Logic module LOGO! - Sitrain

advertisement
LOGO! -
The internal
qualities
count
Innovative
Switching & Control
Introduction
Wiring
Integrated
functions
LOGO! –
Innovative
Switching & Control ... In detail
Operation on
device
The Original!
LOGO! Soft
Comfort V6.1
Application
example
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
LOGO! in detail overview
Introduction
Wiring
Integrated
functions
Wiring




Hardware assembly
Connecting power supply
Connecting inputs and outputs
Switch-on behavior
Integrated functions
 Connectors
 Basic functions
 Special functions
Operation on
device
Operation on device
LOGO! Soft
Comfort V6.1




Control for operation
First program
LOGO! in run mode
Configuring LOGO!
Application
example
LOGO! Soft Comfort V6.1




Help functions
Realizing typical tasks step by step
Modem wizard
Other options
Application example
 Control of bottle filling conveyor
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
LOGO! wiring
Introduction
L1
K2
Wiring
Integrated
functions
I:
0.. 123456789
4
1..0123456789
2..01234
Operation on
device
LOGO! Soft
Comfort V6.1
Application
example
K2
N
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
LOGO! ..0BA5 hardware structure
Introduction
8 inputs
Power supply for expansion modules
Power supply
4 inputs
Wiring
Switch for
electrical
connection
Integrated
functions
Operation on
device
LOGO! Soft
Comfort V6.1
Connection
interface for
LOGO! TD
Backlit display
Adjustable contrast
The internal
qualities
count
RUN/STOP
Application
example
E-Stand (ESx)
4 outputs
4 outputs
Maximum configuration: 24 digital inputs + 8 analog inputs
+16 digital outputs + 2 analog outputs
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
LOGO! wiring
Introduction
To connect LOGO! to the power supply:
Integrated
functions
LOGO! ..... with
AC supply voltage
LOGO! ..... with
DC supply voltage
Wiring
L+
L1
M
N
Operation on
device
L+
M
I1
I2
I3
I4
I5
L1
N
I1
I2
I3
I4
LOGO! Soft
Comfort V6.1
Application
example
Protection by fuse
if required (recommended) for:
12/24 RC...:
24:
Logic module LOGO!
0.8 A
2.0 A
With voltage spikes, use a varistor
(MOV) with an operating voltage
at least 20% higher than nominal
voltage.
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Connecting LOGO! inputs
Introduction
Wiring
Integrated
functions
Operation on
device
LOGO! Soft
Comfort V6.1
Application
example
Connect sensors to the inputs. Sensors may be:
 pushbuttons, switches, photoelectric barriers, etc.
 temperature, pressure or ultrasound sensors (Beros) etc., with 0...10V outputs directly at
the 4 analog inputs of the 12 and 24 V DC basic devices or the analog module AM2
 or the appropriate device with current output 0...20mA/4...20mA to the inputs of the
analog module AM2
 or connect up to 2 resistance thermometer PT100 to AM2 PT100 in 2 or 3 wire connection
technology
LOGO! 230 ...
2-wire technology
LOGO! 12/24 ...
3-wire technology
L+
L3
L2
L1
N
M
L+ M I1 I2 I3 I4 I5
L1 N I1 I2 I3 I4
I5 I6
The inputs of these devices are
grouped into 2 blocks of
4 I each. Different phases are
only possible between, not
within the blocks.
Logic module LOGO!
I8
The inputs of these devices are
non–isolated and therefore
require the same reference
potential (ground) as the power
supply.
With 2-wire connections no
correction of the impedance of
the measurement line occurs.
3-wire connection suppresses
this influence.
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Connecting LOGO! outputs
DM8 24
Introduction
Wiring
Integrated
functions
Operation on
device
LOGO! Soft
Comfort V6.1
LOGO! with
transistor outputs
Q5 M
Q1 M
Q2 M
load
You can connect
different loads to the
outputs, e.g.:
 lights
 motors
 switches
 etc. ...
load
max. switched current per output is 0.3 A
DM8...R
L1 / L+
Application
example
1
1
LOGO! with
relay outputs
Q6 M
Q1
2
1
Q2
load
Q5
2
1
Q6
2
2
load
N/M
max. switched current per output is 10 A /
for expansion modules 5 A
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Connecting LOGO! outputs
Introduction
Wiring
LOGO! with
analog outputs
Ground
Profile rail
Integrated
functions
You can connect
different devices to
analog outputs, e.g.:
 frequency converter to
control drives
Operation on
device
LOGO! Soft
Comfort V6.1
Output signals: *)
 0-10V
 0-20mA
 4-20mA
Application
example
*)
6ED1 055-1MM00-0BA0:
6ED1 055-1MM00-0BA1:
Logic module LOGO!
0..10V
0..10V and 0/4..20mA.
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Connecting LOGO! TD text display
Connection interface for
LOGO! TD Cable
Introduction
LOGO! ..0BA6 basic
module
Wiring
Integrated
functions
Operation on
device
LOGO! Soft
Comfort V6.1
Application
example
Function keys
Standard
LOGO! keys
unipolar power supply
connector
12V DC, 24V AC/DC
Recommended fuse: 0,5A
Logic module LOGO!
LOGO! TD Cable 2,5m,
extendable to up to 10
meters with standard
Sub-D serial cable
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
LOGO! reaction when switched on depends on:
Introduction
Wiring

whether a program is stored in the internal LOGO! memory
or
 whether a memory card (memory module) is connected
s
Integrated
functions
Operation on
device
LOGO! Soft
Comfort V6.1
Application
example
No Program
Press ESC
No program on
memory card and no
program in internal
memory
LOGO!
If there is a program on the memory
card, it is automatically
copied to the internal LOGO! memory
when switching on . Any program in
the internal LOGO! memory is
overwritten.
s
> Program..
Card..
Setup..
Start
Warning!
Program on memory
card or program in
internal memory
LOGO!
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
LOGO! reaction when switched on depends on:
Introduction

