24 l Basic information 25 l RDLTS 26 l DRUE 27 l DRUF 28 l DRUL 29 l RDST 30 l DRET Basic information Three-phase transformers 24 Star point loading capacity: For the star point loading capacity for three-phase transformers the following must be heeded for avoidance of additional losses and neutral point displacements: In a wye-wye connection the star point can only be loaded with the full nominal current (phase conductor current) if the neutral conductor of the supply grid is rigidly connected with the primary-side transformer star point. If this is not the case, the star point can only be loaded with approx. 10% of the phase conductor current. This rule also applies to 3-phase AC autotransformers designed with wye autotransformer connections. Alternatively, the double zigzag connection has a 100% loading capacity. The following connection types yield a 100% star point loading capacity without any special measures: Dyn5, Dyn11, Dzn0, Yzn5, YNzn5 If 3-phase AC sets are formed from 3 single-phase transformers the star point must not be loaded. Designation Vector groups: In contrast to the standardised annotation for vector groups for transformer windings (high voltage side = higher phase conductor voltage, low voltage side = lower phase conductor voltage) we connect and label our three-phase transformers using the following method which is customary worldwide and easier to understand for the user: The 1st uppercase letter describes the primary (input) winding and the 2nd lowercase letter describes the secondary (output) winding. Depending on whether the star point (N) is on the primary or secondary side the vector group is supplemented by a capital or small N (examples: Dyn5, YNzn5). The last digit stands for the lagging phase position of the secondary to primary winding in the form of the clock hand model (each 30° = 1 hour). Symbols on the voltages on the rating plate provide additional identification. Clock hand diagram primary Secondary Circuit diagram primary Secondary Secondary star point Dd0 not available Yy0 10% loadable Dz0 Fully loadable Dy5 Fully loadable Yd5 not available If no order specifications to the contrary with specific position assignments for high and low voltages are formulated, the above identification method is selected! Yz5 Fully loadable 3-phase AC transformers are preferentially manufactured with Dyn5 if no specifications are available. Dd6 not available Yy6 10% loadable Dz6 Fully loadable Dy11 Fully loadable Yd11 not available Yz11 Fully loadable Ya0 10% loadable 0 5 If higher secondary currents are required for low voltages Yd(5/11) is preferentially manufactured. 6 11 0 Subject to technical changes RDLTS 25 c Three-phase transformers d a e b General information: Single-phase autotransformers according to VDE 0570 part 2-13, EN 61558-2-13 The transformers in the RDLTS series are single-phase autotransformers with 5 steps and are specially designed for air conditioning and ventilation. They are designed as Autotransformers according to VDE 0570 Design: Single-phase autotransformers with open delta connection for 3-phase AC fan motors (one set composed of 2 individual transformers) Open frame, stationary, for device installation and assembly in dry rooms, windings. Connection to leakage current-resistant transformer terminals with screw and tab connectors 