DESIGN AND CONSTRUCTION STANDARDS FACILITIES MANAGEMENT SERVICES DIVISION 15 MECHANICAL SYSTEMS DIVISION 15 MECHANICAL SYSTEMS Division 15 of the Carnegie Mellon University Design and Construction Standards Manual addresses the following requirements for mechanical construction: 15010 15050 15100 15135 15140 15170 15250 15330 15410 15430 15440 15453 15460 15481 15488 15510 15520 15530 15540 15545 15582 15680 15683 15685 15711 15755 15781 BASIC MECHANICAL REQUIREMENTS BASIC MECHANICAL MATERIALS AND METHODS VALVES METERS AND GAGES SUPPORTS AND ANCHORS MOTORS AND DRIVES INSULATION FIRE SUPPRESSION SYSTEMS PLUMBING PIPING PLUMBING SPECIALTIES PLUMBING FIXTURES PUMPS WATER HEATERS COMPRESSED AIR SYSTEMS NATURAL GAS SYSTEMS HYDRONIC PIPING STEAM AND STEAM CONDENSATE PIPING REFRIGERANT PIPING HVAC PUMPS CHEMICAL WATER TREATMENT STEAM CONDENSATE RETURN UNITS WATER CHILLERS RECIPROCATING WATER CHILLER WATER-COOLED CENTRIFUGAL CHILLERS FACTORY-FABRICATED COOLING TOWERS HEAT EXCHANGERS PACKAGED HEATING AND COOLING AIR HANDLING UNITS DIVISION 15 DESIGN AND CONSTRUCTION STANDARDS MECHANICAL SYSTEMS FACILITIES MANAGEMENT SERVICES DIVISION 15 MECHANICAL SYSTEMS (CONT) 15782 15790 15831 15832 15835 15840 15850 15854 15860 15865 15870 15886 15891 15920 15930 15932 15970 15975 15985 15990 P. 15-2 ROOFTOP HEATING AND COOLING UNITS AIR COILS FAN COIL UNITS FINNED-TUBE RADIATION UNIT HEATERS UNIT VENTILATORS FANS AND EXHAUST SYSTEMS CENTRAL STATION AIR HANDLING UNITS CENTRIFUGAL FANS TUBULAR CENTRIFIGALS POWER VENTILATORS AIR FILTERS METAL DUCTWORK SOUND ATTENUATORS AIR TERMINALS AIR OUTLETS AND INLETS HVAC CONTROLS CONTROL SYSTEM EQUIPMENT SEQUENCE OF OPERATION TESTING, ADJUSTING, AND BALANCING December 1998 DESIGN AND CONSTRUCTION STANDARDS FACILITIES MANAGEMENT SERVICES DIVISION 15 MECHANICAL SYSTEMS 15010 BASIC MECHANICAL REQUIREMENTS The Design Consultant shall be expected to analyze a minimum of three alternative systems and justify the selected system. For example: typically variable air volume (VAV) systems are preferable to individual fan coil units because of reduced maintenance requirements. Fan coil systems will be allowed in special circumstances such as where ceiling space is limited, and there is adequate room for ductwork. As another example: typically VAV systems are preferable to constant volume in fume-hood exhaust applications, but one- or two-hood laboratories may not warrant the expense. Mechanical Rooms All mechanical equipment shall be located inside the building wherever possible. The Design Consultant shall allow for adequate mechanical space during the programming phase. (Architectural graphics standards shall be used as a guideline.) Mechanical rooms shall be designed in accordance with all applicable codes. Mechanical rooms shall be designed to provide adequate maintenance clearances for all equipment (such as tube and coil pull spaces). Adequate means of access shall be provided for replacement of the largest piece of equipment without removing walls. Clearance shall be adequate to allow maintenance activity without disassembly of any fixed piping, supports, and so forth. Clearance shall be provided around boilers and pressure vessels in accordance with the Pennsylvania Boiler Code. Mechanical rooms with heat-producing equipment shall be provided with an automatic ventilation system. Mechanical rooms shall be provided with a minimum of one floor drain. Floor drains shall be piped to a sanitary system. Mechanical rooms shall be provided with at least one hose bib with backflow preventer in the supply piping. All equipment drains, blowdown lines, and such shall be piped to a floor drain with an approved air gap fitting. (See Section 15510 Hydronic Piping.) Mechanical rooms shall be located to provide access directly from the building exterior. Where this is not possible, mechanical rooms shall be accessed from public spaces. Mechanical rooms shall not be located where vibration and/or noise will be objectionable. Mechanical rooms shall be heated to maintain 55 °F minimum. Janitor Rooms Janitor rooms are not accessible to maintenance employees. Therefore, mechanical equipment, valves, electric panels, thermostats, and so forth shall not to be placed in these rooms. December 1998 P. 15-3 DIVISION 15 DESIGN AND CONSTRUCTION STANDARDS MECHANICAL SYSTEMS FACILITIES MANAGEMENT SERVICES Design Guidelines The following are general design guidelines for inside and outdoor design conditions. Design Guidelines for Indoor and Outdoor Temperatures Area Season Indoor (Note 3) Outdoor Comfort Areas (Note 1) Summer 76°F DB 91 °F DB, 72 °F WB Winter 70°F DB 0 °F DB Summer Consult with User 91 °F DB, 72 °F WB Winter Consult with User 0 °F DB Summer As specified in latest edition of “Guide for Care and Use of Laboratory Animals” 95 °F DB, 75 °F WB Winter As specified in latest edition of “Guide for Care and Use of Laboratory Animals” -10 °F DB Labs & Critical Areas Animal Rooms (Note 2) Note 1 Consideration shall be given to morning warm-up cycle. Note 2 Typically these systems are required to be 100% outdoor air systems, therefore, the outdoor design conditions are altered for these and any other 100% outside air systems. Specified discharge air temperatures shall be maintained at all times. Note 3 Design conditions shall be scheduled on the Contract documents for each room. Rooms may be grouped by number for simplicity of document preparation. Design conditions shall appear on the first sheet of the heating, ventilating, and air-conditioning drawings, per the BOCA code. Minimum and maximum relative humidity requirements shall be identified by the Design Consultant in conjunction with the end user. Energy Costs Life Cycle Cost Analyses are required, or alternative system evaluations such as for constant volume vs. variable volume hood exhaust systems and for any energy-saving features incorporated into the project. Alternative system evaluations shall be required in all moderate and complex projects, involving new mechanical systems. Energy costs will be identified by the University and shall be used in all Life Cycle Cost Analyses. As energy costs are modified from time to time, the Design Consultant shall consult the University for the most recent revisions. Design Calculations The University requires a record copy of calculations for all projects to be submitted at the end of Design Development. P. 15-4 December 1998 DESIGN AND CONSTRUCTION STANDARDS DIVISION 15 FACILITIES MANAGEMENT SERVICES MECHANICAL SYSTEMS Equipment (Non-Typical) Loads or Process Heat Gains Equipment or process heat gains, excluding people, lights, conduction, and solar loads, in critical and special areas such as computer rooms, microcomputer labs, and research labs shall be scheduled on the drawings by room number for future reference. General Pressure Relationship and Ventilation Requirements The following table provides the pressure and ventilation requirements for University buildings. University Building Pressure and Ventilation Requirements Area Pressure Relationship to Adjacent Areas Minimum Outdoor Air Requirement All Air Exhausted to Outdoors Recirculation Permitted ** Animal Rooms * * * * Auditoriums E Note 1 No Yes Classroom E Note 1 No Yes Computer Rooms E Note 1 No Yes Copy Centers N Note 1 Yes No Darkrooms N Note 1 Yes No Dining Areas P Note 1 No Yes Janitors Closets N Note 3 Yes No Kitchens N Note 1 Yes No Laboratories Note 4 Note 1 Note 4 Note 4 Laundry N Note 1 Yes No Libraries E Note 1 No Yes Locker Areas N Note 1 Yes No Lounges N Note 1 No Yes Mech/Elect Room N Note 2 Yes No Music Rooms E Note 1 No Yes Offices E Note 1 No Yes PC Labs E Note 1 No Yes Toilet Rooms N Note 3 Yes * Refer to “Guide for Care and Use of Laboratory Animals” ** Does not apply to units serving this area only. The air may be recirculated by roof units. P,E,N= Positive, Equal, Negative No Note 1 Conform to ASHRAE STANDARD 62, Ventilation for Acceptable Air Quality (latest edition) and Mechanical Ventilation, BOCA, latest edition. Note 2 Quantity required to maintain a maximum of 10 °F above Summer Outdoor Design DB temperatures. Note 3 Transfer from corridors permitted when allowed by code. Exhaust air quantity shall be greater of 2.5 cfm/ft 2 or 10 air changes per hour (AC/HR). Note 4 Review specific requirements with the University Project Manager and the University EH&S Office. Requirements may vary. December 1998 P. 15-5 DIVISION 15 MECHANICAL SYSTEMS DESIGN AND CONSTRUCTION STANDARDS FACILITIES MANAGEMENT SERVICES Central Chilled Water The chiller run-around pumps are constant volume, decoupled from the distribution loop, and as load is added to the system, the load is decoupled from the distribution loop via a “primary/secondary” piping bridge. The distribution loop is sized for a 15 °F water temperature drop and served by variable-speed pumps. Load side pumps are typically constant volume, but variable-speed pumps may be warranted in some cases. Zoning Zoning of the systems shall be in accordance with sound engineering judgment relating to varying load conditions, function of space, occupancy schedules, and such. Final zoning shall be discussed at the conceptual design stage with the University Project Manager. All-Air Systems Ducted supply and return systems are required. Return plenums are not permitted without prior approval. 100% shutoff variable air volume systems are not permitted. Minimum airflow must be maintained to satisfy ventilation requirements. Reheat shall be provided for all interior zone VAV boxes where there is potential for no internal load (such as conference rooms). Fan powered boxes using re-circulated air may be considered as a last resort. Economizer cycle (see Section 15985) shall be utilized on all systems over 2000 cfm (with the exception of computer rooms or other rooms with strict RH requirements) for areas requiring year-round cooling. For all systems 5 tons and over that use economizer cycles, a separate return or exhaust fan shall be used to provide positive relief. The requirement for duct air leakage tests shall be reviewed on a project basis with the University Project Manager. Standby Equipment for Critical Areas Standby equipment requirements shall be discussed with the University Project Manager for systems serving critical areas such as: • Laboratories • Research buildings • Animal rooms Contract documents shall indicate equipment that is intended for standby service. Animal rooms, in addition to being tied into the main building’s chilled water system, shall have an alternate connection to city water for emergency use. Auto changeover shall be provided for all standby equipment. Changeover shall be alarmed to the direct digital control (DDC) system. P. 15-6 December 1998 DESIGN AND CONSTRUCTION STANDARDS FACILITIES MANAGEMENT SERVICES DIVISION 15 MECHANICAL SYSTEMS Equipment Locations Terminal units and air handling equipment shall not be located above an occupied space without prior approval from the University. All equipment must be readily accessible for maintenance. Equipment located 4 ft or more above the finished floor level shall include access platforms or walkways. Floor-mounted HVAC equipment (including specialty laboratory equipment such as nuclear magnetic resonators (NMRs) shall be installed on concrete housekeeping pads. Pads shall be isolated from the surrounding slab if vibration requirements warrant. All equipment installed on grade outdoors shall be installed on reinforced concrete pads. Foundation requirements shall be analyzed for large pad-mounted equipment. Locations of mechanical equipment that affects the aesthetics of a building or the campus shall be approved by the University Architect. Approval procedures shall be discussed with the University Project Manager. Identification All motor-driven equipment shall be individually numbered on the drawings by the Design Consultant (for example, unit heaters may be numbered UH-1, UH-2, etc., even though both units may be the same size and type). Numbers shall be in accordance with the University’s Preventative Maintenance database numbering guidelines. Where possible, numeric sequence shall follow the last number for each building. The University Project Manager will obtain this information for the Design Consultant from the Preventative Maintenance Manager. All motor-driven equipment, including associated electrical devices, shall be tagged in accordance with the University’s Preventative Maintenance numbering guidelines. Tags shall be engraved, black, laminated, micarta tags with white-reading symbols secured to equipment (not the motor), usually inside the access door for the equipment in finished areas and exposed in all other areas. Tags should be sized to include the University barcode label (2.5-in. x 1.0-in.), mechanically fastened to the equipment. GLUE OR WIRE IS PROHIBITED. Where possible, numeric sequence shall follow the last number in that building. The University Project Manager will obtain this information from the Preventative Maintenance Manager for the Design Consultant. Condensing Units and Condensers The manufacturer’s minimum recommended clearances, including distances from landscaping, shall be maintained. Where