Major Changes to the 2009 IECC & Above Code Programs Introduction Tim Guiterman, LEED AP Energy Engineer and Consultant Navigant Consulting Burlington, VT (802) 526-5114 Tim.Guiterman@navigant.com 2 Overview • • • • • • • Objective Administration Building Envelope Mechanical Systems Electrical Power & Lighting Q&A Above Code Programs Objective Highlight the major changes between 2006 and 2009 IECC that will affect your upcoming projects in New Hampshire. Source for Changes to 2006 IECC: http://www.energycodes.info/Code%20Q%20and%20A_files/MAJOR%20CHANGES %20BETWEEN%20THE%202006%20AND%202009%20IECC.pdf Suggested Reading • Combined 2009 IECC/ASHRAE 90.1-2007 • 2009 IECC Commentary • 2009 IECC Study Companion – Available combined with code • ASHRAE 90.1 User’s Manual • Did you get the free downloads? Introduction to the Commercial Energy Code Compliance Process Must the Project Comply with the IECC? Comply with the Envelope Requirements Section 502 90.1 Section 5 Comply with the Mechanical/SWH Requirements Sections 503 and 504 90.1 Section 6 Comply with the Power & Lighting Requirements Section 505 90.1 Section 9 Document Compliance with the IECC Plan Review Inspection 6 CHAPTER 1: ADMINISTRATION Major Changes to Chapter 1 • Adds exemptions to Additions, Alterations, Renovations and Repairs section • Change in Occupancy section revised • Change in Space Conditioning requires full compliance with code 8 101.4.3 Additions, Alterations, Renovations and Repairs Working on an existing building? If you touch it, bring it up to code… Additions, alterations, renovations or repairs to an existing building, building system or portion thereof shall conform to the provisions of this code… without requiring the unaltered portion(s) of the existing building or building system to comply with this code. With some exceptions… 9 101.4.3 Additions, Alterations, Renovations and Repairs • New Exceptions: – If you replace an existing door, separating conditioned space from exterior, you do not need to add a vestibule; however, if a vestibule is part of the door assembly that is modified, it must remain on the building or be replaced – Up to 50% of the luminaires can be replaced as long as the load is not increased in the building – Bulb & ballast replacements are exempt providing the alteration does not increase the load. 10 101.4.4 Change in Occupancy – 2006 IECC required buildings undergoing a change in occupancy that results in increased load to comply with the code – 2009 IECC maintains above (“space” in lieu of “building”) and requires installed lighting wattage to comply with IECC if the space changes from one use to another use as defined in Table 505.5.2 11 Scenario: An online retail company based in Manchester is converting 5,000 SF of open office space to warehouse space. All of the lighting will be changed. The IECC requires: 0% 0% 0% 1. Full compliance with the code for that space 2. Compliance with only the lighting power allowance for that space 3. The space is exempted from the code 101.4.4 Change in Occupancy 13 CHAPTER 5: COMMERCIAL ENERGY EFFICIENCY What are My Options for Complying with the IECC? • Chapter 5 of the IECC General Prescriptive Approach • Use for ≤ 40% of gross wall area in vertical fenestration • Use for ≤ 3% of gross roof area in skylights • Section 506 Total Building Performance Approach • ASHRAE/IESNA Standard 90.1-2007 • – 2006 IECC allowed individual sections to comply with either IECC or ASHRAE 90.1 – 2009 IECC requires compliance with either IECC or ASHRAE 90.1 in its entirety Note: Code now references ASHRAE 90.1-2007 SECTION 502: BUILDING ENVELOPE Commercial Envelope Compliance Process Must the Project Comply with the IECC? Comply with the Envelope Requirements Section 502 90.1 Section 5 Comply with the Mechanical/SWH Requirements Sections 503 and 504 90.1 Section 6 Comply with the Lighting Requirements Section 505 90.1 Section 9 Document Compliance with the IECC Plan Review Inspection 17 Major Changes to Envelope Requirements • Added U-factor table to correspond to R-Value table • Added Group R category for insulation • Envelope stringency increased • Additional descriptions added for metal building walls/roofs • Consolidated skylight categories into one category 18 Table 502.1.2: Envelope Requirements Category Roofs Insulation Entirely Above Deck Metal Building Attic and Other Walls-Above Grade Mass Metal Building Metal Framed Wood Framed and Other 2006 IECC CZ 5 CZ6 R-20ci R-19 R-30 