2.8x0.8mm to 5A, 6.3x0.8mm to 20A. The 2.8x0.8mm tab connector must only be loaded to 5A in accordance with DIN 46249 and 6.3x0.8mm to 20A. The 0V and 400V connections are each provided only once on terminal. The terminals are protected against back of hand and finger contact according to accident prevention regulations (BGV A3). PE connection as 6.3x0.8mm tab connector. IP 00, insulation class E, max. ambient temperature 40°C (ta40°C/E). Voltage range: Input voltage: AC 400V 3~ Output voltages: AC 140/180/230/280/400V Other designs upon request (voltages, currents, connections, mounting etc.) Open delta connection: Type RDLTS 95 RDLTS 190 RDLTS 285 RDLTS 380 RDLTS 475 RDLTS 660 RDLTS 950 RDLTS 1330 RDLTS 1800 RDLTS 2465 RDLTS 3410 Current A Item no: 1 2 3 4 5 7 10 14 19 26 36 0097-00000095 0097-00000190 0097-00000285 0097-00000380 0097-00000475 0097-00000660 0097-00000950 0097-00001330 0097-00001800 0097-00002465 0097-00003410 Copper kg Total kg a b Dimensions approx. in mm c d e Mounting 0,6 1,4 1,8 2,2 4,0 7,1 10,9 12,4 18,0 23,0 27,0 4,0 6,8 7,8 13,0 14,6 17,1 20,2 28,4 40,1 44,0 55,0 78 105 105 120 120 150 150 174 174 195 195 74 81 89 88 100 107 150 138 169 175 182 89 110 110 121 121 145 145 157 157 178 178 56 84 84 90 90 122 122 135 135 150 150 54 62 69 70 82 84 127 106 136 110 150 M4 M4 M4 M5 M5 M6 M6 M6 M6 M8 M8 Storage types l Subject to technical changes DRUE 26 c Three-phase transformers d a e b General information: Three-phase grid transformers according to VDE 0570 part 2-1, EN 61558-2-1, Single-phase isolation transformers according to VDE 0570 part 2-4, EN 61558-2-4 Three-phase safety transformers according to VDE 0570 part 2-6, EN 61558-2-6 Three-phase autotransformers according to VDE 0570 part 2-13, EN 61558-2-13 The transformers in the DRUE series meet national and international requirements for worldwide use. They can be delivered upon request with approval as Grid transformers according toVDE 0570 part 2-1, EN 61558-2-1, Isolation transformers according to VDE 0570 part 2-4, EN 61558-2-4, Safety transformers according to VDE 0570 part 2-6, EN 61558-2-6, (sum of all idle secondary voltages: max. 50V) Design: Open frame, stationary, for device installation and assembly in dry rooms, separate windings. Connection to leakage current-resistant transformer terminals with screw fastening. For over 50A leakage current-resistant terminal blocks are mounted on top brackets (note: dimensions b and c are enlarged by this). The terminals are protected against back of hand and finger contact according to accident prevention regulations (BGV A3). Other designs available upon request (voltages, currents, connections, mounting etc.). IP 00, insulation class E, ambient temperature 40°C (ta40°C/E). Fig. Upright design with terminal blocks All types are also available as 3-phase transformers (for calculation please see 'Transformers with autotransformer windings' in the section containing general information). Type DRUE 50 DRUE 110 DRUE 150 DRUE 260 DRUE 410 DRUE 500 DRUE 630 DRUE 800 DRUE 1000 DRUE 1100 DRUE 1200 DRUE 1500 DRUE 1750 DRUE 2000 DRUE 2200 DRUE 2400 DRUE 2700 DRUE 3000 DRUE 3400 DRUE 4400 DRUE 5000 DRUE 6000 DRUE 6300 DRUE 8000 DRUE 8200 DRUE 10000 DRUE 13000 DRUE 16000 DRUE 18000 DRUE 20000 DRUE 25000 DRUE 30000 DRUE 36000 Power VA ≈ % Core 50 110 150 260 410 