Engineering Encyclopedia Saudi Aramco DeskTop Standards Designing Low Voltage Non-Motor Industrial Feeder Circuits Note: The source of the technical material in this volume is the Professional Engineering Development Program (PEDP) of Engineering Services. Warning: The material contained in this document was developed for Saudi Aramco and is intended for the exclusive use of Saudi Aramco’s employees. Any material contained in this document which is not already in the public domain may not be copied, reproduced, sold, given, or disclosed to third parties, or otherwise used in whole, or in part, without the written permission of the Vice President, Engineering Services, Saudi Aramco. Chapter : Electrical File Reference: EEX10301 For additional information on this subject, contact Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits CONTENTS PAGES CALCULATING AMPACITY RATINGS OF FEEDERS CONDUCTORS................ 1 Factors Affecting Ampacity Ratings ........................................................................ 1 Factors Affecting Continuous Current Ratings ........................................................ 2 Busway................................................................................................................... 14 CALCULATING SHORT CIRCUIT RATINGS OF FEEDER CONDUCTORS........................................................................................................... 16 Introduction ............................................................................................................ 16 Factors Affecting Conductor Short Circuit Ratings ............................................... 16 Conductor Temperature Rise.................................................................................. 20 Protective Device Clearing Times.......................................................................... 24 CALCULATING VOLTAGE DROPS OF A FEEDER CONDUCTOR CIRCUIT...................................................................................................................... 27 Introduction ............................................................................................................ 27 Factors Affecting Voltage Drop Calculations ........................................................ 28 Effects of Resistance Variables on Voltage Drop .................................................. 31 Effects of Reactance Variables on Voltage Drop ................................................... 33 Voltage Drop Limits............................................................................................... 34 Approximation Formula......................................................................................... 35 SELECTING FEEDER PROTECTIVE DEVICES...................................................... 38 Types of Protective Devices................................................................................... 38 Low Voltage Power Circuit Breaker (LVPCB) Ratings......................................... 43 Protective Device Time/Current (T/C) Characteristics........................................... 45 Factors Affecting Selection .................................................................................... 60 SELECTING FEEDER CONDUCTOR RACEWAY SIZES ...................................... 63 Types of Raceways................................................................................................. 63 Factors Affecting Raceway Size ............................................................................ 65 WORK AID 1: RESOURCES USED TO DESIGN A LOW VOLTAGE NON-MOTOR FEEDER CIRCUIT............................................................................. 68 Work Aid 1A: 1993 National Electric Code Handbook......................................... 68 Work Aid 1B: ANSI/IEEE Standard 141-1986 (Red Book) .................................. 68 Work Aid 1C: SAES-P-114 ................................................................................... 68 Saudi Aramco DeskTop Standards Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits Work Aid 1D: SAES-P-100 ................................................................................... 70 Work Aid 1E: SAES-P-104.................................................................................... 71 Work Aid 1F: Applicable Procedures for Calculating Ampacity Ratings of Feeder Conductors ............................................................................................. 73 Work Aid 1G: Applicable Procedures for Calculating the Short Circuit Rating of a Feeder Conductor ................................................................................ 75 Work Aid 1H: Applicable Procedures for Calculating the Voltage Drop of a Feeder Conductor............................................................................................ 78 Work Aid 1I: Applicable Procedures for Selecting a Feeder Conductor Protective Device ................................................................................................... 79 Work Aid 1J: Applicable Procedures for Selecting a Feeder Conductor Raceway Size ......................................................................................................... 80 Work Aid 1K: Feeder Circuit Design Flow Chart.................................................. 81 GLOSSARY................................................................................................................. 82 Saudi Aramco DeskTop Standards Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits CALCULATING AMPACITY RATINGS OF FEEDERS CONDUCTORS Note: Work Aid 1F has been developed to teach the Participant procedures to calculate feeder conductor ampacity ratings. Factors Affecting Ampacity Ratings Although there are many factors that affect the ampacity ratings of conductors, this Module will restrict the discussion to the following three factors: • • • Continuous Current Short Circuit Current Voltage Drop Continuous Current The National Electric Code (NEC) defines the continuous current rating of a conductor as ampacity, which means “the current in amperes that a conductor can carry continuously under the conditions of use without exceeding its temperature rating”. The NEC recognizes that the maximum continuous current carrying capability of a conductor varies with the different conditions of use and the insulation temperature rating of the conductor itself. For example, ambient temperature is a condition of use. A 75°C conductor installed outdoors in Saudi Arabia would have very little ampacity capability compared to the same temperature-rated conductor installed indoors in an air-conditioned space. Another example of condition of use is the number of conductors that are installed in a raceway (conduit). Short Circuit Current The short circuit current rating of a conductor is the maximum current that a conductor can carry, for a specific and very short time interval, without reaching temperatures that will permanently damage the conductor insulation. Note: The next Information Sheet will discuss in detail the calculation of the short circuit ratings of conductors. Voltage Drop Because most electrical equipment is voltage-sensitive, it is very important to have within equipment and design standard tolerances, the proper voltage at the terminals that are serving the equipment. Any excessive voltage drop could possibly damage the equipment and impair its proper operation. Note: Calculating the voltage drop of feeder conductors will be discussed later in this Module. Saudi Aramco DeskTop Standards 1 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits Factors Affecting Continuous Current Ratings Conductor Material Types The resistivity of a conductor, represented by the Greek letter rho (ρ), is defined as the resistance, in ohms (Ω), of the material for a specific sample of given cross-sectional area (A) and with given length (L). The most commonly used dimension for ρ is circular-mil-foot. Resistance (R) is directly proportional to ρ, and it is represented by the following equation: • • R = ρL/A where: R ρ L A = = = = dc resistance of the conductor in ohms (Ω) resistivity of the conductor in Ω-cmil/ft length of the conductor in feet (ft) cross-sectional area of the conductor (cmil) in circular mils The relationship should be very obvious that, if the resistivity (ρ) of the material is greater (Figure 1), the resistance (R) of the material also increases. Type of Material Resisitivity at 200C Ω-cmil/ft silver 9.8 copper 10.4 aluminum 17.0 tungsten 33.0 nickel 50.0 iron 60.0 nichrome 650.0 Figure 1. Resistivity Table Saudi Aramco DeskTop Standards 2 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits Aluminum is widely used as a transmission-line conductor, especially on high-voltage lines. Compared to a copper conductor of the same physical size, the aluminum wire only has 60 percent of the conductivity, only 45 percent of the tensile strength, and only 33 percent of the weight. An aluminum wire, to have the same conductivity as copper, would have to be 1.64 (100/61) times larger than the copper conductor. For the same conductor current carrying capacity, an aluminum wire would have approximately 75 percent of the tensile strength and 55 percent of the weight of a copper wire. This lighter weight makes aluminum conductors the preferred choice for longer spans; fewer towers, crossarms, insulators, etc., are required for the spans. Note: Although permitted by the NEC, SAES-P-104 does not permit the use of aluminum conductors for wires and cables in buildings, direct burial cables, overhead cable feeders, etc. ACSR is permitted for overhead distribution lines only. This section on aluminum is presented for general information purposes only. When an aluminum conductor is stranded, the center strand is most often made of steel, which provides greater strength. ACSR is especially suited for long spans. Figure 2 shows the comparison (cross-sectional area) between a copper, an aluminum, and an ACSR conductor, each of which has equal current-carrying capacity. Figure 2. Conductor Type Comparison Saudi Aramco DeskTop Standards 3 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits Copper (Annealed) is the most generally used building conductor in insulated wires and cables. When covered with rubber insulation, the copper is coated with tin or lead alloy for its own protection, as well as for protection of the insulation, because both copper and insulation contain substances that attack each other. Copper is also quite often used in overhead distribution line conductors. Three kinds of copper are used: hard-drawn copper, medium hard-drawn copper, and annealed copper, which is often called “soft-drawn” copper. Copper wire is hard-drawn as it comes from the drawing die. To obtain soft or annealed copper wire, the hard-drawn wire is heated to a very high temperature (red heat) to soften it. Most utilities use medium hard-drawn copper for distribution lines, especially in wire sizes smaller than No. 2 AWG. Stranded Versus Solid Conductors - Conductors are classified as either solid or stranded and by size, ranging from very small (AWG No. 18) to very large (2000 kcmil) sizes. As the name implies, a solid conductor is a single strand conductor with a solid circular cross section. Size AWG No. 1 is approximately the largest solid conductor that is manufactured. Anything larger would not be flexible enough to run in ducts, conduits, etc. Large solid conductors also are easily damaged by bending. Stranded conductors are a group of solid wires (single strands) made into a single conductor. The strands of the conductor are arranged in concentric layers around a single core. Size AWG No. 1/0 and larger are the usual sizes for stranded wire, although, because of its flexibility, it is available and readily used in smaller sizes as well. The smallest number of wires in a stranded conductor is three, and this number increases to a very large number for special applications. Note: SAES-P-104 requires the use of Class B or