R-7.6ci CZ 5 2009 IECC CZ6 No Change No Change R-38 R-9.5ci R-11.4ci R-13 + R-13 R-13 + R-13 R-13 + R-5.6ci R-13 + RR-13 + R3.8ci 3.8ci R-13 + R-7.5ci R-13 R-13 R-13 + R-3.8ci R-13.3ci R-13 + R-5.6ci R-13 + R-7.5ci R-13 + R-7.5ci 19 Table 502.1.2: Envelope Requirements (Cont’d) Category Walls-Below Grade Below Grade Wall Floors Mass Joist/Framing Slab-On-Grade Floors Unheated Slabs Heated Slabs Opaque Doors Swinging Roll-up or Sliding 2006 IECC 2009 IECC CZ 5 CZ6 CZ 5 CZ6 NR NR R-7.5ci R-7.5ci R-10ci R-19 R-10ci R-30 R-10ci R-30 R-12.5ci R-30 NR R-10 for 24 in. below NR NR R-7.5 for 24 R-10 for 36 in. R-15 for in. below below 24 in. below U-0.70 U-1.45 U-0.70 U-0.50 U-0.70 U-0.50 R-15 for 24 in. below U-0.70 U-0.50 20 In CZ 5 and below, more insulation is required for metal-framed walls than for wood-framed walls. Why? 0% 0% 0% 1. Heat transfer is greater in metal than in wood 2. Metal-framed walls are spaced closer so there is more thermal-bridging 3. Heavy lobbying by the wood industry to drive up costs for metal-framing Below-grade walls are defined as exterior walls that are… 0% 1. At least 50 percent below grade 0% 2. At least 85 percent below grade 0% 3. The below grade portion of a basement 0% 4. Any exterior wall not classified as above grade Slab-on-Grade Floors (502.2.6) • Unheated slab – insulation required in NH CZ 5: Only required for Group R CZ 6: R-10 for 24 inches below • Heated slabs – insulation required CZ 5 & 6: R-15 for 24 inches below • What are you seeing in practice? 23 Roof R-Value – Insulation Placed on Suspended Ceiling with Removable Ceiling Tiles • Will not count for code compliance • Will not comply with Section 502.4.3 – “Sealing of the building envelope” Dropped Ceiling 24 Roof R-Value – Metal Buildings Insulation Parallel to Purlin Thermal Blocks Insulation Draped Over Purlin Picture from NAIMA • R-5 thermal blocks required on all metal buildings or must use Ufactor Compliance Method • Require two layers of insulation CZ 5: R-13+R-13 CZ 6: R-13+R-19 • Example (R-13+R-19): – R-13 draped perpendicularly to the purlins – R-19 running parallel to the purlins supported by the R-13 25 Vertical Fenestration Requirement (502.3.1) - Prescriptive Percentage of Vertical Fenestration Area to Gross Wall Area • Allows up to 40% maximum of above grade wall • Question: What are typical fenestration percentages you see? 26 A commercial building in North Conway, NH will have a gross wall area of 15,000 ft2. The building will have a vertical fenestration area of 7,500 ft2. What building envelope compliance options are available for this project? 0% 0% 0% 0% 1. ASHRAE 90.1-2007 only 2. IECC Section 506 (Total Building Performance) only 3. IECC Section 502 (Building Envelope Requirements) and Section 506 (Total Building Performance) 4. 1 and 2 only Vertical Fenestration Requirement (502.3.1) • Based on above-grade wall area (gross) – Includes walls between conditioned space and unconditioned space or the outdoors • Includes walls that are > 15% above grade • Total fenestration area (includes frame and glazing) – Does not include opaque door area 28 Glazed Fenestration SHGC (502.3.2) What is Solar Heat Gain Coefficient? “The ratio of the solar heat gain entering the space through the fenestration assembly to the incident solar radiation.” 29 Fenestration SHGC Requirements The Effect of Overhangs on Fenestration SHGC • • Overhangs allow a higher SHGC product to be installed Projection factor must be calculated 30 Skylight U-Factor / SHGC • 2006 IECC classified glass and plastic skylights • 2009 IECC condensed into one category – Limited to ≤ 3% of Roof Area – U-factor and SHGC Based – NFRC 100 Rating for U-factor or Default Table Category 2006 IECC CZ 5 CZ6 2009 IECC CZ 5 CZ6 0.60 0.60 0.40 0.40 Skylights U-factor SHGC Glass: 0.60 Plastic: 1.30 Glass: 0.40 Plastic: 0.62 Glass: 0.90 Plastic: 1.30 Glass: 0.40 Plastic: 0.62 31 Mandatory Requirements – Sealing of the Building Envelope (502.4.3) • All penetrations, openings, joints and seams in the building envelope must be sealed. Materials that can be used include: Caulking Gasketing Tapes Moisture vapor-permeable wrapping material • Sealing materials spanning joints between dissimilar materials must allow for expansion and contraction 32 SECTION 503: BUILDING MECHANICAL SYSTEMS Mechanical Systems Compliance Process Must the Project Comply with the IECC? Comply with the Envelope Requirements Section 502 90.1 Section 5 Comply with the Mechanical/SWH