m be certain. Multi-Pump Control Manager (MPCM) Product Information Supervisor and Basic Connection Interface (BCI) 100-249-603 A Copyright information Trademark information © 2011 MTS Systems Corporation. All rights reserved. MTS and SilentFlo are registered trademarks of MTS Systems Corporation within the United States. These trademarks may be protected in other countries. All other trademarks or service marks are property of their respective owners. Publication information Manual Part Number 100-249-603 A Publication Date November 2011 Contents Introduction 5 Intended Use Specifications 6 7 Safety 9 General Safety Practices 9 Installation 15 Placement of Components Mount the BCI 15 Spacing Requirements Cabling 15 16 16 Lifting Instructions 16 AC Power Disconnect Requirements External Device Connections 16 16 Operation 17 Set HPU to Remote Operation for use with the MPCM Supervisor Setup 18 Startup and Main Screen System Unit 17 19 20 23 Status Screen Setup 27 31 Station 32 Operating the HPU Locally or Remotely How to Clean the MPCM 33 34 Appendix 35 Setting Up System Run On Demand (ROD) Run On Demand Detailed Example Multi-Pump Control Manager 35 36 Contents 3 4 Contents Multi-Pump Control Manager Introduction The Multi-Pump Control Manager (MPCM) product family consists of a Basic Connection Interface (BCI) and typically the optional dedicated PC running the Supervisor software, with remote E-Stops, Station Flow Managers (SFM), and/or light stacks as options. Together, these components allow you to remotely run multiple HPUs similar to operation at the main HPU HMI panel. This manual assumes you are familiar with local operation of the HPU. That is, the descriptions of the controls and indicators that are similar to the controls and indicators on the HPU will be abbreviated in this manual, and it is assumed that you understand the full description provided in the HPU manual. Note The Multi-Pump Control Manager and associated components can only be used on the G2 HPU models. It will not work with the older HPU models. Contact MTS for additional information. In a typical configuration, there is one BCI, one Supervisor running on a dedicated PC, up to eight large HPUs, and a combination of up to eight remote E-Stops and SFMs. One or more optional light stack(s) can be included for HPU status away from the control room. Multi-Pump Control Manager Introduction 5 Intended Use Note MTS can provide the BCI without the Supervisor and dedicated PC. In this case, the BCI commons the signals required for the HPU(s) to work as a system controlling the cooling solenoids, bypass solenoids, and E-Stop chain (which includes external E-Stops). In this case, all control of the HPUs is accomplished at the HPU HMIs. BCI HPU #1 E-STOP #1 OR SFM #8 HPU #2 E-STOP #2 OR SFM #7 HPU #8 E-STOP #8 OR SUPERVISOR PC SFM #1 SUPERVISOR E-STOP LIGHT STACK(S) (DAISY CHAIN MULTIPLE LIGHT BARS,2 AMPS PER CHANNEL NOT TO EXCEED 6 AMPS TOTAL) Intended Use The intended use is to provide remote operation and status information for one or more HPUs. Before you attempt to use your MTS product, read and understand the manuals that accompany this product. Improper installation or operation of this product can result in hazardous conditions that can cause severe personal injury or death, and damage to your equipment and test specimen. 6 Introduction Multi-Pump Control Manager Specifications Specifications Parameter Specification Temperature 5ºC–40ºC (41ºF–104ºF) Humidity 5–85%, non-condensing Altitude 2000 m (6,561 ft) maximum IP rating IP40 Pollution Degree 2 Weight 41 kg (90 lb) Dimensions See illustration 29.94 MTG. KIT DIMENSION 25.56 MTG. HOLES 9.04 27.06 MTG. KIT DIMENSION 28.50 MTG. HOLES 30.00 ECLOSURE DIMENSION Multi-Pump Control Manager 24.00 ENCLOSURE DIMENSION 8.76 8.00 ENCLOSURE DIMENSION Introduction 7 Specifications Note Electrical connections must be made by qualified personnel and conform to local codes and regulations. Local electrical codes supersede any information found here. Parameter Specification 100–240 V AC (single phase) Input Voltage power factor corrected universal input Input Frequency 50–60 Hz 4 A at 100 V AC Input Current 2 A at 240 V AC Facility Power Requirements Provide a dedicated circuit for the chassis, computer, and monitor. Input Surge <50 A Over Voltage Category II Mark for Canada This product has been tested to the requirements of CAN/CSA-C22.2 No. 610101, 2nd Edition, including Amendment 1, or a later version of the same standard incorporating the same level of testing requirements. 8 Introduction Multi-Pump Control Manager General Safety Practices Safety General Safety Practices The Multi-Pump Control Manager (MPCM) product family consists of a Basic Connection Interface (BCI) and typically the optional dedicated PC running the Supervisor software, with remote E-Stops, Station Flow Managers (SFM), and/or light stacks as options. Together, these components allow you to remotely run multiple HPUs similar to operation at the main HPU HMI panel. The HPU provides high-pressure hydraulic fluid to system components for system operation. This section provides general information about safety issues that pertain to system hydraulic supply and distribution components. These issues include statements to the intended use and foreseeable misuse of the system and definition for the graphical hazard labeling that is affixed to your product, and other (more general) safety information that relates to the highpressure and high-performance characteristics of MTS servohydraulic and electromechanical systems. When you prepare to operate a system that includes hydraulic components, ensure the following: • Do not use or allow personnel to operate the system who are not experienced, trained, or educated in the inherent dangers associated with high-performance servo hydraulics and who are not experienced, trained, or educated with regard to the intended operation as it applies to this test system. • Do not disable safety components or features (including limit detectors, light curtains, or proximity switches/detectors). • Do not attempt to operate the system without appropriate personal safety gear (for example, hearing, hand, and eye protection). • Do not modify the system or replace system components using parts that are not MTS component parts or effect repairs using parts or components that are not manufactured to MTS specifications. • Do not use the system in a test area where uncontrolled access to the test