Class C stranding for all power conductors for normal power requirements. Classification of stranded cables for industrial applications are as follows: • Class B - This class of stranding is used for industrial cables for 600, 5000, and 15,000 volt power systems. The number of strands vary from 7 to 127, depending on the wire size. • Class C - This class of stranding is used when there is a need for additional flexibility. The number of strands varies from 19 to 169. Also, the diameter of each strand is smaller than it is in wires of the same size that have Class B stranding. The combination of more strands and smaller diameter strands allows for more flexibility. • Classes G and H - These classes of stranding allow for extremely flexible cables. Classes G and H also are called rope or bunch stranding. Class G uses 133 strands, and Class H uses 259 strands. Welding cable is an example of Class G and Class H cables. Saudi Aramco DeskTop Standards 4 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits Saudi Aramco DeskTop Standards 5 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits Figure 3 shows various strand configuration for cables. Figure 3. Stranded Cable Configuration Saudi Aramco DeskTop Standards 6 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits Conductor Sizes American Wire Gage (AWG) System - Wire sizes are expressed in numbers. Because there are different numbering methods, it is imperative to always state which numbering method is being used when stating wire sizes. In America, the most often used wire gage is Browne and Sharpe, which is also called the American Wire Gage (AWG). Wire sizes range from No. 40 AWG (very small) to 0000 AWG or 4/0 AWG (pronounced four-aught). Larger wires greater than No. 4/0 AWG are sized in circular mils (cmil) or kilo-circular mils (kcmil), where 1 kcmil equals 1000 cmils. The previous term for kcmil was MCM, which is now obsolete. One cmil equals the diameter of the wire in mils (1/1000 of an inch) squared. As the wire size diameter and cross-sectional area (A) increases, its resistance decreases, which is once again expressed by the following formula: • R = ρL/A International System (SI) - Saudi Aramco specifies the nearest metric wire size to the standard U.S. ICEA NEMA standard sizes (AWG or kcmil). Note: See Work Aid 1, Figure 36. The following formula is presented for informational purposes only: • 1 cmil = 5.067 x 10-4 mm2 = 7.854 x 10-7 in2 Temperatures Operating Temperature - The maximum continuous current carrying capability of a conductor is determined by the temperature at which it is allowed to operate over its lifetime. The type of insulation surrounding the material ultimately determines the operating temperature. The NEC temperature rating classifications are 60°C, 75°C, and 90°C. Note: SAES-P-104 does not permit use of 60°C insulation. If the operating temperature is exceeded for any long periods of time, the insulation ages prematurely, becomes hard and brittle, and eventually leads to early failure. Ambient Temperature - The ambient temperature is defined as the temperature of the medium (air or earth) surrounding the conductor. When the ambient temperature increases, there is less of a temperature differential surrounding the conductor, which means that the heat dissipating rate of the conductor is less. As the ambient temperature increases, the current carrying capability of the conductor must be decreased to prevent the conductor’s operating temperature, which is based on the insulation material, from being exceeded. The NEC ampacity ratings for building wire are based on an ambient temperature of 30°C. SAESP-100 specifies an ambient temperature of 35°C in indoor air-conditioned spaces, whereas SAES-P-104 specifies 30°C in indoor air-conditioned spaces. See Work Aid 1 for other SAES-P-100 and SAES-P-104 listed ambient temperatures. Saudi Aramco DeskTop Standards 7 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits NEC Derating Factors - If the ambient temperature exceeds 30°C, the NEC requires derating of the conductor in accordance with the correction factors listed in NEC Table 310-16 (see Work Aid 1A, Handout 1). Example A: NEC Table 310-16 lists the ampacity rating of a 500 kcmil (240 mm2) 75°C copper conductor at 380 A. What is the ampacity rating of the conductor at 35°C? Answer A: The correction factor listed in the NEC is 0.94. The corrected ampacity is 357 A (.94 x 380). Conductor Insulations Types - The five most common types of insulation are listed as follows: • • • • • Thermosetting compounds, solid dielectric Thermoplastic compounds, solid dielectric Paper-laminated tapes Varnished cloth, laminated tapes Mineral insulation, solid dielectric - granular Current industrial applications use synthetic materials for cable insulation. Their resistance to moisture and ease of handling make synthetic materials popular. These synthetic materials also have excellent electrical and mechanical properties. Synthetic insulations are grouped into either thermoplastic or thermosetting. Thermosetting type cables have little tendency to soften upon reheating, whereas thermoplastic will soften when reheated. Saudi Aramcoapproved insulations for power conductors are the following: • Polyvinyl chloride (PVC) - Thermoplastic Compound This cable is flexible and has excellent electrical properties. PVC cables are used for 600 volt systems. The maximum operating temperature is 60°C. The maximum short-circuit temperature rating is 150°C. PVC cable is available in many different colors, and it usually carries a designation of T or TW. The maximum voltage of PVC cable is 600 volts. Note: Polyvinyl chloride cable is not used on Saudi Aramco installations. • Cross-Linked Synthetic Polymer This cable insulation is also for 600 volt systems, and it is moisture and heat resistant. The maximum operating temperature is 90°C, and the insulation is designated as XHHW. Saudi Aramco DeskTop Standards 8 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits • Ethylene Propylene Rubber (EPR) This type of insulation offers excellent resistance to ozone, heat, and weather. The maximum operating temperature is 90°C. The voltage range of EPR cable is 600 to 69,000 volts. • Silicone Rubber - Thermosetting Compound This insulation system is highly resistant to flame, corona, and ozone, but it has very poor mechanical strength. Silicone rubber insulation has a maximum operating temperature of 125°C with a short circuit temperature rating of 250°C. Silicone rubber cable is used in high temperature areas or fire protection applications only. The voltage range of silicone rubber cable is from 600 to 5000 volts. • Crossed-Linked Polyethylene (XLPE) - Thermosetting Compound This cable has excellent electrical, moisture-resistant, and environmentalresistant properties. Corona affects XLPE type insulation. The maximum operating temperature is 90°C. The maximum short circuit temperature is 250°C. XLPE cable voltages range from 600 to 69,000 volts. Applicable Provisions - NEC Table 310-13 lists the applicable provisions for insulated conductors. For example, certain types of conductors may be used only in dry locations, whereas another type may be used only in wet or damp locations. Some of the conductors may be used in both locations. The applicable provisions ultimately determine the conductor ampacity ratings. For example, a type XHHW conductor is rated for 90°C in dry and damp locations, and for 75°C in wet locations. Example B: What is the ampacity rating of a No. 4/0 AWG, type XHHW copper conductor that is being used in a wet location? Answer B: Because the conductor is being used in a wet location, NEC Table 310-13 (applicable provisions) lists the conductor operating temperature as 75°C. Per NEC Table 310-16, the ampacity rating of a No. 4/0 AWG, type XHHW copper conductor, is 230 A. Number of Conductors The ampacity ratings of conductors, as listed in NEC Table 310-16, are based on no more than three conductors installed in a raceway (conduit) at a given ambient temperature of 30°C. Exceeding the number of conductors (3) requires derating. Saudi Aramco DeskTop Standards 9 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits Current Carrying Conductors - Only conductors that normally carry current are considered as current carrying conductors for determining the number of conductors in a raceway. For example, the equipment grounding conductor (green wire) is not considered a current carrying conductor. On the other hand, in a 3-phase, 4-wire, wye-connected system, the common conductor (neutral) carries approximately the same current as the phase conductors, and is therefore considered to be a current carrying conductor. Note: See Note 10 to NEC Table 310-16 for other examples. Fill Rate and Derating Factors - When the number of current carrying conductors, as explained above, exceeds 3 in a raceway, Note 8 to Article 310-16 requires derating of the conductors. For example, 4 to 6 current carrying conductors in a raceway require that each conductor be derated by 20 percent (.80 reduction factor). Seven to 9 conductors require that each conductor be derated by 30 percent (.70 reduction factor). Note: For a complete listing of the reduction factors, see Note 8 to NEC Table 310-16 (Work Aid 1J, Handout 2). Example C: Determine the ampacity of a 3-phase, 4-wire, feeder conductor that is using 500 kcmil copper conductors, type THHN insulation (90°C), installed in steel conduit, 40°C ambient temperature, and feeding a mercury vapor lighting load. Answer C: Because the ambient temperature exceeds 30°C, the conductors must be derated using the correction factor (0.91) from NEC Table 310-16. Note 10 to NEC Table 310-16 also requires that the neutral conductor be considered as a current carrying conductor for arc discharge (i.e., mercury vapor) lighting. Therefore, the conductors must be derated using the adjustment factor (0.80) for 4 to 6 current carrying conductors in a raceway (Note 8A to NEC Table 310-16). The conductor ampacity is listed in NEC Table 310-16 is 430 A. Therefore, the ampacity rating is 315 A (430 x 0.91 x 0.80). Example D: What is the ampacity rating of 6, type THHW, 75°C, size No. 4/0 AWG copper conductors in a raceway? Assume that the ambient temperature is 30°C. Answer D: Per NEC Table 310-16, the ampacity is 230 A for no more than three conductors in a raceway. Per Note 8 to NEC Table 310-16, the ampacity should be reduced to 80 percent for 6 conductors. Therefore, the ampacity rating is 184 A (.80 x 230). Parallel Conductors - NEC Article 310-4 permits parallel conductors as long as all of the following conductor conditions are met: same length, same conductor material, same insulation type, and the same terminations. Because of the skin effect in ac circuits, the current carrying capability per cmil of conductor area decreases with the size of the conductor. Additionally, it is harder to dissipate the heat within large conductors. It is also more difficult to “pull” a large conductor through raceway. Saudi Aramco DeskTop Standards 10 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits For these reasons, it is often preferable to parallel small conductors rather than to use large conductors. Saudi Aramco DeskTop Standards 11 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits Conductor Terminations Although the NEC specifies the ampacity ratings of conductors, the Underwriters Laboratories, Inc. (UL) approves the use and conditions of the electrical equipment. The termination provisions of the UL-approved equipment are based on 60°C and 75°C terminations (terminals, lugs, etc.). 