SUMMARY
Section Includes:
Pipe, fittings, valves, and connections for sprinkler systems.
Related Sections:
Section 01042 - Mechanical, Refrigeration, Food Service Equipment and Electrical Coordination.
Section 01400 - Quality Control.
Section 01720 – [Phased Turnover and] Project Closeout.
Section 15140 - Supports and Anchors.
Section 15190 - Mechanical Identification: Piping identification.
Section 15240 - Vibration Isolation and Seismic Restraints.
Section 15325 - Sprinkler Systems: Sprinkler systems design.
Division 16 – Electrical.
QUALITY CONTROL
The following publications form a part of this specification to the extent they are applicable:
Section 01400 – Quality Control.
ASME Boiler and Pressure Vessel Code Section IX - Welding and Brazing Qualifications.
ASME B16.1 - Cast Iron Pipe Flanges and Flanged Fittings, Class 25, 125, 250, and 800.
ASME B16.3 - Malleable Iron Threaded Fittings, Class 150 and 300.
ASME B16.4 - Cast Iron Threaded Fittings, Class 125 and 250.
ASME B16.5 - Pipe Flanges and Flanged Fittings.
ASME B16.9 - Factory-made Wrought Steel Buttwelding Fittings.
ASME B16.11 - Forged Steel Fittings, Socket-welding and Threaded.
ASME B16.18 - Cast Copper Alloy Solder Joint Pressure Fittings.
ASME B16.22 - Wrought Copper and Copper Alloy Solder Joint Pressure Fittings.
ASME B16.25 - Buttwelding Ends.
ASME B36.10 - Welded and Seamless Wrought Steel Pipe.
ASTM A135 - Electric-Resistance-Welded Steel Pipe.
ASTM A47 - Malleable Iron Castings.
ASTM A53 - Pipe, Steel, Black and Hot-Dipped, Zinc-coated Welded and Seamless.
<insert project name and location>
June 2010
FIRE PROTECTION PIPING
15310 - 1
p.
ASTM A234 - Piping Fittings of Wrought Carbon Steel and Alloy Steel for Moderate and Elevated
Temperatures.
ASTM A795 - Black and Hot-Dipped Zinc-Coated (Galvanized) Welded and Seamless Steel Pipe for Fire
Protection Use.
ASTM B32 - Solder Metal.
ASTM B75 - Seamless Copper Tube.
ASTM B88 - Seamless Copper Water Tube.
ASTM B251 - General Requirements for Wrought Seamless Copper and Copper-Alloy Tube.
ASTM D3309 - Polybutylene (PB) Plastic Hot- and Cold-Water Distribution Systems.
ASTM F438 - Socket-Type Chlorinated Poly(Vinyl Chloride) (CPVC) Plastic Pipe Fittings, Schedule 40.
AWS A5.8 - Brazing Filler Metal.
AWS D10.9 - Specifications for Qualification of Welding Procedures and Welders for Piping and Tubing.
AWWA C110 - Ductile Iron and Gray Iron Fittings.
AWWA C151 - Ductile Iron Pipe, Centrifugally Cast.
NFPA 13 - Installation of Sprinkler Systems, Latest Edition.
NFPA 24 - Installation of Private Fire Service Mains and Their Appurtenances
UL - Fire Resistance Directory.
UL 262 - Gate Valves for Fire-Protection Service.
UL 312 - Check Valves for Fire-Protection Service.
UL 405 - Fire Department Connections.
q.
r.
s.
t.
u.
v.
w.
x.
y.
z.
aa.
bb.
cc.
dd.
ee.
ff.
gg.
1.3
QUALIFICATIONS
a.
Manufacturer Qualifications: Company specializing in manufacturing the Products specified in this section
with minimum three documented experience.
Installer Qualifications: Company specializing in performing the work of this section with minimum 5 years
documented experience, and approved by the manufacturer.
b.
1.4
SUBMITTALS
1.4.1.
Submittals for Review:
Section 01400 - Submittals: Procedures for submittals. Manufacturer’s data demonstration compliance
with this specification for:
a.
(1)
(2)
(3)
(4)
b.
c.
d.
1.4.2.
a.
b.
c.
Piping
Valves
Pipe hangers and supports
Mechanical couplings
Product Data: Provide manufacturers catalogue information. Indicate valve data and ratings.
Shop Drawings: Indicate pipe materials used, jointing methods, supports, floor and wall penetration seals.
Indicate installation, layout, weights, mounting and support details, and piping connections. Prepare in
accordance with NFPA 13, latest edition.
Operation and Maintenance Data.
Submittals At Project Closeout:
Section 01720 - Phased Turnover and Contract Closeout: Procedures for submittals.
Project Record Documents: Record actual locations of components and tag numbering.