system is allowed when the system is in operation. • For servohydraulic systems, do not operate the system unless an interlock is installed to monitor supply pressure into the HSM and initiate a system interlock if a low or no pressure event occurs. • Mists of DTE 25 are combustible. Refer to MSDS. You are responsible for fire prevention measures as per facility or building or other local regulations and codes If you have system-related responsibilities (that is, if you are an operator, service engineer, or maintenance person), you should study safety information carefully before you attempt to perform any test system procedure. Multi-Pump Control Manager Safety 9 General Safety Practices You should receive training on this system or a similar system to ensure a thorough knowledge of your equipment and the safety issues that are associated with its use. In addition, you should gain an understanding of system functions by studying the other manuals supplied with your test system. Contact MTS for information about the content and dates of training classes that are offered. It is very important that you study the following safety information to ensure that your facility procedures and the system’s operating environment do not contribute to or result in a hazardous situation. Remember, you cannot eliminate all the hazards associated with this system, so you must learn and remain aware of the hazards that apply to your system at all times. Use these safety guidelines to help learn and identify hazards so that you can establish appropriate training and operating procedures and acquire appropriate safety equipment (such as gloves, goggles, and hearing protection). Each test system operates within a unique environment which includes the following known variables: • Facility variables (facility variables include the structure, atmosphere, and utilities) • Unauthorized customer modifications to the equipment • Operator experience and specialization • Test specimens Because of these variables (and the possibility of others), your system can operate under unforeseen circumstances that can result in an operating environment with unknown hazards. Improper installation, operation, or maintenance of your system can result in hazardous conditions that can cause death, personal injury, or damage to the equipment or to the specimen. Common sense and a thorough knowledge of the system’s operating capabilities can help to determine an appropriate and safe approach to its operation. Read all manuals Study the contents of this manual and the other manuals provided with your system before attempting to perform any system function for the first time. Procedures that seem relatively simple or intuitively obvious may require a complete understanding of system operation to avoid unsafe or dangerous situations. Locate and read hazard placards/labels Find, read, and follow the hazard placard instructions located on the equipment. These placards are placed strategically on the equipment to call attention to areas such as known crush points, electrical voltage, and high pressure hazards. Know facility safe procedures Most facilities have internal procedures and rules regarding safe practices within the facility. Be aware of these safe practices and incorporate them into your daily operation of the system. Know controls Before you operate the system for the first time, make a trial run through the operating procedures with the power off. Locate all hardware and software controls and know what their functions are and what adjustments they require. If any control function or operating adjustment is not clear, review the applicable information until you understand it thoroughly. 10 Safety Multi-Pump Control Manager General Safety Practices Have first aid available Accidents can happen even when you are careful. Arrange your operator schedules so that a properly trained person is always close by to render first aid. In addition, ensure that local emergency contact information is posted clearly and in sight of the system operator. Know potential crush and pinch points Be aware of potential crush and pinch points on your system and keep personnel and equipment clear of these areas. Remember, when hydraulic power is interrupted on a servohydraulic system, it is likely that stored accumulator pressure will persist for some time within the system. In addition, it is likely that as stored energy dissipates, gravity will cause portions of the system to move. Be aware of component movement with hydraulics off Know electrical hazards The actuator rod can also drift down when hydraulics are turned off hitting anything in its path. This uncommanded movement is because of oil movement between the pressure/return ports and oil blow by across the piston hub. Be aware that this can happen and clear the area around the actuator rod when hydraulics are turned off. When the system electrical power is turned on, minimize the potential for electrical shock hazards. Wear clothing and use tools that are properly insulated for electrical work. Avoid contact with exposed wiring or switch contacts. Whenever possible, turn off electrical power when you work on or in proximity to any electrical system component. Observe the same precautions as those given for any other high-voltage machinery. Make sure that all electrical components are adequately grounded. Grounds must remain connected and undisturbed at all times. Keep bystanders safely away Wear proper clothing Keep bystanders at a safe distance from all equipment. Never allow bystanders to touch specimens or equipment while the test is running. Do not wear neckties, shop aprons, loose clothing or jewelry, or long hair that could get caught in equipment and result in an injury. Remove loose clothing or jewelry and restrain long hair. Practice good housekeeping Keep the floors in the work area clean. Hydraulic fluid that is spilled on any type of floor can result in a dangerous, slippery surface. Do not leave tools, fixtures, or other items not specific to the test, lying about on the floor, system, or decking. Protect hoses and cables Protect electrical cables from spilled hydraulic fluid and from excessive temperatures that can cause the cables to harden and eventually fail. Ensure that all cables have appropriate strain relief devices installed at the cable and near the connector plug. Do not use the connector plug as a strain relief. Protect all system hoses and cables from sharp or abrasive objects that