100 A or Less - NEC Article 110-14 (c) (1) specifies that termination provisions of equipment for circuits rated 100 A or less or marked for sizes No. 14 through No. 1 AWG conductors shall be used with conductors rated for an operating temperature of 60°C. The NEC permits the following two exceptions: • Higher-temperature-rated conductors may be used, provided the ampacity of the conductors is based on the 60°C operating temperature ampacity ratings. • The equipment is listed for the higher-temperature-rated conductors. Greater Than 100 A - NEC Article 110-14 (c) (2) specifies that termination provisions of equipment for circuits rated over 100 A or marked for conductors larger than No. 1 AWG shall be used with conductors rated for an operating temperature of 75°C. The same two exceptions apply for circuits rated more than 100 A, except that the ampacity of the conductors is based on an operating temperature of 75°C. Example E: What is the ampacity rating of a 75°C, type THHW, size No. 4 AWG conductor that is being terminated at a 70 A molded case circuit breaker (MCCB)? Answer E: Because the MCCB is rated at less than 100 A, the ampacity rating of the conductor must be limited to its 60°C rating of 70 A versus its 75°C rating of 85 A. Types of Feeders and Sizing Guidelines Bus Feeders - SAES-P-104 specifies that bus feeders be sized in accordance with the NEC, but that a 20 percent growth factor must be added. However, the size, including the 20 percent growth factor, must not exceed the maximum rating of the bus. SAES-P-104 allows deletion of the growth factor where 2 or more feeders serve the same load bus. Transformer Feeders - SAES-P-104 specifies that feeders shall have an ampacity rating of not less than the full load ratings (fan-cooled ratings if fans are installed) of all connected transformers and all other connected loads. Saudi Aramco DeskTop Standards 12 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits Other Feeders - Although not explicitly specified in SAES-P-104, other feeders should be sized to carry the load in accordance with the NEC. Saudi Aramco DeskTop Standards 13 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits Busway In large commercial and industrial complexes, where high density (ampacity) loads are connected, it is usually not economical to use insulated conductors as feeders. An alternative method is to use a busway, which is a metal enclosure containing factory assembled conductors of copper bars. It is standard industry practice, as well as Saudi Aramco practice, to consider the use of a copper busway whenever the load is greater than or equal to 1000 A. Ampacity Ratings Busways are available in the following three design types: low impedance feeder busway, high impedance feeder busway, and simple plug-in busway (Figure 4). Plug-in busways are available in ampacity ratings ranging from 100 to 3000 A and in short circuit current withstand ratings ranging from 10 to 85 kA. Feeder type busways are available in ampacity ratings ranging from 600 to 5000 A and in short circuit current withstand ratings ranging from 42 to 200 kA. Saudi Aramco DeskTop Standards 14 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits Figure 4. Busway Types Industrial Feeder Uses In industrial applications, feeder busways are almost exclusively used for horizontal runs from the main switchboards to the major power centers located throughout the plant. Busway risers are also often used to distribute power to all floors of multistory buildings. Saudi Aramco DeskTop Standards 15 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits CALCULATING SHORT CIRCUIT RATINGS OF FEEDER CONDUCTORS Note: Work Aid 1G has been developed to teach the Participant procedures to calculate short circuit ratings of feeder conductors. Introduction A cable must be protected from overheating due to excessive short circuit (fault) currents. The fault point may be on a section of the protected cable or on any other part of the electric system. During a phase fault, the I2R losses in the phase conductor elevate first the temperature of the conductor, followed by the insulation materials, protective jacket, raceway, and surroundings. Since the short circuit current should be interrupted either instantaneously or in a very short time by the protective device, the amount of heat transferred from the metallic conductors outward to the insulation and to other materials is very small; therefore, the heat from I2R losses is almost entirely in the conductors. For practical purposes, it is assumed that 100% of the I2R losses is consumed to elevate the conductor temperature. During the period that the short circuit current is flowing, the conductor temperature should not be permitted to rise to the point where it may damage the insulation. Providing cable protection during a short-circuit condition involves, as a minimum, the following factors: • • • • Maximum available short circuit currents. Maximum conductor temperature that will not damage the insulation. Cable conductor size that affects the I2R value and its capacity to contain the heat. Longest time that the fault will exist and the fault current will flow. Factors Affecting Conductor Short Circuit Ratings Operating Temperature Versus Short Circuit Temperature The operating temperature is the initial temperature of the conductor prior to the occurrence of the short circuit. This operating temperature is assumed to be the temperature of the conductor in a 30°C ambient temperature environment and at rated ampacity, which is 60°C, 75°C, or 90°C, as discussed in the previous section of this Information Sheet. The short circuit temperature is the final temperature of the conductor after the short circuit occurs. This short circuit temperature is assumed to be the maximum temperature rise that the conductor can sustain for a specified period of time without damaging the insulation. Saudi Aramco DeskTop Standards 16 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits Figure 5 lists the initial and final temperature ratings for various types of insulation commonly used in industrial applications. The temperature rise is related by the following formula, which will be discussed in detail later in this Information Sheet. • (I/A)2t = 0.0297 log10 [(T2 + 234)/(T1 + 234)] Type of Insulation Continuous (Initial) Temperature Rating T10C Short Circuit (Final) Temperature Rating T20C Rubber 75 200 Cross-Linked Polymer 90 250 125 250 60, 75, 90 150 Paper 85 200 Varnished Cloth 85 200 Silicone Rubber Thermoplastic Figure 5. Conductor Temperature Ratings Operating Speed of Protective Devices The extraordinary temperatures generated under short circuit conditions may damage cables over their entire length if the fault current is not interrupted quickly enough. The upstream protective devices must clear the fault before the damaging temperatures occur. Many engineers select cables and/or protective devices such that the backup protective device could also clear the fault before thermal damage occurs. Cable Impedance Although the cable impedance decreases as the cable size increases, the increased crosssectional area of the cable increases the withstand capability of the cable. For example, a No. 2/0 AWG copper conductor having an impedance of 0.1150 Ω/1000 ft can withstand 30 kA of short circuit current for approximately 4 cycles (≈ .067 sec). Conversely, a 500 kcmil copper conductor having roughly half the impedance (0.0551 Ω/1000 ft) can withstand the same 30 kA of short circuit current for almost 48 cycles (≈ 0.8 sec). The increased diameter of the cable allows the cable to absorb more heat without damaging the insulation. Saudi Aramco DeskTop Standards 17 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits Conductor Insulation Figure 5 listed the maximum conductor temperature ratings. Any prolonged load/ambient temperature combinations that increase the conductor temperature above the continuous (initial) temperature ratings, for example 75°C for a type THWN conductor, will damage the insulation. Short circuits that elevate the conductor temperature above the final temperature, for example 150°C for the type THWN conductor, will also damage the insulation. Short Circuit Current Available (ISCA) It is general industry practice to use the subtransient reactance (X”d) to calculate the RMS symmetrical short circuit current available where instantaneous overcurrent relays (ANSI Device 50) are used to protect cables. And where cables are protected by fuses, cable limiters, or low voltage breakers, it is industry practice to use X”d to calculate the asymmetrical current available. Note: Short circuit currents were discussed in detail in EEX 102. Type of Fault Three-phase faults and line-to-ground faults in a solidly grounded system are typically of such a large magnitude that the protective devices quickly detect and clear the faults instantaneously, and therefore, usually provide adequate protection for the cables. On the other hand, high impedance arcing faults are often persistent and escalate into more serious, high magnitude phase-to-phase faults, resulting in extensive cable damage. Type of System Grounding For solidly grounded systems, although the fault current magnitudes are high, extensive cable damage is usually avoided because of the very quick detection and clearing of faults. Cable damage in low resistance grounded systems is also typically not extensive because the ground fault current magnitudes are small (100 - 1200 A) and are quickly detected and cleared. Because of the very low current magnitudes in high-resistance-grounded systems, cable damage is limited unless the fault is not cleared and another ground fault escalates to a phaseto-phase fault resulting in extensive damage. Line-to-ground faults in ungrounded systems can result in extensive cable insulation damage by the sustained overvoltages rather than by the fault current magnitudes (typically 1 - 10 A). Saudi Aramco DeskTop Standards 18 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits In ungrounded systems, cables should have, as a minimum, 133% or 173% insulation level ratings. Note: Saudi Aramco design standards do not permit use of ungrounded systems. Saudi Aramco DeskTop Standards 19 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits Conductor Temperature Rise Insulation, Material Type, Size On the assumptions that all heat is absorbed by the conductor metal (copper or aluminum) and that there is no heat transmitted from the conductor metal to the insulation, the temperature rise is a function of the conductor size (area in cmils), the magnitude of the short circuit current (ISCA in amperes), and the fault duration (time in sec). These variable are related by the following formula: • (I/A)2t = (k1) log10 [(T2 + k2)/T1 + k2)] • where: I A t T1 = = = = short circuit current (asymmetrical) in amperes (A) conductor cross-sectional area in circular mils (cmils) time of short circuit in seconds (sec) initial conductor temperature in degrees Celsius (°C), as listed by the manufacturer T2 = final conductor temperature in degrees Celsius (°C), after the short circuit, as listed by the manufacturer k1 = 0.0297 for copper = 0.0125 for aluminum k2 = 234 for copper = 228 for aluminum Variables in Formula for Allowable Short Circuit Interrupting Time The initial (T1) and final (T2) conductor temperatures are predetermined on the basis of the continuous current rating and the insulation material. For low voltage thermoplastic conductors specified in Saudi Aramco design standards, T1 will equal 75°C or 90°C and T2 will always equal 150°C (see Figure 5). Because Saudi Aramco design standards do not permit the use of low voltage aluminum conductors, R1 equals 0.0297 and k2 equals 234. The short circuit current (I) used in the formula to plot the cable damage curves is not necessarily the short circuit current available (ISCA) in the event of a fault. The operating time of the protective device must, however, allow the device to clear the fault for all values of fault current in less time than the time (t) calculated in the above equation. Saudi Aramco DeskTop Standards 20 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits Short Circuit Cable Damage Charts Cable damage charts (curves) are often used to ensure that the protective device will clear the fault prior to damaging the conductor. Figure 6 shows an Insulated Cable Engineers Association (ICEA) format for representing cable damage curves, and Figure 7 shows cable damage representative curves used by many coordination engineers. Example F: How quickly must a protective device clear a 30 kA (asymmetrical current) fault to protect a size No. 4/0 AWG copper conductor? Answer F: A No. 4/0 AWG copper conductor can withstand a 30 kA fault for approximately 16 cycles (≈ 0.2667 sec). Example G: A low voltage power circuit breaker (LVPCB), with an instantaneous operating time of .05 sec (≈ 3 cycles), is used to protect a 90°C rated thermoplastic conductor in a circuit where 35 kA of asymmetrical fault current is available. What is the minimum size conductor (cross-sectional area in cmil) that will safely carry the 35 kA for 0.05 sec? Answer G: Rewriting the formula described previously in this Information Sheet yields the following: • A =[(I2t)/(.0297 log10 ((T2 + 234)/(T1 + 234)))]1/2 =[(35000)2 (.05)/(.0297 log10 ((150 +234)/(90+234)))]1/2 =167, 165 cmil • Per NEC Table 8, Chapter 9, a size 3/0 AWG conductor has a crosssectional area of 167,800 cmil. Saudi Aramco DeskTop Standards 21 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits Figure 6. ICEA Cable Damage Curves Saudi Aramco DeskTop Standards 22 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits Figure 7. Cable Damage Curves For Thermoplastic Insulation Saudi Aramco DeskTop Standards (750C - 1500C) 23 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits Protective Device Clearing Times The total clearing time of various types of protective devices depends on the types of circuit breakers (molded case or low voltage power) or fuses (current or non-current limiting) that are being used. Circuit Breakers Note: All of the following times are approximate; the time/current characteristics of the specific device being used should be checked for exact times. Molded Case Circuit Breakers (MCCBs) typically operate in 1.1 (0.018 sec) cycles for less than or equal to 100 ampere frame (AF) sizes and 2.25 cycles (0.038 sec) for 225 AF and larger sizes in their instantaneous ranges (5 times ampere trip), and over 100 seconds for low magnitude overloads. Low Voltage Power Circuit Breakers (LVPCBs) typically operate in 3 cycles (0.05 sec) in their instantaneous ranges, 6 - 30 cycles (0.10 - 0.50 sec) in their short time ranges, over 6000 cycles (100 sec) in their long time ranges, and 6 - 30 cycles (0.10 - 0.50 sec) in their ground fault ranges. Low Voltage Fuses Low voltage fuses clear faults in approximately 60,000 cycles (1000 sec) at 1.35 to 1.5 times their continuous current ratings and in 0.25-0.50 cycles (0.004-0.008 sec) in their currentlimiting ranges. Typical Time/Current (T/C) Plot Circuit Breakers - Figure 8 is a time/current characteristic plot of a LVPCB (DS-206) protecting a 500 kcmil copper conductor. Saudi Aramco DeskTop Standards 24 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits Figure 8. LVPCB Protection of a Cable Saudi Aramco DeskTop Standards 25 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits Fuses - Figure 9 is a time/current characteristic plot of a 20 A fuse protecting a No. 12 AWG copper wire and a 400 A fuse protecting a 500 kcmil copper wire. Figure 9. Fuse Protection of Cables Saudi Aramco DeskTop Standards 26 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits CALCULATING VOLTAGE DROPS OF A FEEDER CONDUCTOR CIRCUIT Note: Work Aid 1H has been developed to teach the Participant procedures to calculate voltage drops of a feeder conductor circuit. Introduction Designers of power systems must have practical knowledge of voltage drop calculations, not only to meet required codes and standards, but to ensure that the required voltage of a particular piece of equipment, for example a motor, is kept within manufacturer’s specified tolerances in order to prevent damage to the equipment. Note: The effects of voltage drops on different types of electrical equipment was discussed in Modules EEX 102.02 and EEX 102.04. Saudi Aramco DeskTop Standards 27 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits Factors Affecting Voltage Drop Calculations The voltage drop on a feeder depends on the following factors (Figures 10 and 11). • Load Data • Feeder Lengths • Feeder Impedance Figure 10. One-Line Diagram Figure 11. Feeder Diagrams Saudi Aramco DeskTop Standards 28 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits Load Data Voltage - The voltage drop (VD) is the difference between the voltage at the source end (VS) of the feeder, which is assumed to be a fixed value, and the voltage at the load end (VL) of the feeder, which varies as a function of the load or feeder current (IL). The voltage drop VD calculated is a line-to-neutral drop (one-way), the line-to-line voltage drop calculated for a single-phase system is 2VD, and the line-to-line voltage drop calculated for a three-phase system is 3VD. Current - The current (IL) flowing in the circuit is assumed to be the load or feeder current. The voltage drop is the load current times both the resistance (ILR) and reactance (ILX) of the circuit. Power Factor - The power factor (p.f.) of the load directly affects the voltage drop. As the power factor decreases, the voltage drop will increase. For purposes of this Module, assume that all power factors are lagging power factors. Feeder Lengths The voltage drop (ILZ) is directly proportional to the feeder lengths because the line impedance Z depends on the length. As the length of the feeder increases, the impedance of the line increases. Feeder Impedance Resistance - The resistance (R) per unit of length depends on the following factors. • Conductor Material • Conductor Size/Length • Conductor Operating Temperature Reactance - The inductive reactance (X) per unit of length depends on the following factors: • Conductor Diameter • Conductor Spacing • Power Supply Frequency • Raceway Type Saudi Aramco DeskTop Standards 29 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits Saudi Aramco DeskTop Standards 30 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits Effects of Resistance Variables on Voltage Drop Conductor Material The resistance (R) of a conductive material is directly proportional to the resistivity (ρ) of the material as expressed by the following formula: • R = ρL/A Because the resistivity of copper is 10.4 Ω-cmil/ft, versus 17.0 Ω-cmil for aluminum, the resistance of a copper wire, of a given length and cross-sectional area, is less than the resistance of an aluminum wire of the same length and cross-sectional area. Conductor Size/Length Resistance is inversely proportional to the size (cross-sectional area) and directly proportional to the length, which is again expressed by the following formula: • R = ρL/A Saudi Aramco DeskTop Standards 31 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits Operating Temperature Resistance values of conductors are usually provided at a given temperature, for example, 30°C (86°F). As the temperature of the conductor increases, either because of an increase in load or because of ambient temperature, resistance will also increase. For a copper conductor, the change in resistance as a function of temperature can be represented by the following formula (Figure 12): • R2 = R1 [(234.5 + T2)/(234.5 + T1)] • where R1 and R2 are the resistances of the conductor in ohms (Ω) at temperatures T1 and T2 respectively, in degrees Celsius (°C). Figure 12. Resistance Versus Temperature Relationships Saudi Aramco DeskTop Standards 32 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits Example H: The ac resistance of a 500 kcmil copper conductor in steel conduit in a 30°C ambient environment is .029 Ω/1000 ft. What is the ac resistance of 2500 ft of a 500 kcmil copper conductor in a 50°C ambient environment? Answer H: • T1 = 30°C, T2 = 50°C • R1 = (.029 Ω/1000 ft)(2500 ft) = .0725 Ω • R2 = R1 [(T2 + 234.5)/(T1 + 234.5)] = (.0725)[(50 + 234.5)/(30 + 234.5)] ≈ .078 Ω Effects of Reactance Variables on Voltage Drop Conductor Diameter As the conductor diameter increases (larger wire sizes), the reactance of the conductor decreases because of mutual self-inductance. Conductor Spacing The total reactance of a line (X) actually consists of two terms, Xa and Xd, where Xa is a function of the conductor material and Xa is a function of conductor spacing. As the spacing increases, the reactance (Xd) increases because of mutual inductance. This increase in reactance is typically not evident for low voltage conductors because the reactance values in tables already account for spacing. Frequency As indicated by the following formula, conductor reactance is directly proportional to frequency: • X = ωL = 2πfL • where: Example I: ω = angular frequency in radians/sec f = frequency in cycles/sec or Hertz (Hz) The reactance of a 2000 ft run of a 500 kcmil copper conductor in steel is .096 Ω at 60 Hz. What is the conductor’s reactance at 50 Hz? at 400 Hz? Saudi Aramco DeskTop Standards 33 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits Answer: (1) X60/60 = X50/50 X50 = (50/60) X60 = (5/6)(.096) = .08 Ω (2) X60/60 = X400/400 X400 = (400/60) X60 = (20/3)(.096) = .64 Ω Raceway Type If the material (raceway) surrounding the conductor is magnetic, such as steel conduit, the reactance is greater than if the raceway is non-magnetic, such as aluminum or plastic conduit. Voltage Drop Limits National Electric Code (NEC) NEC Article 215-2(b), FPN No. 2, states that “conductors for feeders as defined in Article 100, sized to prevent a voltage drop exceeding 3 percent at the farthest outlet of power, heating, and lighting loads, or combinations of such loads, and where the maximum total voltage drop on both feeder and branch circuits to the farthest outlet does not exceed 5 percent, will provide reasonable efficiency of operation”. Saudi Aramco Standard SAES-P-100 SAES-P-100 specifies the following criteria pertaining to feeder voltage drops for non-motor circuits under 600 volts: • Maximum steady state voltage drop for a main, feeder, and branch circuit shall not exceed five (5) percent. • Summation of voltage drops in circuit from main to distribution center, and from feeder breaker to panelboard shall be two (2) percent at full load. Saudi Aramco DeskTop Standards 34 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits Approximation Formula Phasor Relationships Due to the phasor relationships shown in Figure 13, exact methods of calculating line voltage drops require extensive knowledge of complex phasor algebra as was previously discussed in Module EEX 102.03. However, in most industrial electrical distribution systems, such as found on Saudi Aramco installations, the approximate method formula, as presented below, is adequate for most line voltage drop calculations. • Approximate Method Formula: VD = IR cos θ + IX sin θ = I(R cos θ + X sin θ) = IZ • where: VD = line-to-neutral voltage drop, volts (V), (one way) I = line current, amperes (A) R = circuit line resistance, ohms (Ω) X = circuit line reactance, ohms (Ω) Z = circuit line impedance, ohms (Ω) Z = R cos θ + X sin θ θ = load power factor angle, degrees cos θ = load power factor, decimals sin θ = load reactance factor, decimals VS = source voltage, line-to-neutral, volts (V) VL = load voltage, line-to-neutral, volts (V) VD(line-to-line, 1φ system) = 2VD VD(line-to-line, 3φ system) = 3VD Saudi Aramco DeskTop Standards 35 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits Figure 13. Voltage Drop Phasor Diagrams Saudi Aramco DeskTop Standards 36 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits Variable Assumptions The error caused by variation of load current and power factor because of the voltage applied to the load is not considered in the above formula for calculating voltage drops. In other words, the load current (IL) is assumed to be constant regardless of the voltage. However, if the error is significant, an iterative method may be used. Once the voltage drop is calculated, subtract the voltage drop (VD) from the source voltage (VS) and use this value to