in which state LOGO! was prior to POWER–OFF
Prior to power-off
Wiring
Integrated
functions
Operation on
device
s
In
editing mode or
menu in stop
status
After power-on
s
Q1
LOGO!
> Program..
Card..
Setup..
Start
LOGO!
LOGO! Soft
Comfort V6.1
Prior to power-off
Application
example
s
In
RUN time
Logic module LOGO!
After power-on
s
I:
0.. 123456789
1..0123456789
2..01234
I:
0.. 123456789
1..0123456789
2..01234
LOGO!
LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Connectors (CO)
Introduction
Wiring
Integrated
functions
Operation on
device
LOGO! Soft
Comfort V6.1
Application
example
I1
I2
I3
I4
I5
I6
I7
I8
.
.
I21
I22
I23
I24
Q1
Q2
Q3
Q4
.
.
.
.
.
.
Q13
Q14
Q15
Q16
Inputs/outputs
basic/purevariants
I3-I6 up to 5 KHz
switchingfrequency on DC
powered options
AI1
AI2
AI3
.
.
AI8
M1
.
.
M8
M25
M26
M27
hi
lo
C
C
C
C
AQ1
AQ2
Analog
I/O
AM1
.
AM6
Flags/
Analog flags
Initialization flag
Backlight flags
F1
F2
F3
F4
Cursor
Keys
LOGO! TD
Function
keys
Character set flag
Signal status
„1“
„0“
Connectors
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Basic functions
AND
Introduction
AND
(edge)
NAND NAND
(edge)
OR
NOR
XOR
NOT
Wiring
Integrated
functions
Operation on
device
LOGO! Soft
Comfort V6.1
Application
example
8 basic
functions
Logic module LOGO!
The
internal
qualities
count
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
AND function
Introduction
Wiring
Integrated
functions
A look at the circuit diagram shows that the light H1 is only on when
S1 and S2 and S3 are closed. Input and output states are dependent
on each other.
The circuit to the right is called AND logic.
In words contact S1 and S2 and S3 have to be closed for the light to
burn.
Symbol for this connection is
.
S2
S3
H1
Operation on
device
LOGO! Soft
Comfort V6.1
S1
AND
S1
S2
S3
x
&
H1
Application
example
Output of the AND function is 1 only
when all inputs are 1.
If one input pin of this block is not
connected, the status is automatically 1.
Logic module LOGO!
Series circuit
normally open
contact
Logic table for AND block:
Input 1
Input 2
Input 3
Output
0
0
0
0
1
1
1
1
0
0
1
1
0
0
1
1
0
1
0
1
0
1
0
1
0
0
0
0
0
0
0
1
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
OR function
Introduction
Wiring
To turn the lamp H2 on, the contact S1 or S2 or S3 have to be
closed. The dependence of output states from inputs states is
called OR logic.
In words at least one of the contacts S1 or S2 or S3 have to be
closed for the lamp H2 to light up.
Symbol for this connection is
.
S1
LOGO! Soft
Comfort V6.1
Application
example
Parallel circuit
normally open contact
OR
S1
S2
S3
x
>
H2
Output of the OR function is 1, when at
least one input is 1.
If one input pin of this block is not
connected, the status is automatically 0.
Logic module LOGO!
S3
H2
Integrated
functions
Operation on
device
S2
Logic table for OR block:
Input 1
Input 2
Input 3
Output
0
0
0
0
1
1
1
1
0
0
1
1
0
0
1
1
0
1
0
1
0
1
0
1
0
1
1
1
1
1
1
1
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
AND with edge triggering
Introduction
Wiring
S1
S1
S2
Electro mechanical counter
0 6 1 5
Integrated
functions
S3
Operation on
device
H2
S2
S3
H2
LOGO! Soft
Comfort V6.1
Application
example
AND with edge triggering
S1
S2
S3
x
Logic module LOGO!
&
H2
Output of AND with edge triggering is 1, only when all
inputs are 1 and in the previous cycle at least one
input was 0. If one input pin of this block is not
connected, the status is automatically 1.
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
NAND (not-AND) function
Introduction
Wiring
A look at the circuit diagram shows that the light H2 is not on,
only when all contacts are switched.
The circuit to the right is called NAND logic.
In words S1 and S2 and S3 have to be switched for the light H2
not to burn.
Symbol for this connection is
.
S1
S2
S3
H2
Integrated
functions
Operation on
device
LOGO! Soft
Comfort V6.1
Application
example
Parallel circuit
normally closed
contact
NAND
S1
S2
S3
x
&
H2
Output of NAND is 0, only when all
inputs are 1.
If one input pin of this block is not
connected, the status is automatically 1.
Logic module LOGO!
Logic table for NAND block:
Input 1
Input 2
Input 3
Output
0
0
0
0
1
1
1
1
0
0
1
1
0
0
1
1
0
1
0
1
0
1
0
1
1
1
1
1
1
1
1
0
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
NAND (not-AND) with edge triggering
Introduction
S1
S3
0 6 1 5
S3
Wiring
S1
S2
H2
Integrated
functions
S3
Electro mechanical counter
H2
Operation on
device
LOGO! Soft
Comfort V6.1
Application
example
NAND with edge triggering
S1
S2
S3
x
Logic module LOGO!
&
H2
Output of NAND with edge triggering is 1, only when
at least one input is 0 and in the previous cycle all
inputs were 1.
If one input pin of this block is not connected, the
status is automatically 1.
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
NOR (not-OR) function
Introduction
Wiring
A look at the circuit diagram shows that the light H1 is only on,
when the normally closed contact S1 and S2 and S3 are not
switched.
The circuit to the right is called NOR logic.
In words when S1 or S2 or S3 are switched, the light is not on.
Symbol for this connection is
.
S1
S2
S3
Integrated
functions
H1
NOR
Operation on
device
LOGO! Soft
Comfort V6.1
S1
S2
H1
S3
x
Application
example
Output of NAND is 1, only when all inputs
are 0. As soon as any input is switched
(status 1), the output is switched off. If one
input pin of this block is not connected, the
status is automatically 0.
Logic module LOGO!
Series circuit
normally closed
contact
>1
Logic table for NOR block:
Input 1
Input 2
Input 3
Output
0
0
0
0
1
1
1
1
0
0
1
1
0
0
1
1
0
1
0
1
0
1
0
1
1
0
0
0
0
0
0
0
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
XOR function
Introduction
Wiring
A look at the circuit diagram shows that the light H1 is only on,
when only one of either S1 or S2 is switched.
This circuit is called XOR logic.
In words when either contact S1 or contact S2 are switched, the
light is on.
Symbol for this connection is
.
Integrated
functions
Operation on
device
S1
S2
H1
XOR
S1
=1
H1
S2
LOGO! Soft
Comfort V6.1
Logic table for XOR block:
Application
example
Output of XOR is 1, when inputs have
different states.
If one input pin of this block is not
connected, the status is automatically 0.
Logic module LOGO!
Input 1
0
0
1
1
Input 2
0
1
0
1
Output
0
1
1
0
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
NOT function
Introduction
Wiring
A look at the circuit diagram shows that the light H1 is only on,
when the switch S1 is not switched.
This circuit is called NOT logic.
Symbol for this connection is
Integrated
functions
Operation on
device
.
S1
K1
H1
NOT
1
S1
H1
LOGO! Soft
Comfort V6.1
Application
example
Output is 1, when the input is 0, i.e. NOT inverts the status
at the input.
The advantage of NOT is for instance: You will not need a
normally closed contact any more for LOGO!. You can use a
normally open contact and change it with NOT to a normally
closed contact.
If the input pin of this block is not connected, the status is
automatically 1.
Logic module LOGO!
Logic table for NOT block:
Input 1
Output
0
1
1
0
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Special functions - overview
On-delay
Wiring
Integrated
functions
Operation on
device
LOGO! Soft
Comfort V6.1
Analog
Timer
Introduction
On-/ Off-delay
Off-delay
Wiping relay
Pulse generator
(pulse output)
Edge triggered
wiping relay
Analog comparator
Retentive
On-delay
Analog amplifier
Analog differential
trigger
Random
generator
Analog
MUX
Analog
watchdog
PI controller
Stairway
Weekly
lighting switch
timer
Multiple function
switch
PWM
Analog threshold
trigger
Analog Math
Ramp
Yearly
timer
Application
example
Miscellaneous
Latching relay
Message text
Pulse relay
31
special
functions
Logic module LOGO!
Up/Down
counter
Counter
Hours
counter
Threshold trigger
Softkey
Shift register
Analog Math
Error Detection
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Timer – On-delay
Introduction
A look at the circuit diagram shows that the motor only starts after
expiry of the delay time.
S1
K1
This function is called On-delay.
Wiring
In words the motor will be switch on with a programmed ON delay
time.
Integrated
functions
Symbol for this function is
.
K1
M
Diagram:
Operation on
device
Trg
LOGO! Soft
Comfort V6.1
Q
T
T
Ta
(Timer active)
Application
example
Description of the function:
With 0 to 1 transition of input Trg the timer starts. If the status of input Trg is 1 for long
enough, the output is set to 1 on expiration of the time T. The output follows the input with
on delay. The output is reset to 0 when the status at input Trg is 0.
If the status of input Trg changes to 0 before the time T has expired, the time is reset. The
time elapsed is reset after a power failure.
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Timer – Off-delay
Introduction
A look at the circuit diagram shows that the motor only stops after
expiry of the delay time.
S1
K1
This function is called Off-delay.
Wiring
Integrated
functions
In words the motor will be switch off with a programmed OFF delay
time.
Symbol for this function is
K1
.
M
Diagram:
Operation on
device
Trg
Ta
LOGO! Soft
Comfort V6.1
T
T
R
Q
(Timer active)
Application
example
Description of the function:
When the input Trg is 1, the output Q is switched instantaneously to 1. When the status of
Trg changes from 1 to 0, the timer will be activated. The output remains set. When the timer
reaches the configured value (Ta=T), output Q is reset to 0. When input Trg is switched on
and off again, the time Ta restarts. Input R (Reset) is used to reset the time Ta and the
output before Ta has expired.
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Timer – On-/Off-delay
Introduction
Wiring
A look at the circuit diagram shows that:
 when S1 is closed, contact K1 closes with a delay
time and the motor runs.
 when S1 is opened, contact K2 opens with a delay
time and the motor stops.
S1
K1
K2
K1
Integrated
functions
This function is called On-/Off-delay. In words the motor is
switched on and off with a programmed delay time.
Symbol for this function is
.
Operation on
device
K2
M
Diagram:
Trg
LOGO! Soft
Comfort V6.1
Q
TH
Application
example
TL
Description of the function:
The time TH starts after a 0 to 1 transition at input Trg. If the status at input Trg is 1 for the
duration of the time TH, the output is set to 1 on expiration of the time TH.
(the output follows the input on delayed). When the status at input returns to 0, TL starts. If
the status at input Trg is 0 for the duration of time TL, the output is set to 0 on expiration of
the time TL.
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Timer – Retentive On-delay
Introduction
Wiring
A look at the circuit diagram shows that the motor M starts
delayed after pressing the pushbutton S1. Pushbutton S2
(n.c. contact) stops the motor again.
S1
K2
S2
This function is called retentive On-delay.
Symbol for this connection is
K1
K1
.
K1
K2
M
Integrated
functions
Operation on
device
Diagram:
Trg
LOGO! Soft
Comfort V6.1
R
Application
example
Q
Ta
T
Description of the function:
The current time Ta starts with a 0 to 1 transition at input Trg. Output Q is set to 1 when Ta
reaches the time T. The output Q is only reset to 0 when the status at input R is 1. Further
switching actions at input Trg have no influence on output Q.
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Timer – Wiping relay (pulse output)
Introduction
Wiring
A look at the circuit diagram shows that the light H1 is only on,