Requirements Sections 503 and 504 90.1 Section 6 Comply with the Lighting Requirements Section 505 90.1 Section 9 Document Compliance with the IECC Plan Review Inspection 34 Major Changes to Mechanical Requirements • Revises equipment efficiency tables for water-chilling packages • Requires snow melt control • Requires demand control ventilation (DCV) for certain spaces • Removes exception for energy recovery ventilation for lab fume hood systems ≤ 15,000 cfm • Lowers the system capacity for economizer requirement for NH climate zones 5A and 6A • Introduces fan power limitations • Reorganizes hydronic water loop heat pump section • Introduces supply air temperature reset controls for multiplezone systems 35 Section 503 Building Mechanical Systems Simplified to Include Only Four Sections: • • • • What Provisions of the Code Apply (503.1) Mandatory Provisions (503.2) Simple HVAC Systems and Equipment (503.3) Complex HVAC Systems and Equipment (503.4) 36 Simple Versus Complex Systems Section 503.3 Simple Systems Section 503.4 Complex Systems Buildings served by unitary or packaged HVAC each serving 1 zone controlled by 1 thermostat. Two-pipe heating systems serving multiple zones are included if no cooling system is installed [Tables 503.2.3(1) through 503.2.3(5)] All buildings served by HVAC systems not covered under 503.3 A non-packaged HVAC system that is designed to serve multiple building zones would be referred to as a ______. 0% 0% 0% 0% 1. 2. 3. 4. Simple system Complex system Variable air volume system Unitary or packaged system Simple Versus Complex Systems Equipment and System Sizing (503.2.2) Output capacity SHALL NOT exceed sizing – • Select the system which serves the greater load, heating or cooling – Exceptions • Standby Equipment with Required Controls • Multiple Units with Combined Capacities Exceeding Loads – Sequencing Controls Required 40 Multiple boilers-allowed to exceed loadif sequenced 41 Table 503.2.3(2) 42 According to Chapter 5, simple HVAC systems and equipment that meet the minimum equipment requirements listed in Tables 503.2.3 (1-11) shall be verified… 0% 0% 0% 0% 1. By an approved certification program, or if none exists, with manufacturer’s data 2. By the building official 3. Through testing procedures found in the ASHRAE Handbook of Fundamentals 4. By an onsite contractor at the time of equipment inspection The automatic controls for a snow-melt system shall be capable of shutting off the system when the pavement temperature is above _____ and no precipitation is falling. 0% 0% 0% 0% 1. 2. 3. 4. 35°F 45°F 40°F 50°F Demand Controlled Ventilation (503.2.5.1) • 2006 IECC had no DCV requirement • 2009 IECC: DCV must be provided for each zone with spaces > 500 ft² and the average occupant load > 40 people/1000 ft² of floor area where the HVAC system has: An air-side economizer Automatic modulating control of the outdoor air damper, or A design outdoor airflow > 3,000 cfm Demand control ventilation (DCV): a ventilation system capability that provides for the automatic reduction of outdoor air intake below design rates when the actual occupancy of spaces served by the system is less than design occupancy. 45 Demand Controlled Ventilation (503.2.5.1) - Exceptions • Systems with energy recovery per 503.2.6 • Multiple zone systems without direct digital control of single zones communicating with central control panel • Systems with design outdoor airflow < 1,200 cfm • Spaces where supply airflow rate minus any makeup or outgoing transfer air requirement < 1,200 cfm 46 Demand Controlled Ventilation (503.2.5.1) The wall and duct-mounted carbon dioxide (CO2) sensors are designed especially for demandcontrolled ventilation zone applications. 47 Demand Controlled Ventilation (503.2.5.1) 48 Demand Controlled Ventilation (503.2.5.1) 49 Energy Recovery Ventilation (503.2.6) • 2006 IECC: Exception for lab fume hood systems ≤ 15,000 cfm • 2009 IECC: Removed only this exception, maintained all others 50 Economizers (503.3.1) • 2006 IECC: CZ 5A and 6A - Economizers required on all systems ≥ 135,000 Btu/h • 2009 IECC: Revised to 54,000 Btu/h Table 503.3.1(1) CLIMATE ZONES ECONOMIZER REQUIREMENT 1A, 1B, 2A, 7, 8 No requirement 2B, 3A, 3B, 3C, 4A, 4B, 4C, 5A, 5B, 5C, 6A, 6B Economizers on cooling systems ≥ 54,000 Btu/ha a The total capacity of all systems without economizers shall not exceed 480,000 Btu/h per building, or 20 percent of its air economizer capacity, whichever is greater *Note: CZs 2B, 3B and 4B can trade off economizer requirement with improved equipment efficiency (10-20%) A cooling system rated at 135,000 Btu/h capacity is proposed for an office building in Portland (CZ 5A). The proposed EER for the system will be 11.0. Is an economizer required for this system? 