calculate a new load current, and then, using the new load current calculated, repeat the voltage drop calculation. Generally, if the total drop calculated is less than ten percent, the iterative method is not used. By convention, in the above formula, sin θ is considered to be positive for lagging power factor loads. As the angle of the load voltage approaches the angle of the line voltage, the error in the calculation approaches zero. Saudi Aramco DeskTop Standards 37 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits SELECTING FEEDER PROTECTIVE DEVICES Note: Work Aid 1I has been developed to teach the Participant procedures to select feeder protective devices. Types of Protective Devices Note: SAES-P-114 restricts low voltage line protection to circuit breakers. Circuit Breakers Molded-Case Circuit Breakers (MCCB) are a class of breaker rated at 600 volts and below, and they consist of a switching device and an automatic protective device assembled in an integral housing of insulated material. MCCBs are capable of clearing a fault more rapidly than a low voltage power circuit breaker (LVPCB). Solid-state trip units incorporated into some styles of MCCBs provide for their coordination with LVPCBs. MCCBs are generally sealed to prevent tampering, and this sealing, in turn, precludes any inspection of the MCCB contacts. MCCBs are generally not designed to be maintained in the field, and manufacturers recommend total replacement if a defect appears. MCCBs are available in several different types. The thermal magnetic type, which is the most widely used, employs thermal tripping for overloads and magnetic tripping for short-circuits. The magnetic type MCCB employs only instantaneous magnetic tripping for cases where only short circuit interruption is required. The integrally-fused type MCCB combines regular thermal magnetic protection, together with current limiting fuses, to respond to applications where higher short circuit currents are available. In addition, the current limiting type MCCB offers high interrupting capacity protection, while at the same time limiting the let-through current to a significantly lower value than is usual for conventional MCCBs. Low-Voltage Power Circuit Breakers (LVPCB), like MCCBs, are rated 600 volts and below. They differ from MCCBs, however, because they are typically open-construction assemblies on metal frames and all parts are designed for accessible maintenance, repair, and ease of replacement. LVPCBs are intended for service in switchgear compartments or in other enclosures of dead- front construction. Tripping units are field-adjustable and include electromagnetic, direct-acting, and solid-state types. LVPCBs can be used with integral current-limiting fuses to meet interrupting requirements up to 200 kA RMS symmetrical. Saudi Aramco DeskTop Standards 38 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits Saudi Aramco Applications of Fuses Low voltage fuses (600 volts or less) come in two basic shapes: the plug fuse and the cartridge fuse. Fuses may be current limiting or non-current limiting. Cartridge fuses are either renewable or nonrenewable. Nonrenewable cartridge fuses are assembled at the factory, and they are replaced after they open (melt) in service. Renewable cartridge fuses can be disassembled, and the fusible element can be replaced. A special type of low voltage fuse that is sometimes used is the dual-element or time-delay fuse. The dual-element fuse has one element that is fast-acting, and it responds to overcurrents in the short circuit range, while its other element permits short-duration overloads, but melts if the overload is sustained. Note: Saudi Aramco has very limited application of low voltage fuses. Molded Case Circuit Breaker (MCCB) Ratings The MCCB gets its name from the material (plastic) and manufacturing process (molded) used to make the frame (case) of the breaker. Figure 14 describes a MCCB. The MCCB serves as the disconnect, overload, and fault protection for the feeder circuit. Figure 14. Molded Case Circuit Breaker (MCCB) Saudi Aramco DeskTop Standards 39 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits Frame Size The frame size of the MCCB describes the physical size and continuous current ratings of the MCCB. Each different type and size of MCCB is assigned a frame designation. MCCBs have many different trip and interrupting ratings for the numerous frame sizes. Figure 15 lists the different frame sizes for typical MCCBs. Trip Ratings The function of the trip unit in a MCCB is to trip the operating mechanism in the event of a prolonged overload or short circuit current. The traditional MCCB uses electromechanical (thermal-magnetic) trip units. Protection is provided by combining of a temperature sensing device (bimetallic strip) with a current sensing electromagnetic device, both of which act mechanically on the trip mechanism. More modern breakers use sophisticated electronic trip units, which can be more precisely modeled than the electromechanical trip units. NEC Article 240-6 lists the standard trip ratings of MCCBs. Figure 15 also lists the continuous current or trip ratings of typical MCCBs. Saudi Aramco DeskTop Standards 40 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits Interrupting Ratings The interrupting rating or short circuit rating at a 40°C ambient temperature is commonly expressed in root mean square (RMS) symmetrical amperes. The interrupting capability of the breaker may vary with the applied voltage. For example, a breaker applied at 480 volts could have an interrupting rating of 25,000 A at 480 volts, but the same breaker applied at 240 volts may have an increased interrupting rating of 65,000 A. Saudi Aramco DeskTop Standards 41 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits All MCCBs operate instantaneously at currents well below their interrupting rating. Nonadjustable MCCBs will usually operate instantaneously at current values approximately five times (5x) their trip rating. Low voltage breaker contacts separate and interrupt the fault current during the first cycle of short circuit current. Because of this fast operation, the momentary and interrupting duties are considered to be the same. Therefore, all fault contribution from generators, motors, and the dc components of the fault waveform must be considered. Figure 15 also lists the symmetrical and asymmetrical interrupting ratings of typical MCCBs. Line No. Frame Size (amps) (AF) Rated Continuous Current (amps) (AT) Interrupting Current Rating (AIC) (amps) 240 Volts 480 Volts 600 Volts Sym Asym Sym Asym Sym Asym 1 100 10-100 18,000 20,000 14,000 15,000 14,000 15,000 2 100 10-100 65,000 75,000 25,000 30,000 18,000 20,000 3 100 10-100 100,000 4 225 125-200 22,000 25,000 18,000 20,000 14,000 15,000 5 225 70-225 25,000 30,000 22,000 25,000 22,000 25,000 6 225 70-225 65,000 75,000 35,000 40,000 25,000 30,000 7 225 70-225 100,000 -- 8 225 70-225 35,000 40,000 9 400 200-400 65,000 10 400 200-400 100,000 11 400 200-400 42,000 12 600 300-600 100,000 13 800 300-800 42,000 50,000 30,000 35,000 22,000 25,000 14 800 300-800 65,000 75,000 35,000 40,000 25,000 30,000 15 800 600-800 100,000 16 1000 600-1000 42,000 50,000 30,000 35,000 22,000 25,000 17 1200 700-1200 42,000 50,000 30,000 35,000 22,000 25,000 -- 75,000 -50,000 -- -- 100,000 -- 100,000 25,000 35,000 -- 100,000 -- -- 30,000 22,000 25,000 40,000 25,000 30,000 100,000 30,000 100,000 -35,000 100,000 -- 100,000 -- 100,000 22,000 100,000 100,000 -25,000 -- -- Figure 15. Typical MCCB Ratings Saudi Aramco DeskTop Standards 42 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits Low Voltage Power Circuit Breaker (LVPCB) Ratings Frame Size The rated continuous current of a LVPCB is the designated limit of RMS current, at rated frequency, that it is required to carry continuously without exceeding the temperature limitations based on a 40°C ambient temperature. The temperature limit on which the rating of circuit breakers are based are determined by the characteristics of the insulating materials used and the metals that are used in the current carrying components and springs. Standard frame size ratings for low voltage power circuit breakers are 800, 1600, 2000, 3200, and 4000 amperes. Some manufacturers may have additional frame sizes. LVPCPs have either an electromechanical trip or a solid-state trip that is adjustable or interchangeable from a minimum rating up to the ampere rating of the frame. Figure 16 lists the frame sizes of typical LVPCBs. Frame Size (amperes) 800 1600 2000 3200 4000 Available Sensor Ratings (amperes) 50, 100, 150, 200, 300, 400, 600, 800 100, 150, 200, 300, 400, 600, 800, 1200, 1600 100, 150, 200, 300, 400, 600, 800, 1200, 1600, 2000 2400, 3200 4000 Figure 16. LVPCB Frame and Sensor Ratings Sensor Ratings A sensor on an LVPCB is simply a current transformer that reduces (transforms) the high magnitude line currents to a magnitude that the trip units (typically electronic) can safely carry for short periods of time. Figure 16 also lists the sensor ratings for an LVPCB. Saudi Aramco DeskTop Standards 43 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits Short Time Ratings LVPCBs are designed and marked with the maximum voltage at which they can be applied. LVPCBs can be used on any system where the voltage is lower than the breaker rating. The applied voltage will affect the interrupting rating of the breaker. Standard maximum voltage ratings for LVPCBs are 635 volts, 508 volts, and 254 volts. LVPCBs are usually suitable for both 50 and 60 Hz. The short-time current rating of a LVPCB specifies the maximum capability of the circuit breaker to withstand the effects of short circuit current flow for a stated period, typically 30 cycles or less. The short-time delay on the breaker’s trip units corresponds to the short-time current rating. This time delay provides time for downstream protective devices closer to the fault to operate and to isolate the circuit. The short-time current rating of a modern day LVPCB without an instantaneous trip characteristic is usually equal to the breaker’s short circuit interrupting rating. By comparison, MCCBs usually do not have a short-time rating. Figure 17 lists the short-time interrupting rating of typical LVPCBs. Frame Size (amperes) 800 1600 2000 3200 4000 Interrupting Ratings (RMS Symmetrical Amperes) With Instantaneous Trip Short-Time Ratings (30cycles) (With Short-Delay) 208-240V 42,000 65,000 65,000 85,000 130,000 480 V 30,000 50,000 65,000 65,000 85,000 600 V 30,000 42,000 50,000 65,000 85,000 208-240V 30,000 50,000 65,000 65,000 85,000 480 V 30,000 50,000 65,000 65,000 85,000 600V 30,000 42,000 50,000 65,000 85,000 Figure 17. LVPCB Short-Time and Interrupting Ratings Interrupting Ratings The interrupting rating of a LVPCB is the RMS symmetrical current rating of the circuit breaker. The asymmetrical interrupting rating is implied, and it is based on an X/R ratio of 6.6 for unfused breakers and on an X/R ratio of 4.9 for fused breakers. An X/R ratio of 6.6 corresponds to an asymmetrical factor (Ma) of 1.17. Under short circuit conditions, most low voltage systems have an X/R ratio of less than 6.6. Therefore, if an asymmetrical interrupting rating is not listed by the manufacturer, assume that the asymmetrical rating is 1.17 times the symmetrical rating. Figure 17 also lists the symmetrical interrupting ratings of typical LVPCBs. Saudi Aramco DeskTop Standards 44 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits Protective Device Time/Current (T/C) Characteristics The response curves of all protective devices are plotted on common graphs so that they may be compared at all current and time points. The standard means used to plot device T/C characteristics is to plot the devices on log-log graph paper (Figure 18). Standard log-log graphs are 4.5 cycles on the horizontal scale that represents current. The current axis ranges from 0.5 to 10,000 amperes. The vertical axis, representing time, ranges from 0.01 to 1000 seconds and/or 0.6 to 60,000 cycles. Because