when the switch S1 is closed, but only as long as the set time at
timer T1.
Symbol for this connection is
S1
.
T1
T1
Integrated
functions
H1
Diagram:
Operation on
device
Trg
LOGO! Soft
Comfort V6.1
Ta
Application
example
Q
Description of the function:
When the input Trg is set to 1, the output Q is immediately switched to 1. The current time
Ta starts in LOGO! at the same time and the output remains set. When Ta reaches the value
specified in T (Ta=T), the status of output Q is reset to 0 (pulse output). On input Trg
transition from 1 to 0 before the specified time has expired, the output follows immediately
with a 1 to 0 transition.
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Timer – Edge triggered wiping relay
Introduction
Wiring
A look at the circuit diagram shows that the light H1 remains on
for the time specified on the timer T1 when the switch S1 is
closed.
Symbol for this connection is
T1
S1
.
T1
H1
T1
Integrated
functions
Diagram:
Operation on
device
Trg
LOGO! Soft
Comfort V6.1
Ta
Application
example
Q
T
T
Description of the function:
The output status is switched to 1 after the input Trg is set to 1. Time Ta is started at the
same time. After Ta has reached the value specified in T (Ta=T) the output Q status is reset
to 0 (pulse output). If input Trg changes again from 0 to 1 (retriggering) before the specified
time has expired, the time Ta is reset and the
output remains switched on.
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Timer – Weekly timer
Introduction
Wiring
Integrated
functions
Operation on
device
LOGO! Soft
Comfort V6.1
The output is controlled via a specified on–/
off–date. The function supports any
combination of weekdays. You select the
active weekdays by deselecting the inactive
days.
Mon TueWedThurs Fri Sa So
Cam 1
On
07 : 30
Off
16 05
Cam 2
08 : 00
12 00
Cam 3
10 : 00
12 30
Wednesday
Application
example
Description of the function:
Monday
Every weekly timer has three cams.
You can configure a time hysteresis for
each cam. Within the cam setting you
specify the on/off times.
If you enable “pulse output”, the timer
will be reset after one cycle. “Pulse
output” applies to all three cams.
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Timer – Yearly timer
Introduction
Wiring
Integrated
functions
Operation on
device
LOGO! Soft
Comfort V6.1
Description of the function:
Every yearly timer has an on- and off-timer. At the
specified on-time the yearly timer switches on the output.
At the specified off–time the yearly timer switches off the
output. The off–date specifies the day/year on which the
output is reset to 0 again.
By selecting the option field
 “Monthly”, the timer switches on or off at a specified
day each month.
 “Yearly”, the timer switches on or off each year at a
specified month and day.
 “Pulse Output”, the timer output switches on at the
specified On Time for one cycle. Then it is reset.
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
Application
example
On 05.10
15.05.2005
Logic module LOGO!
Off 10.20
15.05.2005
08.11.2005
08.11.2005
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Timer – Asynchronous pulse generator
Introduction
The pulse profile of the output can be
customized via pulse/ pause ratio.
Symbol for this function is
.
Wiring
Diagram:
Integrated
functions
En
Operation on
device
Inv
LOGO! Soft
Comfort V6.1
Q
pulse period / pause width
Application
example
Description of the function:
In the parameters you can adjust the pulse period and the pause width. With input INV you
can also invert the output. You can customized the time period in seconds, minutes or
hours. The time basis of both parameters can be set independently. The input block INV
only negates the output if it is enabled via EN.
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Timer – Random generator
Introduction
Wiring
With a random generator the output is
switched on and off again within a specified
time.
Symbol for this function is
.
Diagram:
Integrated
functions
Operation on
device
En
LOGO! Soft
Comfort V6.1
Q
Q
Application
example
max. ON delay / max. OFF delay
Description of the function:
With a 0 to 1 transition of the input En a random time e.g. between 0 and 10 seconds is
started. The output is set to 1 on expiration of the on delay time, if the input En is 1 at
least for the duration of the on delay time. The time is reset if the status at input En
returns to 0 before the on delay time has expired. When the input En changes from 1 to
0, a random off delay time between 0 and e.g. 15 seconds is started. The time is reset if
the status at input En returns to 1 before the on delay time has expired.
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Timer – Stairway lighting switch
Introduction
Wiring
The input pulse (edge control) starts a
specified time. The output is reset on
expiration of this time. Prior to the expiration
of this time (e.g. 15 s) an off pre–warning is
generated.
Symbol for this function is
.
Integrated
functions
Diagram:
Trg
Ta
Q
T (OFF delay)
1s
15s
Operation on
device
LOGO! Soft
Comfort V6.1
Application
example
Description of the function:
With a 0 to 1 transition at input Trg, the current time starts and the output Q is set to 1. E.g.
15 s before Ta reaches the time T, the output Q is reset to 0 for a time of 1 s (configurable
time). When Ta reaches the time T, the output Q is reset to 0. When input Trg is switched on
and off again before Ta expires, Ta is reset (retriggering option).
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Timer – Multiple function switch
Introduction
Wiring
Switch with two different functions:
 Pulse switch with off delay
 Switch (continuous lighting)
Symbol for this function is
.
Integrated
functions
Diagram:
Operation on
device
Trg
Q
5s
LOGO! Soft
Comfort V6.1
Application
example
>20s
Description of the function:
The output Q is set to 1 with a 0 to 1 transition of the status at input Trg. When the input Trg
changes to 0 before expiration of the continuous lighting time, the output resets to 0 with
an off delay of e.g. 5 seconds. With a 0 to 1 transition of the status at input Trg and if the
status ’1’ is set at least for the duration of e.g. 20 seconds, the continuous lighting function
is enabled and the output Q is
switched on continuously. If the input Trg is switched once again from 0 to 1 and again to
0, the output Q is switched off.
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Counter – Up and Down counter
Introduction
A look at the circuit diagram shows that the switch S1 triggers the counter pulses. Switch
S2 determines whether the counter increases or decreases. When the counter status
reaches a value >= 5, the light switches on.
Wiring
Diagram:
Integrated
functions
S1
Cnt
Dir
6
Operation on
device
5
4
3
2
6
5
S2
5
4
4
3
3
3
2
2
1
Counter
LOGO! Soft
Comfort V6.1
R
Q
Application
example
1
C1
-
+
0
>=5
H1
Description of the function:
With every positive edge at input Cnt the internal counter increments (Dir = 0) or
decrements (Dir = 1) by one count. Output Q is set to 1 when the internal value is greater
than or equal to the value specified in Par. You can use reset input R to reset the output and
the internal count value to the start value. When R=1, the output is 0 and the pulses at input
Cnt are not counted.
If you set a “Start Value” the counter begins to count either up or down from this value.
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Counter – Hours counter
Introduction
R
En
Wiring
Ral
Integrated
functions
Q
MN = MI
Operation on
device
3
3
2
2
1
MN = 0
1
0
0
4
LOGO! Soft
Comfort V6.1
3
2
1
OT
Application
example
Description of the function:
The hours counter monitors the input En. As long as the status of this input is 1, LOGO!
determines the expired time OT and the time–to–go MN. LOGO! displays the times in
parameter assignment mode. Output Q is set to 1 when the time–to–go MN = 0. Use input R
to reset output Q and time–to–go counter to the specified value MI. The internal counter OT
continues the count. Use input Ral to reset output Q and the time–to–go counter MN to the
specified value MI. The internal counter OT is reset to 0.
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Counter – Threshold trigger
Introduction
The output is switched on and off, depending
on two specified frequencies.
Symbol for this function is
.
Diagram:
Fre > On
Fre > Off Fre < Off Fre < On
Wiring
Q
Fre =12 Fre = 5
Integrated
functions
Fre = 3
Fre = 5
Fre
gate
time
Operation on
device
On = 10 Off = 4
LOGO! Soft
Comfort V6.1
Application
example
Description of the function:
The threshold trigger measures the signals at input Fre. The pulses are captured across a
specified period (gate time).
Output Q is switched on, if the value measured within the gate time is higher than the ON
threshold. Q is switched off again when the threshold drops below OFF.
On
: is the ON threshold. It may be between 0000 and 9999.
Off
: is the OFF threshold. It may be between 0000 and 9999.
Gate time: is the time interval during which the pulses at Fre are measured.
It may be 00.05s and 99.99s.
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Analog – Analog threshold trigger
Introduction
Wiring
Integrated
functions
Operation on
device
LOGO! Soft
Comfort V6.1
Description of the function:
The output is switched on when the analog
value exceeds a specified on threshold. The
output is switched off when the analog value
drops below a specified off threshold
(hysteresis).
This function reads the analog value AI1 to
AI8 as a value between 0 and 1000. The offset
parameter is then added to the analog value.
The result is multiplied by the gain
parameter. Output Q is set to 1 if this value
exceeds the on threshold (On). Q is reset to 0
again after the value drops below the off
threshold (Off).
Diagram:
Application
example
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Analog – Analog comparator
Introduction
Wiring
Integrated
functions
Operation on
device
LOGO! Soft
Comfort V6.1
Description of the function:
The function calculates the difference
between the analog values Ax-Ay. The offset
parameter is added to the difference.
Then the difference is multiplied by the gain
parameter.
If this differential value exceeds the
parameterized threshold, output Q is set to 1.
Q is reset to 0, when the threshold drops
below again.
Diagram:
Application
example
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Analog – Analog differential trigger
Introduction
Wiring
Integrated
functions
Operation on
device
Description of the function:
The function reads the analog value of the
signal at analog input Ax. This value is
multiplied by the gain parameter. The offset
parameter is added to the analog value.
Output Q is set or reset depending on the
specified threshold (On) and the differential
value ( ).
Diagram:
Timing diagram A: Function with negative differential delta value
LOGO! Soft
Comfort V6.1
Application
example
Timing diagram B: Function with positive differential delta value
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Analog – Analog watchdog
Introduction
Wiring
Integrated
functions
Operation on
device
LOGO! Soft
Comfort V6.1
Description of the function:
If the status at input En changes from 0 to 1, then
the analog value of the signal at analog input Ax
will be saved. This saved value is called “Aen”. The
updated values Ax and Aen are each multiplied by
the gain parameter. Then the offset parameter is
added to the analog value. Output Q is set, if the
input En is 1 and the updated value at the input Ax
