Cleaver Brooks Interface
The Cleaver Brooks Interface (part number
CEPL130366) is a CIO Module equipped with software
which allows communication between a Carrier Comfort Network (CCN) and Cleaver Brooks boiler control
equipment. It allows you to map up to 500 points in the
Cleaver Brooks system to a table of user-defined CCN
points which resides in the interface. These points can
then be accessed by BEST/BEST++ programs or
Carrier’s Network Service Tool, Building Supervisor, or
ComfortWORKS software in the same manner as any
CCN controller. The interface provides for the following
features.
• A database which allows for access to up to 500
Cleaver Brooks points
• Both read and write operations (where permissible)
• Support for ComfortWORKS graphics
• Programmable CCN names for each point
• Individual poll rates for each point
• Viewing of both configuration and maintenance tables
for each point
• Support for both discrete and analog points
• Port communication supervision with alarm
CIO Module Specifications
In addition, the interface has tables which allow you to
configure alarm settings and RS-485 communication
parameters.
The interface connects to a Cleaver Brooks General
Purpose Interface ControlBus™ Module (Model 8332757), equipped with a QS7850 card. The ControlBus
module provides the RS-485 port to which the interface
is connected with a user-supplied cable. Once the
interface is connected to the ControlBus Module, you
can include in its database points from any Cleaver
Brooks control device which is accessible to the
ControlBus Module, including the CB-Hawk System
and CB780/783/784 burner controls. The interface uses
a subset of Honeywell's BDI protocol as implemented
on the QS7850 card to communicate with the Cleaver
Brooks devices.
Power Requirements ............ PWR1: 20 Vac @ 0.5 A
(28 Vdc @ 0.25 A)
PWR2 (separate/isolated): 20 Vac @ 0.25 A
(28 Vdc @ 0.25 A)
Dimensions ....... 11 1/4 in H X 1 7/8 in W X 6 7/8 in D
(28.6 cm H X 4.8 cm W X 17.5 cm D)
Operating Temperature ........................ 32°F to 120°F
(0°C to 49°C)
Storage Temperature .......................... -40°F to 185°F
(-40°C to 85°C)
Operating Humidity ..........10 to 90%, non-condensing
Conforms to guidelines for radiated and conducted
emissions for a Class A device as stated in FCC Rules
and Regulations Part 15, Subpart J.
UL 916 listed
Specifications subject to change without notice
© 1997, Carrier Corporation
ControlBus™ is a trademark of Aqua-Chem, Inc. Cleaver Brooks® is a registered trademark of Aqua-Chem, Inc.