current limiting fuses and molded case circuit breakers may operate in less than 0.5 cycles (.00835 seconds), manufacturers of these devices may reproduce T/C characteristic curves with 6 cycle vertical scales that represent times ranging from 0.001 to 10,000 seconds (.06 to 600,000 cycles). The horizontal current scale is also often “shifted” for a particular plot by multiplying the current scale by a factor of 10, 100, or 1000 (x10, x100, x1000). Thermal-Magnetic MCCB SAES-P-114 permits thermal-magnetic (inverse-time) MCCBs for the protection of feeders. The MCCB is sized to protect the low voltage feeder conductors in accordance with their ampacities after all derating factors have been applied. The NEC permits the next standard size MCCB that is available to protect the conductor if the MCCB rating does not exceed 800 A. If the breaker rating being selected exceeds 800 A, the NEC requires the next smaller size breaker to be selected. Figure 19 shows a 600 A MCCB that protects a parallel set of 500 kcmil, copper, type THWN feeder conductors. Saudi Aramco DeskTop Standards 45 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits Figure 18. Typical Log-Log Paper Saudi Aramco DeskTop Standards 46 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits Figure 19. MCCB Protecting A Feeder Conductor Saudi Aramco DeskTop Standards 47 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits An MCCB is tested in open air (not in an enclosure) to verify its nameplate ampere rating. The nameplate specifies a value of current that the circuit breaker is rated to carry continuously, without tripping, within specific operating temperature guidelines. In most cases, however, an MCCB is used in an enclosure, but not in open air. Therefore, the performance of a breaker inside an enclosure, as with any other overcurrent device, could be adversely affected by heat dissipation and temperature rise. These factors must be considered regarding the ability of the breaker to comply with its nameplate ampere rating. Section 220-10(b) of the NEC, which covers continuous and noncontinuous loads, states that: “Where a feeder supplies continuous loads or any combination of continuous and noncontinuous loads, the rating of the overcurrent device shall be less than the noncontinuous load plus 125% of the continuous load”. The same NEC section permits the following exception: “Where the assembly including the overcurrent devices protecting the feeder(s) are listed for operation at 100% of their rating, neither the ampere rating of the overcurrent device nor the ampacity of the feeder conductors shall be less than the sum of the continuous load plus the noncontinuous load”. Figure 20a shows a typical application using a standard design approach and Figure 20b shows the same application using 100 percent rated MCCBs. Saudi Aramco DeskTop Standards 48 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits Figure 20. Typical MCCB Applications Saudi Aramco DeskTop Standards 49 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits Low Voltage Power Circuit Breaker (LVPCB) Long Time Functions include the long time pickup and the long time delay functions. Long time pickup (LTPU) functions or long delay pickup (LDPU) settings are adjustable from 0.5 - 1.0 times the plug rating (In). The plug rating is also a function of the sensor rating (current transformer), which establishes the continuous current rating of the breaker. Typical tolerances for a modern day solid-state trip (SST) (e.g., Westinghouse Digitrip RMS) are 0%, + 10% (Figure 21). Figure 21. Long Time Pickup (LTPU) T/C Characteristics Saudi Aramco DeskTop Standards 50 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits Long time delay (LTD) or long delay time (LDT) settings are adjustable from 2 - 24 seconds at 6 times the plug rating (6In). Typical tolerances are + 0%, - 33% (Figure 22). Figure 22. Long Time Delay (LTD) T/C Characteristics Short Time Functions include the short time pickup and short time delay functions. Short time pickup (STPU) or short delay pickup (SDPU) settings are adjustable from 2 to 6 times the plug rating (2 - 6In) plus two variable settings of S1 (8In) and S2 (10In). Typical tolerances are + 10%, - 10% (Figure 23). Saudi Aramco DeskTop Standards 51 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits Figure 23. Short Time Pickup (STPU) T/C Characteristics Saudi Aramco DeskTop Standards 52 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits Short time delay (STD) or short delay time (SDT) settings are available with five flat responses of 0.1, 0.2, 0.3, 0.4 and 0.5 seconds. Typical tolerances are variable depending on the setting (Figure 24). I2t Function settings are available in three responses of 0.1*, 0.3*, and 0.5* seconds, and the settings revert back to a flat response at 8In (Figure 24). The asterisk (*) refers to I2t settings. Figure 24. Short Time Delay (STD) With I2t T/C Characteristics Saudi Aramco DeskTop Standards 53 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits Instantaneous Trip (IT) settings are adjustable from 2 to 6 times the plug rating (2 - 6In) plug two variable settings of M1 (8In) and M2 (12In). Typical tolerances are + 10%, - 10% (Figure 25). Figure 25. Instantaneous Trip (IT) T/C Characteristics Ground Fault Functions - SAES-P-114 requires ground fault protection, where required by the NEC, that uses window-type current transformers (CTs) similar to the BYZ CT, as shown in Figure 26. The tripping function, unlike its MCCB counterpart, is part of the same SST unit. Saudi Aramco DeskTop Standards 54 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits Figure 26. GFP With Window-Type CT Saudi Aramco DeskTop Standards 55 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits Ground fault pickup (GFPU) settings have eight discrete adjustments (A, B, C, D, E, F, H, K), which are a function of the plug ratings (In). Figure 27 shows a sample listing of the settings for plug ratings of 100, 200, 250, and 300 amperes. Typical tolerances are + 10%, - 10% (Figure 28). In 100 200 250 300 A 25 50 63 75 B 30 60 75 90 C 35 70 88 105 D 40 80 100 120 E 50 100 125 150 F 60 120 150 180 H 75 150 188 225 K 100 200 250 300 Figure 27. Sample GFPU Code Letters and Settings Figure 28. Ground Fault Pickup (GFPU) T/C Characteristics Saudi Aramco DeskTop Standards 56 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits Ground fault time (GFT) or ground fault delay time (GFDT) settings, like the SDT settings, are available with 5 flat responses of 0.1, 0.2, 0.3, 0.4, and 0.5 seconds. Typical tolerances are variable depending on the setting (Figure 29). I2t functions settings are also available for ground fault functions in 3 responses of 0.1*, 0.2*, and 0.3* seconds, and the settings revert back to a flat response at 0.625 In (Figure 29). Figure 29. Ground Fault Time (GFT) With I2t T/C Characteristics Saudi Aramco DeskTop Standards 57 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits Coordination Principles Molded Case Circuit Breakers (MCCBs) are difficult to coordinate, especially in the smaller frame sizes of 100 and 225 amperes. Even the larger frame breakers are difficult to coordinate unless sufficient impedance (very long cable runs) exists between the feeder breakers and the other downstream breakers. Modern-day larger frame breakers with solidstate (electronic) trips are much easier to coordinate. Two MCCBs in series will coordinate if their plotted T/C characteristic curves do not overlap or cross one another. Low Voltage Power Circuit Breakers (LVPCBs) are fairly simple to coordinate because of the numerous settings and adjustments available for their long time, short-time, instantaneous, and ground fault functions. As with MCCBs, two LVPCBs in series will coordinate if their plotted T/C characteristic curves do not overlap or touch one another. Figure 30 shows a main breaker (DS-632) coordinating with a feeder breaker (DS-206) that is protecting a 500 kcmil copper conductor. Saudi Aramco DeskTop Standards 58 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits Figure 30. LVPCB Coordination Saudi Aramco DeskTop Standards 59 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits Factors Affecting Selection The properly rated MCCB for a specific application can be selected by determining the following listed parameters. There are other factors, for example, unusual operating conditions, altitude, frequency, etc; however, for purposes of this Module, the factors affecting MCCB selection are limited to the following: • • • • • Temperature Continuous Loads Voltage Round-up Rule Round-down Rule Temperature Thermal magnetic circuit breakers are temperature sensitive. At ambient temperatures below 40°C, circuit breakers carry more current than they are rated to carry in continuous current. Nuisance tripping is not a problem under these lower temperature conditions, although consideration should be given to closer protection coordination to compensate for the additional current carrying capability. In addition, the actual mechanical operation of the breaker could be affected if the ambient temperature is significantly below the 40°C standard. Note: The 40°C standards for MCCBs is based on the fact that 40°C is the average temperature of an enclosure, for example, a lighting panelboard. For ambient temperatures above 40°C, breakers will carry less current than they are rated to carry in continuous current. This condition promotes nuisance tripping, and it can create unacceptable temperature conditions at the terminals. Under this condition, the circuit breaker should be recalibrated for the higher ambient temperature. Recalibrating MCCBs is not a “user” option; recalibration must be accomplished by the manufacturer. The best option when ordering new breakers is to order ambient-compensated breakers. Continuous Loads MCCBs are rated in amperes at a specific ambient temperature. The ampere rating is the continuous load current that the breaker will carry in the ambient temperature for which it is calibrated. Most manufacturers calibrate their standard breakers for a 40°C (104°F) ambient. The continuous current ampere rating typically signifies the amount of current that the MCCB is designed to carry continuously in open air. In accordance with Article 220-10(b) of the NEC, all overcurrent protection devices may be loaded to a maximum of 80% of their continuous ampere rating, unless specifically listed for 100% application. A number of manufacturers offer circuit breakers that can be applied at 100% of their continuous rating. These 100% rated breakers specifically outline on their nameplates the minimum size Saudi Aramco DeskTop Standards 60 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits enclosure, the minimum ventilation (if needed), and the minimum conductor size for application at 100% of their ratings. Saudi Aramco DeskTop Standards 61 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits Voltage The voltage rating of an MCCB is determined by the maximum voltage that can be applied across its terminals, the type of distribution system, and how the breaker is applied in the system. For example, the most prevalent secondary distribution voltage in commercial and institutional buildings today is 480Y/277 volts, with a solidly grounded neutral. It is also a very common secondary voltage in industrial plants and even in some high rise commercial buildings that are centrally air-conditioned. In panelboards, it is important that the MCCB have the lowest possible voltage rating that will do the job and meet the specifications. An overly conservative selection can make a considerable difference in the cost. It is critical that the proper application, testing, and governing standards be understood before any attempt is made to apply dual voltage-rated breakers. Article 240-83(e) of the NEC defines the allowed application of circuit breakers with straight or slash voltage markings. International applications, where 415Y/240, 380Y/220, or 220Y/127 volt