is outside of the range of Aen +/.
Threshold 1 defines the difference value above Aen,
Threshold 2 defines the difference value below Aen.
Diagram:
Application
example
1
2
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Analog – Analog amplifier
Introduction
Wiring
Integrated
functions
Description of the function:
The function reads the analog value of the
signal at analog input Ax. This value is
multiplied by the gain parameter. Then the
offset parameter is added to the analog value,
i.e. (Ax * gain) + offset = updated value Ax.
Output AQ shows the updated value Ax.
Operation on
device
LOGO! Soft
Comfort V6.1
Application
example
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Analog – PI controller
Introduction
Wiring
Integrated
functions
Operation on
device
LOGO! Soft
Comfort V6.1
Application
example
Description of the function:
If the input A/M is set to 0, then the special function sets
output AQ with the value that is set with parameter Mq.
If the input A/M is set to 1, then automatic mode
commences. As an integral sum the value Mq is
adopted, the controller function begins the calculations
of the formulas.
The updated value PV is used within the formulas.
Updated value PV = (PV * gain) + offset
If the updated value PV = SP, then the function does not
change the value of AQ. With a disturbance, AQ
continues to increase / decrease until the updated value
PV again corresponds to SP. The speed with which AQ
changes depends on the parameters KC and TI. If the
input PV exceeds the parameter Max, then the updated
value PV is set to the value of Max. If the PV falls short
of the parameter Min, then the updated value PV is set
to the value of Min. If the input R is set to 1, then the AQ
output is reset. As long as R is set, the input A/M is
disabled. The sampling time is fixed at 500 ms.
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Analog – PI controller
Introduction
Wiring
Integrated
functions
Operation on
device
LOGO! Soft
Comfort V6.1
Application
example
Parameter:
Sensor: Type of sensor used
Min: Minimum value for PV
Max: Maximum value for PV
Gain: Gain for PV
Offset: Zero offset for PV
SP: Set point assignment
Mq: Value of AQ in manual mode
Parameter sets: applied presets for KC, TI
and Dir
KC: Gain
TI: Integral time
Dir: Action direction of the controller
Number of decimal places in message text
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Analog – PI controller
Introduction
Parameter sets:
To simplify the use of the PI controller, parameters for KC, TI and Dir are preset as
sets for the following applications:
Wiring
Parameter Set
Integrated
functions
Operation on
device
LOGO! Soft
Comfort V6.1
Application
example
Applications
Parameter
KC
Parameter
TI (s)
Parameter Dir
Temperature
fast
Temperature, low temperature control
for small rooms; small volumes
0.5
30
+
Temperature
slow
Heater, ventilation, temperature, low
temperature control for large rooms,
large volumes
1.0
120
+
3.0
5
+
1.2
12
+
1.0
1
+
0.7
20
+
Pressure 1
Pressure 2
Filling level 1
Filling level 2
Fast pressure change,
compressor control
Slow pressure change,
Differential pressure control
(flow control)
Barrel, container filling without
downpipe/ drain
Barrel, container filling with downpipe/
drain
Parameters can manually be specified via the parameter set “User defined”.
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Analog – Ramp
Introduction
Wiring
Integrated
functions
Operation on
device
LOGO! Soft
Comfort V6.1
Application
example
Description of the function:
At the analog output, this special function starts up one of two
levels or offset. Here you can set how quickly the level should
be reached. If the input En is set, then the function issues the
value StSp + offset at output AQ for the first 100 ms.
Then, depending on the connection of Sel, the function runs
from value StSp + offset to either level 1 or level 2 at the
acceleration set in Rate.
If the input St is set, the function runs to the value StSp + offset
at the acceleration set in Rate. Then the function issues the
value StSp + offset at output AQ for 100 ms. Finally offset is
issued at output AQ.
If the input St is set, the function can only be restarted once the
inputs St and En have been reset.
If input Sel has been changed, depending on the connection of
Sel, the function runs from level 1 to level 2 or the other way
round. If the input En is reset, the function immediately issues
offset at output AQ. The analog value at the output is
recalculated every 100 ms.
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Analog - Ramp
Introduction
Wiring
Integrated
functions
Operation on
device
LOGO! Soft
Comfort V6.1
Application
example
Parameter:
Gain: Gain for AQ in message text
Offset: Zero offset for AQ in message text
L1 and L2: Levels to be reached
Largest output value: Maximum value that
must not be exceeded under any
circumstances
Start/ stop offset: value that is issued for
100ms in addition to parameter offset after
starting the function and before reaching the
offset value (prompted by input St). This
parameter is intended for controlling motors.
Speed of change: Acceleration with which level
1, level 2 or offset is reached.
Steps/ second are input.
Number of decimal places in message text
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Analog - Ramp
Introduction
Diagram:
Wiring
Integrated
functions
Operation on
device
LOGO! Soft
Comfort V6.1
Application
example
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Analog – Analog MUX
Introduction
Wiring
Integrated
functions
Description of the function:
This special function outputs one of four predefined analog values or 0 at the analog
output. If input En is set, then the function issues one of 4 possible analog values V1 to V4
at output AQ, depending on the value of S1 and S2. If the input En is not set, then the
function issues the analog value 0 at output AQ. All 4 analog values V1 to V4 can be
parameterized as a reference to another analog function, so the analog values can be
dynamically changed in runtime (e.g. via potentiometer at an analog input).
Operation on
device
LOGO! Soft
Comfort V6.1
Application
example
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Analog – Pulse Width Modulator (PWM)
Introduction
Wiring
Integrated
functions
Operation on
device
LOGO! Soft
Comfort V6.1
Application
example
Description of the function:
The PWM function modulates the analog input
value Ax into a pulsed digital output signal. The
pulse width is proportional to the analog value Ax.
The function reads the value of the signal at the
analog input Ax. This value is multiplied by the
value of parameter A (gain). Parameter B (offset) is
added to the product, as follows:
(Ax * Gain) + Offset = Actual value Ax
The function block calculates the proportion of the
value Ax to the range. The block sets the digital
output Q high for the same proportion of the PT
(periodic time) parameter, and sets Q low for the
remainder of the time period.
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Analog – Pulse Width Modulator (PWM)
Introduction
Calculation rule :
Q = 1, for Ax / (Max - Min) of time period PT
Q = 0, for PT - [Ax / (Max - Min)] of time period PT
Wiring
Note: Ax in this calculation refers to the actual value Ax as calculated using the Gain and Offset.
Min and Max refer to the minimum and maximum values specifed for the range.
Integrated
functions
Example 1:
Operation on
device
LOGO! Soft
Comfort V6.1
Application
example
Periodic time (PT) = 4 sec.
Ax = 500
1) 500 / (1000-0) = 0,5
2) 4 sec. * 0,5 = 2 sec.
Q = 2 sec. high , 2 sec. low
Example 2:
Periodic time (PT) = 10 sec.
Ax = 300
1) 300 / (1000-0) = 0,3
2) 10 sec. * 0,3 = 3 sec.
Q = 3 sec. high , 7 sec. low
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Analog - Analog Math
Introduction
Description of the function:
Wiring
The function combines four values
and three operators to form an
equation. The operator can be any
one of the four standard operators:
+,-,x,/
Integrated
functions
Operation on
device
Operator /
Priority
Value 1
LOGO! Soft
Comfort V6.1
Value 2
Application
example
Value 3
Value 4
For each operator, you must set a
unique priority of High ("H"), Medium
("M"), or Low ("L").
The high operation will be performed
first, followed by the medium
operation and the low operation. The
operand values can reference
another previously-defined function
to provide the value.
You can also configure the behavior
of the function when the Enable
parameter "En"=0.
The function block can either retain
its last value or be set to 0.
The result is an internal analog value
(-32768 - +32767). A result out of
this range causes an overflow-error.
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Analog - Analog Math
Introduction
Examples:
Wiring
Integrated
functions
Operation on
device
LOGO! Soft
Comfort V6.1
Application
example
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Miscellaneous - Analog Math Error Detection
Introduction
Wiring
Integrated
functions
Operation on
device
LOGO! Soft
Comfort V6.1
Application
example
Description of the function:
The analog math error detection block sets the output when the referenced analog math
function block has an error. You can program the function to set the output on a zero
division error, an overflow error, or when either type of error occurs.
If you select the “Automatically reset” checkbox, the output is reset prior to the next
execution of the function block. If not, the output retains its state until the analog math error
detection block is reset with the R parameter.
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Miscellaneous – Latching relay
Introduction
A look at the circuit diagram shows that the coil K1 has current
with the pushbutton S1. The switch K1 closes (latch).
This function is called latching relay.
Wiring
Symbol for this connection is
S1
K1
K1
S2
.
K1
K2
M
Integrated
functions
Diagram:
Operation on
device
S
LOGO! Soft
Comfort V6.1
R
Application
example
Q
Description of the function:
Input S sets output Q, input R resets output Q again.
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Miscellaneous – Pulse relay
Introduction
A look at the circuit diagram shows that the light H1 is switched
on and off with the pushbuttons S1 or S2.
S1
S2
K1
This function is called pulse relay.
Wiring
In words a short pulse at S1 or S2 switches the light H1 on and
off.
Integrated
functions
Symbol for this connection is
.
K1
H1
Diagram:
Operation on
device
Trg
LOGO! Soft
Comfort V6.1
R
Application
example
Q
Description of the function:
Output Q changes its status, i.e. the output is set or reset, with each 0 to 1 transition at
input Trg. You reset the pulse relay to 0 with a signal at input R.
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Miscellaneous – Message text
Introduction
Wiring
Features:
Integrated
functions
 Only one programming tool for basic
module and LOGO! TD
Operation on
device
 Selection / enabling of different
character sets
LOGO! Soft
Comfort V6.1
 Up to 24/32 characters per line
(depending on selected character set)
 Ticker text
Application
example
 Selection of message destination
 Bar graph functionality
 Display state of analog input values
 Digital I/O states
 Display of remaining time of all
timers (except weekly/yearly timer)
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Miscellaneous – Message text
Introduction
Display of a configured message text in run
mode.
Symbol for this function is