500 630 800 1000 1100 1200 1500 1750 2000 2200 2400 2700 3000 3400 4400 5000 6000 6300 8000 8200 10000 13000 16000 18000 20000 25000 30000 36000 85,0 86,0 87,0 91,0 92,0 92,5 93,5 94,0 94,0 94,0 94,5 95,0 95,5 95,5 96,0 96,0 96,5 96,5 96,0 96,5 96,6 96,8 96,8 97,1 97,0 97,4 97,1 97,6 97,8 97,8 98,2 98,0 98,1 3UI 48/26 3UI 60/21 3UI 60/31 3UI 75/26 3UI 75/41 3UI 90/31 3UI 90/41 3UI 90/51 3UI 102/46 3UI 114/40 3UI 102/57 3UI 120/51 3UI 114/64 3UI 120/61 3UI 120/66 3UI 120/71 3UI 120/75 3UI 132/72 3UI 150/52 3UI 150/65 3UI 150/77 3UI 150/92 3UI 168/75 3UI 168/92 3UI 180/78 3UI 180/93 3UI 210/73 3UI 210/88 3UI 210/103 3UI 210/133 3UI 210/133 3UI 240/110 3UI 240/140 Item no: 0300-00000050 0300-00000110 0300-00000150 0300-00000260 0300-00000410 0300-00000500 0300-00000630 0300-00000800 0300-00001000 0300-00001100 0300-00001200 0300-00001500 0300-00001750 0300-00002000 0300-00002200 0300-00002400 0300-00002700 0300-00003000 0300-00003400 0300-00004400 0300-00005000 0300-00006000 0300-00006300 0300-00008000 0300-00008200 0300-00010000 0300-00013000 0300-00016000 0300-00018000 0300-00020000 0300-00025000 0300-00030000 0300-00036000 Copper kg Total kg a b Dimensions approx. in mm c d e Mounting 0,22 0,70 0,80 1,10 1,50 2,20 2,50 2,80 3,20 4,20 3,60 4,60 5,20 6,30 6,80 8,00 8,90 8,40 11,30 12,20 12,60 15,60 16,40 20,20 20,50 26,60 37,70 46,80 48,60 49,80 54,80 79,40 88,90 1,20 1,70 2,40 3,90 5,70 6,60 8,40 10,20 11,30 13,10 13,40 17,00 18,90 21,00 22,60 25,00 26,80 29,20 31,20 36,60 41,10 49,60 51,30 62,50 62,00 76,00 90,00 110,00 122,00 144,00 146,00 181,00 218,00 96 120 120 150 150 180 180 180 210 228 210 240 228 240 240 240 240 265 300 300 300 300 336 336 360 360 420 420 420 420 420 480 480 86 81 91 86 101 91 101 111 108 110 119 121 134 131 136 141 145 152 140 153 165 180 150 170 180 195 180 195 210 240 240 240 270 100 110 110 135 135 155 155 155 175 195 178 205 195 205 205 205 205 230 260 260 260 260 290 290 310 310 360 360 360 360 360 415 415 71 90 90 113 113 136 136 136 150 176 150 185 176 185 185 185 185 200 224 224 224 224 248 248 264 264 316 316 316 316 316 356 356 48 39 49 49 64 57 67 77 80 71 91 81 95 91 96 101 105 102 94 108 120 134 127 144 140 155 143 158 173 203 203 184 214 M4 M4 M4 M5 M5 M6 M6 M6 M8 M6 M8 M8 M6 M8 M8 M8 M8 M8 M8 M8 M8 M8 M8 M8 M8 M8 M10 M10 M10 M10 M10 M14 M14 Fast delivery l Subject to technical changes DRUF 27 c Three-phase transformers d a e b General information: Three-phase grid transformers according to VDE 0570 part 2-1, EN 61558-2-1, Three-phase isolation transformers according to VDE 0570 part 2-4, EN 61558-2-4 Three-phase safety transformers according to VDE 0570 part 2-6, EN 61558-2-6 The transformers in the DRUF series meet national and international requirements for worldwide use. They can be delivered upon request with approval as Grid transformers according toVDE 0570 part 2-1, EN 61558-2-1, Isolation transformers according to VDE 0570 part 2-4, EN 61558-2-4, Safety transformers according to VDE 0570 part 2-6, EN 61558-2-6, (sum of all idle secondary voltages: max. 50V) Design: Open frame, stationary, for device installation and assembly in dry rooms, separate windings. Connection to leakage current-resistant transformer terminals with screw fastening. For over 50A leakage current-resistant terminal blocks are mounted on top brackets (note: dimensions b and c are enlarged by this). The terminals are protected against back of hand and finger contact according to accident prevention regulations (BGV A3). Other designs available upon request (voltages, currents, connections, mounting etc.). IP 00, insulation class F, ambient temperature 40°C (ta40°C/F). Three-phase autotransformers according to VDE 0570 part 2-13, EN 61558-2-13 Fig. Upright design with terminal blocks All types are also available as 3-phase transformers (for calculation please see 'Transformers with autotransformer windings' in the section containing general information). Type DRUF 6000 DRUF 7500 DRUF 8000 DRUF 9600 DRUF 10000 DRUF 12000 DRUF 16000 DRUF 19000 DRUF 21500 DRUF 25000 DRUF 30000 DRUF 36000 DRUF 40000 Power VA ≈ % Core 6000 7500 8000 9600 10000 12000 16000 19000 21500 25000 30000 36000 40000 95,2 95,4 95,6 95,8 95,9 96,3 96,8 96,8 97,0 97,5 98,0 97,8 97,9 3UI 150/77 3UI 150/92 3UI 168/75 3UI 168/92 3UI 180/78 3UI 180/93 3UI 210/73 3UI 210/88 3UI 210/103 3UI 210/133 3UI 210/133 3UI 240/110 3UI 240/140 Item no: 0310-00006000 0310-00007500 0310-00008000 0310-00009600 0310-00010000 0310-00012000 0310-00016000 0310-00019000 0310-00021500 0310-00025000 0310-00030000 0310-00036000 0310-00040000 Copper kg Total kg a b Dimensions approx. in mm c d e Mounting 12,6 15,6 16,4 20,2 20,5 26,6 37,7 46,8 48,6 55,6 54,8 79,4 88,9 41,1 49,6 51,3 62,5 62,0 76,0 86,0 110,0 122,0 150,0 146,0 181,0 218,0 300 300 336 336 360 360 420 420 420 420 420 480 480 165 180 150 170 180 195 180 195 210 240 240 240 270 260 260 290 290 310 310 360 360 360 360 360 415 415 224 224 248 248 264 264 316 316 316 316 316 356 356 120 134 127 144 140 155 143 158 173 203 203 184 214 M8 M8 M8 M8 M8 M8 M10 M10 M10 M10 M10 M14 M14 DRUF 50000-100000: Design with sheet metal strip (like the RDST series), but cost-optimised. Type DRUF 50000 DRUF 63000 DRUF 80000 DRUF 100000 Power kVA Item no: 50 63 80 100 0310-00000050 0310-00000063 0310-00000080 0310-00000100 Copper kg Total kg a Dimensions approx. in mm b* c c1 94 117 129 147 280 330 385 440 550 550 650 650 300 320 310 330 470 470 570 570 c+100 c+100 c+100 c+100 Fast delivery l Subject to technical changes l Subject to technical changes DRUL UL-CSA 28 c Three-phase transformers d a e b General information: Three-phase grid transformers according to VDE 0570 part 2-1, EN 61558-2-1, Single-phase isolation transformers according to VDE 0570 part 2-4, EN 61558-2-4 Three-phase safety transformers according to VDE 0570 part 2-6, EN 61558-2-6 Three-phase autotransformers *1 according to VDE 0570 part 2-13, EN 61558-2-13 Industrial control transformers UL 5085 / CSA 22.2 allowed The transformers in the DRUL series are specially approved for the North American market. The also meet the requirements of EN 61558. Industrial control transformers UL 5085 / CSA 22.2 allowed (sum of all secondary voltages: max. 600V) Grid transformers according toVDE 0570 part 2-1, EN 61558-2-1, Isolation transformers according to VDE 0570 part 2-4, EN 61558-2-4, Safety transformers according to VDE 0570 part 2-6, EN 61558-2-6, (sum of all idle secondary voltages: max. 50V) Autotransformers *1 adapted in terms of installed capacity (current intensity max. 360A per connection terminal) The respective version must be given with the order. The particular advantages of the