systems are used, are all grounded “Y” systems similar to the U.S. 480Y/277 volt system. Only IEC 947-2 breakers tested per Appendix C and marked accordingly (C 480V) are suitable for application on delta systems. Single pole testing at maximum voltage is not a requirement of IEC 947-2 except for this optional test under Appendix C. This test is a standard test under the UL 489 requirements for all voltage ranges. Round-up and Round-down Rules Per NEC Article 240-3, conductors should be protected against overload in accordance with their ampacities as specified by NEC Article 310-15 and Tables 310-16 through 310-19 for conductors rated 0-2000 V. The next higher standard device is permitted if the protective device does not exceed 800 A (round-up rule). See NEC Article 240-3(b). The conductor ampacity must be greater than the protective device setting/rating if the protective device exceeds 800 A (round-down rule). See NEC Article 240-3(c). Saudi Aramco DeskTop Standards 62 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits SELECTING FEEDER CONDUCTOR RACEWAY SIZES Note: Work Aid 1J has been developed to teach the Participant procedures to select feeder conductor raceway sizes. Types of Raceways Note: For purposes of this Module, only wireways and conduits will be considered in selecting of feeder conductor raceway sizes. Wireways The NEC (Article 362-1) defines wireways as sheet metal troughs with hinged or removable covers for housing and protecting electric wires and cable and in which conductors are laid in place after the wireway has been installed. Figure 31 describes a typical length of wireway with a hinged cover. Note: The NEC does not permit concealment of wireway; it must remain exposed. Figure 31. Length of Wireway Conduits SAES-P-114 lists the following specifications pertaining to conduits: • Conduit, above ground in outdoor, industrial facilities shall be hot-dip galvanized rigid steel. • Direct buried conduit shall be (a) threaded, hot-dip galvanized rigid steel and polyvinyl chloride (PVC) coated or (b) type direct burial (DB) PVC conduit per NEMA TC 8. • Other types of conduits shall be permitted where used and installed in accordance with the NEC. Saudi Aramco DeskTop Standards 63 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits Saudi Aramco DeskTop Standards 64 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits Rigid Metal Conduit (RMC) has almost unlimited restrictions for use in industrial installations. RMC is most often used where moisture is present and where cables are subjected to mechanical damage. RMC uses threaded fittings. Intermediate Metal Conduit (IMC) is very similar to RMC, and it also has very limited restrictions for use. The major difference between the two conduits is that RMC provides better mechanical damage for conductors than does IMC. Note: SAES-P-104 prohibits the use of IMC in classified areas. Electric Metallic Tubing (EMT) is a non-threaded metallic conduit used primarily for indoor protection of conductors. EMT is not permitted in permanent moisture locations, although it is permitted for both exposed and concealed wet locations. EMT uses compression type couplings and fittings. Rigid Nonmetallic Conduit (PVC) is permitted for both concealed and exposed locations as long as it is not subject to physical damage. PVC is not permitted in hazardous locations. Flexible Metal Conduit is most often used for motor circuits or other types of circuits subjected to vibrations. Flexible metal conduit is not permitted in underground installations, in most hazardous locations, in wet locations, or in any areas subject to physical damage. Factors Affecting Raceway Size The number of conductors permitted in a raceway is restricted by the NEC. The total crosssectional area of the conductors, which includes the insulation, must not exceed a specified percentage of the wireway or conduit cross-sectional area. The NEC refers to this restriction as “percentage fill”. Exceeding the percentage fill can cause physical damage to the conductors as they are being installed (pulled) through the raceway. Additionally, the heat buildup in the raceway could be excessive, resulting in damage to the insulation. Conductor Insulation Because each type of conductor has different insulation thicknesses, the percentage fill for each type of conductor (insulation) is different. Chapter 9, Table 5, of the NEC lists the dimensions (diameter and area) for each size and type of rubber-covered and thermoplasticcovered conductors. Saudi Aramco DeskTop Standards 65 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits Number of Conductors The number of the same type of conductors (insulation) in conduit can be determined from Chapter 9, Tables 3A and 3B of the NEC. The number of conductors in wireway, or mixed sizes and types of conductors (insulations), must be calculated based on the fill rates permitted by the NEC. Tables - NEC Tables 3A and 3B are based on a 40 percent fill rate of conductors in a given trade size of conduit (Figure 32). If conductor insulation types are mixed, the tables cannot be used and the fill rate for a particular mix of conductors in a given trade size of conduit must be calculated. The number of conductors, for fill rate purposes, includes all conductors, regardless of whether they are considered as current-carrying conductors. For example, the “green” equipment grounding conductor is considered for percentage fill restrictions even though it does not carry current except under line-to-ground fault conditions. Figure 32. Conduit Fill Rate Example Example J: Referring to Table 3B of the NEC, what is the maximum number of 500 kcmil, type THHN conductors in 3-inch conduit? Answer J: Per Table 3B (page 914 of Work Aid 1A, Handout 1), the maximum number of 500 kcmil type THHN conductors in 3-inch conduit is 4. Saudi Aramco DeskTop Standards 66 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits Fill Rate Calculations - NEC Article 362-5 restricts the fill rate of wireways to the following: no more than 30 current-carrying conductors, and/or the sum of all conductor areas shall not exceed a fill rate of 20 percent of the interior cross-sectional area of the wireway. Note: The derating factors specified in Article 310 for more than 3 conductors in a raceway are not applicable to the 30 current-carrying conductors and 20 percent fill rate specified above. Table 1, Chapter 9, of the NEC specifies a fill rate of 40 percent for more than three conductors in a raceway. Table 4 lists the diameter, total area, and 40 percent fill rate area of conduit. Tables 5, 5A, and 5B lists the dimensions (diameter and area) of bare, rubbercovered, and thermoplastic-covered conductors. All of the tables must be used to calculate the fill rate of a conduit, when the insulation types and wire sizes installed in conduit are mixed. Example K: Given the following list (Figure 33) of conductors, what is the minimum size conduit permissible to enclose the conductors? Circuit Identification Insulation Type Feeder A Feeder B Feeder C THHW THHN THHN Size of Copper Conductors 3-No.4/0, 1-No.2/0 4-No.2/0, 1-No.1/0 4-No.1/0, 1-No.2 Figure 33. Example K Conductor Listing Answer K: Feeder A: 3 x 0.3904 + 1 x 0.2781 Feeder B: 4 x 0.2265 + 1 x 0.1893 Feeder C: 4 x 0.1893 + 1 x 0.1182 Total = = = = 1.4493 in2 (Table 5) 1.0953 in2 (Table 5) 0.8754 in2 (Table 5) 3.4200 in2 Per Table 4, a 3.5-inch conduit (3.96 in2) is acceptable at a 40 percent fill rate. Saudi Aramco DeskTop Standards 67 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits WORK AID 1: RESOURCES USED TO DESIGN A LOW VOLTAGE NON-MOTOR FEEDER CIRCUIT Work Aid 1A: 1993 National Electric Code Handbook For the content of Work Aid 1A, refer to Handout 1. Work Aid 1B: ANSI/IEEE Standard 141-1986 (Red Book) For the content of Work Aid 1B, refer to Handout 2. Work Aid 1C: SAES-P-114 1. Section 4.2.1 specifies that all system and equipment protection shall conform to NFPA 70 (National Electric Code - NEC) as supplemented by this Standard. 2. Section 4.7.1 specifies that low voltage feeder circuits shall be protected by circuit breakers and that all interrupting devices shall be fully rated. 3. Section 4.7.3 specifies that overcurrent protection for wires and cables connected to full-size molded case circuit breakers shall be based on NEC Article 110-14. 4. Section 4.8.3 specifies that all low voltage power circuit breakers shall include either an integral protective device with adjustable ground unit or shall be tripped by a ground overcurrent relay. 5. Section 4.8.4 specifies that low voltage 480 volt molded case circuit breakers rated 70 amperes and greater shall be provided with one of the following: 6. a) An electronic trip device with adjustable ground unit, where available from the manufacturer for the required frame size, or b) A thermal-magnetic trip unit with separate adjustable 50G ground sensor and shunt trip device. Section 10.2.3 specifies that protection of low voltage radial feeders may be provided by integral solid-state breaker trip devices, which shall be supplied with long-time, short-time phase overcurrent trips, and time-delayed ground fault trips. Instantaneous trips shall only be provided for dedicated feeders where there is no downstream protective device. Saudi Aramco DeskTop Standards 68 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits Saudi Aramco DeskTop Standards 69 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits Work Aid 1D: SAES-P-100 1. Section 5.6 specifies that maximum steady state total voltage drop for a main, feeder, and branch circuit shall not exceed five (5) percent. 2. Section 5.6.1 (E) specifies that summation of voltage drops in circuit from main to distribution center and from feeder breaker to panelboard shall be two (2) percent at full load. 3. Section 5.6.1 (F) specifies that other voltage drops shall average two (2) percent with a maximum of four (4) percent to the most distant outlet at full load. 4. Section 6.2 specifies that the following criteria shall be used to establish equipment derating when specific requirements are not covered in an SAES or SAMSS. Location Ambient Temperature Average Monthly Maximum Normal Maximum Daily Peak 0 0 C C Outdoors 45 50 Indoors Well Ventilated Buildings 40 50 Indoors Air-Conditioned Buildings Unmanned Areas 35 35 Indoors Air-Conditioned Buildings Manned Areas 30 30 Figure 35. SAES-P-100 Ambient Temperatures Saudi Aramco DeskTop Standards 70 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits Work Aid 1E: SAES-P-104 1. Section 4.1 specifies that design and installation of wiring and cable systems shall be in accordance with NFPA 70 (National Electric Code - NEC), as supplemented by this Standard. 2. Section 4.2.1 specifies that wire and cable shall have copper conductors. 3. Section 4.2.2 specifies that low voltage wire and cable (600 V or 600/1000 V and below) shall have a minimum rating of 75°C. 4. Section 4.2.5 specifies that power conductors shall be of stranded copper, except that 2 solid copper conductors 6 mm (No. 10 AWG) and smaller may be used in nonindustrial locations and for specialty applications. 5. Section 4.2.10 specifies that for 600 V and below power conductors, the minimum size permitted is 2.5 mm2 (No. 14 AWG). 6. Section 4.3.1 specifies that direct buried conduit shall be threaded, rigid steel, hot-dip galvanized, and PVC coated, or type DB PVC conduit. 7. Section 4.3.2 specifies that conduit above ground in outdoor industrial facilities shall be threaded, rigid steel, and be hot-dip galvanized. 8. Section 4.3.4 specifies that the minimum conduit size shall be 3/4 inch, except on instrument panels, inside buildings, and on prefabricated skids, where the minimum size conduit shall be 1/2 inch. 9. Section 4.3.6 specifies that electric metallic tubing (EMT) is acceptable only in nonhazardous indoor locations. 