.
Wiring
Integrated
functions
Operation on
device
Description of the function:
LOGO! Soft
Comfort V6.1
Application
example
With a 0 to 1 transition of the input signal and
when the system is in RUN, the corresponding
message text is output to the display. The
message text is hidden when the status of the
signal at input changes from 1 to 0. When
multiple message text functions are triggered
with En=1, the message text that has the highest
priority is shown. Changing between the
standard display and the message texts display
is possible by using the keys and
. If
“acknowledge message” is chosen, the
respective message text will be hidden by
pressing any key on LOGO!, if En=0.
Logic module LOGO!
s
Motor on
I:
0..1123456789
234
Alarm!
1..0123456789
Current
Temp
ESC OK
2..01234
97 °C
LOGO
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Miscellaneous – Message text
Selection/enabling of character sets
To be able to use all features of the
message text function in LOGO! ..0BA6,
“Use new feature” must be enabled
(File -> Message text settings).
Introduction
Wiring
LOGO! ..0BA6 supports several languages.
Integrated
functions
To ensure, that all characters of a language
used in a message text can be displayed
correctly, it is necessary to activate an
accordant character set.
Operation on
device
6 character sets are available *)
LOGO! Soft
Comfort V6.1
Application
example
ISO_8859_1
German, English, Italian, Spanish
(partly), Dutch (partly)
ISO_8859_5
Russian
ISO_8859_9
Turkish
ISO_8859_16
French
GBK
Chinese
SJIS *)
Japanese (partly)
*) since E-Stand 3 (ES3)
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Miscellaneous – Message text
Selection/enabling of character sets
Introduction
Wiring
Integrated
functions
Character set 1
(e.g. ISO_8859_1)
Operation on
device
LOGO! Soft
Comfort V6.1
In the same
message text 2
different character
sets can be
selected.
By using the Flag
M27 character set
1 or character set
2 gets activated.
Application
example
Character set 2
(e.g. GBK)
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Miscellaneous – Message text
Settings for the ticker text
Introduction
For the LOGO! on-board display and for LOGO! TD ticker text can be used.
Wiring
You can ticker the text in 2 ways:
 Character by character or
 Line by line
Integrated
functions
Operation on
device
Character by character …
(one character after another tickers through the display)
LOGO! Soft
Comfort V6.1
Application
example
1st
half
2nd
half
… or Line by line.
(the display alternates between the 1st half and the
2nd half of the message text)
Logic module LOGO!
In the function block
message text you can choose
“Character by character” or
“Line by line” and enable one
or more lines which shall be
tickered.
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Miscellaneous – Message text
Settings for the ticker text
Introduction
Wiring
The ticker speed can be adjusted via the menu item File -> Message Text Settings -> Ticker
Timer Setting .
You can set the speed for “Character by character” in milliseconds. This time has also
effect to the time for “Line by line” (Character by character x10).
Integrated
functions
Operation on
device
LOGO! Soft
Comfort V6.1
Application
example
“Message destination” is another
properties parameter in the function
block message text:
Here you can decide, on which device
the message text shall appear:
 LOGO! on-board display
 LOGO! TD
 Both displays
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Miscellaneous – Message text
Inserting bar graphs
Introduction
Wiring
Example 1:
Step 1: Click at
„Insert a bar graph into the message“
Step 2: Select a function block which
is already placed in the circuit
diagram to indicate its value.
Integrated
functions
Operation on
device
LOGO! Soft
Comfort V6.1
Application
example
Step 3: Scale the bar graph by defining
the range of the value, bar graph size
and its direction on the display.
The vertical adjustment of the
bar graph is from the bottom
to the top !
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Miscellaneous – Message text
Inserting bar graphs
Introduction
Wiring
Integrated
functions
Example 2:
The analog value of a temperature
sensor (PT100) is to be indicated over
its entire measuring range as bar
graph horizontally in the message
text.
Operation on
device
The horizontal adjustment of the bar
graph is from left to right !
LOGO! Soft
Comfort V6.1
Application
example
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Miscellaneous – Message text
Status indication of the analog input values
2 analog input values (AI)
can be displayed in one
message text if they are
used in the circuit diagram.
Introduction
Wiring
The value is updated
according to the “analog
input filter timer”.
Integrated
functions
Operation on
device
LOGO! Soft
Comfort V6.1
Application
example
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Miscellaneous – Message text
Analog input filter timer
Introduction
Wiring
Integrated
functions
Operation on
device
If an analog input value is indicated in a
message text, via the menu item
File -> Message Text Settings can be
defined, how often LOGO! refreshes the
analog values in a message text.
LOGO! Soft
Comfort V6.1
Application
example
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Miscellaneous – Message text
Status indication of the digital inputs/outputs
Introduction
You can assign names such as "On" or "Off" to the two states of a digital input or output.
With the LOGO! 0BA6 series, you can display this name of a digital I/O state in a message
text.
Wiring
Example:
Integrated
functions
Operation on
device
Step 1:
Place 1 input, 1 output and an enabled
message text in your circuit diagram.
LOGO! Soft
Comfort V6.1
Application
example
Step 2:
Open message text with a double click,
define area for the status indication of
“I1” with a mouse click and select
“ON/OFF” button.
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Miscellaneous – Message text
Status indication of the digital inputs/outputs
Step 3:
Introduction
Select “Digital Inputs”
Wiring
Integrated
functions
Operation on
device
LOGO! Soft
Comfort V6.1
Application
example
Step 4:
Automatically the first input “I1” is
selected.
Type in a text you want to display for both
states of “I1”.
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Miscellaneous – Message text
Status indication of the digital inputs/outputs
Introduction
Step 5:
Do the same for “Digital Outputs” and
display the state of “Q1”.
Wiring
Integrated
functions
Now try out the program in simulation mode!
Operation on
device
LOGO! Soft
Comfort V6.1
Application
example
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Miscellaneous – Message text
Static editor (Edit manually)
Introduction
Wiring
Integrated
functions
Operation on
device
LOGO! Soft
Comfort V6.1
Application
example
LOGO! Soft Comfort V6.1 provides a static
editor for message texts that can help when you
need to reposition text elements.
For example, it has a “recycle bin” area where
you can temporarily move message text
elements in order to rearrange the position of
elements on the display area. You can move
elements up, down, left, or right without
changing the position of any other elements.
To use the static editor, click the "Edit
manually" button. You will also be prompted to
edit manually if you try to place or move
elements in the message area that have a
position conflict with existing elements.
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Miscellaneous – Softkey
Introduction
Wiring
Integrated
functions
Operation on
device
LOGO! Soft
Comfort V6.1
Application
example
Description of the function:
Diagram:
This special function has the effect of a
mechanical pushbutton or switch. In parameter
assignment mode, the output is set with a signal
at input En, if the ’’Switch” parameter is set to
“On” and confirmed with OK. Whether the
function was configured for pushbutton or
switching action is of no concern here. The
output is reset to “0” in the following three
cases:
 After a 0 to 1 transition at input En.
 When the function was configured for
momentary pushbutton action, and one
cycle has expired since it was switched on.
 When the position “Off” was selected at the
“Switch” parameter and confirmed with OK
in parameter assignment mode.
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Miscellaneous – Shift register
Introduction
Wiring
Integrated
functions
Operation on
device
LOGO! Soft
Comfort V6.1
Description of the function:
Diagram:
The function reads the value at input In with a
positive edge at input Trg. This value is
applied to shift register bit S1 to S8,
depending on the shifting direction:
Shift up: The value at input In is set at S1; the
previous value at S1 is shifted to S2; the
previous value at S2 is shifted to S3 etc.
Output Q returns the value of the configured
shift register bit. If retentivity is disabled, the
shift function restarts at S1 to S8 after a
power failure. When enabled, retentivity
always applies to all shift register bits.
S4 = Q (example)
Shift
up
Shift
down
Application
example
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Operation on device
Introduction
Have you designed a circuit?
Do you want to enter it into LOGO! ?
How do you do this?
Wiring
s
Integrated
functions
Operation on
device
Connect LOGO! to the power supply and
switch it on. The display now shows you
this message.
No Program
Press ESC
ESC OK
LOGO!
LOGO! Soft
Comfort V6.1
Application
example
s
Press ESC to get to the main menu.
> Program..
Card..
Setup..
Start
ESC OK
LOGO!
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
s
Main menu / programming menu
Introduction
Wiring
> Program..
Card..
Setup..
Start
The first character in the first line is the ”>” cursor.
Press
to move the ”>” cursor up and down.
Move it to “Program..” and confirm with OK .
LOGO! opens the programming menu.
Integrated
functions
> Edit..
Clear Prg
Password
Msg Config
Operation on
device
LOGO!
s
LOGO! Soft
Comfort V6.1
Application
example
Here you can also move the ”>” cursor by pressing
Move the ”>” cursor to ”Edit..” and confirm with OK .
In the next sub-menu please chose “Edit Prg.” You are
now in programming menu.
Press
to select all output, marker and open
connectors.
The following applies when you edit a circuit: ....
Logic module LOGO!
ESC OK
LOGO!
s
.
> Edit Prg
Edit Name
AQ
Memory?
LOGO!
s
B1
ESC OK
ESC OK
Q1
ESC OK
LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
LOGO! - rules for operation
Introduction
Wiring
1. You have to create your
circuit by working from the
output to the input.
I1
Q1
I
Q
Integrated
functions
B002
Q1
&
Q
Operation on
device
LOGO! Soft
Comfort V6.1
2. You can connect an output
to several inputs.
B002
>
Application
example
B002
3. You can’t connect an output to
an upstream input within the
same path (recursion).
Logic module LOGO!
&
B001
Q2
&
Q
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
LOGO! - rules for operation
Introduction
Wiring
4. You can move the cursor with
underscore ( _ ) :
if it appears in the form of an
Integrated
functions
Operation on
device
LOGO! Soft
Comfort V6.1
Application
example
B02
1
I3
B01
x
B02
I1
x
Logic module LOGO!
B01
&
Q1
x
B02
I1
B01
&
Q1
B01 Q1
B01 Q1
x
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
LOGO! - rules for operation
Introduction
Wiring
5. When the cursor appears as a solid square ( ), press with
to select a connector (Co), a basic function (GF) or a special function:
Integrated
functions