water-cooled condensing units are specified, cooling towers, evaporative condensers, or a central chilled water system shall be used. Cooling water to waste system is NOT permitted. December 1998 P. 15-7 DIVISION 15 MECHANICAL SYSTEMS DESIGN AND CONSTRUCTION STANDARDS FACILITIES MANAGEMENT SERVICES Packaged Heat Pumps Use of air-cooled packaged heat pumps on the University campus is not permitted. Potential water-cooled applications shall be reviewed with the University Project Manager. Sound Pressure Level Requirements The sound pressure levels around mechanical and electrical equipment (boilers, fans, pumps, pressure-reducing valves, motors, turbines, elevators, transformers, etc.) in equipment spaces shall not exceed 85 dBA at any point 3 ft from the equipment, with all equipment in the room operating. Sound calculations shall be required. The sound criterion applies to the complete operating range of each piece of equipment. Exceptions shall be reviewed by the University Project Manager. The maximum room criteria (RC) levels for various usage within the building shall be as indicated in Table 2, Design Guidelines for HVAC System Noise in Unoccupied Spaces, Chapter 43, “Sound and Vibration Control,” of the latest edition of the ASHRAE Systems and Applications Handbook. Sound pressure level measurements shall be made in accordance with “Sound Testing Procedures” outlined in the latest edition of the ASHRAE Systems and Applications Handbook. Tests shall be made with all equipment operating, and space unoccupied. Equipment installed outside the building, at grade, in areaways, attached to walls, and on the roof, such as cooling tower fans, air conditioning units, refrigerant condensers, fans, exhaust silencers, air intakes, etc., shall comply with all local, city, state, and federal sound level regulations (as well as any existing University covenants or agreements with neighbors). When equipment or space sound pressure levels exceed the specified criteria, the Contractor and/or the Design Consultant shall, at no cost to the University, determine the source of the noise and make the necessary corrections to reduce it to the acceptable levels. Guarantee The specifications shall be prepared to include a one-year labor and material guarantee for the entire installation, with the exception of extended guarantee periods for the following: • Refrigeration Compressors - Five years • Automatic Temperature Control (ATC) Systems - Two years P. 15-8 December 1998 DESIGN AND CONSTRUCTION STANDARDS FACILITIES MANAGEMENT SERVICES DIVISION 15 MECHANICAL SYSTEMS 15050 BASIC MECHANICAL MATERIALS AND METHODS Ceiling Access Panels Screwdriver-actuated locks are required on ceiling access panels. Access panels are not required in lift-out ceilings, but each panel must be identified with a color button, cleated through. The color code of the principal service shall be used. Access panel sizes shall be suitable for application. Access panel locations and sizes shall be indicted on Contract drawings. 15100 VALVES General All valves of a particular type and size range on any one project shall be the product of one manufacturer. Valves shall be right handed. Small balancing cocks shall be the type that can be used for shut-off without disturbing the balancing point setting. Where possible, valves shall be installed with the valve bonnet in an upright position to prevent deterioration or corrosion of the bonnet and packing. Valve body materials shall be compatible with piping system materials. A valve drain shall be provided at the base of each water piping riser and manual air vents shall be provided at the top of each riser and at the high point of the system. All valve, strainers, and steam traps shall be provided with reusable strap-on insulation covers. Valve tags shall be 1- x 2-in. laminated, black micarta attached by a 10-gage brass “S” hook. Valve numbers shall be engraved as large as possible and shall read white. Where possible, the numbering sequence shall follow the last number used in that building. Valve charts shall be typewritten on white bond paper and mounted in a glass front frame. Charts shall indicate service, number, and location. On renovation projects, the Contractor shall be directed to revise existing valve charts as required. All exposed valves in finished areas shall be chrome-plated. Ball Valves All branch lines in the water supply piping up to 3-in. in diameter shall be fitted with ball valves. Ball valves shall also be used for sectioning the water distribution system. Where insulation is required, extended stems shall be provided. December 1998 P. 15-9 DIVISION 15 MECHANICAL SYSTEMS DESIGN AND CONSTRUCTION STANDARDS FACILITIES MANAGEMENT SERVICES Butterfly Valves Butterfly valves are acceptable for shut-off service and balancing and should be used on piping 2-in. in diameter and greater. (For branch lines over 3-in. in diameter see “Ball Valves.”) Gate Valves A gate valve, angle valve, or compression stop shall be placed immediately below each plumbing fixture on each hot and cold supply so that service can be readily shut off for maintenance. Pump Valves All circulating pumps shall have a check valve and a balancing valve on discharge. In lieu of this, in-line triple-duty valves are acceptable. Shutoff Valve Isolation shutoff valves shall be installed at each piece of equipment, terminal unit, and each branch takeoff to facilitate shutdown for repair. Positive shutoff balancing valves with memory may satisfy this requirement at terminal units. Balancing Valves Balancing valves shall be installed in all three-way control valve bypass lines and at all flow meters. Gate valves shall NOT be used in a throttling application. Globe plug valves or ball valves shall be used. Gate valves shall be limited to shutoff service only. Where balancing valves are installed, there shall be some means (not including Pete’s Plugs) to read flow. Circuit setters shall be used on pipe less than 2-in. in diameter. Check Valves Where check valves are required, they shall be installed on the equipment side of all shutoff valves to facilitate servicing of the check valve. Drain Valves Drain valves shall be a minimum diameter of 0.75 in. with hose end connection and cap. Control Valves The design documents shall include a valve schedule for all ATC valves. The schedule shall indicate service, flow, CV, and pressure drop. P. 15-10 December 1998 DESIGN AND CONSTRUCTION STANDARDS FACILITIES MANAGEMENT SERVICES DIVISION 15 MECHANICAL SYSTEMS 15135 METERS AND GAGES Gages Differential pressure gages shall be provided across the supply and return of water meters, water filters, coils, and pressure reducing valves (PRVs). “PT” Pete’s Plugs may be used on reheats. Thermometers shall be provided on supply and return of water coils, chiller tube bundles, heat exchangers, boilers and reheats. Regardless of whether the control system is pneumatic or DDC, dial thermometers shall be placed on all air handler system discharge, return, mixed air, and outside air ductwork. The location of dial thermometers shall be shown on plans. Normal Use Gages shall have screw-type recalibration, bronze bushed movements, quality unit construction, and 4.5-in. dial. The Plumbing Contractor shall provide similar gages for water and air. Gages shall be calibrated for static head. All gages shall be equipped with shutoff valves and snubbers. Gages located overhead shall have a 6-in. diameter, and shall be positioned so that they are readable from floor level. Siphons shall be used with all steam gages. Also, all gages shall have snubbers and gage cocks or isolation valves suitable for the pressure involved. Thermometers for general use shall be RED “V” series as manufactured by Marshalltown Manufacturing, Incorporated. Remote-reading Model V-7 vapor tension and bulb shall be used and mounted in panelboards where possible. When the above is not possible or practical, the Model V-3 with three-way mounting bracket shall be used. Field thermometers on an air handler shall include discharge air, return air, outside air, and mixed air. Field thermometers on water lines shall be “tree” type. Gages and thermometers shall be read to twice the operating pressure or temperature including static head for water. The Design Consultant shall specify gage and thermometer ranges. 15140 SUPPORTS AND ANCHORS Pipe Hangers and Supports An adequate pipe suspension system shall be designed and installed in accordance with recognized engineering practices, using standard, commercially accepted pipe hangers and accessories. The use of pipe hooks, chains, or perforated iron for pipe supports is not acceptable. Pipe suspension systems for fire suppression systems shall be designed and installed in conformance with applicable sections of BOCA and NFPA. December 1998 P. 15-11 DIVISION 15 MECHANICAL SYSTEMS DESIGN AND CONSTRUCTION STANDARDS FACILITIES MANAGEMENT SERVICES The Contractor shall submit data sheets for approval on all pipe hanger items prior to installation. All piping shall be arranged to maintain the required pitch and shall provide for proper expansion and contraction. No holes shall be drilled or burned in structural building steel for hanger rod supports. Vertical runs of pipe shall be supported with riser clamps made specifically for pipe or for tubing. Hanger rods shall be threaded 1.5 in. on each end or continuous thread. Eye rods shall be welded. The minimum diameter shall be no less than 0.375-in. for support of pipe with a 2-in. diameter or smaller, or 0.5-in. for support of pipe with a 2.5-in. diameter or larger (per ANSI/ASME B31.1 Power Piping Code). Supports for plastic and copper piping shall be spaced at a maximum of 6 ft on center. For steel pipe, the maximum spacing of supports shall be per Table 121.1.4 of ANSI/ASME B31.1 Power Piping Code. Where there are concentrations of valves and fittings, closer spacing may be necessary. Hangers shall be installed not more than 12 in. from each change in direction of pipes. All hangers for piping shall have a means of vertical adjustment. If adjustment is not incorporated in the hangers, turnbuckles are acceptable. Piping suspension systems with vibration isolation capability shall be provided as required. More information on vibration isolation requirements for piping suspension systems is provided in Resilient Pipe Hangers, Page 38, Chapter 43, “Sound and Vibration Control,” of the latest edition of the ASHRAE Systems and Applications Handbook. Copper clamps and hangers shall be used on copper piping. Pipe Expansion The Design Consultant shall examine the piping system and shall design expansion compensation into the system by use of expansion loops, flexible connectors or, where space is limited, self-aligning bellows-type expansion joints. The Design Consultant shall design all anchors and guide supports as needed and shall detail them on the drawings. Vibration Control Mechanical and electrical equipment and associated piping and duct work shall be mounted by vibration isolators as specified and as required to minimize transmission of vibrations and noise to building structures or spaces. Selection of isolator type shall be as given in Table 41, Equipment Vibration Criteria, Chapter 43, “Sound and Vibration Control,” of the latest edition of the ASHRAE Systems and Applications Handbook. P. 15-12 December 1998 DESIGN AND CONSTRUCTION STANDARDS FACILITIES MANAGEMENT SERVICES DIVISION 15 MECHANICAL SYSTEMS All rotating equipment shall be balanced both statically and dynamically. Vibration shall not exceed the guidelines given in Table 41, Equipment Vibration Criteria, Chapter 43, “Sound and Vibration Control,” of the latest edition of the ASHRAE Systems and Applications Handbook. All motors over 5 hp must be solidly attached to a common base with the driven unit to minimize alignment problems. Solid sheaves and band belts shall be used to minimize vibration in multiple V-belt driven equipment over 15 hp. Vibration analysis shall be conducted by the Contractor in the presence of the University representative and the Design Consultant. The Contractor shall furnish, at no cost to the University, qualified personnel and all instrumentation to conduct the analysis. The Contractor shall remove housings and covers and dismantle equipment as required to take vibration readings. After readings have been completed, the Contractor shall reassemble all equipment. It shall be necessary to check only equipment that, in the opinion of the University and the Design Consultant, does not meet the specification requirements. Where equipment vibration exceeds levels specified, the Contractor shall be directed to make corrections to reduce vibration frequencies and amplitude to within specified limits. If this cannot be accomplished, the equipment shall be replaced with equipment that will meet all requirements of the specifications at no cost to the University. The Contractor shall submit a report for approval to the University and the Design Consultant. The report shall include the vibration analysis of all rotating equipment of 0.5 hp and larger. Isolation Equipment Isolation shall be stable during starting and stopping of equipment without