0% 0% 0% 0% 1. Yes, the system is greater than 90,000 Btu/h 2. No, the system meets the 10.9 EER requirement for tading-off 3. Yes, economizers cannot be traded off in CZ 5 4. No, there is no economizer requirement in CZ5. Supply and return ducts and plenums are required to be insulated to… 0% 0% 0% 0% 0% 1. 2. 3. 4. 5. R-8 in all locations R-5 in all locations R-5 in unconditioned spaces; R-8 exterior R-8 in unconditioned spaces; R-5 exterior None of the above Air System Design and Control (503.2.10) • 2006 IECC: No Requirement • 2009 IECC: HVAC systems with total fan system power > 5 hp to meet 503.2.10.1 and 503.2.10.2 – Allowable Fan Floor Horsepower – Motor Nameplate Horsepower 54 Allowable Fan Floor Horsepower • Each HVAC system at fan design conditions to not exceed allowable fan system motor nameplate hp (Option 1) or fan system bhp (Options 2) in Table 503.2.10.1(1) • Exceptions – Hospital and laboratory systems using flow control devices on exhaust and/or return for health and safety or environmental control permitted to use variable fan power limitation – Individual exhaust fans ≤ 1 hp – Fans exhausting air from fume hoods 55 Motor Nameplate Horsepower • Selected fan motor to be no larger than first available motor size greater than bhp • Fan bhp on design documents • Exceptions – Fans < 6 bhp, where first available motor larger than bhp has nameplate rating within 50% of bhp, next larger nameplate motor size may be selected – Fans ≥ 6 bhp, where first available motor larger than bhp has nameplate rating within 30% of bhp, next larger nameplate motor size may be selected 56 bhp = brake horsepower Hydronic Water Loop Heat Pump Systems (503.4.3.3) • All of 503.4.3.3 changed from the 2006 IECC. • Question: Are these systems commonplace in NH new construction? What are impacts of new requirements? • Temperature dead band of at least 20ºF (503.4.3.3.1) Exception: where system loop temp optimization controller is installed and can determine the most efficient operating temp based on real time conditions of demand and capacity 57 Hydronic Water Loop Heat Pump Systems (503.4.3.3) – cont’d • Heat rejection equipment Open- or closed-circuit cooling tower used • Must have a separate heat exchanger to isolate cooling tower from heat pump loop • Heat loss controlled by shutting down circulation pump on cooling tower loop and providing an automatic valve to stop flow of fluid • Two position valve (503.4.3.3.3) Required on each hydronic heat pump with total pump system power > 10 hp 58 Supply-Air Temperature Reset Controls (503.4.5.4) • 2006 IECC: No requirement • 2009 IECC: Multiple zone HVAC systems to have controls to automatically reset supply-air temperature in response to building loads or outdoor air temperature • Controls to be capable of resetting supply air temperature at least 25% of difference between design supply-air temperature and design room air temperature • Exceptions Systems that prevent reheating, recooling or mixing of heated and cooled supply air 75% of energy for reheating is from site-recovered or site solar energy sources Zones with peak supply air quantities of ≤ 300 cfm 59 SECTION 505: ELECTRICAL POWER AND LIGHTING SYSTEMS The IECC Code Compliance Process Must the Project Comply with the IECC? Comply with the Envelope Requirements Section 502 90.1 Section 5 Comply with the Mechanical/SWH Requirements Sections 503 and 504 90.1 Section 6 Document Compliance with the IECC Comply with the Power & Lighting Requirements IECC Section 505 90.1-2007 Section 9 IECC Section 506 Building Performance Method Plan Review Inspection 61 Major Changes to Electrical/Lighting Systems Requirements • Adds high-efficacy lighting requirement for dwelling units • Requires separate controls for daylight zones • Allows for use of photocell in tandem with other controls on certain exterior lighting applications • Adds exempted lighting applications that can be excluded from total connected interior lighting power calculations • Revises additional lighting power allowance calculations for retail areas • Creates four exterior lighting zones based on lighting need 62 When do the Lighting and Power Requirements Apply? • Original