10. Section 5.1 specifies that the minimum burial depths for 600 V and below underground installations shall be the following: • Direct Buried cables - 600 mm (24 in.) • Direct buried PVC conduit - 460 mm (18 in.) • Duct bank and direct buried rigid steel conduit - 460 mm (18 in.) • PVC conduit, rigid steel conduit, or duct bank under roads, parking lots, and other areas that are subject to vehicular traffic - 600 mm (24 in.) Saudi Aramco DeskTop Standards 71 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits 11. Section 8.1 specifies that the sizing of power cables in the Saudi Aramco system shall be the following: • load factor - 100 percent of maximum steady state load • direct buried cable - 40°C ambient temperature • cable in conduit (in air) - 60°C exposed to sun and 50°C shaded or indoor. 12. Section 8.2.1 specifies that feeders supplying transformers shall have an ampacity of not less than the sum of the full-load ratings (fan-cooled ratings, if fans are installed) of all connected transformers and all other connected loads. 13. Section 8.2.2 specifies that a feeder cable serving a load bus shall be sized in accordance with the NEC plus a 20 percent growth factor, but the size is not to exceed the maximum rating of the bus. Note: Section 8.2.3 permits deletion of the growth factor where two or more feeders serve the same bus. 14. Section 8.2.4 specifies that the ampacity of a feeder directly connecting the secondary of a transformer to a load bus shall not be less than the full-load rating (forced-air rating, if fans are installed) of the transformer. 15. Section 8.2.5 specifies that a derating factor of 15 percent shall be applied to power cable that requires fireproofing. Saudi Aramco DeskTop Standards 72 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits Work Aid 1F: Step 1. Applicable Procedures for Calculating Ampacity Ratings of Feeder Conductors Determine the feeder load current in accordance with the following formulas: Note: 1.2 factor is the 20 percent growth factor required by SAES-P-104. a. b. Three-phase non-motor loads: • IL = 1.2 x kVA/( 3 x kV) or • IL = 1.2 x kW/( 3 x kV x p.f.) Three-phase transformer feeder loads based on the self-cooled (OA) rating or forced-air (FA) rating if fans are installed: • IL = kVA/( 3 x kV) Step 2. Initially select a 75°C or 90°C conductor form NEC Table 310-16 (Handout 2, page 248). Note: Consider use of parallel conductors for required conductor sizes 500 kcmil and larger. Step 3. Apply derating (correction) factors (if applicable) as follows: Step 4. a) Fireproofing (where required): 15 percent b) Ambient temperature: Select the correction factor from NEC Table 310-16 (Handout 2, page 248). c) More than three current-carrying conductors in a raceway: Select the correction factor from Note 8 to NEC Table 310-16 (Handout 2, page 253). Specify the selected conductor (or parallel conductors) as follows: • Size - AWG or kcmil Note: See Figure 36 for the nearest metric equivalent size conductor. • Material - Copper (Cu) • Insulation Type - i.e., THWN, THHN, etc. • Number of Conductors - i. e., 4/C, 8/C Saudi Aramco DeskTop Standards 73 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits CONDUCTOR SIZES AWG or kcmil* mm2 14 12 10 8 6 4 2 1/0 2.5 4 6 10 16 25 35 50 AWG or kcmil* mm2 2/0 4/0 250* 350* 500* 750* 1000* 70 120 120 185 240 400 500 Figure 36. Standard Saudi Aramco Wire Sizes Saudi Aramco DeskTop Standards 74 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits Work Aid 1G: Step 1. Step 2. Applicable Procedures for Calculating the Short Feeder Conductor Circuit Rating of a Estimate the protective device clearing times as follows: a) Molded Case Circuit Breakers (MCCBs): 1.1 cycles (18 msec) for less than 100 ampere frame (AF) and 1.5 cycles (25 msec) for 225 AF and larger in the MCCB’s instantaneous range (approximately five times the ampere trip), and over 100 sec at low magnitude overloads. b) Low Voltage Power Circuit Breakers (LVPCBs): 3 cycles (0.05 sec) for instantaneous ranges, 6 to 30 cycles (0.10 - 0.50 sec) in the short time ranges, over 100 sec in the long time ranges, and 6 to 30 cycles (0.10 - 0.50 sec) for their ground fault ranges. Calculate the magnitude of the fault current (total asymmetrical) in accordance with the following formula: • Iasy = Isym x ko • where: Isym = rms symmetrical fault current Note: Isym is assumed as a “given quantity” for purposes of this Work Aid. ko= correction factor accounting for the dc component of current. = 1.6 for MCCBs = 1.3 for LVPCBs Step 3. Calculate the duration (t) of of the short circuit in accordance with the following formula: • t = .0297 log10 [(T2 + 234)/T1 + 234)] x (A/Iasy)2 • where: t = short circuit duration in seconds T1 = initial conductor temperature in degrees Celcius (°C) = 75°C or 90°C for NEC thermoplastic (PVC) conductors T2 = final conductor temperature in degrees Celsius (°C) = 150°C for NEC thermoplastic (PVC) conductors A = conductor cross-sectional area in circular mils (cmils) Note: See Table 8 of the NEC Handbook (Handout 1, page 919). Iasy= maximum asymmetrical short circuit current in amperes calculated in Step 2. Saudi Aramco DeskTop Standards 75 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits Saudi Aramco DeskTop Standards 76 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits Step 4. Compare the short circuit duration (t) calculated in Step 3 to the estimated protective device clearing times from Step 1. If t is less than the protective device’s clearing time, increase the conductor size to the next standard available size and repeat Steps 3 and 4 until t is greater than the protective device’s clearing time. Saudi Aramco DeskTop Standards 77 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits Work Aid 1H: Applicable Procedures for Calculating the Voltage Feeder Conductor Step 1. Obtain the specified one-line diagram. Step 2. Calculate load current (IL). Drop of a IL = (kVA)/[( 3)(kV)] = (kW)/[( 3)(kV)(p.f.)] Step 3. Calculate the load power factor angle θ = cos-1 p.f. Step 4. Calculate the load reactive factor (sin θ). sin θ = sin (cos-1 p.f.) Step 5. Determine feeder impedance (ZΩ) per 1000 feet from NEC Table 9 (Handout 1, page 920). Step 6. Calculate the feeder impedance. ZΩ = ((R + jX) Ω per 1000 ft) (number of feet) Step 7. Calculate VD line-to-neutral. VD = I(R cos θ + X sin θ) Step 8. Calculate VD line-to-line. VD = 3 VD (3f system) VD = 2VD (1φ system) Step 9. Calculate the load voltage (VL). VL = VS - VD Step 10. Calculate VD as a percentage (VD%). VD% = 100[(VS - VL)/VS] Step 11. If VD% exceeds 2 percent, increase the conductor to the next standard size and repeat Steps 6 through 11. Saudi Aramco DeskTop Standards 78 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits Work Aid 1I: Applicable Procedures for Selecting a Feeder Conductor Protective Device Step 1. Select the ampacity rating of an MCCB or an LVPCB based on the ampacity of the conductors as calculated in Work Aid 1F. Note: NEC Article 240-6 (Handout 1, pages 142 and 143) lists the standard ampere ratings of circuit breakers. Note: NEC Article 240-3 (Handout 1, page 141) requires low voltage conductors to be protected in accordance with their ampacities as listed in NEC Tables 310-16 through 310-19 (Handout 1, pages 248 through 251) and their accompanying notes (Handout 1, pages 252 through 255). Step 2. If the conductor ampacity does not correspond with a standard ampere rating of a circuit breaker, select the next standard ampere-rated device. (Note: See NEC Article 240-3(b) (Handout 1, page 141). If the next standard ampere-rated protective device exceeds 800 A, the conductor ampacity must be increased to equal or exceed the device rating or the protective device must be decreased to the next standard lower ampere-rated protective device. Note: See NEC Article 2403(c) (Handout 1, page 141). Saudi Aramco DeskTop Standards 79 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits Work Aid 1J: Applicable Procedures for Selecting a Feeder Conductor Raceway Size Step 1. Select the size of the equipment grounding conductor from NEC Table 250-95 (Handout 1, page 199) based on the size of the selected protective device from Work Aid 1I. Step 2. For type of conductor and number of conductors all of the same size, select the conduit (raceway) size from Tables 3A, 3B, or 3C of the NEC (Handout 1, pages 913, 914, and 915). Note: The term “conductors” includes the phase conductors, the neutral conductor, and the equipment grounding conductor. Step 3. For type of conductor and number of conductors of different sizes: a) Using Table 5 of the NEC (Handout 1, page 916), compute the total crosssectional area of the conductors. b) Select a conduit from Table 4 of the NEC (Handout 1, page 915),where the 40% fill rate area of the standard conduit size is greaterthan the conductor cross-sectional area computed in Step 3a. Saudi Aramco DeskTop Standards 80 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits Work Aid 1K: Feeder Circuit Design Flow Chart Figure 37. Feeder Circuit Design Flow Chart Saudi Aramco DeskTop Standards 81 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits GLOSSARY AWG American Wire Gauge branch circuit The circuit conductors that are between the final overcurrent protective device and the load. bus feeder A type of feeder that supplies power to the main bus of switchgear, a switchboard, or a panelboard. busway Solid copper bars that are insulated and covered in a metal enclosure and that are used to carry large currents for short distances. cable A stranded conductor or a combination of conductors that are insulated from each other. circuit conductor The conductor that is the current carrying element of a branch or feeder circuit. This circuit conductor is usually cable or busway. circular mils (cmil) A measure of the diameter of a wire that equals the diameter of the wire in mils (1/1000 of an inch) squared. conduit A metallic or non-metallic tube that is used to mechanically protect electrical wires and cables. correction factor Factors that are used to derate equipment due to high ambient temperatures, type of installation, spacing, etc. derating factor Factors that are used to derate equipment due to high ambient temperatures, type of installation, spacing, etc. See correction factor. direct burial A method of installing cable underground, where the cable is placed in a trench or ditch and covered with soil. duct bank A method of underground installation of cable, where the duct bank consists of metallic or non-metallic conduit encased in concrete. The complete assembly is buried in a trench or ditch. feeder circuit All circuit conductors that are between a source and the final branch circuit overcurrent protective device. forced-cooled rating Saudi Aramco DeskTop Standards A kVA rating on a transformer that is the transformer (FA) rating with the fans operating. 82 Engineering Encyclopedia Electrical Designing Low Voltage Non-Motor Industrial Feeder Circuits growth factor expansion. A factor that is applied to equipment to allow for future ICEA Insulated Cable Engineers Association IEC International Electrotecnical Commission kcmil (cmil). A unit of measure of wire sizes that equals 1000 circular mils NEC National Electric Code NEMA National Electrical Manufacturer’s Association power cable equipment. A conductor or a group of conductors that supplies current to raceway Any channel that holds wires, cables, or bus bars and it may be metallic or non-metallic. Examples of raceway are conduit, cable duct, and cable tray. self-cooled rating (OA) A rating on a transformer that is the kVA rating of a transformer without the use of any additional cooling methods, such as fans. transformer feeder A type of feeder that supplies power to a transformer. utilization voltage The operating voltage required by a specific piece of equipment. Utilization voltage is the equipment’s rated operating voltage. voltage drop The amount of voltage that is measured (lost) on a conductor between the source and the load. The amount of voltage drop depends on the cable impedance, amount of current, cable size, and length of cable. Saudi Aramco DeskTop Standards 83