any transverse and eccentric movement of equipment that would damage or adversely affect operation of the equipment or appurtenances. Isolation shall be selected for the operating speed of the equipment. Isolators, including springs, exposed to the weather shall be hot dipped galvanized after fabrication. Hot dipped zinc coating shall comply with ASTM Method A-123 and shall not be less than 2 oz per square foot. Isolators shall be selected and located to produce uniform loading and deflection even when equipment weight is not evenly distributed. The type of isolation, base, and minimum static deflection shall be as required for each specific equipment application when supported on a solid (150 lb/ft3) concrete structural slab having a thickness of not less than 6 in. If vibration isolators with a deflection greater than the minimum specified are required to meet the noise criteria for the adjacent spaces, suitable isolation systems shall be submitted for approval prior to installation. Should vibration isolators installed for the equipment prove inadequate to prevent transmission of equipment vibrations to the building structure or limit equipment December 1998 P. 15-13 DIVISION 15 MECHANICAL SYSTEMS DESIGN AND CONSTRUCTION STANDARDS FACILITIES MANAGEMENT SERVICES vibration noise in the building spaces to their specified noise criteria levels, the isolators shall be replaced with units having the largest deflection that can be practically installed at no additional cost to the University. Piping and Ductwork Vibration isolation shall be provided for the following: • All high-pressure ducts (over 6 in. wc), for 20 ft from air handling equipment mounted on vibration isolators • All piping connected to equipment mounted on vibration isolators for a distance of 20 ft or 50 pipe diameters, whichever is longer • All piping connected to pumps, including the main supply and return risers, for 20 ft from the branch connection at each floor Vibration isolation shall be provided where there are flexible connections between equipment and ductwork. Hanger vibration isolators shall be selected for not less than the deflection provided for the equipment to which the piping is connected. The vibration isolator units selected shall provide for the thermal movement of the piping systems. Spring hanger isolators shall be substituted for elastometric type supports when their permissible hanger rod angular deflection will be exceeded. 15170 MOTORS AND DRIVES For requirements related to motors and drives, contact the University Project Manager. 15250 INSULATION Insulation shall be applied on clean, dry surfaces and only after tests and approvals required by the specifications have been completed. All pipe insulation on piping operating below ambient temperature shall be continuous through wall and ceiling openings and sleeves. Insulation on all cold surfaces must be applied with a continuous, unbroken vapor seal. Hangers, supports, anchors, etc., that are secured directly to cold surfaces shall be adequately insulated and vapor sealed to prevent condensation. Specified adhesives, mastics, and coatings shall be applied at the manufacturer’s recommended minimum coverage per gallon. Edges of vapor barrier insulation at valve stems, instrument wells, unions, and other raw edges shall be sealed adequately to prevent moisture from penetrating the insulation. P. 15-14 December 1998 DESIGN AND CONSTRUCTION STANDARDS FACILITIES MANAGEMENT SERVICES DIVISION 15 MECHANICAL SYSTEMS Fire Hazard Ratings All insulation shall have composite (insulation jacket and adhesive used to adhere the jacket to the insulation) Fire and Smoke Hazard ratings as tested under procedure ASTM E 84, NFPA 225, and UL 723. Insulation Protection Shields Insulation protection shields shall be installed at all pipe hangers and supports. Shields shall span an arc of 180°. An 18-gage stainless steel shield shall be installed fully over all insulated piping located on the roof. The shield shall be a minimum length of 36 in. and field located to prevent damage to the insulation while walking over the piping. Within mechanical equipment rooms (MERs), all piping below 7 ft shall have insulation jacketing of PVC. In steam tunnels, an aluminum jacket shall be used; above ceilings, a standard all-service fiberglass (ASF) jacket shall be used. Duct Insulation Insulation systems shall conform to the requirements in the Commonwealth of Pennsylvania Act 1980-222. The use of duct liner is discouraged. Duct liner may be considered for acoustical purposes only. Special sound attenuators shall be used wherever required to eliminate fan noise. The University representative shall be contacted for approval. All duct insulation in mechanical rooms shall be rigid fiberglass board, with a minimum density of 6 lb/ft3. All other duct insulation shall be blanket type. Pipe Insulation Insulation systems shall conform to requirements in the Commonwealth of Pennsylvania Act 1980-222. In general, piping systems shall be insulated with fiberglass piping insulation with an allpurpose jacket. Fittings, flanges, and valves shall be insulated with fiberglass inserts and premolded polyvinyl or PVC jackets. Refrigerant piping systems shall be insulated with elastromeric pipe insulation. Calcium silicate or high-temperature fiberglass shall be used in steam applications. Special insulation protection shall be considered for areas subject to abuse and moisture, such as outside areas, washdown areas, public areas, and classrooms. Removable insulated jackets shall be provided on all valves. The following equipment shall be provided with insulation: • Air eliminators • Boilers December 1998 P. 15-15 DIVISION 15 MECHANICAL SYSTEMS • • • • • • DESIGN AND CONSTRUCTION STANDARDS FACILITIES MANAGEMENT SERVICES Chilled water pump bodies Hot water storage tanks Heat exchangers Cold surfaces of chillers Flue pipe Engine exhaust 15330 FIRE SUPPRESSION SYSTEMS Fire suppression systems shall be provided per BOCA code, unless exempted by local code. A fire standpipe protection for buildings during construction shall be referenced to the requirements of the code, the fire department, and/or the underwriters, Factory Mutual. Submittals and Approvals All devices and equipment installed in the systems shall be approved and listed by Underwriters Laboratories and/or Factory Mutual. The Design Consultant should make early contact with the University’s Fire Safety Specialist (in the University EH&S Office). Prior to final approvals by the University, the Design Consultant shall submit plans and specifications to the insurer for approval. These approvals shall then be submitted to the University. The Contractor’s final shop drawings and specifications shall be submitted to United States Fidelity and Guaranty Company (USF&G) for approval prior to submittal to the University Architect for approval. All projects involving street-pressure sprinkler systems, street-pressure fire standpipe systems, or fire pumps require hydrant tests on the mains in all streets that can be used to feed the building. The University will provide flow test data on request. All sprinkler lines shall be equipped with an inspector’s test connection piped directly into a drain capable of handling discharge from a fully-opened test valve. Materials All control valves shall be of butterfly indicator type or outside stem and yoke (OS&Y) type. P. 15-16 December 1998 DESIGN AND CONSTRUCTION STANDARDS FACILITIES MANAGEMENT SERVICES DIVISION 15 MECHANICAL SYSTEMS 15410 PLUMBING PIPING Piping shall be pitched and valves installed to facilitate complete drainage of the system. All piping run within the building shall be concealed in the finished portions of the building in pipe spaces, ceilings, or furred chases and exposed only in mechanical rooms and where shown on the drawings. No pipe shall pass in front of or interfere with any openings, doors, or windows. Headroom in front of openings and doors shall in no case be less than the top of the opening. No pipe shall pass in front of or interfere with clearances around mechanical equipment. Piping shall not pass exposed through electrical rooms or be erected over any switchboard or other electrical gear (except as may be required by local code for fire suppression). Pipe sizes shall be indicated on the plans at each change in direction and at all branch take-off locations. Two-in. clearance shall be provided between insulated piping and other obstructions. No union shall be placed in a location that will be inaccessible. Unions shall be installed adjacent to all equipment for repair and replacement. Flexible piping connections shall be provided at piping connections to all rotating mechanical equipment, and at piping connections to all equipment mounted on vibration isolators. Connectors shall have a pressure rating suitable for the piping systems in which they are installed. Dielectric unions shall be provided between dissimilar materials for electrolysis control. Bypasses Bypasses shall be installed around water meters, control valves, and pressure-reducing stations serving critical areas (to be reviewed with the University Project Manager). Ball or butterfly valves shall be used. No other equipment is to be provided with a bypass unless approved by the University Project Manager. Sleeves All pipes passing through masonry construction shall be fitted with sleeves. Each sleeve shall extend through its respective floor, wall, or partition and shall be cut flush with each wall surface unless otherwise specified. Sleeves shall be two pipe sizes larger than the pipe when un-insulated and of sufficient size to allow for the insulation without binding. Floor sleeves in mechanical rooms shall extend 4 in. above the finished floor; for all other spaces, the floor sleeves shall be a minimum 1 in. above the finished floor. Sleeves in load-bearing and masonry walls, floors, and partitions shall be standard weight steel pipe finished with smooth edges. For other than masonry partitions, through suspended ceilings, and for concealed vertical piping, sleeves shall be No. 22 USG December 1998 P. 15-17 DIVISION 15 DESIGN AND CONSTRUCTION STANDARDS MECHANICAL SYSTEMS FACILITIES MANAGEMENT SERVICES galvanized steel. No sleeve is required where an opening is core-drilled through concrete floors or ceilings. Space between sleeves and pipes shall be filled with fireproofing material and caulked. Where pipes pass through waterproofed floors or walls, the design of the sleeves shall be such that waterproofing can be flashed into and around the sleeves. Sleeves through exterior walls below grade shall have the space between pipes and sleeves caulked watertight or fitted with a “link-seal.” One-piece chrome-plated escutcheon plates shall be installed with setscrews at sleeves for all pipes exposed in finished areas. Where pipes pass through fire-rated partitions, the annular space around the pipes shall be sealed and/or filled with fireproofing sealers. System and Equipment Drains All piping shall be arranged to completely drain the system. Drain locations shall be indicated on the drawings. Where sectionalizing valves are installed, a drain shall be installed on the downstream side of the valve to drain that section of the system. All cooling tower drains and overflow shall be piped to a sanitary system (not onto the roof). All system and equipment drains and air vents shall be piped to a floor drain. Welding All welding shall be done in accordance with the American Welding Society (AWS). All boiler, pressure vessel, and gas piping welding must be done by certified welders. Pressure Tests All piping must be tested prior to receiving insulation. Prior to filling the systems, all joints and potential leak sources shall be painted with a water-power blue line caulk mixture and allowed to dry. During the test, each joint shall be inspected visually. Test pressures shall be a minimum 1.5 times system operating pressure or as specified by the Design Consultant. Pressure tests shall be witnessed by a University representative. P. 15-18 December 1998 DESIGN AND CONSTRUCTION STANDARDS DIVISION 15 FACILITIES MANAGEMENT SERVICES MECHANICAL SYSTEMS Identification Three-fourth in. wide, adhesive-backed vinyl cloth labels shall be used on all piping 2 in. and smaller. Label lettering shall identify both the medium being conveyed and the direction of the flow. Labels shall be spaced on maximum 15-ft centers, as well as at branch take-offs, and on either side of wall penetrations. Labels shall be positioned for easy viewing. Identification Symbols and Colors for Plumbing Piping Service Symbol Field Color Service Symbol Field Color Fire line Fire Red Domestic hot water return SCWS Green Sprinkler line Spr. Red Deionized water supply DI Green Sanitary waste SW Blue Drinking water supply DWS Green Sanitary vent SV Blue Drinking water return DWR Green Soil stack San. S. Blue Gas Gas Yellow Soil vent San V. Blue Vacuum Vac. Gray Down spout Rain Blue Compressed air (laboratory) Air Brown Domestic cold water supply CWS Light brown Compressed air Air Dark blue Domestic hot water supply HWS Dark brown Soil, Waste, and Vent Piping Cast Iron Cast iron soil pipe and