DRUL series Fig. Upright design with terminal blocks UL-file No.: E164203 Category: XPTQ2/8 (not „Contruction only“ or „Insulating System“) Design: *1) Suffix -A (DRUL-A) = Autotransformer Type DRUL 110 UL-CSA DRUL 150 UL-CSA DRUL 260 UL-CSA DRUL 410 UL-CSA DRUL 500 UL-CSA DRUL 630 UL-CSA DRUL 800 UL-CSA DRUL 1000 UL-CSA DRUL 1100 UL-CSA DRUL 1200 UL-CSA DRUL 1500 UL-CSA DRUL 1750 UL-CSA DRUL 2000 UL-CSA DRUL 2200 UL-CSA DRUL 2400 UL-CSA DRUL 2700 UL-CSA DRUL 3000 UL-CSA DRUL 3400 UL-CSA DRUL 4400 UL-CSA DRUL 5000 UL-CSA DRUL 6000 UL-CSA DRUL 7500 UL-CSA DRUL 8000 UL-CSA DRUL 9600 UL-CSA DRUL 10000 UL-CSA DRUL 12000 UL-CSA DRUL 16000 UL-CSA DRUL 19000 UL-CSA DRUL 21500 UL-CSA DRUL 25000 UL-CSA DRUL 30000 UL-CSA DRUL 36000 UL-CSA DRUL 40000 UL-CSA DRUL 50000 UL-CSA Input voltage 3AC 200-600V freely selectable; output voltage: see table below. Maximum 4 voltage taps, e.g. +-5% in given voltage range optional Maximum 4 separate windings with a sum lying inside the voltage range window, maximum current: 360A each Copper shield / magnetic shield between windings (optional). Temperature-bimetal switch for temperature monitoring (optional). Upon request by the customer for secondary volltage to 50VAC (V no-load) non-isolated cable lug connection (optional). Power VA Item no: 110 150 260 410 500 630 800 1000 1100 1200 1500 1750 2000 2200 2400 2700 3000 3400 4400 5000 6000 7500 8000 9600 10000 12000 16000 19000 21500 25000 30000 36000 40000 50000 0323-00000110 0323-00000150 0323-00000260 0323-00000410 0323-00000500 0323-00000630 0323-00000800 0323-00001000 0323-00001100 0323-00001200 0323-00001500 0323-00001750 0323-00002000 0323-00002200 0323-00002400 0323-00002700 0323-00003000 0323-00003400 0323-00004400 0323-00005000 0323-00006000 0323-00007500 0323-00008000 0323-00009600 0323-00010000 0323-00012000 0323-00016000 0323-00019000 0323-00021500 0323-00025000 0323-00030000 0323-00036000 0323-00040000 0323-00050000 Connection to leakage current-resistant transformer terminals with screw fastening. For over 50A terminal blocks are mounted on top brackets (note: dimensions b and c are enlarged by this). The terminals are protected against back of hand and finger contact according to accident prevention regulations (BGV A3). (ta40°C/F). Copper kg Total kg a b Dimensions approx. in mm c d e Mounting 0,8 0,9 1,2 1,7 2,4 2,8 3,1 3,5 4,6 4,0 5,1 5,7 6,9 7,5 8,8 9,8 9,2 12,4 13,4 15,0 13,9 17,2 18,0 22,2 22,6 29,3 41,5 51,5 53,5 60,3 60,3 87,3 97,8 99,0 1,7 2,4 3,9 5,7 6,6 8,4 10,2 11,3 13,1 13,4 17,0 18,9 21,0 22,6 25,0 26,8 29,2 31,2 36,6 41,1 41,1 49,6 51,3 62,5 62,0 76,0 90,0 110,0 122,0 150,0 146,0 181,0 218,0 220,0 120 120 150 150 180 180 180 210 228 210 240 228 240 240 240 240 265 300 300 300 300 300 336 336 360 360 420 420 420 420 420 480 480 480 81 91 86 101 91 101 111 108 110 119 121 134 131 136 141 145 152 140 153 153 165 180 150 170 180 195 180 195 210 240 240 240 270 270 110 110 135 135 155 155 155 175 195 175 205 195 205 205 205 205 230 260 260 260 260 260 290 290 310 310 360 360 360 360 360 415 415 415 90 90 113 113 136 136 136 150 176 150 185 176 185 185 185 185 200 224 224 224 224 224 248 248 264 264 316 316 316 316 316 356 356 356 39 49 49 64 57 67 77 80 71 91 81 95 91 96 101 105 102 94 108 108 120 134 127 144 140 155 143 158 173 203 203 184 214 214 M4 M4 M5 M5 M6 M6 M6 M8 M6 M8 M8 