can cause the hose or cable to fail. Never walk on hoses or cables or move heavy objects over them. Consider hydraulic distribution system layout and route hoses and cables away from areas that expose them to possible damage. Do not disable safety devices Multi-Pump Control Manager Your system may have active or passive safety devices installed to prevent system operation if the device indicates an unsafe condition. Do not disable such devices as it may result in unexpected system motion. Safety 11 General Safety Practices Use appropriately sized fuses Whenever you replace fuses for the system or supply, ensure that you use a fuse that is appropriately sized and correctly installed. Undersized or oversized fuses can result in cables that overheat and fuses that explode. Either instance creates a fire hazard. Provide adequate lighting Ensure adequate lighting to minimize the chance of operation errors, equipment damage, and personal injury. You need to see what you are doing. Provide means to access out-of-reach components Make sure you can access system components that might be out of reach while standing on the floor. For example, ladders or scaffolding might be required to reach load cell connectors on tall load units. Wear appropriate personal protection Wear eye protection when you work with high-pressure hydraulic fluid, breakable specimens, or when anything characteristic to the specimen could break apart. Wear ear protection when you work near electric motors, pumps, or other devices that generate high noise levels. Some systems can create sound pressure levels that exceed 70 dbA during operation. Wear appropriate personal protection equipment (gloves, boots, suits, respirators) whenever you work with fluids, chemicals, or powders that can irritate or harm the skin, respiratory system, or eyes. Handle chemicals safely Whenever you use or handle chemicals (for example, cleaning fluids, hydraulic fluid, batteries, contaminated parts, electrical fluids, and maintenance waste), refer to the appropriate MSDS documentation for that material and determine the appropriate measures and equipment required to handle and use the chemical safely. Ensure that the chemical is disposed of appropriately. Know system interlocks Interlock devices should always be used and properly adjusted. Interlock devices are designed to minimize the chance of accidental damage to the test specimen or the equipment. Test all interlock devices for proper operation immediately before a test. Do not disable or bypass any interlock devices as doing so could allow hydraulic pressure to be applied regardless of the true interlock condition. The Reset/Override button is a software function that can be used to temporarily override an interlock while attempting to gain control of the system. Ensure secure cables Do not change any cable connections when electrical power or hydraulic pressure is applied. If you attempt to change a cable connection while the system is in operation, an open control loop condition can result. An open control loop condition can cause a rapid, unexpected system response which can result in severe personal injury, death, or damage to equipment. Also, ensure that all cables are connected after you make any changes in the system configuration. Stay alert Avoid long periods of work without adequate rest. In addition, avoid long periods of repetitious, unvarying, or monotonous work because these conditions can contribute to accidents and hazardous situations. If you are too familiar with the work environment, it is easy to overlook potential hazards that exist in that environment. 12 Safety Multi-Pump Control Manager General Safety Practices Know the causes of unexpected actuator motions Do not use RF transmitters Multi-Pump Control Manager The high force and velocity capabilities of MTS actuators can be destructive and dangerous (especially if actuator motion is unexpected). The most likely causes of unexpected actuator response are operator error and equipment failure due to damage or abuse (such as broken, cut, or crushed cables and hoses; shorted wires; overstressed feedback devices; and damaged components within the servocontrol loop). Eliminate any condition that could cause unexpected actuator motion. Keep radio frequency (RF) transmitters away from the workstation computers, remote terminals, and electronics consoles. Intense RF fields can cause erratic operation of the more sensitive circuits in the system. Safety 13 General Safety Practices 14 Safety Multi-Pump Control Manager Placement of Components Installation The Multi-Pump Control Manager (MPCM) allows you to operate up to eight Hydraulic Power Units (HPUs) remotely. Standard installation involves placement of the components and cabling connections. Placement of Components Because all connections between components run through the Basic Connection Interface (BCI), it is usually placed in a central location; typically next to the HPUs. The dedicated PC running the Supervisor software is usually placed in the control room. Station Flow Managers (SFMs) are usually placed in alternate control rooms or next to the test rig. Remote E-Stops are usually placed at strategic locations, such as near exits from the test rig. Light stacks are strategically placed to be able to observe alarm and fault status in case problems arise that require attention. Mount the BCI Four mounting brackets are provided on the BCI: two top and two bottom. Mount the BCI using hardware that can support 50 kg (110 lbs); including the weight of the BCI and attached cables. Multi-Pump Control Manager Installation 15 Spacing Requirements Spacing Requirements The front of the enclosure requires 65 cm (25.6 in) minimum of clearance so the door can be opened by MTS service personnel. The power entry side of the enclosure requires 16 cm (6.3 in) minimum of clearance for the power cord. The bottom of the enclosure requires 65 cm (25.6 in) minimum of clearance for the cables. The dimensions above are minimum dimensions for the BCI. MTS recommends an additional 1m (40 in) of clearance around the BCI to ease installation and should service be necessary. Cabling Cabling consists of connecting the cables from all the associated components to the BCI. Shown below is a block diagram of connections. A detailed field wiring diagram (MTS Drawing number 700-005-779) can be found on the Product Information CD. HPU #1 BCI E-STOP #1 OR SFM #8 HPU #2 E-STOP #2 OR SFM #7 HPU #8 E-STOP #8 OR SUPERVISOR