installed lighting system in a new building, addition, or tenant build-out • Existing lighting system that is altered • Change in occupancy that increases energy Exceptions: • Historic buildings State or National listing Eligible to be listed • Alterations where less than 50% of the luminaires are replaced and power is not increased • Lighting within dwelling units Where ≥ 50% of permanently installed fixtures are high-efficacy lamps 63 High-Efficacy Lamps • Defined in the 2009 IECC as: – Compact fluorescent lamps, T-8 or smaller diameter linear fluorescent lamps, or lamps with a minimum efficacy based on lamp wattage Lamp Wattage Efficacy > 40 watts 60 lumens/watt 15-40 watts 50 lumens/watt < 15 watts 40 lumens/watt 64 What’s Covered Under Electrical Power and Lighting Systems Requirements? • Mandatory Interior Lighting Requirements Required Controls Wattage/Efficiency Limits • Interior Lighting Power Allowances (watts/ft2) • Exterior Lighting Controls Required Controls Lamp Efficiency • Exterior Lighting Power Allowances (watts/ft2) • Electric Metering 65 Interior Lighting Control (505.2): Basic Control Independent Lighting Control required for each space surrounded by floor-to-ceiling partitions Must be located in the space served, - or Switched from a remote location • Must have indicator that identifies the lights served and their status (off or on) Exemptions • Security or emergency areas that must be continuously lighted • Lighting in stairways or corridors that are elements of the means of egress Intent: Allow occupants to control unneeded lighting! 66 Interior Lighting Control: Light Reduction Light Reduction Controls must allow the occupant to reduce connected lighting By at least 50% In a reasonably uniform illumination pattern Note: Alternate Standard ASHRAE/IESNA 90.1-2007 does not require Light Reduction Control Intent: Allow occupants to moderate light levels to save energy! 67 Light Reduction Control Options Controlling all lamps or luminaires Dual switching of alternate rows of luminaires, alternate luminaires or lamps Switching middle lamp luminaires independently from the outer lamps Each luminaire or each lamp Dimming Alternating lamps Alternating Luminaires D SS Dimmer Switch SS 68 Interior Lighting Control: Light Reduction Exemptions Light Reduction Control Not required for the following: • Areas with only one luminaire • Areas controlled by occupancy sensor • Corridors, storerooms, restrooms or public lobbies • Sleeping units • Spaces with <0.6 w/ft2 69 Which of the following spaces must install light reduction controls? 0% 0% 0% 0% 1. 2. 3. 4. Hotel sleeping unit Public lobby in an office building Office space with two luminaires Restroom Interior Lighting Control: Automatic Shutoff Automatic lighting shutoff control device required in all buildings larger than 5,000 ft2 Building Defined: • “Any structure used or intended for supporting or sheltering any use or occupancy” • Building area surrounded by exterior walls and fire walls Intent: Eliminate after Exempted spaces hours lighting waste! • Sleeping units • Lighting for patient care • When an automatic shutoff would endanger occupant safety or security 71 Interior Lighting Control: Automatic Shutoff Options Automatic Lighting Shutoff Compliance Options 1. Control lights on a scheduled basis (automatic time switch) • Time-of-day controller • Controls ≤ 25,000 ft2 and not more than one floor, or Automatic Lighting Control Occupancy Sensor Open Bay Office Connect to Lighting in Lobby 2. Occupant sensor • Turn lights off within 30 minutes of occupant leaving the space 3. Signal from another control or alarm that indicates the area is unoccupied Lobby Office 50’ Conference Room Connect to Lighting in Open Bay Office Restrooms 110’ Courtesy Britt-Makela Group 72 Interior Lighting Control: Automatic Shutoff Override • • • • • • Readily accessible Within view of the lights or area controlled Manually operated ≤ 2 hour override Controls an area ≤ 5,000 ft2 Exemptions Can be over 2 hour override in malls and arcades, auditoriums, singletenant retail space, industrial facilities and arenas when using captive key override Override in malls and arcades, auditoriums, single-tenant retail space, industrial facilities and arenas can cover up to 20,000 ft2 73 Automatic lighting shutoff is not required in buildings that are a maximum of ______ square feet. 0% 0% 0% 0% 1. 2. 3. 4. 