NFPA 1142 STANDARD ON WATER SUPPLIES FOR SUBURBAN AND RURAL FIRE FIGHTING NFPA 1142 WATER SUPPLY DETERMINING FACTORS •EXTENT OF EVOLUTIONS •SIZE OF and TYPE OF STRUCTURE •CONTENTS •METHOD OF ATTACK •EXPOSURES •RESERVES NFPA 1142 NFPA 1403: 4.2 Structures and Facilities 4.2.23 The lead instructor shall determine the rate and duration of water flow necessary ..., including the water necessary for control and extinguishment of the training fire, the supply necessary for backup lines to protect personnel, and any water needed to protect exposures. NFPA 1142 NFPA 1403: 4.2 Structures and Facilities 4.2.23.1 The minimum water supply and delivery for the live fire training evolutions shall meet the criteria identified in NFPA 1142, Standard on Water Supplies for Suburban and Rural Fire Fighting. NFPA 1142 Definition: 4.1.5 (1) Exposure Hazard STRUCTURE WITHIN 50 FEET and 100 SQUARE FEET OR LARGER. (2) If class 3 or 4 OH, within 50 ft of another building, it is considered an exposure hazard regardless of size. NFPA 1142 Chapter 5 CLASSIFICATION OF OCCUPANCY HAZARD WHAT OCCUPANCY TYPE IS THE MOST LIKELY TO BE USED IN LIVE FIRE TRAINING? NFPA 1142 NFPA 1142 5.2.5 Occupancy Hazard Classification 7 5.2.5.1 Light hazard occupancy Dwellings NFPA 1142 Classification Of Construction 6.2 .... structures shall be classified by type of construction and shall be assigned a construction classification number. NFPA 1142 Classification Of Construction 6.2.1 Type V (Wood Frame) Construction Classification Number 1.5 Dwellings NFPA 1142 Chapter 4 Minimum Water Supply = (TOTAL CUBIC FT) x (CONST CLASS OCCUP 1.5) x ( Exp. Factor 1.5) (CLASS # 7) PER 1142 FOR ALL EXPOSURE HAZARDS MULTIPLY TOTAL BY: 1.5 NFPA 1142 NFPA 1142 4.2 SINGLE STRUCTURES WITHOUT EXPOSURE HAZARDS (2000 gal. minimum) 4.3 SINGLE STRUCTURES WITH EXPOSURE HAZARDS (3000 gal. minimum) NFPA 1142 NFPA 1403 50% Reserve SINGLE STRUCTURES WITHOUT EXPOSURE HAZARDS (3000 gal. minimum) SINGLE STRUCTURES WITH EXPOSURE HAZARDS (4500 gal. minimum) NFPA 1142 Determining Minimum Water Supplies 4.6 The fire department shall develop the capability to deliver the amount of water determined in accordance with Sections 4.2 through 4.5 to the incident scene at the rate shown in Table 4.6.1 NFPA 1142 Table 4.6.1 Total Water Required: Rate Capability: < 2,500 250 2,500 - 9,999 500 10,000 - 19,999 750 > 20,000 1,000 NFPA 1142 What if the exposure is larger than the structure being burned? Calculate water supply based on the larger structure NFPA 1142 Multiple Exposures? NCFRC Exception Add .5 for each Exposure Example: 2 Exposures 1.5 1st Exposure + .5 2nd Exposure 2.0 Exposure Factor NFPA 1142 3 Exposures = 1.5 + .5 + .5 = 2.5 (1) (2) (3) 4 Exposures = 1.5 + .5 + .5 + .5 = 3.0 (1) (2) (3) (4) NFPA 1142 Determining Minimum Water Supplies Go back to NFPA 1403: 4.2.23.2 A minimum reserve of additional water in the amount of 50 percent of the fire flow demand in 4.2.23.1 shall be available to handle exposure protection or unforeseen situations. NFPA 1142 Practice Time! See if your calculations are the same! (Remember – calculate gable roofs as ½ the height from the attic floor to the ridge pole) 50’ NFPA 1142 50 x 24, 2 stories with gable roof, 8’ from attic floor to ridgepole 24’ 50 X 24 = 1,200 square ft. Height = 8 + 8 + 4* = 20’ 1,200 x 20 = 24,000 cubic ft. 2 story w/gable roof 8’ ceilings 8’ to ridgepole (Dwelling) Exp. OCCUP HAZ CLASS = 7 (divide by 7) 3429 GAL. Go to Table 4.6.1 CONST CLASS = 1.5 (multiply by 1.5) 5144 GAL. Table 4.6.1 shows: 500 GPM 1 EXPOSURE HAZARD (multiply by 1.5) 7715 GAL. for about 15 minutes. (7715 gal / 500GPM) Must be capable of flowing 500 GPM Exposure 50% additional reserve per NFPA 1403: 11,573 Total Gallons NFPA 1142 65’ x 30’ = 1,950 square ft Height = 8’ + 4* = 12 ft. 1,950 x 12’ = 23,400 cubic ft 65’ Exp. 30’ 1 story w/gable roof 8’ ceilings 8’ to ridgepole OCCUP HAZ CLASS = 7 (divide by 7) 3343 GAL. CONST CLASS = 1.5 (multiply by 1.5) 5014 GAL. 2 EXPOSURE HAZARDS (multiply 1 + .5 + .5) Go to Table 4.6.1 Exp. Dwelling 750 GPM Flow for about 14 minutes (10,029 gal / 750 GPM) 10,029 Gallons 50% additional per NFPA 1403: Exposures 15,044 Total Gallons NFPA 1142 52’ x 44’ = 2,288 square ft Height = 10’ + 10’ + 10* = 30’ 2,288 x 30’ = 68,640 cubic ft Exp. 52’ 44’ OCCUP HAZ CLASS = 7 (divide by 7) 9806 GAL. CONST CLASS = 1.5 (multiply by 1.5) 14,708 GAL. 3 EXPOSURE HAZARDS (1.5 + .5 + .5 = 2.5) 36,772 Gallons Exp. 2 story w/ mansard roof 10’ ceilings Go to TableDwelling 4.6.1 Exp. 1000 GPM Flow for about 37 minutes (36,772 gal / 1000 GPM) Exposures 50% additional per NFPA 1403: 55,158 Total Gallons NFPA 1142 Remember! • • • • • • • • Calculate Square Footage Calculate Cubic Footage Occupancy Hazard Class Construction Class Exposure factor Required GPM Minutes Flow Sustained 1403 Reserve