which threatens the room. Automatic fire detectors of a type which will detect a fire during its earliest stage. Isonisation type detectors are most suitable for detecting clean burning fires – BS 6266 recommends an equal number of these and optical detectors in the computer room. Other considerations regarding the selection and installation of smoke detectors – An unusually high density of detectors is appropriate to the concentration of valuable machinery which is easily damaged by even small amounts of smoke. They should be installed in any air spaces where fire may spread undetected eg: ceilings and floors. Avoid aerodynamically ‘dead’ zones created by the location of air conditioning ducts or conformation of the room. Detectors are usually arranged symmetrically but they should be at least 1,5 m from fresh air flows. 4/2000 of Under floor detectors should be: easily accessible, positioned to prevent dust from initiating false alarms; and positioned with consideration to air flows. Detectors in the air conditioning ducts will protect: the air conditioning plant rooms; return-air system; and the supply air system. Approximately 20 detectors per zone. Acceptance testing is essential when the effects of the air conditioning and positioning furniture upon the detectors are not predictable. SABS 0139 details the positioning of the appropriate test fires used in these situations. After installation by competent persons, a maintenance contract will ensure that regular inspections are conducted. Coincidence switching – two separate signals are received before activation of the extinguishing system. This reduces the possibility of unwanted discharges. Additional functions performed when detectors operate: sound alarms; stop fans; close air conditioning dampers; isolate power supplies. A manual shut down conducted in a predictable manner may be essential in some cases. An annunciator board should be positioned outside the computer room. Sprinkler Systems The following considerations apply: Many computer suites throughout the world are protected by sprinklers. Sprinklers will normally be selected if the rest of the building is sprinklered. Provided adequate precautions are taken against accidental activation, sprinklers offer a viable alternative to total flooding – especially where large volumes are concerned. A typical system A good concept utilises addressable smoke detectors inside computer cabinets. Having detected smoke within a cabinet, pre-programmed de-energisation of the cabinet is initiated. (See Fig. 1) When an electrical component overheats (T1 > 100°C) and produces smoke, an addressable smoke detector installed in the cabinet must respond to smoke density (DI) at instant (a) Fig.2) – typical for a smouldering fire. At instant (a), a control device initiates shut down of the power supply to the cabinet – a pre-programmed measure, allowing the computer to operate without the particular cabinet being energised. Also at (a), an audio-visual pre-alarm is initiated in the room; available operators will then be able to extinguish the fire. If, however, the fire is not extinguished and the flames spread (T 2 > 400°C), ceiling mounted detectors will respond to smoke density (D2) (Fig.2) and total flooding of the room will be initiated. 4/2000 Fire Precautions A high standard of housekeeping is essential to ensure the safety of computer installations. Before staff leave premises after working hours they should check the following: all doors and hatches between rooms are closed waste paper removed ancillary equipment unplugged from sockets master switches in OFF position automatic fire extinguishing system on automatic control all records returned to storerooms and safes doors locked Finally, concise evacuation and damage control plans should be compiled and regular practices of evacuations conducted. 4/2000 Detection systems – design considerations Floor area coverage per detector – BS 6626 Application Recommended coverage per detector Remarks and recommendations Computer equipment room (ceiling height about 3 m) For minimum room protection, a detector for every 25 m². Where equipment, or information justifies, additional expenditure, detector coverage could be reduced to 15 m² Without ventilation: 20 m² - 30 m² Where the earliest possible warning of fire in a cabinet is required, there is no substitute for the incorporation of a detector or sensing point inside the cabinet. False floor, false ceilings In false ceilings with beams the lower figure should be taken. If the beams are deep so as to compartmentalise the space, a detector should be fitted in each such compartment. With ventilation: Tape stores Electrical distribution boards emergency power supplies Peripheral stores, etc. Corridors rooms: offices, (a) between 15 m² and 20 m² for air velocities of 4 m/s or less (b) 10 m² for air velocities greater than 4 m/s Room protection: 10 m² to 30 The greater the ventilation, the m² smaller fire coverage necessary Room protection: 10 m² to 30 In installations with enclosed m² emergency power cabinets, additional protection is ensured by the installation of detectors inside the cabinets. Each room should have at least one smoke detector Not more than 12 m apart For corridors subdivided by doors at least one detector in each section. Note: For coincidence systems, minimum recommended coverage areas should be used. References: Fire Protection for electronic data processing installations British Standard Code of Practice BS 6266: 1982 Standard for the protection of Electronic Computer/Data processing equipment Code 75, NFPA Fire Prevention No. 173, FPA UK Information Bulletin, Siemens Ltd Fire Protection Handbook, NFPA Code of Practice for the Prevention, automatic detection and extinguishing of fire in buildings, SABS 0139 Published by Fire Protection Association of Southern Africa (Incorporated Association not for Gain) (Reg.No. 73/00022/08) P O Box 15467 Impala Park 1472 4/2000