10,000 7,500 5,000 2,500 Daylight Zone Definition – Under Skylights • The area under skylights whose horizontal dimension, in each direction, is equal to the skylight dimension plus the smaller of: • The floor-to-ceiling height, or • The distance to a ceiling height opaque partition, or • One-half the distance to adjacent skylights or windows 75 75 Daylight Zone Definition – Adjacent to Vertical Fenestration The daylight zone depth is assumed to be 15 feet into the space or to the nearest ceiling height opaque partition, whichever is less The daylight zone width is assumed to be: • the width of the window plus 2 feet on each side, or • the window width plus distance to opaque partitions, or • the window width plus one-half the distance to adjacent skylight or vertical fenestration, whichever is least. 7676 Daylight Zone Control • Daylight zones – Must have individual control of the lights independent of general area lighting 77 Interior Lighting Power Limits (505.5) Connected Interior Lighting Power must not exceed Interior Lighting Power Allowance 1. Calculate Interior Lighting Power Allowance • • Building Area type allowance Additional allowances 2. Calculate proposed connected lighting power • • Wattage calculation “rules” Exempted lighting 3. Compare values: proposed wattage must be less than or equal to allowed wattage Intent: Eliminate waste from sloppy lighting design and application! 78 Interior Lighting Power Allowances Table 505.5.2 • Building Area Type Note: Alternate Standard ASHRAE/IESNA 90.1-2007 provides whole building and space-by-space options 79 Interior Lighting Power Allowance Calculation • First, choose an appropriate “Building Area Type” from the allowance table (505.5.2). – “Building Area” includes all spaces that are associated with that business or function type. For example a space with: • Corridors, • Restrooms, • A lobby, and • Office space …would be considered an Office Building Area Type • Then...multiply the lighting power density (W/ft2) by the building square footage to get allowed watts for compliance 80 Office - Example Table 505.5.2 A 200,000 ft2 office building that contains corridor, restrooms, break rooms and a lobby is given 1.0 W/ft2 for the entire building Office: 200,000 ft2 1.0 W/ft2 = 200,000 W 81 Interior Lighting Power Allowance for Multiple Occupancy Building How is an allowance determined if the building has more than one Building Area Type? Example – A building contains the following area types • Museum: 40,000 ft2 • Retail: 5,000 ft2 • Cafeteria: 10,000 ft2 • Use the more specific building area type where more than one area type exists in the building • Sum the individual (lighting power density X area square footage) values for Total Power Allowance 82 Multiple Occupancy Building - Example Table 505.5.2 Museum: 40,000 ft2 at 1.1 W/ft2 = 44,000 W Cafeteria:10,000 ft2 at 1.4 W/ft2 = 14,000 W Retail: 5,000 ft2 at 1.5 W/ft2 = 7,500 W Total watts allowed = 65,500 W 83 Additional Retail Lighting Power Allowance (Table 505.5.2 – Footnotes) Additional Interior Lighting Power Allowance = 1000 watts + (Retail Area 1 x 0.6 W/ft2) + (Retail Area 2 x 0.6 W/ft2) + (Retail Area 3 x 1.4 W/ft2) + (Retail Area 4 x 2.5 W/ft2), Where: • Retail Area 1 = the floor area for all products not listed in Retail Area 2, 3 or 4. • Retail Area 2 = the floor area used for the sale of vehicles, sporting goods and small electronics. • Retail Area 3 = the floor area used for the sale of furniture, clothing, cosmetics and artwork. • Retail Area 4 = the floor area used for the sale of jewelry, crystal, and china. Exception: Other merchandise categories may be included in Retail Areas 2 through 4 above, provided that justification documenting the need for additional lighting power based on visual inspection, contrast, or other critical display is approved by the authority having jurisdiction. Intent: Allow flexibility in design for critical retail applications! 84 Proposed Lighting Power Calculation • Sum the wattage of all proposed connected lighting power • This must include all lighting that is part of the design for the space including: – Overhead lighting – Task lighting – Decorative lighting Note: Wattage must be calculated based on actual power draw…not just nominal lamp rating 85 When documenting the total connected lighting power for a proposed building, what wattage should be used for a screw lamp holder? 0% 0% 0% 0% 1. Wattage of the light bulb proposed for the fixture 2. Maximum labeled wattage of the luminaire 3. 300 watts per fixture 4. 