fittings shall be service weight with hub and spigot conforming to ASTM A-74 and ANSI A112.5.1. Having no hub is also acceptable. Cast iron soil pipe shall be supported every 5 ft and at every joint. Hangers shall also be installed at branch locations and where lines change directions. Stacks and risers shall be supported at the base by concrete piers and by riser clamps at floor level. Joints shall be made with neoprene, compression-type gaskets conforming to ASTM C564. The University prefers neoprene vent roof flashing with stainless steel damps. PVC or CPVC piping shall be used for fused joints and drainage water vent (DWV) fittings. Galvanized Steel Waste lines from kitchens, laundries, and other areas where very hot water is used shall be Schedule 40, galvanized ASTM A 53 piping with cast iron drainage fittings. December 1998 P. 15-19 DIVISION 15 MECHANICAL SYSTEMS DESIGN AND CONSTRUCTION STANDARDS FACILITIES MANAGEMENT SERVICES Acid Waste Lines (Under Floor/Under Ground to First Manhole) Acid-resistant underground waste and vent lines shall be cast iron hub and spigot alloyed with approximately 14% silicon and shall conform to ASTM D651-48. Piping shall be Durion or equal. Joints in acid-resisting pipe shall be made with caulking lead conforming to ASTM B 29. The need for acid-neutralizing sumps will be determined by the pH of the discharge. Measurements below the acceptable range set by the local sewage authority shall dictate the need for acid neutralization. Acid waste lines within the building shall be glass or mechanical “end-filled” laboratory line at the discretion of the University Project Manager. Water Piping Copper tubing shall be used for all water piping and shall be type L hard drawn. Joints shall be made with no-lead solder. Before being placed into service, all new water lines, except those used exclusively as fire lines, shall be disinfected in accordance with American Water Works Association (AWWA) standards. Final connections to existing water lines shall not be made until this procedure is completed satisfactorily. Water Hammer Arrestors Water hammer arrestors shall be installed on cold water piping to toilet rooms where flush valves are used. The arrestors shall be the hydropneumatic type and shall be sized properly to control water hammer. These should be Absorbtion or equal. Any quick-acting automatic valves supplying equipment shall also have water hammer arrestors installed. Cold Water Make-Up Piping All cold water piping shall be type L hard drawn seamless copper tubing. All cold water piping joints shall be soldered, using no lead. Parallel filters shall be provided on all incoming make-up water lines. 15430 PLUMBING SPECIALTIES Electric Drinking Water Cooling Systems Electric water coolers shall be wall mounted, semi-recessed and shall be supported by carriers similar to Josam No. C-352. The coolers shall be equipped with a basin of 18-8 stainless steel, bubbler, water valve, pressure regulator, and a sealed refrigeration system with air-cooled condenser. P. 15-20 December 1998 DESIGN AND CONSTRUCTION STANDARDS FACILITIES MANAGEMENT SERVICES DIVISION 15 MECHANICAL SYSTEMS The front panel of a unit shall be removable and units shall be so constructed that the refrigeration unit can be removed without moving the cooler from the wall. No “hot water for coffee” type dispensers shall be permitted. In public areas the water cooler shall be accessible to the handicapped. Deionized Water Current piping is stainless steel. Polypropylene is adequate for new extensions. If users need higher quality water than what is available (1 meg-ohm/0.997 micro-moh at the fixture), polishers shall be added in the laboratory. Eyewash An eyewash shall be installed in labs that have at least one fume hood. Where corrosive materials are used in a laboratory, the eyewash shall be installed within 10 feet of the corrosive process. The eyewash instrument shall be dual-port eyewash, which can be operated hands-free, such as Kewaunee model No. W0934-00, or an approved equal. The installation shall allow flow regulation on the eyewash and provide drainage for any spillage. Tempered water at the eyewash is also recommended. Safety Showers Safety showers shall be installed within laboratories where space allows. As a minimum, there should be a safety shower 10 feet from the laboratory (in the hallway). The shower shall be equipped with a continuous flow valve. Tempered water is recommended. Drainage shall be provided for the safety shower. 15440 PLUMBING FIXTURES Water Closets Water closets shall be wall hung where walls are masonry backed up with adequate wall hanger (a Zurn 300-lb support device has feet bolted to the floor and wall support). Floormounted water closets shall be used with non-masonry walls, or in replacement work. Water closets shall be vitreous china with water-saver fixtures. Wall-hung water closets shall be American Standard Afwall EL 1.6 #2257.103 with Olsonite seat. Floor-mounted water closets shall be American Standard Madera EL 1.6 10-in. #2234.015 with Olsonite seat. Cadet #3043.1.2 shall be used at accessible locations. December 1998 R P. 15-21 DIVISION 15 DESIGN AND CONSTRUCTION STANDARDS MECHANICAL SYSTEMS FACILITIES MANAGEMENT SERVICES Flush valves shall be Sloan Royal flushometer valves. Urinals Urinals shall be wall hung, vitreous china with Zurn 300 support device. Urinals shall be similar to American Standard Washbrook 1.0 #6501.1.1 with stainless steel strainer. Allbrook 1.0 #6541.132 shall be used at accessible locations. Flush valves shall be Sloan Royal flushometer. Lavatories Lavatories shall be wall hung, vitreous china, American Standard Lucern #0355.012, or drop-in china sink bowl (American Standard Aqualyn #0476.028) for use with corian countertops. Mildew-resistant caulking shall be used around the bowl. Lavatory carriers shall be of the institutional type with support plate, bearing plate steel uprights, and block bases for supporting lavatory fixtures with concealed hangers. Carriers shall be similar to Josam C-356. Lavatory supply and waste lines shall enter the wall to allow for easier cleaning and better sanitation. At least one hose bib shall be provided on the hot and cold water supply under one lavatory in each restroom. Faucets shall be Chicago faucets: 4-in. center #802A faucet, #317 4-in. blade handles, E12VP aerator, #245 Control-A-Flo cartridge, polished chrome plate finish (CP); #327A non-removable grid drain or #337 offset at an accessible sink; #1005 or #1006 keyed stop, chrome finish. Single Showers Shower heads shall be self-cleaning, water-saver, and vandal-proof type solidly attached to the shower stall. Shower controls shall be Powers Series 420, thermostatically controlled, with chromeplated metal levers. Showers shall have Dole flow controls, limiting water flow to 2 gpm, installed between the mixing valve and the showerhead. Gang Showers Showerheads and controls shall be the same as for single showers. Piping supplies shall be from below the floor. Units shall be manufactured by Bradley or equal. P. 15-22 December 1998 DESIGN AND CONSTRUCTION STANDARDS FACILITIES MANAGEMENT SERVICES DIVISION 15 MECHANICAL SYSTEMS Antifreeze Hose Bibs Antifreeze hose bibs are needed adjacent to all building entrances for the purpose of washing down walks and entrances. Key type shall be used. Service Sinks Service sinks shall be similar to Stonite Precast Terrazzo Mop Service Basins as manufactured by Stonite Products Company. Service basins shall be 24 in. square with 3in. wide and 12-in. high shoulders and shall be cast as a single unit of terrazzo. The sides of the service basins installed against any wall shall be provided with stainless steel tiling flanges cast integral with the basin and extending 2-in. above the shoulders. The exposed side of the service basin shall be provided with integral cast stainless steel caps extending over the top of the shoulder and extending at least 1.5 in. down the sides. A 3-in. drain connection with stainless steel strainer plates and traps shall be provided. Counter flashing shall be installed as required. Service sink fittings shall be equal to Chicago faucet No. 897 with bucket hook, wall brace, 0.75-in. threaded hose connection, vacuum breaker, and integral stops. Roof Drains Roof drains shall be Zurn or equal. The drain body, horizontal rain leaders, and the first vertical 18 in. of roof penetrations shall be insulated. Laboratory Equipment Where laboratory equipment is shown on the general construction drawings, this equipment shall also be shown on the mechanical and electrical drawings. The equipment shall bear the same identification numbers on all sets of drawings. 15453 PUMPS General Standby pumps shall be provided for all hot water heating and chilled water circulating systems. All pumps shall have bronze impellers. Pump schedules shall indicate system served, operation (primary or backup), gpm, pump head, rpm, motor horsepower, location, make and model number, and electrical characteristics. A single gage shall be connected to the discharge and suction side of each pump and across the strainer so that the differential pressure can be observed. No trumpet valve is allowed. December 1998 P. 15-23 DIVISION 15 DESIGN AND CONSTRUCTION STANDARDS MECHANICAL SYSTEMS FACILITIES MANAGEMENT SERVICES Section 15985 provides temperature control requirements. Pumps – Closed Coupled Closed-coupled pumps are not permitted over 0.5 hp. Pumps – Base Mounted, End Suction Pumps shall be electric-motor-driven, centrifugal, single-suction, single-stage pumps. Pumps shall be bronze fitted, with bronze impeller, with close-grained semisteel vertically split casing (125 psi), provided with mechanical seals designed for the operating conditions shown on the plans. Pumps shall be provided with sleeve bearings and an oil reservoir. A drop-out coupling shall be provided. Pumps shall have a sleeve bearing, specially selected for quiet operation at 1750 rpm. The motor size shown on the drawing shall be the minimum acceptable. A pump motor should operate within the service factor of the motor, providing that the service factor is acceptable to the pump manufacturer. The motor shall not exceed the nominal hp at the specified delivery and head. Discharge increasers shall be concentric and located at the pump discharge nozzle. Suction pipe reducers shall be eccentric, located at the pump suction nozzle and at least five diameters of straight pipe shall be installed before the inlet or along the sweep elbow. (Suction diffusers in lieu of straight pipe section may be used.) A 0.75-in. drain shall be provided from each base plate to the nearest floor drain. Pumps shall be selected so that the ratio of impeller diameter to the maximum diameter possible in the casing shall not exceed 0.85. A purge cock shall be provided in the casing and gage tappings shall be provided in pump suction and discharge. All piping connections to pumps shall be supported independently so that no strain is imposed on the pump casing. Pumps installed on “slab-on grade” shall be mounted on a 6-in. high concrete pad with anchor bolts. The space between pad and base shall be grouted to eliminate all voids. Pumps shall have rear pull-out design for removal of the impeller without disturbing the motor alignment or piping. Pumps installed on supported slabs shall be provided with concrete inertia subbases with spring isolators. Pumps shall be B&G, Taco, Armstrong, or equal, as approved by the Design Consultant. In-Line Pumps Pumps shall be centrifugal and single-stage, complete with motor, mechanical seals, bronze fittings, bronze impellers, and a flexible coupler with safety guard. The pumps shall also be dynamically and hydraulically balanced. The pump motor shall be supported independently. P. 15-24 December 1998 DESIGN AND CONSTRUCTION STANDARDS FACILITIES MANAGEMENT SERVICES DIVISION 15 MECHANICAL SYSTEMS Constant Pressure Pumps Where constant pressure pumps are required on the potable water system, they shall be installed in duplicate and be similar to Peerless Pumps’ Variable Frequency Drive pumping system. 15460 WATER HEATERS The design shall include steam-fed capability for winter use, and gas-fired capability for summer use. Electric water heaters shall be storage type, to be used only in building locations that are remote to steam/gas utilities. Instantaneous hot water generators shall contain a cupronickel coil (10% nickel) and all the auxiliaries required for the above type generator with the exception of the circulating pump. The steam control valve on instantaneous hot water generators shall be air-loaded (if air is available) or steam-actuated. Self-contained valves are not acceptable. Instantaneous hot water generators shall be similar to those of Leslie, Constantemp, Armstrong, or Graham companies. 15481 COMPRESSED AIR SYSTEMS Air Compressors Existing compressor capacity shall be verified before tying in new devices. When after coolers are specified on air compressors, they shall be air-cooled or shall be cooled with recirculating process water. Water cooling through equipment to a drain is not permitted. Compressed Air Piping Compressed air piping above grade shall be Schedule 40, black steel conforming to ASTM A 53. Fittings shall be malleable screwed end. 15488 NATURAL GAS SYSTEMS Natural gas piping is available to some, but not all, campus buildings. The University Project Manager shall review whether new service is required. 