HRSG Circulation System Design In the design of Babcock & Wilcox Power Generation Group, Inc’s (B&W PGG) heat recovery steam generator (HRSG), the evaporator circulation system is an important aspect that must be considered for successful operation. An improperly or inadequately designed circulation system can limit the HRSG’s availability during rapid startup and shutdown conditions, and during extreme rates of load change; result in drum level excursions or persistent water level trips; and contribute to flowassisted corrosion. To compensate for an undersized or improper circulation system design, many OEM suppliers require a circulation system that includes a larger-thannormal steam drum with a large water-holding capacity. B&W PGG’s design philosophy is to provide the proper circulation system for the design conditions the boiler is expected to experience during typical operation. Through circulation design analysis, the boiler components can be sized properly and more economically for the expected operational conditions. unit through the use of larger steam drums. Analyzing for flow excursions during load changes and transient operation can be beneficial by eliminating larger and/or additional supply and riser connections to the heat generating surface. An optimized circulation system design provides a reliable HRSG, which will eliminate most of the operational issues that result from an improperly designed unit. B&W PGG has developed an extensive set of design requirements for HRSGs to meet the demanding conditions required for today’s combined cycle power generation operation. Our circulation analysis goes beyond the typical steadystate circulation analysis and investigates the transient operation of the boiler. This type of analysis reduces the need for special and costly features, like additional water holding capacity for the At the heart of B&W PGG’s circulation evaluation is a boiler circulation analysis computer program which utilizes highly advanced techniques for calculation of heat transfer and single- and two-phase fluid flow parameters. With this computer program, a circulation model of each individual circuit of an entire boiler is evaluated. Circulation analysis Circuits within the HRSG are subject to a variation in heat transfer across its width and depth. The computer program manages this by allowing the designer to divide each circuit into zones. The designer is then able to determine the balanced water and steam flow in each zone by solving the energy, mass, and momentum equations. At the balanced flow condition, design criteria are examined allowing the designer to determine whether circulation characteristics are adequate. For each condition analyzed, adjustments are made to individual circuits, when necessary, to bring their flow characteristics within acceptable limits. These limits are based on B&W PGG’s experience, both in the field and through testing at our research center in Barberton, Ohio. Adjustments to improve circuit circulation can include, but are not limited to, determining the appropriate number of steam separators in the steam drum or incorporating a vertical separator; adding orifices at the entrance or within individual circuits; altering the number of supplies and/or risers; and lowering feedwater temperature entering the steam drum. Each circulation analysis is unique and the requirements to achieve acceptable circulation characteristics are casespecific to the boiler and operating conditions being examined. Details that B&W PGG considers when it designs and analyzes an HRSG include exit quality, saturated water head, saturated velocity, sensitivity, stability, departure from nucleate boiling (DNB) and drum internals. Exit quality Maximum exit quality from a circuit is a function of the drum operating pressure. Keeping a circuit’s exit quality below the maximum exit quality assures that boiling in the circuit will be restricted to nucleate boiling, and that the tube metal temperature will be close to saturation temperature. Saturated velocity Adherence to the required minimum circuit saturated velocity helps assure that steam blanketing does not occur and reduces the possibility of solids deposition. Both steam blanketing and solids deposition can cause tube failure. B&W PGG limits on saturated velocity are a function of tube orientation, tube location and type of firing. Circuit velocities must also be below the maximum limit to avoid flow-assisted corrosion. Sensitivity In a correctly designed natural circulation system, steam-water mixture flow increases with increased heat input, until a point where maximum flow is reached. If more heat is added, mixture flow then begins to decrease as specific volume and frictional pressure losses offset the pumping head due to increased heat absorption. Beyond the maximum circuit flow point at a specific load, heat input, and quality, circuits become unstable and may flow upward, stagnate, or flow backward. For a range of heat inputs, sensitivity is the steam-water mixture flow trend (i.e., increasing or decreasing) of circulation capability relative to the maximum continuous steam flow rating. B&W PGG carefully evaluates both steady state and transient operation to assure reliable circulation. Stability