100 watts per fixture Exemptions to Proposed Lighting Power Calculation • Connected power for following not included in calculations: – – – – – – • Lighting equipment used for the following exempt if in addition to general lighting and controlled by an independent control device – – • • • • • • • • • • • • Professional sports arena playing field Sleeping unit lighting Emergency lighting automatically off during normal building operation Lighting in spaces specifically designed for use by occupants with special lighting needs including visual impairment and other medical and age related issues Lighting in interior spaces specifically designated as a registered interior historic landmark Casino gaming areas Task lighting for medical and dental procedures Display lighting for exhibits in galleries, museums and monuments Theatrical, stage, film, and video production Used for photographic processes Integral to equipment or instrumentation installed by manufacturer Plant growth or maintenance Advertising or directional signage Food warming and food prep equipment (in restaurant buildings and areas) Lighting equipment that is for sale Lighting demonstration equipment in lighting education facilities Approved because of safety or emergency considerations, exclusive of exit lights Integral to both open and glass-enclosed refrigerator and freezer cases In retail display windows when the display is enclosed by ceiling-height partitions Furniture-mounted supplemental task lighting controlled by automatic shutoff 87 What if My Proposed Design Does Not Meet Code? • Check calculations – Appropriate area type allowances used? – Actual lighting equipment wattages used? …and design – Reasonable illuminance levels provided? – Efficient light sources used? • Use alternate Standard 90.1-2007* • Use total Building Performance Method *Section 501.2 Application requires 90.1 to be used in its entirety (Envelope, Lighting, Mechanical) if used as an alternate compliance path 88 Exterior Lighting Control Requirements (505.2.4) • For dusk-to-dawn lighting: astronomical time switch or photosensor • For all other: astronomical time switch OR photosensor + time switch • All time switches must have 10 hour battery backup 89 Exterior Efficiency Requirement (505.6.1) Building grounds lighting luminaires over 100 watts must have source efficacy of at least 60 lumens per watt Exceptions: • Controlled by motion sensor • Any of the exterior lighting power allowance exceptions • As approved for a historical, safety, signage, or emergency consideration 90 Exterior Lighting Power Limits (505.6.2) Connected Exterior Lighting Power must not exceed Exterior Lighting Power Allowance – Calculate exterior Lighting Power Allowance • Lighting power densities by exterior function and by applicable lighting zone – Calculate proposed connected lighting power • Wattage calculation “rules” • Exempted lighting – Compare values: proposed wattage must be less than or equal to allowed wattage 91 Exterior Lighting Power Limits (505.6.2) What areas are covered under exterior lighting allowances? – Tradable surfaces Common exterior lighted needs that can be traded for other needs. For example, wattage allowed for parking lot lighting can be “traded” and used for canopy lighting. – Nontradable surfaces Less common exterior lighted needs that cannot be traded for other needs. These applications have more specific security or task illuminance needs. 92 Tradable Surfaces • Uncovered parking lots and areas • Walkways (under and over 10 feet wide) • Stairways • Pedestrian tunnels • Main building entrances • Other doors • Entry canopies • Free-standing and attached sales canopies • Open sales areas • Street frontage sales areas 93 Nontradable Surfaces • Building facades • Automated teller machines and night depositories • Entrances and gatehouse inspection stations at guarded facilities • Loading areas for law enforcement, fire, ambulance and other emergency vehicles • Drive-up windows/doors • Parking near 24-hour retail entrances 94 Exterior Lighting Zones [Table 505.6.2(1)] Lighting Zone Description 1 Developed areas of national parks, state parks, forest land, and rural areas 2 Areas predominantly consisting of residential zoning, neighborhood business districts, light industrial with limited nighttime use and residential mixed use areas 3 All other areas 4 High-activity commercial districts in major metropolitan areas as designated by the local land use planning authority 