Laura Ghorbi, PE, CFM
RAMPP
Familiarize floodplain administrators with building codes
Familiarize building code officials with floodplain ordinances
Identify where building codes and floodplain ordinances overlap and where the gaps are
Discuss the different approaches to adopting floodplain management provisions
Understand where higher standards may exist and how to coordinate with the building code
2
NFIP participating municipalities must adopt and enforce floodplain management regulations that meet the minimum requirements of the
NFIP.
The regulations must:
Be legally enforceable
Applied uniformly throughout the community
Floodplain regulations are usually found in one of, or a combination of, five types of regulations: “stand alone”, zoning ordinances, building codes, subdivision regulations and sanitary regulations.
3
ALL development in the SFHA requires a permit
Definition of development (as per 44 CFR
59):
Any manmade change to improved or unimproved real estate, including, but not limited to buildings or other structures, mining, dredging, filling, grading, paving, excavation or drilling operations, or storage of equipment or materials
Poquoson, VA (from FEMA Region III)
Ensure you have a process for capturing all floodplain development
Set forth in 44 CFR Section 60.3
Site reasonably safe from flooding
Construct to minimize flood damage
Use flood damage-resistant materials
Foundation and elevation requirements
Design to prevent flotation, collapse, lateral movement during flooding
Design or locate equipment to prevent water entry
Substantial Improvement/Substantial
Damage requirements
5
Required below the BFE
Withstand prolonged contact with floodwaters
FEMA guidance in Technical
Bulletin 2
Image source: FEMA file photo
6
A Zones
Slab-on-fill
Fully-enclosed foundation wall
(flood openings required)
Open foundation on piers, posts, pilings, or columns
V Zones
Open foundation on columns or pilings
Designed by a registered design professional
FEMA Quick Reference Guide: Comparison of Select NFIP & Building Code Requirements
A Zones: top of lowest floor to or above BFE
FEMA Region III, Poquoson, VA
V Zones: bottom of lowest horizontal structural member to or above BFE
FEMA Region III, Tinicum, PA
8
Structures and utilities must be anchored to resist the effects of flotation , collapse , and lateral movement
Presenter’s Name June 17, 2003 9
Image source: FEMA file photo
A Zones
Limited to parking, building access, and limited storage
At least two openings no more than 1 foot above grade
One square inch of opening for each square foot of enclosed space
Engineered openings required certification
V Zones
Limited to parking, building access, and limited storage
Space must be free of obstruction, or
Breakaway walls, open lattice, or louvers
Yardley Borough, PEMA
Compliant openings
10
Permitted only for non-residential structures in A Zone floodplains
Structure must be made watertight
To or above BFE (or BFE +1 foot for insurance purposes)
Requires certification by a registered design professional
Image: Whole Building Design Guide, National Institute of Building Sciences
11
• Cost to restore or improve the structure equals or exceeds 50% of its market value
• If damaged, use the pre-damage market value
• Must be brought into full compliance
Middletown Borough, Dauphin County, PA (from PEMA) Town of Bloomsburg, Columbia County, PA (from PEMA)
12
Storage of materials
Paving and grading
Placement of fill
Recreational vehicles and temporary structures
Alteration of watercourse
Must have same or greater capacity
Must maintain capacity over time
Image source: SC Quick Guide for Mapping
13
• NFIP requirements are performance-based
• 11 Technical Bulletins provide prescriptive guidance for compliance
14
The flood provisions of the 2012 and 2009 I-Codes meet or exceed
National Flood Insurance Program minimum requirements for buildings and structures .
I-Codes do not meet the minimum NFIP requirements for other development unless adopting:
• In their entirety,
• Appendix G of the IBC,
• Chapter 1 (administration), AND
• No limiting amendments
15
Prescriptive Code via IRC
The more prescriptive the code, the more engineering is behind the requirements – and the less individual design is required
Details the specifications for construction standards
Design professional only required where proposal is outside of the specifications of the code
Performance Code via IBC
Leave it to the designer and engineer to decide how to achieve that performance
Need a technical professional
References other prescriptive standards (like ASCE 24)
16
Addresses flood-related administrative requirements
The only place in the I-Code that addresses development other than buildings
G101 Administration
G102 Applicability
G103 Powers and Duties
G104 Permits
G105 Variances
G201 Definitions
G301 Subdivisions
G401 Site Improvement
G501 Manufactured Homes
G601 Recreational Vehicles
G701 Tanks
G801 Other Building Work
G901 Temp Structures & Temp
Storage
G1001 Utility & Miscellaneous Group U
17
ASCE 7, Minimum Design
Loads for Buildings and Other
Structures
Cited by IBC
Flood loads include:
Hydrostatic loads
Hydrodynamic loads
Wave loads
Impact loads (from debris and ice)
ASCE 24, Flood Resistant
Design and Construction
Cited by IBC and IRC
Specific limitations, minimum requirements, and performance standards for the design and construction of buildings and structures in flood hazard areas
18
How are administrative provisions of the codes handled?