PC SFM #1 SUPERVISOR E-STOP LIGHT STACK(S) (DAISY CHAIN MULTIPLE LIGHT BARS,2 AMPS PER CHANNEL NOT TO EXCEED 6 AMPS TOTAL) Lifting Instructions The MPCM weighs about 41 kg (90 lb). Improper lifting techniques can cause strained muscles and back injuries. When lifting the MPCM, take the appropriate precautions to prevent injuries to yourself. AC Power Disconnect Requirements Be sure to locate the MPCM so that you have adequate access to disconnect the power cord from the unit. External Device Connections The MPCM is designed to work with MTS supplied devices. Only MTS supplied devices should be connected to the MPCM. 16 Installation Multi-Pump Control Manager Set HPU to Remote Operation for use with the MPCM Operation This section deals with operation of the Multi-Pump Control Manager (MPCM) only. It is assumed that the hydraulic power unit (HPU) has been properly set up and you are familiar with all operating aspects of the HPU. Remote operation of up to eight HPUs can be done from the MPCM. Most operation is the same as operation of the HPU from the Human Machine Interface (HMI) panel on the HPU main electrical enclosure. The MPCM provides all the same operation features as the main operator’s panel on the HPU excluding setup and those dealing with safety. WARNING Due to the various modes of operation, components connected to the MPCM BCI can start without prior notice. Components include but are not limited to: HPUs, Motor Modules, or Cooling Supply Circuits. Lockout tagout procedures should be followed when maintenance is performed on any component connected to the MPCM BCI. Set HPU to Remote Operation for use with the MPCM Supervisor To control the HPUs from the MPCM, the HPU(s) must be in Remote mode. The following procedure is from the HPU manual and provided here for reference. Note Perform the following steps on each HPU in the system. 1. Make a general inspection of the HPU. Ensure that all cooling water valves are open. Ensure the Emergency Stop button is released. 2. If not already displayed, press the Setup button to display the Setup screen. Once on the Setup page press the Setup button again to display the Service screen. Once on the Service screen press the PLC Network button to display the PLC Network screen. 3. Verify that the Control Source button displays Ethernet. If the button displays DIO press the button to toggle the HPU into Ethernet source control. 4. Verify that HPU address is appropriately numbered. 5. Press the Back button to return to the Service screen. Once on the Service screen press the Back button again to return to the Setup screen. Once on the Setup screen, press the Main button to display the Main screen. 6. Verify that the Remote Operation button is green. If the button is not green, press the button to change it to green (indicating remote mode). Multi-Pump Control Manager Operation 17 Setup Note Perform the following steps on the MPCM Supervisor. 7. If not already displayed, press the Unit button to display the Unit screen. 8. Verify that each HPU in the system is in Remote Ethernet mode and does not have a Comm alarm. Note Each HPU in the system will have to be configured on the Supervisor Setup Screen. See Setup section for more information. Setup 1. From Supervisor HMI, enter MPCM Supervisor software if not already displayed. 2. Select desired language and press Main Display. 3. From the Main screen press Setup to go to the Supervisor Setup screen 4. For each HPU Platform in the system, select the model of the HPU. A. Press down on the type of HPU, and toggle up or down using the up or down arrows until the correct model is displayed. B. Press OK to select model. 5. Set System Transducers by pressing each associated button to toggle between Sensor Present and Sensor Not Present 6. Set System Units by pressing each associated button to toggle between Metric and English Units. 7. Set System Design Pressure by pressing on associated value button and toggling up or down using the up or down arrows until the correct System Design Pressure is displayed. Press OK to select System Design Pressure. 8. If flow meters are present on each HPU and the associated System Transducer button for HPU Flow Sensors has been toggled to Present, ROD settings will appear. Adjust each setting following the steps below. A. Press the associated value button to display the keypad. B. With the keypad displayed, use the number keys to set the desired flow level. C. Press Enter to set the value and return to the Setup screen. 9. Press the Status button to display the Status screen. 18 Operation A. Enter a name in the chain for each External E-Stop chain present that has indicate compatibility. B. To display the keypad, press the pushbutton for the associated chain. C. Enter in the name for the external e-stop chain. D. Press Enter to accept the name and return to the Status screen Multi-Pump Control Manager Startup and Main Screen Startup and Main Screen Note The following screen images may be from the 4 or 8 HPU version of the HMI software. Your actual display may vary slightly. Features that only exist in the 8 HPU version of the software will be listed as such. The Startup screen is displayed initially when the MPCM is powered up. The Main screen is displayed after you select the language. The push button/ indicators on the right are used to select the various screens. Multi-Pump Control Manager Operation 19 System System The System screen provides an overview of the status of the entire hydraulic system. The RUN and PRESSURE buttons control application of hydraulic pressure to the system (not individual units). The following table describes the controls and indicators of the System panel. 20 Operation Multi-Pump Control Manager System Item Name Description 1 System gauges: Flow/Pressure/ Temperature System gauges. The parameters of these gauges are determined by settings on the MPCM Setup screen. Flow - LPM or GPM. Gauge full scale is determined by the total number of modules present. Green range is determined by the total number of modules running in the system. Gauge reading is the current flow if a flow meter is present on all HPU(s). If a flow meter is not present, the gauge reading is the flow demand in the Auto mode. If flow meters are not present and the system is being operated in manual mode, gauge will read zero. Pressure (optional)- MPa or PSI. Full scale reading is determined by values set on the Setup screen. Gauge is not shown if sensor is not present and enabled. Temperature (optional)- °C or °F. Full scale reading is determined by values set on the Setup screen. Gauge is not shown if sensor is not present and enabled. Red/green/yellow ranges are normalized based on system setup. 