M6 M8 M8 M8 M8 M8 M8 M8 M8 M8 M8 M8 M8 M8 M8 M10 M10 M10 M10 M10 M14 M14 M14 Fast delivery l Subject to technical changes RDST 29 c Three-phase transformers d a e b General information: Three-phase grid transformers according to VDE 0570 part 2-1, EN 61558-2-1, The delta core packages of our three-phase core transformers of higher power are composed of alternating layers of sheet metal strips. The windings are vacuum-impregnated with the core and then fired for several hours in the drying kiln. Single-phase isolation transformers according to VDE 0570 part 2-4, EN 61558-2-4 Special features of the RDST series: Three-phase safety transformers according to VDE 0570 part 2-6, EN 61558-2-6 Three-phase autotransformers according to VDE 0570 part 2-13, EN 61558-2-13 Available in accordance with VDE 0532 upon request. Core transformers with dry design according to EN 61558 / VDE 0570 Designed for maximum efficiency The solid planning guarantees the nearly unlimited life of our transformers even if overload occurs Connections up to 415A to terminal blocks, additionally bolts, bus bars or cable lugs (non-dimensioned) Insulation classF Individual planning and hence changes in dimensions and weights possible Loss-optimised series All types are also available as 3-phase transformers (for calculation please see 'Transformers with autotransformer windings' in the section containing general information). Fig. Upright design with terminal blocks * Depending on the design and winding type for special currents all dimensions, particularly the dimension b, can be enlarged by up to 100mm! Dimensions d and e upon request Type RDST 40 RDST 50 RDST 63 RDST 80 RDST 100 RDST 125 RDST 160 RDST 170 RDST 200 RDST 250 RDST 320 RDST 400 RDST 500 RDST 630 RDST 800 Power kVA Item no: 40 50 63 80 100 125 160 170 200 250 320 400 500 630 800 0335-00000040 0335-00000050 0335-00000063 0335-00000080 0335-00000100 0335-00000125 0335-00000160 0335-00000170 0335-00000200 0335-00000250 0335-00000320 0335-00000400 0335-00000500 0335-00000630 0335-00000800 Copper kg Total kg a Dimensions approx. in mm b* c c1 from 63A 85 91 113 121 137 176 239 265 287 312 345 381 428 485 708 180 210 250 260 300 380 510 560 630 680 840 1090 1170 1580 1800 550 550 550 650 650 720 720 800 800 800 1060 1060 1060 1060 1060 220 270 300 300 320 320 380 360 400 450 420 470 520 600 710 460 460 470 570 570 570 620 680 680 760 900 900 900 900 900 c+100 c+100 c+100 c+100 c+100 c+150 c+150 c+150 c+150 c+150 c+150 c+150 c+150 c+150 c+150 Fast delivery l Subject to technical changes l Subject to technical changes DRET 30 c Three-phase transformers d e a b General information: Three-phase grid transformers according to VDE 0570 part 2-1, EN 61558-2-1, Single-phase isolation transformers according to VDE 0570 part 2-4, EN 61558-2-4 The Michael Riedel Transformatorenbau GmbH with the new RET series connects high quality requirements of the Riedel products with an energy efficient design. The transformers in the DRET series meet national and international requirements for worldwide use. The particular advantages of the DRET series: Three-phase safety transformers according to VDE 0570 part 2-6, EN 61558-2-6 Three-phase autotransformers according to VDE 0570 part 2-13, EN 61558-2-13 Variable voltages selectable by customer Loss-optimised design through