The Contractor shall submit all certifications and testing data as a supplement to previously submitted O & M
manuals at contract closeout.
<insert project name and location>
June 2010
FIRE PROTECTION PIPING
15310 - 2
1.5
REGULATORY REQUIREMENTS
a.
b.
c.
Welding Materials and Procedures: Conform to ASME Code.
Valves: Provide manufacturer's name and pressure rating marked on valve body.
Products Requiring Electrical Connection: Listed and classified as suitable for the purpose specified and
indicated.
International Building Code (IBC).
d.
1.6
DELIVERY, STORAGE, AND PROTECTION
a.
b.
c.
Deliver and store valves in shipping containers, with labeling in place.
Provide temporary protective coating on cast iron and steel valves.
Provide temporary end caps and closures on piping and fittings. Maintain in place until installation.
PART 2 - PRODUCTS
2.1
BURIED PIPING
a.
Cast Iron Pipe: AWWA C151.
(1)
(2)
(3)
2.2
Fittings: AWWA C110, standard thickness.
Joints: AWWA C111, rubber gasket.
Mechanical Couplings: Shaped composition sealing gasket, steel bolts, nuts, and washers.
ABOVE GROUND PIPING
a.
Steel Pipe: ASTM A53; ASTM A135; ASTM A795; or ASME B36.10; Schedule 10. Threaded pipe and
pipe 2" in diameter and smaller shall be Schedule 40.
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
b.
Steel Fittings: ASME B16.9, wrought steel, buttwelded; ASME B16.25, buttweld ends; ASTM A234,
wrought carbon steel and alloy steel; ASME B16.5, steel flanges and fittings; ASME B16.11, forged steel
socket welded and threaded.
Cast Iron Fittings: ASME B16.1, flanges and flanged fittings; ASME B16.4, threaded fittings.
Malleable Iron Fittings: ASME B16.3, threaded fittings ASTM A47.
Mechanical Grooved Couplings: Malleable iron housing clamps to engage and lock, "C" shaped
elastomeric sealing gasket, steel bolts, nuts, and washers; galvanized for galvanized pipe.
Mechanical Formed Fittings: Carbon steel housing with integral pipe stop and O-ring pocked and O-ring,
uniformly compressed into permanent mechanical engagement onto pipe.
Drain piping shall be galvanized.
Only sprinkler piping located in the customer areas will be painted. Sprinkler heads shall be taped to avoid
receiving any paint residue. Ensure tape is removed once painting is complete.
Sprinkler dry pipe system shall be galvanized.
Copper Tubing: ASTM B75; ASTM B88; or ASTM B251; Type L, hard drawn.
(1)
Fittings: ASME B16.18, cast copper alloy, or ASME B16.22, wrought copper and bronze, solder joint,
pressure type.
<insert project name and location>
June 2010
FIRE PROTECTION PIPING
15310 - 3
(2)
c.
Joints: AWS A5.8 Classification BCuP-3 or BCuP-4 silver braze ASTM B32, solder, Grade 95TA.
Copper Tubing: ASTM B88, Type L, hard drawn.
(1)
(2)
d.
Fittings: ASME B16.18, cast copper alloy, or ASME B16.22, wrought copper and bronze, grooved.
Mechanical Grooved Couplings: Ductile iron housing with alkyd enamel paint coating clamps to engage
and lock, "C" shaped elastomeric sealing gasket, steel bolts, nuts, and washers.
Cast Iron Pipe: AWWA C151.
(1)
(2)
(3)
2.3
Fittings: AWWA C110, standard thickness.
Joints: AWWA C111, rubber gasket.
Mechanical Grooved Couplings: Malleable iron housing clamps to engage and lock, "C" shaped
composition sealing gasket, steel bolts, nuts, and washers; galvanized for galvanized pipe.
PIPE HANGERS AND SUPPORTS
a.
b.
Conform to NFPA 13, latest edition.
Floor Support: Cast iron adjustable pipe saddle, lock nut, nipple, floor flange, and concrete pier or steel
support.
Copper Pipe Support: Carbon steel ring, adjustable, copper plated.
c.
2.4
GATE VALVES CONTROLLING SPRINKLERS
a.
Up to and including 2 Inches:
(1)
b.
Over 2 Inches:
(1)
(2)
2.5
Indicating bronze body, bronze trim, rising stem, handwheel, solid wedge or disc, threaded ends. Provide
approved means for electric signal monitoring.
Iron body, bronze trim, rising stem pre-grooved for mounting tamper switch, handwheel, OS&Y, solid
bronze or cast iron wedge. Flanged or mechanical grooved ends.
Iron body, bronze trim, non-rising stem with bolted bonnet, solid bronze wedge, flanged ends, for use with
iron body indicator post assembly.