2 HPU gauges: Flow (optional) Flow - LPM or GPM. Gauge full scale is determined by the number of modules present on that HPU. Green gauge range is determined by the number of modules running on that HPU. Gauge is configured in the Setup page on the HPU. Gauge is not shown if flow meter is not present and enabled. 3 HPU gauges: Pressure/ Temperature/Level Pressure - MPa or PSI. Gauge reading is determined by HPU’s sensor. Temperature - °C or °F. Gauge reading is determined by HPU’s sensor. Red/green/yellow ranges are normalized based on HPU setup. Level - status bar. Colored area indicates fluid level relative to full capacity (in eights) which is represented by the overall bar: flashing red - 0/8 yellow - 1/8 green - 2/8 to 7/8 flashing red - 8/8 Multi-Pump Control Manager Operation 21 System Item Name Description 4 Module indicators Color scheme for the module icons is: 5 Run/Pressure switch • Dashed outline - not present • Gray with black border - present but not enabled • Gray with green border - present and enabled • Green flashing - running in low pressure • Green solid - running in high pressure • Red - module fault: sequence or overload Run O/I: The O (red) switch stops all HPUs. The I (green) switch starts all enabled HPU modules in low pressure. In Auto, Run starts present modules with lowest hours to meet flow demand. Pressure I/II: The I (yellow) switch will cause all HPU modules running in high pressure to return to low pressure. The II (green) switch changes all HPU modules running in low pressure to high pressure. 6, 7 System background Gray - no faults or alarms HPU background Red - fault Yellow - alarm Note that all HPU alarms will cause a system alarm, but not all HPU faults will cause a system fault. Refer to the HPU manual for additional information. 8 Auto Push button/Indicator. Change between manual mode and auto mode. Auto mode will start the modules with the lowest hours first until the demand is satisfied. Auto - gray: Indicates the system is in manual mode. Auto- green: Indicates the system is in auto mode. When using the auto mode, you need to set the flow demand. Push the associated value pushbutton below the Flow Demand title to display the keypad. With the keypad displayed, use the number keys to set the desired flow level and then press Enter to set the value and return to the Main screen. 9 ROD (Run On Demand) (optional) Pushbutton/Indicator. Used to automatically control pump operation as system demand changes. The ROD button is only shown when in auto mode. ROD - gray: Indicates Run On Demand is not enabled. ROD- green: Indicates Run On Demand is enabled. 22 Operation Multi-Pump Control Manager Unit Unit The Unit screen displays the HPU operational status. All available HPUs will be displayed in individual panes. Shown below is an example. The following table describes the controls and indicators of the Unit panes. Multi-Pump Control Manager Operation 23 Unit Item Name Description 1 Faulted/Ready/Running/High Pressure/Alarm/Overtemp Bypass Indicator. Indicates the various states of the HPU. Faulted - red: Indicates when an interlock has occurred and the HPU has been shut down. Possible faults include E-Stop, watchdog timer, low level and high temperature. Ready - green: Indicates the interlocks are cleared and the HPU is ready to start. Running - green: Indicates the HPU is running in low pressure. High Pressure - green: Indicates at least one pump motor is running in high pressure. Alarm - yellow: Indicates a filter is dirty and needs attention or hydraulic fluid temperature alarm (user set) has been activated. A module fault will also activate an alarm. Overtemp Bypass - yellow: Indicates an overtemperature interlock has occurred and the HPU has been put into a bypass mode to circulate hydraulic fluid through the heat exchanger. Enable Module - blue: Indicates that no modules are enabled. It alerts you to enable one or more modules before the HPU can be started. 2 Module #n Enabled Pushbutton/Indicator. Used to enable and disable the available pump modules. Pressing the button alternates between the two states. Enable Module #N - gray: Indicates the pump module is disabled and cannot be started. Module #N Enabled - green frame: Indicates the pump module is enabled and can be started. Module #N Enabled - flashing green button: Indicates the pump module is running in low pressure. Module #N Enabled - solid green: Indicates the pump module is running in high pressure. Fault - red: lights when the module has an overload or a contactor sequence fault. 24 Operation Multi-Pump Control Manager Unit Item Name Description 3 Run/Stop/Bypass Pushbutton/Indicator. Pushbutton used to start and stop the HPU. Run - gray. black letters: In this state, press to start the HPU. Stop - gray, red letters: In this state, press to stop the HPU. Bypass - blue, white letters: In this state, press to start the HPU in bypass mode. The Faulted state will turn to Overtemp Bypass. Bypass mode only occurs during an overtemperature condition and allows the HPU to run in low pressure to cool the hydraulic fluid. An internal timer allow the bypass mode to run for five minutes. It might be necessary to repeat activating the bypasss mode several times before fluid temperature is within an acceptable range, In remote operation, the run and bypass buttons are disabled. 4 High Pressure Pushbutton/Indicator. Used to put the HPU in high pressure or return to running; pushbutton acts as a toggle between the two modes. High Pressure - gray: indicates the HPU is not in high pressure. High Pressure - green: Directs the HPU to sequence to high pressure. When the HPU is in high pressure it will be indicated on the main display. In remote operation, the High Pressure button is disabled. 5 Local/Remote DIO/Remote ENET Indicators. Used to indicate which method is being used to control the HPU. Note 6 Auto The unit must be in Remote ENET to operate with the MPCM. This can only be changed at the HPU. Pushbutton/Indicator. Change between manual mode and auto mode. Auto mode will start the modules with the lowest hours first until the demand is satisfied. Auto - gray: Indicates the HPU is in manual mode. Auto- green: Indicates the HPU is in auto mode. When using the auto mode, you need to set the flow demand. Push the associated value pushbutton below the Flow Demand title to display the keypad. With the keypad displayed, use the number keys to set the desired flow level and then press Enter to set the value and return to the Main screen. 