15510 HYDRONIC PIPING Manual vents are standard but automatic vents can be considered in special situations. Where vent location is high or otherwise inaccessible, the following procedure can be followed: Install valve at vent chamber, then extend 0.375-in. tubing to the nearest janitor sink or mechanical room floor drain and terminate with a ball valve. Use automatic water December 1998 P. 15-25 DIVISION 15 MECHANICAL SYSTEMS DESIGN AND CONSTRUCTION STANDARDS FACILITIES MANAGEMENT SERVICES feed set to maintain proper system pressure. Add cold water makeup at the air vent line above an air-eliminating device. Glycol systems shall be equipped with a mix-and-fill tank with manual fill capabilities, hose bib from domestic water for tank filling, and tank level alarm. Direct-connect city makeup lines to glycol systems are NOT permitted. Provisions shall be made for draining and air venting of all water coils. All new hot water and chilled water systems that are independent of the central systems shall be arranged for shot feed chemical treatment. In each such system, the equivalent of one Calgon 100L Mircomet pot feeder shall be provided, including pressure gage and flow indicator. The pot feeder to the system shall be hard-piped; using a hose is NOT acceptable. The University will provide all treatment chemicals except for chemicals for the flushing system. A University representative will supervise chemical treatment. After all items of equipment have been connected to the system (but prior to connecting to existing systems and prior to acceptance by the University), the hot and chilled water system shall be chemically cleaned as follows: 1. Drain and refill the system using trisodium phosphate, 1 lb for every 50 gal in the system. 2. Fill, vent, and circulate the system with this solution, allowing it to reach design or operating temperatures. 3. After circulating a few hours, the system should be drained completely, strainers removed and cleaned, dirt legs and pockets opened and cleaned, and then refilled with fresh water. Immediately notify the University Project Manager. Reduced pressure principal backflow preventers shall be installed on all make-up water lines. Drains shall be piped to the nearest floor drain. Hot Water, Chilled Water, Vent Piping All supply water piping shall be graded up and return graded down in the direction of the flow. At all high points in the piping system, manual air vents shall be installed to eliminate air pockets at initial fill. All water piping 2.5 in. and larger shall be black steel pipe, ASTM A 53, Grade B. Pressure requirements shall be met. Piping 2 in. and smaller shall be copper, type L, hard drawn. All water piping that is 2 in. and smaller shall be screwed or soldered as applicable; water piping that is 2.5 in. and larger shall be welded, flanged, or Victaulic (with rolled, not grooved, fittings). P. 15-26 December 1998 DESIGN AND CONSTRUCTION STANDARDS DIVISION 15 FACILITIES MANAGEMENT SERVICES MECHANICAL SYSTEMS Identification Symbols and Colors for Water Piping Service Symbol Field Color Hot water heating supply HWS (Zone No.) Burnt orange Hot water heating return HWR (Zone No.) Burnt orange Hot water heating expansion line HW Exp. Burnt orange Hot water heating drain HW Drain Burnt orange Chilled water supply CHWS (System No.) Dark green Chilled water return CHWR (System No.) Dark green Condenser water supply Cond. Sup. Light green Condenser water return Cond. Ret. Light green Flow arrows shall be provided every 10 feet and at each change in the direction of the pipe and at take-offs. Refer to ANSI A13-1, latest version, for size of lettering. Hydronic Specialties Strainers Construction startup strainers shall be fine mesh. After one month of operation, the strainer shall be changed to a larger mesh specified for normal use. Strainers ahead of circulating pumps shall be large mesh (at least 0.1875 in.) and stainless steel construction. All strainers shall be valved and capped for blowdown. Air Separators Air separators shall be installed in each hydronic system. They shall be full line size. Air separators 2 in. and larger shall have tangential inlets and outlets and be ASME rated. These separators shall be similar to those of Bell & Gossett Rolairtrol. Expansion Tanks Tanks shall be steel, ASME constructed, complete with inlet, drain, overflow, aircharging valve, airtrol fitting, and make-up connections. Expansion tanks shall be diaphragm type. Expansion tanks shall have no direct connection to the air system. A Chicago quick-disconnect fitting shall be provided. It should have a shut-off valve for compressed air, which is necessary for manual charging of the system. December 1998 P. 15-27 DIVISION 15 DESIGN AND CONSTRUCTION STANDARDS MECHANICAL SYSTEMS FACILITIES MANAGEMENT SERVICES Flow Meters Flow meters shall be installed at all terminal equipment and air handling units, as well as any horizontal branches from the building risers (to balance at each floor level). For lines 2 in. and under, meters shall be similar to Armstrong circuit balancing valve with vernier controls. For lines 2.5 in. and larger, a venturi-type measuring device shall be used. Gage Piping All gage piping on steam systems shall be steel (Schedule 40 on low pressure and Schedule 80 on high pressure). Gage cocks (low pressure) or ball valves (high pressure) shall be provided for isolation. Cooling Coil Condensate Drain Piping All cooling coil condensate drain piping shall be Schedule 40 PVC with solvent weld joints. Section 15790 describes appropriate trap sizing. No piping shall be less than 1-in. in diameter. Cleanouts shall be provided as required. 15520 STEAM AND STEAM CONDENSATE PIPING Steam Piping All steam piping shall be graded down in the direction of flow 1 in. in 40 ft. At all low points in the steam piping system, a drip station shall be installed. Offsets and bends shall be provided wherever possible to allow for expansion and to control pipe movement. Anchors and expansion joints shall be provided as required and detailed on the drawings. Steam piping shall be Schedule 40 black steel, ASTM A 53, Grade B. Joints 2 in. and smaller shall be screwed; joints 2.5 in. and larger shall be welded or flanged. All high-pressure piping shall be welded. All steam pipe strainers and traps shall be removed and cleaned prior to acceptance by the University. TO BE ACCEPTABLE, ALL CLEANING WORK IN THIS SECTION MUST BE WITNESSED BY THE UNIVERSITY PROJECT MANAGER. Drip legs shall be, at a minimum, half the size of the steam main, 18 in. in length with a blowdown valve at the bottom. The trap line connection shall be located in the center of the drip leg. Calculations for expansion joints shall be documented, as described in Section 15010. P. 15-28 December 1998 DESIGN AND CONSTRUCTION STANDARDS DIVISION 15 FACILITIES MANAGEMENT SERVICES MECHANICAL SYSTEMS Gasket material shall be included in the specifications for each class of pipe. Submittals are required for high-pressure steam applications. Section 15250 of this document provides the requirements for insulation. Identification Symbols and Colors for Steam Piping Service Symbol Field Color Service Symbol Field Color Steam, high pressure Steam – 175 Green Condensate return from: Steam, high pressure Steam – 125 Yellow High pressure steam Cond. – 175 Yellow Steam, high pressure Steam – 100 Yellow High pressure steam Cond. – 125 Yellow Steam, intermediate pressure Steam – 65 Yellow High pressure steam Cond. – 100 Yellow Steam, intermediate pressure Steam – 25 Yellow Intermediate steam pressure Cond. – 65 Yellow Steam, intermediate pressure Steam – 15 Yellow Intermediate steam pressure Cond. – 25 Yellow Steam, low pressure Steam – 5 Yellow Intermediate steam pressure Cond. – 15 Yellow Condensation Pump Discharge Cond. – PD Yellow Low steam pressure Cond. – 5 Yellow Steam Condensate Return Piping All gravity return condensate lines shall be pitched down toward the direction of flow, in. in 30 ft. 1 All condensate return lines in buildings shall be Schedule 80 black steel, ASTM A 53, Grade B. Joints 2 in. and smaller shall be screwed; joints 2.5 in. and larger shall be welded or flanged. Steam and Condensate Specialties Traps and strainers shall be installed with isolation valves and telltale drains to facilitate cleaning and maintenance and to check proper operation of the trap. For low-pressure drips, float and thermostatic traps shall be used. For high-pressure drips, thermodynamic, or float and thermostatic traps shall be used. For modulating service, float and thermostatic traps with vacuum breakers shall be used. Pressure-Reducing Valves The Main Steam Pressure Control Stations shall consist of an air-operated diaphragm control valve and a remotely-adjustable external air-operated pressure control pilot. Air lines shall be provided under ATC. December 1998 P. 15-29 DIVISION 15 DESIGN AND CONSTRUCTION STANDARDS MECHANICAL SYSTEMS FACILITIES MANAGEMENT SERVICES The diaphragm control valve shall have a flanged cast bronze body with a 250 psi pressure rating. It shall have hardened stainless steel trim with a stellited seat ring. The valve shall be single seated and suitable for dead-end service with a 250 psi pressure drip. It shall operate on a 0 to 22 psi air signal from the control pilot and be normally closed (air to open). The air-operated pressure control pilot shall be of the differential type suitable for readjustment from a remotely-located air loading panel. The pressure controller shall be capable of maintaining an outlet pressure within plus or minus 0.5 psi when passing flow from zero to the maximum specified, regardless of gradual inlet pressure variations. The Steam Pressure Controller shall consist of a diaphragm control valve, type DDL or GPK, and a control pilot, type UDDV, and a remote panel loader, type PPF, all as manufactured by the Leslie Company. The remote panel loader shall have integral filters or be preceded by strainers. Valves shall be as manufactured by the Leslie Company, or an approved equal. Consideration shall be given to two-stage reduction when required by pressure and twostage parallel reduction when required by varying load conditions. 15530 REFRIGERANT PIPING Refrigerant liquid and suction piping shall be type L, hard drawn ACRS tubing. A nitrogen purge shall be maintained when soldering all joints. Copper-to-copper joints shall be made with a brazing alloy similar to Sil-Fos. Copper-to-brass joints shall be made with silver solder. Main piping fittings for dryers, sight glasses, expansion valves, and controls shall be flare or compression-type fittings. Prior to being charged with refrigerant, the system shall be evacuated to 500 microns and held for at least 24 hours under this vacuum. Double-suction risers shall be employed on systems with capacity reduction and where required by lift. Precharged lines are not acceptable. Identification Symbols and Colors for Refrigerants P. 15-30 Service Symbol Field Color Freon 11 Freon 11 Purple Freon 12 Freon 12 Purple December 1998 DESIGN AND CONSTRUCTION STANDARDS FACILITIES MANAGEMENT SERVICES DIVISION 15 MECHANICAL SYSTEMS Refrigerant Specialties Isolation valves shall be provided at all specialties. Refrigeration Installations shall be complete with dryers, sight glass, and thermostatically-controlled solenoid valves for pump down operations. Where defrost units are required, they shall be operated electrically with adequate space provided to replace defrost elements. Defrost shall not be limited to electrical units. In larger installations, hot gas defrost is preferred. Installations shall be provided with necessary protective devices including, but not limited to, electric overload devices, low-suction pressure cutouts (manual reset), high head pressure cutouts (manual reset), low-lube oil pressure cutouts (manual reset), oil traps, crankcase heaters, and antirecycling. Condensing systems shall be designed for 0 °F ambient conditions, using variablefrequency fans. 15540 HVAC PUMPS Chiller run-around pumps shall be constant-volume. They shall be decoupled from the distribution loop, and as load is added to the system, decoupled from the distribution loop via a primary/secondary piping bridge. The distribution loop shall be sized for a 15 °F water temperature drop and served by variable-speed pumps. Load-side pumps shall be typically constant-volume, but variable-speed pumps may be warranted in some cases. 15545 CHEMICAL WATER TREATMENT The Design Consultant shall contact the University HVAC foreman for current requirements. 15582 STEAM CONDENSATE RETURN UNITS Steam condensate pumps shall be duplex type with cast iron receivers (not steel). Steam-powered pumps can be considered, and shall be reviewed with the University Project Manager on a project basis. 