95 Exterior Lighting Zones Zone 1 Zone 2 Zone 3 Zone 4 500 W 600 W 750 W 1300 W 0.06 W/ft2 0.10 W/ft2 0.13 W/ft2 0.7 W/linear foot 0.7 W/linear foot 0.8 W/linear foot 1.0 W/linear foot Special Feature Areas 0.14 W/ft2 0.14 W/ft2 0.16 W/ft2 0.2 W/ft2 Stairways 0.75 W/ft2 1.0 W/ft2 1.0 W/ft2 1.0 W/ft2 Pedestrian Tunnels 0.15 W/ft2 0.15 W/ft2 0.2 W/ft2 0.3 W/ft2 Base Site Allowance Tradable Surfaces Uncovered Parking Areas Parking areas and drives 0.04 W/ft 2 Building Grounds Walkways less than 10 feet wide Walkways 10 feet wide or greater Plaza areas 96 Questions/Discussion 97 ABOVE CODE PROGRAMS Above Code Programs • The field is advancing…quickly 99 Above Code Programs Stretch Codes Green Building Rating Systems Green Building Codes Net Zero/Living Buildings Baseline: ASHRAE 90.1-2007 or 2009 IECC (New Hampshire Amendments) 100 Above Code Programs Why go beyond code? • Owner-driven – Save energy – Marketing – Internal goals • Jurisdictional requirement • Designer-driven What percent of projects that you work on exceed the energy code (best guess)? 1. 2. 3. 4. 5. Less than 25% 25% - 50% 50%-75% 75% + Don’t Know! 0% 1 2 3 4 5 New Buildings Institute (NBI) Core Performance Program • Buildings < 70,000 ft2 • 20% - 30% Savings over ASHRAE 90.1-2004 • Codified in Massachusetts “Stretch Code” • Prescriptive path for LEED Energy & Atmosphere points (Eac1) o No energy modeling required 103 NBI Core Performance Program • Design Process Strategies – • Core Performance Requirements – • Delivers consistent savings across building types, climates Enhanced Performance Strategies – • Integrated Design Optional measures certain systems or building types Energy Modeling – Optional to pursue aggressive energy savings or show alternative compliance to prescriptive path 104 Green Building Rating Systems USGBC LEED / CHPS / Green Globes • • • • Third party certification programs Baseline energy code: ASHRAE 90.1-2007 Energy savings only one focus area – – – – – Sustainable Sites Water Efficiency Materials & Resources Indoor Environmental Quality Innovation & Design Collaborative for High Performance Schools (CHPS): – K-12 schools; Northeast-specific 105 Have you worked on a project that received a green building certification? 1. Yes 2. No 3. Maybe 0% 1 2 3 Are you currently working on a project that is aiming to receive certification? 1. Yes 2. No 3. Maybe 0% 1 2 3 Which rating system (s) have your projects utilized? 1. USGBC LEED (NC, EB, CI, etc) 2. NE-CHPS 3. Green Globes 4. All of the above 5. At least two of the above 0% 1 2 3 4 5 Are you a LEED-Accredited Professional (AP) or LEED “Green Associate”? 1. Yes 2. No 0% 1 2 Green Building Rating Systems Minimum Energy Performance: ASHRAE 90.1-2007 Northeast (NE)-CHPS 25% USGBC LEED v3 10% 0% 5% 10% 15% 20% 25% 30% 110 Green Building Rating Systems Source: USGBC 111 ASHRAE Standard 189.1 • ANSI standard being developed in model code language • Provides minimum requirements for high-performance, green buildings • Applies to all buildings except low-rise residential buildings (same as ASHRAE/IESNA Std 90.1) • Optional Compliance Path to the International Green Construction Code (IgCC) • Not a design guide, not a rating system Source: Introduction to Standard 189.1 www.ashrae.org/publications/page/927 112 ASHRAE Standard 189.1 Topic Areas SS Sustainable Sites WE Water Use Efficiency EE Energy Efficiency IEQ Indoor Environmental Quality MR Building’s Impact on the Atmosphere, Materials & Resources CO Construction and Operations Plans Source: Introduction to Standard 189.1 www.ashrae.org/publications/page/927 International Green Construction Code • High performance, green building code • Consistent with I-Codes • Allows ASHRAE 189.1 to be a compliance option • Energy performance: 30%+ 2006 IECC • Expected full release in early 2012 Source: Introduction to Standard 189.1 www.ashrae.org/publications/page/927 114 Living Building Challenge • No credits, just prerequisites • Requires Net Zero Energy 115 Above Code Resources DOE Stretch Code Programs: www.energycodes.gov/why_codes/stretch_beyond.stm NBI: http://newbuildings.org DOE Net Zero Energy Commercial Building Initiative: www1.eere.energy.gov/buildings/commercial_initiative/ USGBC LEED: www.usgbc.org NE-CHPS: http://neep.org/public-policy/hpse/hpse-nechps Green Globes: www.greenglobes.com ASHRAE 189.1: http://www.ashrae.org/publications/page/927 IGCC: http://www.iccsafe.org/cs/IGCC/Pages/default.aspx 116 Questions/Discussion 117