WLM2-SIP-MODULE
INTRODUCTION
With the increasing use of Building (Energy) Management Systems, OJ
Electronics Ltd has developed, in partnership with Synapsys Solutions, the
WLM2-SIP-MODULE (ModBus/vIQ) interface.
This interface has been designed for simple plug and play connection
between the Trend® front end systems and the WLM2-1FS BMS Waterline
Control System. The primary aim of the development was to help reduce
engineering time and cost, and to meet the demand for more information
and better energy control.
Used in conjunction with a Trend® BMS, it can help ensure a building complies with latest Part L2 Building
regulations.
APPLICATION
SPECIFICATION
Features
Built-in WLM2 ModBus tables
Hostname
DHCP
ModBus or JBus
ModBus TCP/IP
ModBus
Fixed product variants - max. 145 points per
ModBus slave mapped to a specific vIQs on defined
LAN
Supports most ModBus data types
The WLM2-SIP-MODULE product has been designed to easily interface
between the WLM2-1FS/B, and associated networked WLM2-1BA
Masters & add-on modules, to a Trend B(e)MS (Building (energy)
Management System). This allows up to 31* heating manifolds to be
monitored and controlled remotely.
DESIGN AND FUNCTION
The product displays information recorded by ModBus slaves
communicating via ModBus. It exploits their data capability, by
retrieving, logging (‘Map points’ page) and presenting (‘vIQ’ page)
selected types of data, e.g. Temperature, set-point, pump and boiler
demands in real time. This information allows Building managers to
monitor, record and adjust any aspect of the buildings heating or cooling
TCP/IP Protocol
vIQ
Trend compatible Sensor, Digital Input, Knob, and
Switch modules
OS11
Max. 145 Calculations per unit, e.g. set point
Dimensions
78W (exc. brackets) x 108H x 32D mm
102W (inc. brackets) x 108H x 32D mm
OS31
vIQs present ModBus devices as Trend
controllers. Values are transferred as Trend
Sensor, Knob, Digital Input and Switch Modules
TCP/IP Protocol
Max. #1024 plots per unit @ 1000 values per plot#
OS26
Serial Protocol
(RS485)
330g per unit including DIN Rail clips
410g shipped including DIN Rail clips
with optimum efficiency.
Default Setup Parameters
Each SIP includes vIQ (Virtual IQ) software that allows
IP address - 192.168.1.55 (255.0.0.0)
Power Consumption





300mA @24VDC
SIMPLIFIED BLOCK DIAGRAM
Power Input
24VDC ±15V regulated
Storage Temperature
it to connect to a WLM2-1FS/B – BMS Master
to both read and write values to specific heating or cooling areas
it to display information that appears in the Trend BMS.
It to monitor standard or IP alarm conditions.
it to monitor standard or IP alarm conditions.
TCP/IP Network
(BMS, PC or ModBus TCP/IP Devices)
Max. 16 ModBus
RTU Devices
0 to 70C (32 to 158F), 0 to 70% Relative Humidity
RS485/RS232/RS422
P1
Operating Temperature
ModBus
Driver
0 to 70C (32 to 158F), 0 to 90% Relative Humidity
Trend
Driver
Connection Type
1 x 10/100Mbps for TCP/IP and/or ModBus TCP/IP
vIQ
Driver
ModBus RTU Connection Type
SIP ModBus/vIQ
DIP switch controls RS485 (all OFF)
Note
Refer to Installation Guide for wiring details.
WLM2-SIP-MODULE
Technical Datasheet
INSTALLATION
Din rail mounting using DIN rail clips (not provided) or
direct enclosure mounting using the brackets attached.
The 2.5m TIA/EIA 568A Cat 5E cable supplied can be
used to connect the WLM2-SIP-MODULE to the
connection terminals of the WLM2-1FS/B BMS network
master.
CONFIGURATION
Specifically designed web pages support





ModBus/Local IP communications configuration
ModBus slave and register mapping configuration
ModBus Diagnostics
vIQ out-station, module and security configuration
vIQ calculation configuration
REGULATIONS
Designed and manufactured to comply with CE Class
A, FCC Class A, WEEE (Waste Electrical and
Electronic Equipment) and RoHS (Restriction of
Hazardous Substances) regulations.
It also complies with the Council Directive on the
Approximation of the Laws of the Member States
relating to Electromagnetic Compatibility (89/336/EEC).
For the evaluation regarding the electromagnetic
compatibility, the following standards were applied











EN55022:1998/A1:2000+A2:2003 (class A)
EN61000-3-2:2000
EN61000-3-3:1995/A1:2001
EN55024:1998/A1:2001+A2:2003
IEC61000-4-2:1995+A1:1998+A2:2000
IEC61000-4-3:1995+A2:2002
IEC61 000-4-4:1995+A1:2000+A2:2001
IEC61000-4-5:1995+A1:2000
IEC61000-4-6:1996+A1:2000
IEC61 000-4-8:1993+A1:2000
IEC61000-4-11:1994+A1:2000
*31 manifold connections include the WLM2-1FS/BMS, 15 x WLM2-1BA Masters & 15 WLM2-1AO
Add-on modules – please refer to the installation plan literature for more details.