7 ROD (Run On Demand) (optional) Pushbutton/Indicator. Used to automatically control pump operation as system demand changes. The ROD button is only shown when in auto mode. ROD - gray: Indicates Run On Demand is not enabled. ROD- green: Indicates Run On Demand is enabled. Multi-Pump Control Manager Operation 25 Unit Item Name Description 8 Unit Hours Indicator/Display: Indicates total running time of the HPU. 9 Oil Pressure Indicator/Display: Indicates output pressure of the HPU. 10 Oil Temperature Indicator/Display: Indicates the temperature of the hydraulic fluid in the reservoir. 11 Oil Level Indicator/Display: Displays the level of the hydraulic fluid in the reservoir in 1/8 increments. The level is relative to the usable oil volume. Note that the oil level switch, which controls the low level interlock, can be set at a level higher than the oil level sensor. Values will match when the oil level switch is set at its lowest setting. 12 Oil Flow (optional) Indicator/Display: Displays the total hydraulic fluid flow from all running pumps. Requires that the flow meter and ROD are present and enabled. 26 Operation Multi-Pump Control Manager Status Screen Status Screen The Status screen is displayed by pressing the Status button on the Main screen. The following table describes the pushbuttons and indicators on the Status screen. Item Name Description 1 Indicator. Used to indicate whether the HPU’s safety relay is tripped. E- Stop E-Stop - gray - OK: Indicates the HPU’s safety relay has not tripped. E-Stop - red - Fault: Indicates the HPU’s safety relay has tripped. The cause of a safety relay trip is either an external E-stop Button or the HPU watchdog timer (if the watchdog timer is also red). E-Stop Button - red - Fault: Indicates the HPU’s safety relay has tripped. The cause of a safety relay trip is the E-Stop Button on the HPU. 2 Watchdog Indicator. Used to indicate the status of the watchdog timer. Watchdog - gray - OK: Indicates the PLC that controls the HPU is operating normally. Watchdog - red - fault: Indicates there is a problem with the hardware watchdog timer and the PLC is not operating correctly. A watchdog fault cause the HPU to shut down. Multi-Pump Control Manager Operation 27 Status Screen Item Name Description 3 Indicator. Used to indicate if the hydraulic fluid level is within acceptable limits. Oil Level Oil Level - gray - OK: Indicates the hydraulic fluid level is within acceptable limits. Oil Level Fault - red: Indicates the hydraulic fluid level is not within acceptable limits and an interlock is active. 4 Oil Temp Indicator. Used to indicate if the hydraulic fluid temperature is within acceptable limits. Oil Temp - gray - OK: Indicates the hydraulic fluid temperature is within acceptable limits. Oil Temp - yellow - alarm: Indicates that the hydraulic fluid temperature has exceeded the user-configured alarm value. Oil Temp - red - Fault: Indicates the hydraulic fluid temperature is not within acceptable limits and an interlock is active. 5 Return Filter Indicator. Used to indicate if the return filter is within acceptable limits. Return Filter - gray - OK: Indicates the contamination in the return filter is within acceptable limits. Return Filter - yellow - alert: Indicates the contamination in the return filter is not within acceptable limits. This state will not generate an active interlock, but alerts you that the filter requires maintenance. The HPU cannot be started with an active return filter alert. 6 Pressure Filter (optional) Indicator. Used to indicate if the pressure filter is within acceptable limits. Press Filter - gray - OK: Indicates the contamination in the pressure filter is within acceptable limits. Press Filter - yellow - alert: Indicates the contamination in the pressure filter is not within acceptable limits. This state will not generate an active interlock, but alerts you that the filter requires maintenance. The HPU cannot be started with an active pressure filter alert. 7 Module #N Indicator. Used as an identifier for the Status and Hours parameters. Module - gray: Label. #N - gray: #1 is associated with pump module 1. #2 is associated with pump module 2, and so forth. 28 Operation Multi-Pump Control Manager Status Screen Item Name Description 8 Indicator: Indicates the state of the associated module. Status Status - gray: Label. Not Present - light gray: Indicates the module is not present. Ready- green: Indicates the module is present but is not enabled. Enabled - green: Indicates the module is enabled and is ready to into a run condition (replaces READY). Running Low- green: Indicates the associated pump module is running in low pressure. High Pressure - green: Indicates the associated pump module is running in high pressure. Overload - red: Indicates an overload condition exists and a fault is active for the associated module Sequence - red: Indicates that the PLC commanded the motor contactor to close, but the contactor did not close after a 10 second time period and a fault is active. 9 Hours Indicator: Indicates the running time in hours of the associated module. Hours - gray: Label. Value - gray: The number of total hours the associated module has been running. 10 Mute Pushbutton: Allow you to mute the light buzzer if a fault or alarm activates. 11 Stop Relay Indicator Indicates whether the MPCM's safety relay is tripped. E-Stop Relay - gray - OK: indicates the MPCM's safety relay has not tripped. E-Stop Relay - red - Fault: Indicates that the MPCM's safety relay has tripped. The cause of a safety relay trip is either an External E-Stop Button, an HPU E-Stop Button, or an HPU Watchdog timer. 12 HMI E-Stop Indicator Indicates whether the HMI E-Stop Button has been pressed. HMI E-Stop - gray - OK: Indicates that the HMI E-Stop button has not been pressed and is in the reset (closed) state. HMI E-Stop - red - Fault: Indicates that the HMI E-Stop Button has been pressed and is in the open state. 