Operation on
device

Confirm with OK .
Press ESC to return to the
previous step.
B1
In1
In2
In3
In4
&
Q1
SF
Q1
LOGO! Soft
Comfort V6.1
B1
Application
example
I1
In2
In3
In4
B1
&
Q1
OK
Co
In2
In3
In4
&
Q1
B1
B1
OK
In1
In2
In3
In4
&
Q1
OK
In1
In2
In3
In4
&
Q1
&
Q1
Logic module LOGO!
GF Q1
B1
B1
I2
In2
In3
In4
OK
In1
In2
In3
In4
>1
Q1
Co Q1
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Your first LOGO! program
Introduction
Wiring
Integrated
functions
Let us now take a look at the following parallel circuit consisting of two switches.
Circuit diagram
•
•
S1
•
Operation on
device
K1
LOGO! Soft
Comfort V6.1
Application
example
•
K1
S2
The load is switched on with S1 or S2.
E1
•
•
Solution with LOGO!
I1
I2
X
X
>1
Logic module LOGO!
Q1
LOGO! interprets the parallel circuit of
S1 and S2 as an ’OR’ logic, because S1
or S2 switches on the output.
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Wiring
Introduction
• ••
L1
N
S1 switches input I1, while S2 switches
input I2. The load (E1) is
connected to the relay Q1.
Wiring
S1
Integrated
functions
S2
L1 N I1 I2 I3 I4
Operation on
device
I5 I6 I7 I8
s
LOGO! Soft
Comfort V6.1
Q1
Application
example
ESC OK
LOGO! 230RC
•
Q1
L1
Q2
Q3
Let us now input the program (starting at
the output and working towards the
input). LOGO! initially shows the output
Q1. You will see an underscore ( _ )
below the Q in Q1. It is called a cursor.
The cursor indicates your current
position in the program.
Q4
E1
N
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Program input
Introduction
s
Now press the key
.
The cursor moves to the left.
Wiring
Q1
Integrated
functions
Operation on
device
ESC OK
The cursor indicates your current
position in the program. At this point you
only enter the first block (the OR block).
Press OK to select editing mode.
LOGO!
s
LOGO! Soft
Comfort V6.1
Q1
ESC OK
Application
example
LOGO!
s
The cursor is displayed as a solid square
( ):
Selected between the following by
pressing
:
 Connector (Co)
 Basic function (GF)
 Special function (SF)
Logic module LOGO!
Co
Q1
ESC OK
LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Program input
Introduction
s
Select with (GF) the basic functions and
confirm with OK .
Wiring
GF
ESC OK
Integrated
functions
Operation on
device
LOGO! Soft
Comfort V6.1
Application
example
Q1
LOGO!
s
The AND is the first block of the basic
functions (GF) list.
You can choose between the following by
pressing
:
 AND
 AND (edge)
 NAND
 NAND (edge)
 OR
 NOR
 XOR
 NOT
Select the OR block ( >1 ) and confirm with
OK
.
Logic module LOGO!
B1
In1
In2
In3
In4
>1
Q1
ESC OK
LOGO!
s
In1
In2
In3
In4
B1
>1
Q1
ESC OK
LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Program input
s
Introduction
Wiring
Integrated
functions
Operation on
device
LOGO! Soft
Comfort V6.1
Application
example
B1
You have now entered the first block. Each
new block is automatically assigned a
block number (B1). Now you interconnect
the block inputs (B1).
Co
In2
In3
In4
Press OK .
LOGO!
The cursor is displayed as a solid square
( ):
You can choose between the following by
pressing
:
 Connector (Co)
 Basic functions (GF)
 Special functions (SF)
Please select Connector (Co) and confirm
with OK .
The first element of the list (Co) is input I1
Confirm with OK . The underscore cursor
automatically jumps to the next input (In2)
that needs to be allocated.
>1
Q1
ESC OK
s
B1
I1
In2
In3
In4
>1
Q1
ESC OK
LOGO!
s
I1
In2
In3
In4
B1
>1
Q1
ESC OK
LOGO!
Logic module LOGO!
.
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Program input
s
Introduction
Wiring
Integrated
functions
Operation on
device
LOGO! Soft
Comfort V6.1
Application
example
Now you connect input I2 to the input of
the OR block. You already know how to do
this:
1. Switch to editing mode: Press OK
2. To select the Co list: Press
3. To confirm the Co list: Press OK
4. To select I2: Press
5. To apply I2: Press OK
We do not need the last two inputs of the
OR block for this program. In the LOGO!
program you mark the unused inputs with
an ’X’. The process is the same:
1. Switch in editing mode: Press OK
2. To select the Co list: Press
3. To accept the Co list: Press OK
4. To select X: Press
5. To apply X: Press OK
B1
I1
Co
In3
In4
>1
Q1
ESC OK
LOGO!
s
B1
I1
I2
In3
In4
>1
Q1
ESC OK
LOGO!
s
I1
I2
X
X
B1
>1
Q1
ESC OK
LOGO!
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
s
Program start
I1
I2
X
X
Introduction
Wiring
Integrated
functions
Operation on
device
LOGO! Soft
Comfort V6.1
Application
example
Now all block inputs are connected. For
LOGO! the program is complete.
You can review your first program by
pressing the cursor with the 4 arrow keys
( _ ) and moving through the program.
We now exit program input mode and
return to the programming menu with ESC .
The program is automatically saved in the
internal memory (E2PROM).
To start the program, return to the main
menu with ESC .
Move the cursor to “Start”: Press
confirm press OK .
. To
B1
>1
Q1
ESC OK
LOGO!
LOGO!
s
> Edit Prg
Edit Name
AQ
Memory?
LOGO!
s
> Edit..
Clear Prg
Password
Msg Config
ESC OK
ESC OK
s
Program..
Card..
Setup..
> Start
ESC OK
LOGO!
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
LOGO! in RUN mode
Introduction
Wiring
Integrated
functions
Operation on
device
LOGO! Soft
Comfort V6.1
Application
example
Let us have a look at our example:
In RUN mode LOGO! shows the
following display:
L1
Status of inputs
1  Input I status is „1“
1  Input I status is „0“
Status of outputs
1  Output Q status is „1“
1  Output Q status is „0“
• •
•
S1
Tu 09:14
2009-09-22
The window to the left displays time and date.
The window in the middle displays the inputs
states (I1 to I9; I10 to I19; I20 to I24).
The window to the right displays outputs
states (Q1 to Q9; Q10 to Q16).
Also the internal values of all analog
inputs/outputs can be displayed.
=1 =0
S2
I:
0.. 1 23456789
1.. 0123456789
2.. 01234
Q:
0.. 1 23456789
1..0123456
AI :
=1
Q1
N
•
When switch S1 is closed, input I1 is supplied with voltage and the status at input I1 is “1”.
LOGO! program calculates the status for the outputs.
Output Q1 is “1”, in this case.
When Q1 is “1”, LOGO! sets relay Q1, and the load connected to Q1 is supplied with
voltage.
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
LOGO! parameterization mode
Introduction
LOGO! 12/24 RC
s
Parameterization of functions:
Wiring
Integrated
functions
Operation on
device
LOGO! Soft
Comfort V6.1
Application
example
When speaking of parameterization, we refer
to the
configuration of functions.
You can configure the parameters
 in programming mode
or
 in parameter assignment
mode
You can configure:
 the delay times of timer functions
 the switching times of timer switch
 counter thresholds
 the monitoring interval for a hour counter
 on and off threshold for a trigger threshold
 and some other functions
To get to configuration mode press ESC
in RUN mode, set the cursor to Set Param
and confirm with OK .
Logic module LOGO!
I:
0.. 123456789
1..0123456789
2..01234
ESC OK
LOGO!
LOGO! 12/24 RC
s
Stop
> Set Param
Set..
Prg Name
ESC OK
LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
LOGO! parameterization mode
s
Introduction
Wiring
Integrated
functions
Operation on
device
LOGO! Soft
Comfort V6.1
Block selection:
Choose In parameterization mode the desired
block with
.
If the desired block is chosen, press OK . The
cursor jumps to the first parameter that can be
modified. The value can be changed pressing the
arrow keys
.
If the desired value is configured, then press OK .
The next blocks requiring modification, can be
chosen with
etc..
B2
T =10:00s
Ta =00:00
ESC OK
LOGO!
s
B2
T =15:00s
Ta =00:00
ESC OK
Application
example
LOGO!
s
B2
T =15:00s
Ta =00:00
ESC OK
LOGO!
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
LOGO! parameterization mode
Introduction
To return to menu press ESC .
B2LOGO!
T =10:00s
Ta =00:00
Wiring
Integrated
functions
Operation on
device
LOGO!
s
ESC OK
LOGO!
To return to RUN mode press ESC .
s
LOGO! Soft
Comfort V6.1
> Stop
Set Param
Set..
Prg Name
Application
example
LOGO!
ESC OK
s
I:
0.. 123456789
1..0123456789
2..01234
ESC OK
LOGO!
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
LOGO! ..0BA6 – setting the menu language
Introduction
Wiring
Integrated
functions
Operation on
device
LOGO! Soft
Comfort V6.1
You can select the menu language via the
LOGO! menu and acknowledge with OK
(LOGO! must be in Stop-mode).
Available languages:
 EN – English
 IT – Italian
 NL – Dutch
 ES – Spanish
 FR – French
 CN – Chinese
 DE – German
 TR – Turkish
 RU – Russian
 JP – Japanese *)
Application
example
s
Program..
Card..
> Setup..
Start
ESC OK
LOGO!
s
Clock..
LCD..
> Menu Lang
BM AI NUM
ESC OK
LOGO!
s
> EN
This setting can be separately done for
LOGO! TD .
ESC OK
*) since E-Stand 3 (ES3)
Logic module LOGO!
LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
s
LOGO! ..0BA6 – backlight function
Introduction
Program..
Card..
> Setup..
Start
Backlight function for the basic module:
s LOGO!
Wiring
Integrated
functions
Clock..
> LCD..
Menu Lang
BM AI NUM
To activate the backlight of the
LOGO! display permanently, follow
these steps.
Operation on
device
ESC OK
sLOGO!
Contrast
> BackLight
LOGO! Soft
Comfort V6.1
Application
example
ESC OK
You can select between:
 Default (Backlight is ON for 20 sec.
or controlled by user program)
 Always On
This setting can be separately done for
LOGO! TD .
Logic module LOGO!
ESC OK
sLOGO!
> Default
ESC OK
LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
LOGO! TD parameterization mode
Introduction
In the menu of LOGO! TD nearly the same menu items are available as in the
menu of LOGO! basic module - except the possibility to edit the program.
Wiring
Integrated
functions
> Stop
Set Param
Msg Config
Set..
The following table shows on which device
which menu items are available …
Operation on
device
Menu item
LOGO! Soft
Comfort V6.1
LOGO! Basic module
LOGO! TD
Program..
√
-
Card..
√
-
Setup..
√
√
LCD Contrast / Backlight
√
√
Menu language
√
√
2 or 4 AI used on basic module
√
-
Start / Stop
√
√ *)
√
√
√
In STOP mode
Application
example
In RUN mode
Set Param
Msg Config (e.g. Tick Time)
-
*) Since E-Stand 4 (ES4) of LOGO! and LOGO! TD, switching into stop mode can be protected by password.
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
LOGO! program creation
on a PC with LOGO! Soft Comfort V6.1
Introduction
Wiring
Integrated
functions
Support for LOGO! TD
 No separate software necessary
Modem wizard
 for standard 11-bit analog modems
Windows Look and Feel
 e.g. context menu, toolbar
Create the control programs by „drag and drop“
Operation on
device
LOGO! Soft
Comfort V6.1
Application
example
 Control programs „drawing“ –
directly on a PC in FBD or LAD
Testing of control programs
 Offline simulation with status for each function
(color change) and forcing
 Online test in FBD and LAD with color change
for each function and 30 actual values
Professional print and documentation functions
Device selection
 0BA0, 0BA1, 0BA2, 0BA3, 0BA4, 0BA5, 0BA6
with function check
Additionally on the CD ROM:
Manual and 28 complete, usable examples
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Installing LOGO! Soft Comfort V6.1
Introduction
Wiring
Integrated
functions
2.
Operation on
device
LOGO! Soft
Comfort V6.1
3.
Application
example
1.
2.
3.
Insert CD (LOGO! Soft Comfort V6.1) in CD-ROM drive
Display CD content with help of Explorer
Double click on start.html
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Installing LOGO! Soft Comfort V6.1
Introduction
Wiring
Integrated
functions
Start.html functions