Many States modify or rewrite
Some States allow communities to write their own
Some States use a single chapter for all codes
Duties and powers of the building official
Granting modifications
Content of construction documents and plans
Inspections
19
The Floodplain Administrator and the Building Code Official are both responsible for ensuring compliance and confirming as-built conditions
I-Codes call for at least:
Lowest floor or footer inspection to be conducted to allow for correction of possible violation prior to further vertical construction
Survey before final inspection
Final as-built inspection
20
21
Base Flood Elevation (BFE) and Design Flood Elevation (DFE)
DFE is always BFE or higher
In most communities, DFE = BFE
DFE is greater than BFE if a community regulates beyond the
SFHA on the effective FIRM
DFE is NOT BFE + freeboard
Freeboard is typically included as an additional height above the BFE or DFE in lowest floor elevation requirements
22
Delineated using LiMWA
Flood hazards can be much greater than in riverine Zone A:
Waves 1.5 to 3 feet high are capable of causing structural damage and erosion
Older FIRMs may fail to reflect changing site conditions as a result of long-term erosion
Higher Standard: IBC places Zone V requirements in the Coastal A Zone where delineated
Higher Standard: IRC requires 1 foot of freeboard in the Coastal A Zone where delineated
Image source: FEMA P-55
23
Higher elevation requirements for critical and essential facilities, depending on occupancy and purpose of building
Image source: FEMA file photo
Image source: stock photo
24
What edition of the code was adopted and who is the agency?
How is the code adopted? (at the State level, etc.)
Are there amendments or modifications?
The regulations in the building codes and local floodplain management ordinance to meet or exceed the requirements of the NFIP
How to enforce all floodplain management requirements across all codes and ordinances
25
Department of Consumer
Include agency references N/A
Must know how it works in each state – most important to know who to talk to and understand how it is adopted
Maryland
Department of Housing and Community
Development
State-wide code
Municipalities can adopt higher standards
Pennsylvania
Virginia
West Virginia
Department of Labor and
Industry
Department of Housing and Community
Development
Fire Commission, Office of State Fire Marshall
State-wide code
Municipalities can adopt higher standards
State-wide code
Municipalities can adopt higher floodplain standards
State-wide code
Municipalities can adopt higher standards
26
Three main approaches to adoption and enforcement
Stand-alone ordinances
Companion or Wrap-around ordinances
I-Codes: in their entirety, with Appendix G of the IBC, Chapter 1,
AND no limiting amendments
27
Might be easier to administer and enforce
One ordinance contains all NFIP requirements for development standards
Developers and officials can easily see the requirements in one place
Ensure that all offices/agencies are aware of floodplain standards when inconsistent
May not be coordinated with other regulations or codes
– regulations could be in conflict
28
Use the building code for design and construction of buildings and structures
Use a companion ordinance for administrative provisions:
Adoption of effective maps (and map revisions)
Floodway encroachment analyses
SI/SD determinations
Variances/modifications
Use a companion ordinance for development activities that are not regulated by the building code
29
Must have both IBC and IRC, with flood provisions intact
Must capture existing buildings
Must retain administrative provisions (flood)
Must capture buildings exempt from the code
Must adopt Appendix G (administrative and development other than buildings)
Must understand where each NFIP requirement is met
Amendments must not weaken the code
30
If the community has both floodplain management ordinances and the I-Codes in effect:
The more restrictive prevails
Understand which office is responsible for each requirement
Go through coordination process to identify differences and gaps
Decide how best to resolve those differences and eliminate the gaps (change code, change ordinance, rely on case-by-case application of “more restrictive prevails”)
31
NFIP Regulations (44 CFR Parts 59 & 60
)
Local Floodplain
Management
Regulations* or
IBC Appendix G*
Building Code
Flood Resistant
Buildings and
Development
ASCE 7
ASCE 24
32
Worksheets to help ensure communities meet all NFIP requirements
Helps to identify what to capture in a companion ordinance
Crosswalks of I-Codes to NFIP regulations
Sample plan review and inspection checklists
Currently being updated – 4 th
Edition coming in Summer 2014
33
The NFIP minimums regulate all development in the SFHA
Remember, nearly all of the NFIP minimum requirements for buildings and structures are ALREADY found in the building code
But, other forms of development may not be captured in the building code (for instance, placement of fill)
Higher standards likely exist in local floodplain management ordinances
Building Code Officials and Floodplain Administrators must work together on administration and enforcement
Uncoordinated enforcement results in non-compliance, higher insurance premiums, and increased risk to life and property.
34
FEMA Building Science Homepage: http://www.fema.gov/buildingscience
Click on Building Code Resources
Flood Resistant Provisions of the 2012 and 2009 I-Codes
Highlights of ASCE 24-05, Flood Resistant Design and
Construction
Provisions of the I-Codes and ASCE 24 Compared to the NFIP
I-Codes vs. NFIP checklists
Building Science Helpline: 1(866) 927-2104 or FEMA-
Buildingsciencehelp@fema.dhs.gov
For further questions on the NFIP, contact your State Floodplain
Manager
35
FEMA-R3-FMI@fema.dhs.gov
- FEMA Region III Floodplain
Management and Insurance Branch
Washington, D.C.
Delaware
Maryland
Pennsylvania
Virginia
West Virginia
Phetmano Phannavong,
P.E., CFM
Michael Powell, CFM
David Guignet, P.E., CFM
Daniel Fitzpatrick, CFM
Charley Banks, CFM
Kevin Sneed, CFM
202-535-2248 phetmano.phannavong@dc.gov
302-739-9921 michael.powell@state.de.us
410-537-3775 dave.guignet@maryland.gov
717-720-7445 dafitzpatr@state.pa.us
804-371-6135 charley.banks@dcr.virginia.gov
304-957-2571 kevin.l.sneed@wv.gov
36