15680 WATER CHILLERS When tie-in to existing central chilled water has been determined to be not feasible (by consensus between the Design Consultant and the University), selection of a new chiller shall be reviewed with the University Project Manager at the conceptual design stage. December 1998 P. 15-31 DIVISION 15 DESIGN AND CONSTRUCTION STANDARDS MECHANICAL SYSTEMS FACILITIES MANAGEMENT SERVICES The Life Cycle Cost Analysis model provided by the University shall be used as the basis of the selection. Sufficient clear space shall be allowed, equal to the length and width of the machine for tube pull clearance. Refrigerant selection shall be discussed with the University Project Manager prior to equipment selection. A beam with a minimum 4-ft clearance shall be provided above the chiller or sufficient clear space shall be allowed above and around the machine for using a gantry for compressor replacement. Section 15170 describes motor inrush current and voltage drop requirements for starting. The acceptability of across-the-line starters shall be reviewed case by case. The chiller control package shall control run-around and injection pumps, and shall be interfaced with the University DDC system for remote start/stop and chilled water setpoints. 15711 FACTORY-FABRICATED COOLING TOWERS An induced-draft cooling tower is preferred; a forced-draft cooling tower can be considered where space is an issue. Forced-draft units shall be similar and equal to Baltimore Air Coil “V” line with PVC fill. The units shall have complete winterization capability, including heat tracing of piping. Cooling tower location must be approved by the University. Indoor sumps are required where year-round cooling is necessary. Water conditioning equipment for the cooling tower shall be compatible with the University’s current water treatment program (molybdate-based). The University Operations Department will provide specifications. Chemicals shall be provided by the University. Cooling towers shall be selected at 95 °F DB, 78 °F WB Lakos-type particulate separators shall be provided on condenser water systems. 15755 HEAT EXCHANGERS Steam-to-water converters shall have steam in the shell and water in the tubes. ASME rating is required. Tubes shall be 90-10 cupronickel, ASTM B 111, and velocity shall be less than 5 ft/sec. Sufficient clear space (no less than the entire length of the converter) shall be provided to allow for tube bundle removal. Tube bundles shall be straight or “U” tube design. P. 15-32 December 1998 DESIGN AND CONSTRUCTION STANDARDS FACILITIES MANAGEMENT SERVICES DIVISION 15 MECHANICAL SYSTEMS Vacuum breakers shall be installed in the piping for modulating steam supply. There shall be a minimum 12-in. drip leg to trap inlet. Vacuum breakers shall be provided on the shell. Converters shall be selected at 2 psig steam supply and 0.0005 fouling factor. Using a simple check valve for a vacuum breaker is not acceptable. Hoffman Model No. 69 shall be used. “Once-through” air systems shall be considered for heat recovery applications. 15781 PACKAGED HEATING AND COOLING AIR HANDLING UNITS Fans and motors of 5 ton and larger shall be on a common spring isolation base or rail. All fans 0.75 hp and above shall be Class II fans. Casing shall be double-walled, with hinged access doors. Mixed air chambers shall have motor-operated dampers. A full access section width casing with access door shall be used to separate the chilled and preheat coils. Compressor staging shall be a function of unit size, with off-loading capability considered. Dampers shall have edge seals and be low-leakage (2%) type. There shall be access doors to all components. There shall be interface with the University DDC system for remote start/stop and an alarm for compressor failure. All units shall have a dedicated set of minimum outside air dampers for ventilation requirements. The dampers shall be two-position, and a second set of modulating outside air dampers shall be provided, as required, for economizer operation or tracking with exhaust air. Use of “air blenders,” which provide good outside return air mixing, should be considered. 15782 ROOFTOP HEATING AND COOLING UNITS The Design Consultant shall obtain permission from the University Project Manager before designing packaged rooftop units for University projects. Air-cooled packaged air conditioning equipment shall be equipped with low ambient cooling to permit operation to 0 °F ambient temperature. All units shall have a dedicated set of minimum outside air dampers for ventilation requirements. The dampers shall be two-position, and a second set of modulating outside December 1998 P. 15-33 DIVISION 15 DESIGN AND CONSTRUCTION STANDARDS MECHANICAL SYSTEMS FACILITIES MANAGEMENT SERVICES air dampers shall be provided, as required, for economizer operation or tracking with exhaust air. Rooftop package air conditioners 5 ton and larger shall be mounted on structural steel channel curbs with curb vibration isolation rails. Smaller units may be mounted on the manufacturer’s prefabricated curbs. Details and catalog cuts of the unit shall be submitted prior to design. Units must be manufactured for that application. Where steam or hot water is not available, a gas-fired heat exchanger shall be used. (An electric heating coil is NOT acceptable.) A full access section width casing with door shall be used to separate the chilled and preheat coils. Casings shall be double-walled, with hinged access doors where available as an option. 15790 AIR COILS Separate drain pans for each stacked cooling coil shall be provided. A schedule shall be shown on the construction documents with the trap detail, indicating the trap depth dimensions for each coil location (this shall not be left for the Contractor to calculate). The formula used as the basis for these dimensions shall be shown on the schedule as well. Access doors shall be provided on the upstream side of all coils. Clearance shall be provided for the full-finned width of the coil for removal. Cooling coil face velocities shall be designed for 425 fpm and shall not exceed 500 fpm. Water coils shall be fully drainable. Air vents shall be provided at the highest point. Hose and drain valves shall be provided with isolation valves. Steam coils shall be piped to prevent freeze-ups. This shall include vacuum breakers and adequate drip leg-to-trap inlet, which may dictate that units be mounted on an angle iron frame above the housekeeping pad. 100% outdoor air preheat coils shall be of the steam distributing type with external face and bypass control, as manufactured by Wing Coils, or an approved equal. Coils shall be double trapped. Control valves shall not be the modulating type for preheat application. If reheat is required for dehumidification, a dual hot water coil arrangement can be used, splitting the temperature rise between the two coils. Hot water shall be used for all reheat coils and all preheat coils with less than 75% outside air requirement. Water coils shall be piped in counterflow configuration. P. 15-34 December 1998 DESIGN AND CONSTRUCTION STANDARDS FACILITIES MANAGEMENT SERVICES DIVISION 15 MECHANICAL SYSTEMS On runaround loop applications, appropriate corrosion-resistant coating shall be provided for any corrosive atmosphere. Chilled water coils shall be designed for a 15 °F water temperature drop. Tube-wall thickness, fin material, fin spacing (with a maximum of 10 fpi), shall be reviewed based on application with the University. All cooling coil casings and condensate drain pans shall be stainless steel. 15831 FAN COIL UNITS Ceiling-hung fan coil units shall be avoided wherever possible. However, if the use of ceiling-hung units is deemed necessary, then such units shall be made as accessible as possible, preferably installed in corridor ceilings and ducted to the rooms they serve. Vertical floor-mounted units are acceptable alternatives where necessary because of ceiling height limitations for concealing ductwork, and so forth. Specified control valves may be sent to the fan coil manufacturer to be factory-mounted. Fan coils shall be sized so that the NC level does not exceed the recommended levels given in Table 2, Chapter 43 of the ASHRAE Systems and Applications Handbook, latest edition. When fan speed control is not specified, fan speed switches (low-medium-high) are required. Four-pipe fan coil systems are preferred to two-pipe. Finish shall be submitted to the University representative with a color chip for approval. 15832 FINNED-TUBE RADIATION A commercial-grade 16-gage face enclosure shall be used. A residential-grade enclosure is not permitted. The finish shall be submitted to the University Project Manager with a color chip for approval. Finned-tube radiation shall be designed for an average hot water temperature of 180 °F or 1 psig steam supply, to be reset with the outside air temperature. Finned-tube radiation shall be selected to be consistent with the existing perimeter radiation type. December 1998 P. 15-35 DIVISION 15 DESIGN AND CONSTRUCTION STANDARDS MECHANICAL SYSTEMS FACILITIES MANAGEMENT SERVICES 15835 UNIT HEATERS Isolation valves shall be provided on each item. Unit heaters shall be designed for an average hot water temperature of 180 °F or 1 psig steam supply, to be reset with the outside air temperature. Design drawings shall indicate all selection criteria. The heater finish, with a color chip, shall be submitted to the University Project Manager for approval. Inverted flow units shall be used for all floor-mounted units. 15840 UNIT VENTILATORS Unit ventilators shall not be used. 15850 FANS AND EXHAUST SYSTEMS When return air fans are required in variable-volume systems, flow measuring stations shall be provided in the supply and return ducts to ensure proper tracking of the supply and return fans. All fans, including power ventilators over 20 in. in diameter, shall be belt-driven with solid sheaves, as described in Section 15170. When available, permanently-lubricated bearings shall be used, with a minimum 200,000hr life. On others, extended lube shafts, 0.126-in. steel tubing and flush plugs with relief set at 5 psig shall be specified. The fan schedule on the drawing shall be complete, giving area served, fan location, method of control, and performance characteristics. Controls must not be placed in public areas. If fans are interlocked, the schedule shall indicate the unit with which the fan is interlocked. Fans shall be AMCA rated for sound and air performance. All fans shall be statically and dynamically balanced and test run at the factory. The motor horsepower shall not be less than 120% of fan bhp, non-overloading. Fume Hood Exhaust Systems Specific requirements for laboratory and industrial exhaust systems shall be reviewed with the University Project Manager and the University EH&S Office. Fume hood exhaust systems shall be designed in accordance with the American Conference of Governmental Industrial Hygienists (ACGIH) and ANSI Laboratory Exhaust Standards Z 9.5, latest edition. P. 15-36 December 1998 DESIGN AND CONSTRUCTION STANDARDS FACILITIES MANAGEMENT SERVICES DIVISION 15 MECHANICAL SYSTEMS All systems shall have an adequate supply of make-up air tempered to room temperature. Total make-up air quantity shall not exceed that required to maintain the specified pressure relationship for the space (0.05 in. wc, negative static pressure relative to the corridor or adjacent non-laboratory spaces). Temperature control of the space shall not depend on exhaust air bypass through the hood. A specialized hood/exhaust washdown and duct system shall be provided where perchloric acid is used. Fume hood exhaust fans shall have acid-resistant coating, two coats air-dried “Heresite” or equal. Design static shall not be less than 1-in. static pressure. Spark resistance is required for explosive atmospheres. Where design conditions do not permit the use of coatings, requirements shall be discussed with the University Project Manager. Exhaust fans serving fume hoods shall be located at the discharge end of the system to minimize the amount of positively-pressurized ductwork Exhaust fans shall discharge at a sufficient height above the roof level to provide safe discharge and dilution of hazardous chemicals, as outlined in Chapter 15, “Airflow Around Buildings,” in the latest edition of the ASHRAE Fundamentals Handbook. Exit velocity shall be 3,000 fpm (minimum). Duct systems and fans serving hoods used with combustible materials shall be of sparkproof construction and shall not be PVC coated. Type 316 stainless steel ducts using mechanical joints with silicone seal or galvanized ductwork coated with PVC shall be used depending on the chemicals being conveyed in the system. Hoods, fans, and discharges shall be tagged for type of service and fume hoods shall be tagged with a fan service tag. Exhaust fans and ductwork handling toxic fumes and/or radioisotopes shall have a selfadhering CAUTION sticker attached. Existing terra cotta tile exhaust risers at Mellon Institute are of questionable condition with regard to how tightly they may be sealed. Some have been noted to have low leakage rates and others have higher leakage rates. The Design Consultant shall provide flexibility in the sizing of new exhaust fans by oversizing the motors by 25%, but should pick