GLOBE [OR ANGLE] VALVES
a.
Up to and including 2 Inches:
(1)
b.
Bronze body, bronze trim, rising stem and handwheel, inside screw, renewable rubber disc, threaded ends,
with backseating capacity repackable under pressure.
Over 2 Inches:
(1)
Iron body, bronze trim, rising stem, handwheel, OS&Y, plug-type disc, flanged ends, renewable seat and
disc.
<insert project name and location>
June 2010
FIRE PROTECTION PIPING
15310 - 4
2.6
CHECK VALVES
a.
Up to and including 2 Inches:
(1)
b.
Bronze body and swing disc, rubber seat, threaded ends.
Over 2 Inches:
(1)
(2)
2.7
Iron body, bronze trim, swing check with rubber disc, renewable disc and seat, flanged or mechanical
grooved ends with automatic ball check where required.
Iron body, bronze disc, stainless steel spring, resilient seal, threaded, wafer, or flanged ends.
DRAIN VALVES
a.
Ball Valve:
(1)
Brass with cap and chain, 3/4 inch hose thread.
(2)
Listed test/drain assembly.
PART 3 - EXECUTION
3.1
PREPARATION
a.
b.
c.
3.2
Ream pipe and tube ends. Remove burrs. Bevel plain end ferrous pipe.
Remove scale and foreign material, from inside and outside, before assembly.
Prepare piping connections to equipment with flanges or unions.
INSTALLATION
a.
b.
c.
d.
e.
f.
g.
Install piping in accordance with NFPA 13, latest edition, for sprinkler systems.
Route piping in orderly manner, plumb and parallel to building structure. Maintain gradient.
Install piping to conserve building space, to not interfere with use of space and other work.
Group piping whenever practical at common elevations.
Sleeve pipes passing through partitions, walls, and floors.
Install piping to allow for expansion and contraction without stressing pipe, joints, or connected equipment.
Inserts:
(1)
(2)
(3)
(4)
(5)
Provide inserts for placement in concrete formwork.
Provide inserts for suspending hangers from reinforced concrete slabs and sides of reinforced concrete
beams.
Provide hooked rod to concrete reinforcement section for inserts carrying pipe over 4 inches.
Where concrete slabs form finished ceiling, locate inserts flush with slab surface.
Where inserts are omitted, drill through concrete slab from below and provide through-bolt with recessed
square steel plate and nut recessed into and grouted flush with slab.
<insert project name and location>
June 2010
FIRE PROTECTION PIPING
15310 - 5
h.
Pipe Hangers and Supports:
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
i.
j.
k.
l.
m.
n.
o.
p.
q.
r.
s.
Install in accordance with NFPA 13, latest edition.
Install hangers to provide minimum 1/2 inch space between finished covering and adjacent work.
Place hangers within 12 inches of each horizontal elbow.
Use hangers with 1-1/2 inch minimum vertical adjustment. Design hangers for pipe movement without
disengagement of supported pipe.
Support vertical piping at every floor. Support riser piping independently of connected horizontal piping.
Where several pipes can be installed in parallel and at same elevation, provide multiple or trapeze hangers.
Provide copper plated hangers and supports for copper piping sheet lead packing between hanger or support
and piping.
Prime coat exposed steel hangers and supports. Refer to Section 09910. Hangers and supports located in
crawl spaces, pipe shafts, and suspended ceiling spaces are not considered exposed.
Slope piping per NFPA 13 and arrange systems to drain at low points. Use eccentric reducers to maintain top
of pipe level.
Prepare pipe, fittings, supports, and accessories for finish painting. Where pipe support members are welded
to structural building framing, scrape, brush clean, and apply one coat of zinc rich primer to welding. Refer to
Section 09910.
Do not penetrate building structural members unless indicated.
Provide sleeves when penetrating footings, floors, and walls. Seal pipe and sleeve penetrations to achieve fire
resistance equivalent to fire separation required.
When installing more than one piping system material, ensure system components are compatible and joined
to ensure the integrity of the system. Provide necessary joining fittings. Ensure flanges, union, and couplings
for servicing are consistently provided.
Die cut threaded joints with full cut standard taper pipe threads with red lead and linseed oil or other non-toxic
joint compound applied to male threads only.
Install valves with stems upright or horizontal, not inverted. Remove protective coatings after installation.
Provide gate or ball valves for shut-off or isolating service.
Provide drain valves at main shut-off valves, low points of piping and apparatus.
Provide galvanized pipe and fittings for dry pipe systems.
Plastic pipe markers shall be used in identifying sprinkler pipe. Refer to Section 15190, paragraph 2.3.
END OF SECTION
<insert project name and location>
June 2010
FIRE PROTECTION PIPING
15310 - 6