Stability is based on the pressure drop in a circuit between common pressure points. B&W PGG has established limits of circuit pressure drop allowed at a given steam flow and pressure. Circuits with heat absorption rates that vary across the different tube rows are most susceptible to instability. The stability analysis is a measure of the tendency of a circuit to flow in the desired direction. Figure 1 shows possible pressure differential characteristics for a furnace circuit. Line dP2 is the maximum attainable pressure differential for downflow. By forcing the pressure differential to be greater than line dP2, the circuit will flow upward. The graph indicates that for pressure differentials less than line dP2, there are three different flows that may yield the same pressure differential: two downflow and one upflow. In practice, the flow can also oscillate or stall. Therefore, Saturated water head The saturated water head criterion is the relationship between (a) the actual density and pressure drop characteristics of the steam and water mixture, and (b) those of a static column of saturated water of the same vertical height between common pressure points. Circuits operating at a lower percentage saturated water head could have problems with recirculation between parallel paths within the same circuit. B&W PGG has established limits for percentage saturated water head preventing this problem from occurring. Fig. 1 Relationship between boiler tube pressure loss and direction of flow. a circuit operating along line dP1, which does not meet the stability criteria, may operate at point C indefinitely and would be an upflow case. Unfortunately, the inherent nature of an unstable system means that it is sensitive to boundary conditions. The result is that system disturbances or changes, sometimes even small ones, may cause the operating point to be moved from one upflow solution to the potential for either upflow or downflow. Therefore, it is always desirable to operate above line dP2, the stability limit. of cooling liquid near the heated surface of the tube, causing the temperature of the tube to increase rapidly, as seen between points D and S in Figure 2. The point at which the boiling mechanism is interrupted (point D) is called the DNB point. DNB must be avoided in circulation design because it produces serious overheating and/ or rapid corrosion of boiler tubes, which leads to subsequent tube failures. In general, higher boiler tube absorption rates at higher loads and/or higher circulating (drum) pressures tend to cause DNB problems. Departure from nucleate boiling Drum internals HRSG evaporator tubes are cooled by nucleate boiling, which is characterized by a very high heat transfer coefficient. At certain conditions, the boiling mechanism is suddenly impaired, due to a lack Steam and water flow rates to each cyclone separator, as well as the pressure drop through each separator, are checked against B&W PGG-established limits. Conformance with B&W PGG standards reduces the risk of unacceptable carryunder levels of steam into the downcomers and carryover of water out of the drum. B&W PGG’s patented low-pressuredrop cyclone separators improve flow stability, increase drum water level control range, and minimize water carryover and steam carryunder for the highest possible steam purity. What separates B&W PGG from others? Boiler circulation design is one of many technical capabilities B&W PGG offers that separates us from the competition. We have more than 145 years of experience in the boiler industry. This experience, combined with the company’s state-of-the-art technology, have allowed us to offer superior products and services to customers. B&W PGG is considered a leader in the boiler circulation thermal hydraulics field because of our: • Boiler circulation analysis computer program, which was developed and benchmarked using laboratory field data, and features: -- Benchmarking across a wide pressure range (15 - 4000 psig) -- Easy evaluation of gas-side unbalances • Proprietary two-phase flow correlations • Accurate flow stability predictions • Flow sensitivity analyses at steady-state and transient conditions • Technical knowledge of steam separation equipment and its performance • Low-pressure-drop drum internals and economizer cyclones Fig. 2 Boiling conditions in evaporator tubes. www.babcock.com Babcock & Wilcox Power Generation Group, Inc. 20 S. Van Buren Avenue Barberton, Ohio 44203 USA Phone: 330.753.4511 Fax: 330.860.1886 Babcock & Wilcox Power Generation Group, Inc. is a subsidiary of The Babcock & Wilcox Company (B&W). Established in 1867, B&W is a world leader in providing steam generating and emissions control equipment, nuclear operations and components, and defense program management services. The information contained herein is provided for general information purposes only and is not intended nor to be construed as a warranty, an offer, or any representation of contractual or other legal responsibility. For more information, or a complete listing of our sales and service offices, call 1-800-BABCOCK (222-2625), send an e-mail to info@babcock.com, or access our website at www.babcock.com. © 2012 Babcock & Wilcox Power Generation Group, Inc. All rights reserved. SP-588500PS2B