innovative RET - core technology Reduction of the noise emissions through special core nesting Designed for maximum efficiency Insulation class B (ta = 40°C / B) also for large outputs Design: Open frame design, stationary, for device installation and assembly in dry rooms. Connection to leakage current-resistant transformer terminals with screw fastening. The transformer terminals are protected against back of hand and finger contact according to accident prevention regulations (BGV A3). Starting at 50A with terminal blocks on top brackets, starting at 415A on copper flat connections. IP00, suitable for installation up to Protection class IP 23 with natural air self-cooling, insulation class B, max. ambient temperature 40°C. Fig. DRET 100 Type DRET 1 DRET 2 DRET 3 DRET 4 DRET 5 DRET 6 DRET 7 DRET 8 DRET 9 DRET 10 DRET 12 DRET 16 DRET 20 DRET 25 DRET 30 DRET 35 DRET 40 DRET 45 DRET 50 DRET 63 DRET 70 DRET 80 DRET 90 DRET 100 DRET 125 DRET 150 DRET 175 DRET 200 DRET 250 DRET 300 DRET 350 DRET 400 DRET 450 DRET 500 Power KVA % Item no: 1,0 2,0 3,0 4,0 5,0 6,0 7,0 8,0 9,0 10,0 12,0 16,0 20,0 25,0 30,0 35,0 40,0 45,0 50,0 63,0 70,0 80,0 90,0 100,0 125,0 150,0 175,0 200,0 250,0 300,0 350,0 400,0 450,0 500,0 95,50 96,25 96,67 96,88 97,10 97,42 97,64 97,88 97,89 98,05 98,08 98,28 98,40 98,40 98,63 98,71 98,50 98,78 98,50 98,73 98,79 98,81 99,02 98,85 99,00 98,97 98,91 99,03 99,06 99,00 99,07 99,13 99,17 99,20 0340-00000001 0340-00000002 0340-00000003 0340-00000004 0340-00000005 0340-00000006 0340-00000007 0340-00000008 0340-00000009 0340-00000010 0340-00000012 0340-00000016 0340-00000020 0340-00000025 0340-00000030 0340-00000035 0340-00000040 0340-00000045 0340-00000050 0340-00000063 0340-00000070 0340-00000080 0340-00000090 0340-00000100 0340-00000125 0340-00000150 0340-00000175 0340-00000200 0340-00000250 0340-00000300 0340-00000301 0340-00000400 0340-00000450 0340-00000500 Copper kg Total kg a b c d e Mounting 3,80 6,80 8,50 12,60 15,70 16,00 19,30 26,10 27,90 32,60 41,70 57,70 60,10 70,40 84,90 96,50 96,80 102,60 125,00 145,00 155,00 168,00 201,50 182,00 240,00 268,90 272,10 274,00 338,10 378,80 386,10 565,00 580,00 730,00 14 22 30 37 46 52 59 72 72 85 100 129 143 177 206 232 249 276 293 375 417 424 478 474 572 639 692 743 886 996 1068 1474 1575 1771 204 240 264 300 300 300 300 336 360 360 450 450 450 450 540 540 540 540 540 660 660 660 660 660 660 720 720 720 840 840 840 1020 1020 1020 145 149 169 163 177 191 203 199 201 215 205 220 235 265 290 310 320 340 320 330 350 330 340 350 370 350 370 390 400 422 462 452 472 492 253 283 301 340 340 340 340 372 395 395 452 459 452 452 507 507 507 514 559 617 617 687 709 709 723 873 894 894 992 994 994 1104 1104 1104 184 220 244 275 275 275 275 311 335 335 420 420 420 420 500 500 500 500 500 620 620 620 620 620 620 680 680 680 800 780 780 960 960 960 96 101 116 110 124 139 150 143 136 151 140 155 170 200 190 210 220 240 220 225 245 225 235 245 265 235 255 275 270 293 333 318 338 352 M6 M8 M8 M8 M8 M8 M8 M8 M10 M10 M10 M10 M10 M10 M12 M12 M12 M12 M12 M12 M12 M12 M12 M12 M12 M14 M14 M14 M14 M16 M16 M16 M16 M16 * The table shows typical key values of transformers with an input and output voltage of 3AC 400 V. However, the given values can deviate depending on the choice of voltage. Dimensions approx. in mm Fast delivery l Subject to technical changes