a fan that can operate at either the design cfm or a higher cfm (in case leakage is encountered). An extra sheave shall be specified so that the fan can be properly balanced at no additional cost to the University. The preferred system design for multiple hoods is to manifold them with variable-volume control. Where there is a central manifold exhaust system, as a minimum, one fan shall provide stand-by with the capacity to match one of the remaining fans. The OSHA requirement for a face velocity monitor on all fume hoods shall be adhered to. All laboratory hoods and safety cabinets shall be equipped with visual and audible alarms to warn laboratory workers of unsafe air flows. December 1998 P. 15-37 DIVISION 15 DESIGN AND CONSTRUCTION STANDARDS MECHANICAL SYSTEMS FACILITIES MANAGEMENT SERVICES Controls and dampers shall be of a type that, in the event of failure, will fall open to assure continuous draft. In accordance with NFPA Standard 45, automatic fire dampers shall not be used in laboratory hood exhaust systems. Fire detection and alarm systems shall not be interlocked to automatically shut down laboratory hood exhaust fans. Auxiliary air supply hoods shall not be used. 15854 CENTRAL STATION AIR HANDLING UNITS All air handling units shall have, at minimum, a dedicated set of two-position outside air dampers for ventilation requirements plus a second set of modulating outside air dampers, as required, for economizer operation or tracking with exhaust air. A full coil section width casing with access door shall be used to separate the chilled and preheat coils. Schedules shall include area served, location, total and sensible cooling capacities, entering and leaving temperatures (air and water) for all coils, motor horsepower, voltage, heating capacities, steam pressure, team coil condensation rate, fan rpm, total air quantity, outside air, and external and internal static pressures. Insulated casings and plenums shall be specified for all units, including those serving heat and vent applications. Casings for heat and vent applications shall have space for installation of future cooling coil. Units shall be installed to allow removal of all coils and filters. Clearance equal to fullfinned width of coil shall be provided to facilitate removal. Units shall be mounted on internal vibration isolators and concrete housekeeping pads. Units shall have a mixing box and filter box or a combination filter/mixing box properly sized so as not to exceed the filter manufacturer’s recommended face velocities. Low leakage dampers (2%) shall be provided for mixing box dampers. Air blending-devices shall be installed on all central station air-handling units where air stratification is a potential problem. All cooling coil drain pans shall be stainless steel. 15860 CENTRIFUGAL FANS Fan wheels shall be of backward inclined or airfoil design and shall be non-overloading. Precision-ground shafts shall be sized so that the first critical speed is at least 25% over the maximum operating speed. Bearings shall be heavy duty self-aligning or roller pillow block type and selected for a basic rating fatigue life (L-10) of 80,000-hour minimum, at maximum speed. P. 15-38 December 1998 DESIGN AND CONSTRUCTION STANDARDS FACILITIES MANAGEMENT SERVICES DIVISION 15 MECHANICAL SYSTEMS The assembled fan shall be factory-tested and fan vibration shall not exceed 0.15 in./sec peak velocity. 15865 TUBULAR CENTRIFUGALS Wheels shall be non-overloading air foil centrifugal type. Static and dynamic balance shall match the wheel cone and fan inlet cone. Welded steel vanes for air straightening shall be provided for the fan discharge. Bearings shall have a minimum 200,000-hour life at maximum operating speed. 15870 POWER VENTILATORS Power ventilators shall have non-overloading, backward inclined centrifugal wheels. Direct-drive motors may be used for wheels of diameter smaller than 20 in. and shall be matched to fan load. For wheels 20 in. and greater in diameter, a belt drive shall be used. Drives shall be sized for a minimum of 150% of driven horsepower. Birdscreen of 0.5-in. galvanized wire mesh shall be installed. A NEMA 1 disconnect switch shall be factory-wired to the motor. 15886 AIR FILTERS Filters for comfort systems serving offices, classrooms, and other noncritical areas shall be 50% efficiency cartridge filters, where space allows. Filters for systems serving critical laboratory areas, animal rooms, and special areas will be dictated by project requirements. The Design Consultant shall review specific requirements with the University Project Manager. Filters shall have separate holding frames with side access and slide-out frames properly sized in accordance with the filter manufacturer’s guidelines. Frames shall be located to permit removal of the entire frame for filter replacement. Filter sections shall be provided with a filter differential pressure gage. 15891 METAL DUCTWORK General Duct sizes shown shall be the inside clear dimension. ASHRAE and/or SMACNA shall be used as a guide. Pressure classification shall be specified on the drawings. All metal ductwork shall be crossbroke to ensure rigidity. December 1998 P. 15-39 DIVISION 15 DESIGN AND CONSTRUCTION STANDARDS MECHANICAL SYSTEMS FACILITIES MANAGEMENT SERVICES All rectangular elbows with a depth greater than 18 in. shall have double thickness turning vanes. Every branch duct shall include a 45° transition (no splitter dampers required). Inlet and discharge ductwork configuration shall conform to the SMACNA HVAC Duct Design Manual. Two-in. wide, adhesive-backed vinyl cloth labels shall be used on all ductwork. Label lettering shall identify both the medium being conveyed and the direction of flow. Dampers Dampers shall be installed in all branch ducts for balancing and shall be indicated on the drawings. All balancing shall be done with branch duct dampers and NOT with diffuser dampers. Ducts whose smallest dimension is 8 in. or greater shall have multi-leaf opposed blade volume dampers with manual quadrants calibrated to show the position of the damper. Damper blade widths shall not exceed 6 in. Quadrants shall be oriented so that the handle is parallel to the direction of air flow, when the damper is wide open. Access Doors Hinged access doors shall be installed at all automatic dampers, fire dampers, reheat coils, and other apparatus requiring inspection and servicing. Doors shall be suitable for the pressure classification and shall open against static pressure in a duct. Doors shall be fully gasketed and insulated when installed in insulated ductwork. Door sizes shall be specified to be adequate for the intended purpose. Flexible Connections Flexible connections shall be provided at connections to ALL moving equipment. Flexible Ductwork Flexible ductwork shall not exceed 6 ft in length. Fire Dampers Fire dampers shall be installed where required by BOCA and NFPA. Temperature rating of fusible links shall be 160 °F. Frames shall be large enough so that there will be no obstruction to airflow when the dampers are open. Construction and arrangement of fire dampers shall be as approved in each case prior to installation. Access shall be provided for replacement of links and so labeled. P. 15-40 December 1998 DESIGN AND CONSTRUCTION STANDARDS FACILITIES MANAGEMENT SERVICES DIVISION 15 MECHANICAL SYSTEMS Fire dampers shall be UL approved and so labeled and installed, and shall comply with the requirements of BOCA and NFPA 90A. 15920 SOUND ATTENUATORS Section 15010 discusses sound pressure level requirements. Analysis shall be required for both supply and return systems. Self-generated noise shall be taken into account in the designer’s calculations. Drawings shall indicate velocity, static pressure loss, and decibel attenuation through octave bands. Laboratory testing shall be performed by an independent laboratory. 15930 AIR TERMINALS Variable Air Volume Boxes Variable air volume (VAV) systems shall typically be zoned so that three to five offices are ganged on a thermostat/box. Offices grouped together shall be ganged in a logical manner, such as having the same floor area, building face exposure, and similar internal loads. VAV boxes shall have a minimum position setting for ventilation air requirements. Use of reheat coils on the boxes for temperature control shall be minimized to special circumstances, such as interior spaces with the potential for no internal load. VAV boxes with perimeter radiation shall be sequenced from the same room thermostat to ensure that the systems do not “fight” each other. VAV boxes that are DDC type shall have factory-installed controls. The schedule shall include minimum and maximum cfms, noise criteria (NC) levels, and coil ratings. When multiple boxes are used to serve a single zone, all shall be controlled from a single thermostat. Location of all boxes shall be accessible for maintenance. Box controls shall be pressure independent. No system-powered boxes shall be used. 15932 AIR OUTLETS AND INLETS As part of the design and shop drawings, the submittal shall include a complete tabulation of these devices identified by room number and model, velocity, cfm, throw, pressure drop, sound level and flow factor, and/or core area in square feet. The submittal shall also include the manufacturer’s recommendations for air balancing procedures for the devices submitted. December 1998 P. 15-41 DIVISION 15 MECHANICAL SYSTEMS DESIGN AND CONSTRUCTION STANDARDS FACILITIES MANAGEMENT SERVICES Aluminum shall be specified for damp or wet atmospheres. Use of self-controlled diffusers is not permitted without University approval. Where possible, balancing dampers shall be located at the branch take-off instead of at the diffuser to reduce air noise. Where this is not possible, the damper at the diffuser shall be screwdriver operated. Air supply to laboratories must keep temperature gradients and air turbulence to a minimum, especially near laboratory fume hood faces and biological safety cabinets. Diffusers shall be located so that they do not affect air flow patterns at the fume hood face. Outside air intakes shall be located to prevent entrainment of relief air, exhaust air, or fume hood effluent. Wind tunnel tests shall be performed to assure the adequacy of the design configuration where multiple buildings are located on the same site. 15970 HVAC CONTROLS Static pressure control for variable-volume systems shall consist of a high quality sensor, located by the Design Consultant on the drawings. If the system is DDC- controlled, the transmitter shall be capable of controlling as low as 0-0.1 in. wc if necessary, at 0.5% accuracy, comparable to the Dwyer series 607, or an approved equal. With a DDC system, the freezestat and smoke detectors shall be hardwired to alarms, in case of failure or malfunction of the DDC system. These sensors shall work independently of the DDC system, but alarm the DDC system as long as the DDC system is on line. All pneumatic air shall be in copper tubing. Polyethylene tubing is allowed only for the final 12 in. for connections to devices. Polyethhylene tubing is allowed in raceways or conduit, in exposed mechanical spaces. Tubes shall be labeled at both ends. 15975 CONTROL SYSTEM EQUIPMENT DDC controls are justified where more than two controllers are required. Otherwise, the ATC system shall be pneumatic, with the exception that an extra set of contacts shall be provided on the equipment motor starter (and a current switch for proofing), so that it can be interfaced with the campus DDC system (by the University), for on/off control. The DDC system shall be as manufactured by Johnson Control (Metasys), or American Auto Matrix (AAM), unless otherwise notified. This applies to all major construction projects, however the DDC controls typically are limited to central equipment, with all terminal equipment controlled pneumatically. Other projects may require compatibility with the existing ATC system. All materials and equipment used shall be standard components regularly manufactured for automatic temperature control purposes. P. 15-42 December 1998 DESIGN AND CONSTRUCTION STANDARDS FACILITIES MANAGEMENT SERVICES DIVISION 15 MECHANICAL SYSTEMS All product and types shall have been thoroughly factory-tested and field-tested for reliability and accuracy. DDC work shall be bid separately under Division 18 (to be provided later), and the scope limited to setting the panel, programming, and making final connections. All else shall be accomplished by the Controls Contractor, which is bid under Division 15. Supervision and checkout of the ATC system shall be by engineers/technicians employed by the respective DDC or Controls Contractor. Checkout must be witnessed by the University Project Manager or a designee. Work Included The Contractor shall furnish and install all material required for a complete and useable automatic temperature control system. The ATC system shall include: all control wiring, power wiring between the sensors, actuators, valves, control panels, and other miscellaneous devices directly associated with the ATC system. Control dampers shall be furnished by the Controls Contractor and installed by the Mechanical