Direct choice of 10 languages

Software installation

Direct start of software from CD-ROM

Display manuals on CD-ROM

Display online help

Choice of example programs on CD-ROM

Choice of CAD drawings on CD-ROM

Installation of necessary tools such as
Acrobat Reader or printer drivers
Operation on
device
LOGO! Soft
Comfort V6.1
Application
example
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Installing LOGO! Soft Comfort V6.1
Introduction
Wiring
Integrated
functions
The USB cable driver for the LOGO! USB programming cable is also included on the
CD-ROM. During the installation process of LSC V6.1 you will be asked if you want to install
the driver.
HINT: Follow the correct order !
1.
Install the driver (administrator privileges are required!)
2.
Then connect the LOGO! USB programming cable with your PC
Operation on
device
LOGO! Soft
Comfort V6.1
Application
example
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
LOGO! Soft Comfort V6.1 : Overview
Standard Windows
PC -> LOGO! LOGO! -> PC!
Introduction
Title bar
Wiring
Integrated
functions
Operation on
device
Menu bar
Symbol bar for
program installation
Tree structure for fast choice
of all generation elements
Switch to selecting mode
Drawing of connection lines
LOGO! Soft
Comfort V6.1
Display connectors (Co)
Display basic functions (GF)
Application
example
Display special functions (SF)
Text fields for additional
comments
For a better overview
separation of connections
Offline simulation
Online test
Control program generation in the overview control plan via drag & drop
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Help functions – online help
Introduction
The general help can be activated
via the menu item Help ->
Content. You can find further
information sorted by functional
groups in the contents.
Wiring
Integrated
functions
Operation on
device
LOGO! Soft
Comfort V6.1
Application
example
With a mouse click on the
desired topic you get detailed
information about the
corresponding functional
group.
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Help functions – direct help
Introduction
Wiring
Integrated
functions
Direct help can be selected
via the context menu (right
mouse key) of each function.
Operation on
device
LOGO! Soft
Comfort V6.1
Application
example
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Help functions – direct help
Introduction
The direct help will also be
activated via the menu item
Help -> Context-sensitive Help.
Via mouse pointer you can
now select objects, you would
like to have help text with.
Wiring
Integrated
functions
Operation on
device
LOGO! Soft
Comfort V6.1
Application
example
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Help functions – Update Center
Introduction
You can install program expansions,
service packs and additional
languages via the menu item Help ->
Update Center.
Wiring
Integrated
functions
Operation on
device
LOGO! Soft
Comfort V6.1
Application
example
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Typical tasks for LOGO!
Introduction
Wiring
Q1
(drinking water supply)
Cistern control
When the water level drops below the level (I1),
the drinking water supply (Q1) shall automatically
be switched on. When the water level has
reached the level (I2), the drinking water supply
shall automatically be switched off again.
Integrated
functions
I3 (Pump OFF)
Operation on
device
LOGO! Soft
Comfort V6.1
Application
example
I2
(drinking water
supply OFF)
I1
(drinking water
supply ON)
I4
(Pump
OFF)
Logic module LOGO!
P
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Step 1: Insert connectors (CO)
Introduction
How many inputs and outputs are necessary to solve the task?
Wiring
Integrated
functions
Within the tree structure on the left side of
the software you can choose quickly and
clearly all necessary input and output blocks,
markers or constants (high, low) and all basic
and special functions and you can place them
on the configuration interface.
1.
Operation on
device
LOGO! Soft
Comfort V6.1
After having chosen an element the following
cursor will appear on the configuration
interface:
Application
example
2.
Logic module LOGO!
Move the mouse to the desired position.
Clicking on the left mouse button inserts the
block.
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Step 2: Insert basic functions (GF)
Introduction
Which basic functions are necessary to solve the task?
Wiring
Integrated
functions
Operation on
device
LOGO! Soft
Comfort V6.1
Application
example
2.
1.
Logic module LOGO!
After placing both inputs I1 and I2 and the
output Q1 on the interface a basic function
(NOT) is necessary. As already learned in
the first step you choose via the tree
structure on the left the appropriate
function and place it via a simple mouse
click.
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Step 3: Insert special functions (SF)
Introduction
Which special functions are necessary to solve the task?
Wiring
Integrated
functions
Operation on
device
LOGO! Soft
Comfort V6.1
2.
Application
example
1.
Logic module LOGO!
As the last function element a special
function (latching relay) is also necessary. As
already learned in the previous steps you
choose via the tree structure at the left the
appropriate function and place it via simple
mouse click.
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Step 3: Insert special functions (SF)
Introduction
In this programming example the NOT function block could be replaced by a direct negation
of the S-input of the latching relay function.
Wiring
Integrated
functions
Operation on
device
LOGO! Soft
Comfort V6.1
Application
example
Via the context menu (right mouse button) on
the digital input pins of all function blocks it
is possible to negate the signal directly. This
is also possible by a double click on the pin.
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Step 4: Connecting
Introduction
To complete the control circuit you need to connect the blocks with one another:
Wiring
Integrated
functions
Operation on
device
1.
LOGO! Soft
Comfort V6.1
2.
Application
example
Normally you can directly draw the connection line with the cursor
after placing a block. If you are in a different mode, you will have to
select the tool
to get to the connecting mode.
Now move the cursor over the connection pin of a block (a small blue
box will be shown) and click the left mouse key. While holding down
the key move the cursor to the pin you would like to connect with the
first pin, and release the mouse key. The connection is drawn.
Continue the same way with the other connections.
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Step 5: Insert text fields
Introduction
By inserting text fields the program can be understood more easily.
With LOGO! Soft Comfort V6.1 there are several ways of embedding text into the program
structure:
Wiring
Adding a comment to each block in the
program via the context menu (right
mouse key).
Integrated
functions
Operation on
device
LOGO! Soft
Comfort V6.1
Application
example
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Step 5: Insert text fields
Introduction
Wiring
By inserting a free text field.
Integrated
functions
Operation on
device
LOGO! Soft
Comfort V6.1
1.
A
Application
example
2.
Logic module LOGO!
3.
4.
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Step 6: Assigning connection names
Introduction
For better program readability, comprehensive names can be assigned to inputs and
outputs in addition to the text fields.
Wiring
Integrated
functions
Operation on
device
LOGO! Soft
Comfort V6.1
Application
example
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Step 7: Moving elements
Introduction
Wiring
The control program is completed with insertion of function blocks and their connections.
To get a reasonable, i.e. a clear view of the prepared control program, some further work is
necessary. Placed objects such as function blocks, lines, and text fields can be moved
accordingly.
Integrated
functions
This tool
has to be
selected, when you want to
move function blocks, text
fields or connection lines.
Operation on
device
LOGO! Soft
Comfort V6.1
Application
example
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Step 8: Aligning
Introduction
To design everything more neatly and more clearly, you can align the individual function
blocks vertically and horizontally.
Wiring
This button
has to be activated to
align the highlighted function blocks
vertically.
Integrated
functions
Operation on
device
LOGO! Soft
Comfort V6.1
Application
example
Firstly the function blocks must be
selected to align them.
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Step 9: Parameterization of blocks
Introduction
With special functions and basic functions in addition to the dialogues for comments there
also exists one or more dialogues for parameters. Here you can preset set points or
settings for each particular function block.
Wiring
Integrated
functions
Operation on
device
LOGO! Soft
Comfort V6.1
Application
example
Select function block, click right mouse
key and select menu item Block attribute.
OR
Double click with left mouse key on the
function block.
Logic module LOGO!
In the configuration another
address can be allocated for each
single input and output block.
Only inputs and outputs are
regarded in the selection when
they are not yet assigned in the
control program.
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Step 9: Parameterization of blocks
Introduction
Additionally there is the possibility to change and check all block attributes centrally.
Wiring
Integrated
functions
Operation on
device
LOGO! Soft
Comfort V6.1
Application
example
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Step 10: Formatting texts
Introduction
Comments and text fields can be given user-designed formatting.
Wiring
Integrated
functions
Operation on
device
LOGO! Soft
Comfort V6.1
Application
example
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Step 11: Documentation
Introduction
For program documentation all used connectors, basic functions and special functions can
be displayed.
Wiring
Integrated
functions
Operation on
device
LOGO! Soft
Comfort V6.1
Application
example
A list of all used blocks can be displayed via the menu item Edit
-> Go to block. The list comprises information about block
number and block type. You can display e.g. which special
functions you have used. The abbreviations of the block I1, Q2,
B02, etc. can be entered in the search function (block number)
and it will be displayed where the block is located in the list.
When you complete the dialog field with OK, the desired block
will be highlighted in the program.
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Step 11: Documentation
Introduction
Further information about the program documentation can be viewed via the information
window. It is shown at the bottom window frame by default.
Wiring
Integrated
functions
Operation on
device
LOGO! Soft
Comfort V6.1
Application
example
You can access the information window
anytime via the menu item View -> Info
Window or the F4 key. In the information
window the resources used in the program,
are displayed with current date and time.
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Step 11: Documentation
Introduction
Program and plant information can be entered under File -> Attributes on the properties
dialogue General. They appear in the program printout in the footer.
Wiring
Integrated
functions
Operation on
device
LOGO! Soft
Comfort V6.1
Application
example
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Step 11: Documentation
Introduction
The program including the entered plant data can be viewed from the attribute window
under File -> Print preview.
Wiring
Integrated
functions
Operation on
device
LOGO! Soft
Comfort V6.1
Application
example
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Step 11: Documentation
Introduction
You can select which documents shall be printed, under Properties… in the print preview
window. By default the circuit diagram, the parameter list and the list with connection
names are selected.
Wiring
Integrated
functions
Operation on
device
LOGO! Soft
Comfort V6.1
Application
example
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Step 11: Documentation
Introduction
It makes sense to divide the circuit diagram onto more pages for larger or more complex
programs.
Wiring
Integrated
functions
Operation on
device
LOGO! Soft
Comfort V6.1
Application
example
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Step 11: Documentation
Introduction
Due to the split-up of the program across several pages, connection lines might have to be
separated.
Wiring
Integrated
functions
Operation on
device
LOGO! Soft
Comfort V6.1
Application
example
Connections can easily be separated by selecting the scissor symbol. The interfaces are
clearly labeled with the page number, block number and input pin. Clicking a second time
with the scissor symbol on one of the interface placeholders undoes the separation.
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Step 12: Program testing
Introduction
After configuration and documentation, program testing via offline simulation is the next
step.
Wiring
Integrated
functions
Operation on
device
LOGO! Soft
Comfort V6.1
Application
example
Now you know that the program can be run in LOGO!, but you still have to check whether
your program works the way you intended it. Perhaps you would like to change some