13 External E-Stops Pushbutton Indicator Indicates whether an external E-Stop chain has been pressed. User defined text. Text - gray - OK: Specific external e-stop chain does not have a button that has been pressed and is in the reset (closed state). Text - red - Fault: Indicates that the specific external e-stop chain has an e-stop button that has been pressed, and is in the open state. Multi-Pump Control Manager Operation 29 Status Screen Item Name Description 14 Indicates whether the user(s) are demanding a total flow demand that is within the maximum capacity of the system. Flow Demand Indicator Flow Demand - gray - OK: Indicates that the Total Flow Demand is within the maximum capacity of the system. Flow Demand - yellow - Alarm: Indicates that the Total Flow Demand is above the maximum flow capacity of the system. 15 PLC Comm Indicator Indicates whether the Supervisor PC is able to communicate with the PLC. PLC Comm - gray - OK: Supervisor PC is communicating with the PLC. PLC Comm - Alarm: Indicates that the Supervisor PC has lost communication with the PLC. The PLC will continue to operate in the last commanded state until communication is regained. 16 HPU # Comm Indicator Indicates whether the PLC is able to communicate with the HPU. HPU # Comm - gray - OK: PLC is communicating with the HPU. HPU # Comm - Alarm: Indicated that the PLC has lost communication with the HPU. The HPU will continue to operate in the last commanded state until communication is regained. 17 Status 1-4 Pushbutton (8 HPU version only) Displays the status of Units 1-4 Status 1-4 - black - Status of units 1-4 are being displayed. Status 1-4 - gray - Status of units 5-8 are being displayed. 18 30 Status 5-8 Pushbutton (8 HPU version only) Operation Displays the status of Units 5-8 Status 5-8 - black - Status of units 5-8 are being displayed. Status 5-8 - gray - Status of units 1-4 are being displayed. Multi-Pump Control Manager Setup Setup On the Supervisor HMI, press the Setup button to display the System Setup screen. The following table describes the pushbuttons and indicators on the Setup screen. Item Name Description 1 HPU Platform Indicator. Displays the MTS model number of the HPU. 2 System Transducers Indicators. Used to indicate the presence of various sensors. Sensor not present - gray. Sensor present - black. 3 System Units Pushbutton/Indicator: Used to select the units for display. Push to alternate between Metric and English units. Pressure Display in PSI, °F, GPM- gray. Pressure Display in MPa, °C, LPM - black. 4 System Design Pressure Multi-Pump Control Manager Indicator. Displays the system hydraulic pressure: 21 MPa (3000 psi), 27.5 MPa (4000 psi), or 34.0 MPa (5000 psi). Operation 31 Station Item Name Description 5 Serial Number, HMI Software Part Number, PLC Software Part Number Information fields. 6 System ROD Setup (flow sensor must be present and enabled) These pushbutton/indicators [Minimum Flow, Flow Buffer, On Delay (sec), and Off Delay (sec)] allow you to set up the Run On Demand parameters. Refer to “Setting Up System Run On Demand (ROD)” on page 35 and “Run On Demand Detailed Example” on page 36 for a detailed description. Station The Station Flow Manager screen allows you to control the flow demand inputs. Item 32 Operation Description 1 Display. Clicking this field shows an alpha-numeric keypad that lets you enter a name for the station. 2 Pushbutton/Indicator. Used to turn on/off the associated channel. Gray = off. Green = on. Green with hash marks = the channel is controlled by DIO. These only function with the system in the Auto mode. Multi-Pump Control Manager Operating the HPU Locally or Remotely Item Description 3 Clicking this field brings up a numeric keypad that lets you enter the flow demand requirement for the associated channel. 4 Total Flow Demand indicator. This displays the total demand as defined by the Flow Demand entries (item 3) plus the flow demand available from the System screen, This indicator turns yellow if the flow demand exceeds total capacity. Refer to “Auto,” on page 22. Operating the HPU Locally or Remotely The HPU can be operated locally using the controls on the user interface panel or remotely using your Supervisor HMI. Note Local operation The BCI safety relay needs to be in the "go" state or not tripped. If the BCI does not have power and the HPU is connected to the BCI then the HPU cannot be run locally. 1. Make a general inspection of the HPU. Ensure that all cooling water valves are open. Ensure the Emergency Stop button is released. 2. If not already displayed, press the Status button to display the Status screen. 3. Verify that Unit does not have any faults or alarms. If a fault or alarm exists press the Reset button to attempt to reset. If unit does not reset consult HPU manual for further information. If not already displayed, press the Main button to display the Main screen. 4. Verify that the Remote Operation button is gray. If the button is green, press the button to change it to gray (indicating local mode). 5. Verify that at least one pump is enabled. Enable additional pumps as necessary. 6. Press Run to start the pumps. The pumps start sequentially to reduce inrush current amplitude. Each pump starts in low pressure mode. 7. Check the HPU for leaks and unusual sounds. Stop the HPU immediately if leaks or unusual sounds are noted. Determine the cause and fix the problem before restarting the HPU. 8. Press High Pressure to turn on high hydraulic pressure. Note If the HPU generates an interlock during operation (such as low fluid level or high temperature), the HPU will stop. Once the cause has been corrected, press the Reset button before restarting. 9. Run the HPU for about 30 minutes or until the hydraulic fluid is up to operating temperature [typically 43°C to 49°C (110°F to 120°F)] before using your test system. 10. When in high pressure mode, press the High Pressure button to return to low pressure mode. 11. To stop the HPU, press the Stop button. Multi-Pump Control Manager Operation 33 How to Clean the MPCM Remote operation Note Perform the following steps on the MPCM Supervisor. 1. Configure each HPU according to the “Set HPU to Remote Operation for use with the MPCM Supervisor” section. 2. If not already displayed, press the Status button to display the Status screen. 3. Verify that each Unit and System does not have any faults or alarms. If a fault or alarm exists press the Reset button to attempt to reset the fault or alarm. If unit does not reset consult HPU manual for further information. 4. Press the Unit button to display the Unit screen 5. Verify that the Remote Operation button is green on each HPU that is to be run. If the button is not green on a specific HPU, revisit "Set HPU to Remote Operation for use with the MPCM Supervisor" section to insure that the HPU has been put into remote mode. 6. Verify that at least one pump is enabled. Enable additional pumps as necessary. 