Contractor. Control valves and wells for immersion elements shall be furnished by the Controls Contractor and installed by the Mechanical Contractor. Power wiring to the local ATC panel and wiring between fan motor holding coils and the local ATC panel shall be the responsibility of the Electrical Contractor and coordinated with Division 16. Control wiring shall be the Controls Contractor’s responsibility; the DDC Contractor shall be responsible for power wiring any panels that are not shown on bid documents at no cost to the University. Submittals The Design Consultant and the University shall review shop drawings concurrently. Two complete sets will be required by the University for review. The Design Consultant shall obtain the University’s review comments prior to forwarding comments to the Contractor. Submittals shall include the following: • Written sequence of operation, which shall conform with the intent of the Specified Sequence of Controls in the bid documents • System schematic diagrams, including flow diagrams (DDC systems) and control diagrams (pneumatic systems) • Component list, including the manufacturer’s model numbers • Wiring diagrams, including interlock wiring details • Panel layoutinterior wiring interconnections and exterior panel face layout December 1998 P. 15-43 DIVISION 15 MECHANICAL SYSTEMS • • • DESIGN AND CONSTRUCTION STANDARDS FACILITIES MANAGEMENT SERVICES A separate control valve submittal that includes valve location, model number, design flow, capacity factor (CV), and corresponding pressure drop at the design flow A separate control damper submittal A factory-printed specification sheet for review (for each device proposed) Approval of submittal is required prior to installation of any equipment or part of a system. Equipment The University has standardized on two DDC systems to be used on campus: AAM and Metasys. If the renovation is within a building where one of these systems is well established, the established system shall be specified as a proprietary system for the renovation. If no system is established, both systems shall be specified competitively. The architecture of the DDC system shall include distributed (standalone) controllers compatible with the Metasys or AAM system, wired back to the central system. A reduced copy of the schematic of the system served shall be installed on the face of the control panel under an 11-in. x 17-in. plastic sheet. 15985 SEQUENCE OF OPERATION Typical Control Sequences The bridge control valve shall close when the “load side” circulating pump is off. The conditions for the pump shutting off may vary, but normally when airside economizers are available for off-season cooling, these pumps can shut off below 50 °F ambient temperature. Airside economizers shall be provided on all air handling units over 2000 cfm for free cooling capabilities when outside air conditions warrant. Controls for economizer cycle shall be based on dry bulb comparison of return air to outside air. Enthalpy control is not required. For VAV applications, the discharge air temperature shall automatically reset upwards (based on a schedule from 55 °F to 65 °F) during colder outside air temperatures (say 75 °F to 30 °F). Laboratory Fume Hood Controls Laboratory exhaust control shall be based on room pressurization control (by TSI) for new buildings (where air leakage from the room can be minimized), and fan tracking for existing structures. Fume hood face velocity control shall be based on closed-loop design, as manufactured by Tech Air or Autoflow, Inc. (with parallel tube pitot-type sensor). P. 15-44 December 1998 DESIGN AND CONSTRUCTION STANDARDS FACILITIES MANAGEMENT SERVICES DIVISION 15 MECHANICAL SYSTEMS The fume hood control system manufacturer shall provide all the laboratory controls including the air handling control, radiation controls, and room temperature controls as well as the fume hood face velocity control and laboratory air flow tracking/room pressure control system. Each laboratory shall have individual room control. Humidification Control Humidification is not required unless needed to protect sensitive equipment or animals. In laboratories where equipment may be operating below the dewpoint of the air supply, the make-up air system shall be equipped with a reheat coil and controls to provide dehumidification capabilities year round. This is the case in biology laboratories that have freezers and water-cooled equipment that may sweat on days when the outside temperature is cool, but the air is 100% saturated with moisture. 15990 TESTING, ADJUSTING, AND BALANCING Maintenance Manuals Three complete copies of the Maintenance Manual labeled as described here shall be submitted to the University for approval in as many three-ring loose-leaf binders as required. The copies shall be submitted a minimum of two weeks prior to any instructions and demonstrations to University personnel. The manuals shall be typewritten and include a table of contents. The information shall be arranged in a logical order for use by the University in maintaining the project. The manuals shall include but not be limited to the following: 1. Table of Contents 2. Materials list with place of purchase 3. List of normally replaced items, such as filters, fuses, belts, seals, screens, etc., indicating style, rating, size, etc., and place of purchase 4. Installation, servicing, maintenance, and operating instructions for all systems and components with the place of original purchase and name, address, and phone number of the person servicing the system 5. Manufacturers’ guarantees and warranties 6. Approved copies of shop drawings, including component wiring diagrams and ATC wiring piping diagrams of all installed systems indicating all connections, color coding, functions, locations, and so on. Approved as noted shop drawing submittals shall be corrected to incorporate all approval notes prior to inclusion in maintenance manuals. 7. Schedule of all motors, starters, and controllers under this Contract with the following information included: December 1998 P. 15-45 DIVISION 15 DESIGN AND CONSTRUCTION STANDARDS MECHANICAL SYSTEMS • • • • • FACILITIES MANAGEMENT SERVICES Location All nameplate data Overload rating and manufacturer’s number Actual full-load amperes Overcurrent protection 8. System and equipment startup, seasonal changeover, and seasonal shutdown with prestart checklists and precautions 9. System and equipment troubleshooting guides 10. Reference documents that include a construction drawings list, a record set of drawings list, and test and balance records 11. Testing and balancing procedures for each system and system components 12. Copies of all inspection certificates and approvals from all inspection agencies 13. A copy of an approved balancing report. Where duct leakage has been deemed critical, test documentation shall be included in the balancing report. Instruction/Demonstration Instruction manuals shall be furnished to University personnel a minimum of two weeks prior to any instructions and demonstrations. At the completion of the work, the Contractor shall instruct and demonstrate to those University employees who will have charge of the equipment, the care, adjustment, and operation of all parts of the system. Such instruction shall cover a minimum period as determined by the University, eight hours per day, after the University has taken over the operation of the building, except as mentioned previously, and shall be arranged for at the University’s convenience. University maintenance and operations personnel shall be given a minimum two-week notice of scheduled instruction date. Startup The Contractor shall arrange for special startup service from the equipment manufacturer, or an appointed agent, for the following equipment: • Chillers • Pumps • Cooling towers • ATC systems • Boilers • Air handling units The startup shall include, but not necessarily be limited to: • Alignment and balance P. 15-46 December 1998 DESIGN AND CONSTRUCTION STANDARDS FACILITIES MANAGEMENT SERVICES • • • • • • • • • • • DIVISION 15 MECHANICAL SYSTEMS Lubrication Electrical connections, voltage, rotation Motor amperage readings Pump discharge and suction readings Chiller head and suction readings Chiller head and suction pressures Condenser water flow and temperature Chilled water flow and temperature chiller lock, sequences and safety controls Water systems Supervision of flushing and cleaning Performance of pH readings University maintenance and operations personnel shall be notified at least two weeks prior to scheduled startup dates to observe procedures. This does not preclude the requirements for operating instructions. Following startup, the manufacturer shall submit a report of findings to the Contractor, with a copy to the University. If the work is state funded, the report shall also be submitted to the State Department of General Services. Testing and Balancing All testing, adjusting, and balancing (TAB) shall be done in accordance with the National Environmental Balancing Bureau (NEBB) or Associated Air Balance Council (AABC). On major construction projects, as determined by the University, the balancing subcontractors must be NEBB-certified. Procedures Environmental systems, including all equipment, apparatus, and distribution systems, shall be tested and balanced in accordance with the AABC or NEBB procedural standards. Fume hood testing shall be in accordance with the procedure outlined in the AABC manual. All instruments used for measurements shall be accurate, and calibration histories for each instrument shall be available for examination. Calibration and maintenance of all instruments shall be in accordance with the requirements of AABC or NEBB. Accuracy of measurements shall be in accordance with AABC or NEBB standards. During the operating tests of the chilled water system, the Contractor shall provide, if necessary, a false load equal to full capacity on the chiller and submit data on gpm flow, pressure drop, inlet and outlet temperatures of chilled water, amperage of chiller, and ambient air temperature at condenser. December 1998 P. 15-47 DIVISION 15 MECHANICAL SYSTEMS DESIGN AND CONSTRUCTION STANDARDS FACILITIES MANAGEMENT SERVICES In addition, the Contractor shall check the operation of all automatic temperature control equipment; verify all thermostat, aquastat, airstat, etc., set-points and operations; and enlist the aid of the control subcontractor to make necessary adjustment where required. Reports Three copies of the final reports shall be submitted on applicable AABC or NEBB Reporting Forms for review and approval by the Design Consultant and the University Project Manager. Each individual final reporting form submitted shall bear the signature of the person who recorded the data and the signature of the testing and balancing supervisor of the performing firm. If more than one certified firm performs the TAB work, all final reports shall be submitted by that certified firm having managerial responsibility. Identification of all types of instruments used and their last dates of calibration shall be submitted with the final report. The final test report shall include appropriate reference to all problems regarding the system(s) encountered prior to, during, and after testing and what action was taken to correct the problem(s), including noise and vibration problems. Each report shall include a print (or sketch) reduced in size, showing all supply, return, and exhaust air outlets for easy reference to report data. An approved copy of the balancing report shall be included in the maintenance manual submittal. Fan Sheaves The fans shall be balanced and the unit sheaves shall be left approximately in the midrange of adjustment. The Contractor shall, where necessary, change the originallyfurnished sheaves to achieve this mid-range adjustment. It is not acceptable for a balancing contractor to indicate that the system has been balanced as far as the existing sheaves, etc. as required. Pressure Vessels All pressure vessels shall be installed in accordance with the requirements of the Commonwealth of Pennsylvania, Department of Labor and Industry Code for Unfired Pressure Vessels. Tanks and pressure vessels shall be inspected, stamped, and certified to be constructed in accordance with the above code and the ASME Code for Unfired Pressure Valves. Operating certificates shall be turned over to the University upon completion of the project. P. 15-48 December 1998 DESIGN AND CONSTRUCTION STANDARDS FACILITIES MANAGEMENT SERVICES DIVISION 15 MECHANICAL SYSTEMS Acceptance of Completed ATC Installation Upon completion of the installation, the ATC Contractor shall start up the system and shall perform all necessary testing and run diagnostics to ensure proper operation, including piping systems testing and hydrostatic testing. All piping shall be tested prior to receiving insulation. Prior to filling the systems, all joints and potential leak sources shall be painted with a water and powder blue line caulk mixture and allowed to dry. During the test, each joint shall be visually inspected. The Design Consultant shall specify test pressures. December 1998 P. 15-49