parameters. You can effortlessly change input values, check the behavior upon power
failure and compare your calculations or expectations with the real behavior of the outputs.
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Step 12: Program testing
Introduction
An excellent tool is available for program testing.
Wiring
Integrated
functions
Operation on
device
LOGO! Soft
Comfort V6.1
Application
example
By clicking on the
buttons on the tool
bar or on the inputs in
the circuit diagram
you can change the
status of the inputs.
The signal run can be
tracked with the color
change from blue (low
signal) to red (high
signal) of the
connection lines. This
makes error tracking a
lot easier.
Logic module LOGO!
This tool
has to be selected when
you want to test the
program. With the
activation of the offline
simulation a tool bar for
monitoring and operation
of inputs and outputs is
selected. A plug symbol
provides a simulation of
power failure to test the
behavior in regards to
retentivity.
For time-critical simulations you can also set
the output of a block (forcing), by clicking the
output with the right mouse button.
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Step 12: Program testing
Introduction
As an additional program testing feature, each input can be allocated to a certain switch
function.
Wiring
Integrated
functions
Operation on
device
LOGO! Soft
Comfort V6.1
Application
example
Each input of a block can be allocated to a certain switch function via the context menu
(right mouse key) of an input block. You can chose between pushbutton (n.o. contacts, n.c.
contacts), switches and frequency inputs at digital inputs. With frequency inputs the
simulated frequency can be adjusted in Hz. With analog inputs the value range and the start
value is preset. These parameters can centrally be changed and reviewed as well via the
menu item Tools -> Simulation parameters.
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Step 13: Assign program password
Introduction
To protect the program and your know how you can place a valid up to 10-digit password
for that program.
Wiring
Integrated
functions
Operation on
device
LOGO! Soft
Comfort V6.1
Application
example
This password protects your program only on LOGO!. There you can not delete, change or
view it without the password! To load a password protected program onto a PC, the
password is necessary as well. To delete an assigned password, enter Old password and
leave New Password empty.
To be able to reuse a LOGO! with program and password when password is lost, the
password has to be entered incorrectly three times at program deletion. Then the program
and the PW is automatically deleted. This can alternatively be done by software. *)
*) since E-Stand 4 (ES4) only possible via software or memory card
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Step 14: Transfer program to LOGO!
Introduction
Wiring
With LOGO! Soft Comfort V6.1 you have the possibility to either first realize your circuit
diagram and then determine the required device via menu item Tools -> Determine LOGO!
or you can firstly determine via Tools -> Select Hardware which LOGO! device you want to
create your circuit diagram for.
Integrated
functions
Operation on
device
LOGO! Soft
Comfort V6.1
Application
example
In the device choice you can view for every
LOGO! generation which resources are
available. All available function blocks or
resources are offered in configuration mode
depending on the selected version.
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Step 14: Transfer program to LOGO!
Introduction
After testing the program successfully you need to transfer it to the LOGO!. Therefore
LOGO! has to be connected with the PC cable to the PC.
Wiring
Integrated
functions
Operation on
device
LOGO! Soft
Comfort V6.1
Application
example
Upon successful transfer a
message appears in the status
bar.
You have to click on this
button
to transfer a circuit diagram to
LOGO!. Before transferring,
the LOGO! version required for
the configured circuit program,
is identified. If the configured
circuit program cannot be
transferred to the available
LOGO!, an error message is
displayed and the transfer is
aborted.
If the connection between LOGO! and PC is not
established correctly, an error message will be
displayed.
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Step 15: Starting LOGO!
Introduction
Wiring
Integrated
functions
Operation on
device
After transferring the program LOGO! has to be set to RUN-mode. Then the program can be
tested in real life.
s
LOGO! 12/24 RC
s
> Program..
LOGO! 12/24 RC
Program..
s
LOGO! 12/24 RC
I:
Card..
Card..
0.. 123456789
Setup..
Setup..
1..0123456789
Start
ESC OK
LOGO!
2..01234
> Start
ESC OK
LOGO!
LOGO! Soft
Comfort V6.1
ESC OK
LOGO!
Q1
Application
example
I3
I2
I1
I4
Logic module LOGO!
P
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Step 16: Online-Test
Introduction
Additional to the offline simulation an online test can be done in FBD and LAD after
transferring the program to the LOGO! device.
Wiring
Integrated
functions
Operation on
device
LOGO! Soft
Comfort V6.1
Application
example
1.
Logic module LOGO!
3.
2.
To start the online test after
transferring the program this
button has to be activated
.
After this the LOGO! device
can be set into RUN-mode with
this button
.To see now the
online-status off the device the
eyeglasses-symbol has to be
activated
. Now you can
simulate your program online
on the device by using the real
inputs.
If you have to watch function
blocks which contain actual
values, you have to click at the
eyeglasses-symbol below the
respective block separately,
e.g.:
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Step 17: Setting the clock
Introduction
With help of the software you can set the system clock of LOGO! as well. Of course, you
can also set the time directly on the device.
Wiring
Integrated
functions
Operation on
device
LOGO! Soft
Comfort V6.1
Application
example
LOGO! and PC have to be connected via
the PC cable to transfer the set time to
LOGO!, then you have to click on the
button Write.
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Step 17: Setting the clock
Introduction
With LOGO! you have the possibility to configure an automatic summer / winter clock
change. You can do this on the software or directly on the device.
Wiring
Integrated
functions
Operation on
device
LOGO! Soft
Comfort V6.1
Application
example
LOGO! and PC have to be connected via the PC
cable to transfer the set summer / winter clock
change to LOGO!. Depending on the chosen
region this clock change is used.
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Setting the position of analog inputs AI3 and AI4
Introduction
Wiring
Integrated
functions
Operation on
device
LOGO! Soft
Comfort V6.1
Application
example
With Set AI3 and AI4 position you can choose to
enable the optional AI3 and AI4 on the LOGO!
0BA6 devices that have an option of four analog
inputs. Your choices are as follows:
 2 AIs: Only AI1 and AI2 corresponding to input
terminals I7 and I8 are available for use in your
circuit program.
 4 AIs: AI1 and AI2 corresponding to input
terminals I7 and I8 are available for use in your
circuit program. Additionally, AI3 and AI4
corresponding to input terminals I1 and I2 are
available for use.
Set via software:
Double-click at
in your circuit program
or go to File -> Properties -> Parameter
or at LOGO! basic module:
Setup > BM AI NUM
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Modem wizard
Introduction
Wiring
LOGO! Soft Comfort V6.1 provides a wizard to configure 11-bit analog modems that use
standard AT commands and to connect them via an analog telephone line.
You can use the modems to transfer circuit programs between LOGO! Soft Comfort V6.1
and LOGO! devices.
Integrated
functions
Operation on
device
LOGO! Soft
Comfort V6.1
Application
example
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Modem wizard
Introduction
First you have to make a few settings for you COM-Port:
Select in Windows Start -> Settings -> Control Panel -> System -> Hardware -> Device
Manager. Then select Ports -> open the properties window of your COM-Port.
Wiring
Integrated
functions
Operation on
device
LOGO! Soft
Comfort V6.1
Application
example
The port settings must be as follows:
 Bits per second:
 Data bits:
 Parity:
 Stop bits:
 Flow control:
Logic module LOGO!
9600
8
Even
1
None
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Modem wizard
Select the Tools -> Connect Modem menu command to
start the wizard. LOGO! Soft Comfort V6.1 displays a
dialog that guides you through the configuration process.
Introduction
Wiring
Integrated
functions
1.
Operation on
device
LOGO! Soft
Comfort V6.1
2.
Application
example
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Modem wizard
Introduction
First the remote modem has to be configured. This configuration has to be made via a
direct connection between PC and modem.
Wiring
Integrated
functions
4.
Operation on
device
LOGO! Soft
Comfort V6.1
5.
Application
example
Now you can click at “Configure
Remote Modem”.
Logic module LOGO!
Every modem that you configure gets a
name. In the wizard default AT-commands
are already entered which are used of
most modems. You can type in other ATcommands if necessary for your modem.
Disable default in this case.
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Modem wizard
Introduction
Next step is to configure the local modem. The procedure is similar to the configuration of
the remote modem.
Wiring
7.
Integrated
functions
Operation on
device
LOGO! Soft
Comfort V6.1
Application
example
The modem wizard
provides a list of
telephone numbers.
Here several numbers
of remote stations can
be entered. Select the
number you want to
call and click Dial.
Logic module LOGO!
8
.
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Modem wizard
Introduction
After dialing the remote modem, you are able to up-/download the user program, set LOGO!
in run/stop and do online- test.
Wiring
Integrated
functions
Operation on
device
LOGO! Soft
Comfort V6.1
Application
example
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Delete user program and password
Introduction
Wiring
Integrated
functions
To be able to reuse a LOGO! with program and password when password is lost, the
password has to be entered incorrectly three times at program deletion. Then the program
and the PW is automatically deleted. *)
In LOGO! ..0BA6 it is possible to delete user program and password by LOGO! Soft Comfort
V6.1 .
This function is especially helpful for LOGO! pure versions, where it is not possible to
delete the program directly on the device via the keys. In generations prior ..0BA6, a
memory cartridge was necessary to get the program deleted.
Use Tool -> Transfer -> Clear User Program and Password.
Operation on
device
LOGO! Soft
Comfort V6.1
Application
example
*) since E-Stand 4 (ES4) only possible via software or memory card
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Power-on Screen for LOGO! TD
Introduction
Use Tools -> Transfer -> Set LOGO! TD Power-on Screen to configure a power-on screen for
the LOGO! TD. This screen gets displayed during LOGO! TD powers up.
Wiring
Integrated
functions
Operation on
device
LOGO! Soft
Comfort V6.1
Application
example
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Miscellaneous options
Introduction
Other miscellaneous settings can be made via the menu item Tools -> Options.
Wiring
Integrated
functions
Operation on
device
LOGO! Soft
Comfort V6.1
Application
example
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Application example
Introduction
Conveyor controller
Wiring
Integrated
functions
Operation on
device
LOGO! Soft
Comfort V6.1
Application
example
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Conveyor control
I2 (filling)
Introduction
I3
(light barrier)
Wiring
Q1
Integrated
functions
Operation on
device
LOGO! Soft
Comfort V6.1
Application
example
I1
(ON/OFF)
Function description:
A bottle filling conveyor shall be controlled.
Part 1
The conveyor control is switched on and off via (I1).
When the conveyor control is switched on, the conveyor motor (Q1) runs. If the
light barrier (I3) is interrupted, the motor shall be switched off.
Part 2
When the sensor (I2) detects a bottle, the motor is to be switched off for 3 sec.
(filling action). After that the motor runs again.
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Solution: Conveyor control part 1
I2 (filling)
Introduction
I3
(light barrier)
Wiring
Q1
Integrated
functions
I1
(ON/OFF)
Function description:
Operation on
device
LOGO! Soft
Comfort V6.1
Part 1
The conveyor control is switched on and off via (I1).
When the conveyor control is switched on, the conveyor motor (Q1) runs. If the light barrier
(I3) is interrupted, the motor shall be switched off.
Application
example
Invertierter
Eingang
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications
Solution: Conveyor control part 2
I2 (filling)
Introduction
I3
(light barrier)
Wiring
Q1
Integrated
functions
I1
(ON/OFF)
Function description:
Operation on
device
LOGO! Soft
Comfort V6.1
Part 2
When the sensor (I2) detects a bottle, the motor is to be switched off for 3 sec.
(filling action). After that the motor runs again.
Application
example
Edge triggered
wiping relay
Logic module LOGO!
I IA AS FA PS4
© Siemens AG 2009 - Subject to modifications