7. Start each HPU in low pressure by pressing Run for each HPU that is to be run. 8. Check the HPU for leaks and unusual sounds. Stop the HPU immediately if leaks or unusual sounds are noted. Determine the cause and fix the problem before restarting the HPU. 9. Select High Pressure for each HPU that is to be at High Pressure. Note There are other methods for running the system. Refer to the System and Unit screen information, or the videos supplied on the CD. How to Clean the MPCM Remove dust and dirt from the chassis with an appropriate cleaner for electronics. 34 Operation Multi-Pump Control Manager Setting Up System Run On Demand (ROD) Appendix Contents Setting Up System Run On Demand (ROD) Run On Demand Detailed Example 35 36 Setting Up System Run On Demand (ROD) The ROD option automatically starts or stops pumps to meet the hydraulic flow demand from the system. The PLC monitors the hydraulic fluid flow. When the flow changes beyond a trigger point for a set period of time, one or more of the pumps are turned on or off. Note Flow meters must be present on all HPU(s) within the system for ROD to operate properly. Refer to the previous table for a description of the controls referenced in the following procedure. 1. On each HPU in the system, from the current screen, press the AUTO Setup button. When the Auto Setup screen displays, make sure the Flow Meter indicator is in the Flow Meter Present state (blue-green). 2. On each HPU in the system, check the Rated Flow Per Module. If necessary, press the associated value pushbutton to change the flow value. This value should only require change if the HPU is provided with pump modules that have a different full flow rating. Refer to the HPU manual for further information. 3. On the Supervisor HMI, from the current screen, press the Main button and then the Setup button. When the Setup screen displays. make sure the Flow Meter indicator is in the HPU Flow Sensors Present state (black). 4. Set the Minimum Flow. If necessary, press the associated value pushbutton to display the numeric keypad and change the value. Press Enter to set the value and return to the Auto Setup screen. The range shown on the numeric keypad depends on the number of pump modules present. 5. Set the Flow Buffer. If necessary, press the associated value pushbutton to display the numeric keypad and change the value. Press Enter to set the value and return to the Auto Setup screen. The range shown on the numeric keypad depends on the number of pump modules present. 6. Check the On Delay. If necessary, press the associated value pushbutton to change the delay time. Use the numeric keypad described above to increase or decrease the delay. Multi-Pump Control Manager Appendix 35 Run On Demand Detailed Example 7. Check the Off Delay. If necessary, press the associated value pushbutton to change the delay time. Use the numeric keypad described above to increase or decrease the delay. 8. Press the System button to return to the System screen. 9. Press the Auto button to enable Auto. The button will turn green. 10. Press the ROD button to enable the run on demand option. The button will turn green. 11. Press I (green) to start the HPU in low pressure. 12. Press II (green) to select high pressure mode. The number of pumps running will be determined by the setting on the Setup screen. 13. Pressing the O (red) button will turn off the HPU(s) that are running. Run On Demand Detailed Example Run On Demand (ROD) is a system that monitors the output flow of the Hydraulic Power Units (HPUs) and turns on and off pumping modules as needed to best meet the users demands. The parameters for ROD that need to be set by the user include: • On Delay: the period of time that must pass where the criteria are met or exceeded before the next module(s) will be turned on. • Off Delay: the period of time that must pass where the criteria are met or exceeded before the next module(s) will be turned off. • Module Flow: the flow capability of a single pumping module within the HPU (see table). This must be confirmed at each HPU. • Minimum Flow: the minimum flow capacity that should be available when the system is on. • Flow Buffer: the minimum flow that should be available beyond the actual current flow. Flow is added for each HPU to compensate for the circulation pump within each running HPU. For reference in setting up run on demand, the following table shows the flow capacity of the available pump modules. Pressure Frequency 50 Hz 36 Appendix 21 MPa 27.5 MPa 34.4 MPa 3000 psi 4000 psi 5000 psi 100 lpm 75 lpm 50 lpm 26 gpm 20 gpm 13 gpm Multi-Pump Control Manager Run On Demand Detailed Example 60 Hz 113 lpm 85 lpm 61 lpm 30 gpm 22 gpm 16 gpm An example is shown below. In the example Module Flow is set at 30 gpm, Minimum Flow is set at 10 gpm, Flow Buffer is set at 4 gpm (which means the total actual buffer is 10 gpm), Δton represents the on delay, and Δtoff represents off delay. The system starts out with one module running to create 30 gpm of available flow. This satisfies both the Minimum Flow requirement (10 gpm) and the Flow Buffer requirement (10 gpm). The demand rises and eventually hits 20 gpm. At this point the on delay is started because the 20 gpm of actual flow and 10 gpm of Flow Buffer meet or exceed the available 30 gpm. Because the flow stays above 20 gpm for the length of time Δton, another pump module is started and available flow goes to 60 gpm. Then a spike occurs which exceeds the available flow but because the duration of the spike is less than Δton, another pump module is not started. Flow then continues to increase but never exceeding the next trigger point of 50 gpm for a duration of Δton. Then flow drops off below 20 gpm. Because the flow does not stay below 20 gpm for the period of time Δtoff, no pump modules are turned off. Finally the flow tapers off and flow is below 20 gpm for the time Δtoff and the second pump module is turned off. Flow buffer Flow buffer Multi-Pump Control Manager Appendix 37 Run On Demand Detailed Example 38 Appendix Multi-Pump Control Manager m MTS Systems Corporation 14000 Technology Drive Eden Prairie, Minnesota 55344-2290 USA Toll Free Phone: 800-328-2255 (within the U.S. or Canada) Phone: 952-937-4000 (outside the U.S. or Canada) Fax: 952-937-4515 E-mail: info@mts.com http://www.mts.com ISO 9001 Certified QMS