Energy and operational cost-saving analysis of air conditioning in a production hall by solar powered vapour absorption chiller Muhammad Khizar Farooq 1*, Dr.AsadNaeem Shah1, Muhammad Farooq2 1. Department of Mechanical Engineering, University of Engineering and Technology, Lahore 54000, Pakistan 2. Department of Mechanical, Mechatronics & Manufacturing Engineering, KSK Campus, University of Engineering and Technology Lahore Pakistan Abstract: Rapid industrialization rising economic development and exponential growth in the world’s population has led to an increasing global demand for energy. In present era, Energy crisis is one of the major issues of Pakistan. Due to non-availability of resources, Pakistan has not been able to completely utilize its Hydel and Thermal power potentials for the production of electricity. Therefore alternate energy resources need to be explored to make up the deficiencies in this sector. A lot of research work has been done to convert solar energy to cost effective commodity over the past few years. Prospects of solar energy are attractive and efficient in countries like Pakistan where we have abundant sunshine hours. The biggest solar contribution to our energy needs can be through solar cooling technology. The use of solar energy for building cooling may potentially provide the solution to these economic and environmental problems. In present research; experiments have been carried out to calculate tons of cooling loads required in a production hall located near Lahore. The dimensions of production area are 128 x 43 x 13 feet to accommodate 75 occupants at a time. Two conventional air conditioning units of 4, 60,000 Btu / h i.e. of 38 tons of refrigeration capacity are currently being used for cooling purpose. Existing cooling load was calculated by Hourly Analysis Program (HAP) which is one of most widely used software at commercial level by HVAC engineers. A graphical demonstration gives relation between varying ambient temperature and corresponding changes in cooling load requirement and amount of KW input required for different number of compressors in use. From this data a comparison is derived between conventional air conditioning and solar powered vapour absorption technology for KW input and operational cost saved as per existing air conditioner operating hours and electricity tariff. Key words: Energy saving by solar energy, vapour absorption chiller, Hourly Analysis Program (HAP). *Corresponding author E-mail: khizarshk@gmail.com 1 1) Introduction Air conditioning is the most widely used medium for meeting cooling demand and maintaining indoor air quality in a room or a hall. However factors like fossil fuel consumption for electricity generation, Global Warming Potential (GWP) and Ozone Depletion Substances (ODS) due to usage of refrigerants are associated with conventional methods of air conditioning. Rise in electricity demand is directly influenced by Industrial and domestic consumer from which major portion of demand and consumption is shared by HVAC sector especially of industrial areas. Continuous and affordable power supply for air conditioning can be assured by research, planning and development of indigenous energy resources, however it is a long term process and exploitation of new resources requires huge capital investment. Turner et al., (2006) explains comprehensively about benefits of alternate energy resources potential in terms of operational cost saving as well as environment friendly emissions. Reduction in Green House Gases (GHGs), controlling GWP and most important of all decreasing dependency on fossil fuels for electricity generation can be done by using alternate energy resources. By using alternative energy resources, different objectives like energy security and universal access to modern energy services could be achieved. Exploration of alternate energy resources as well as energy management can help us in developing a supply chain between energy generation and demand. Problems of energy resources scarcity and environmental hazardous emissions needs to be considered while establishing of long term energy policy and plans. Doubts about return on investment and operational efficacy of renewable energy resources are well addressed by renewable energy power plants operating all over the world. Gelamn (2012) highlighted that in Germany alone installed electricity generation capacity with Photo voltaic (PV) and Concentrated Solar Power (CSP) is over 30 GW and around 8 GW in the US. Kroll (2013) explains one of most practical approach for operational cost estimation of renewable energy resources; it involves not only cost calculation of unused renewable energy resources in place of exhaustible fossil fuels but also by estimation of probability of non-availability of future fossil fuels for future energy demands. This criterion of cost comparison between conventional existing system and non-utilization of an alternate energy system which is renewable, free of cost and inexhaustible has been used in this experimental analysis by a different methodology i.e. with operational cost estimation of both conventional and renewable systems. 2 Substantial amount of energy can be saved if consumption of energy is controlled and monitored. Thus approximately saving 1 KW of energy at consumer end can subsequently result in 5.5 KW energy saving at source taking operational and transfer / distribution efficiency of around 30% and 60 % respectively (Vaishnav, 2013). Philibert (2011) highlighted one of biggest contributions of solar power to our energy needs which are solar heating and cooling technologies. Operating air conditioners by solar energy reduces electricity requirement to run a conventional compressor. One of most widely used type of solar cooling technology category is closed solar absorption cycle. Solar powered vapour absorption chiller is one of complete unit which can be used as substitute of electrically operated conventional air conditioner (Hwang et. al., 2008). Although electricity is also required in Solar powered vapour absorption chiller for its auxiliary parts but it is very less as compared to conventional air conditioner. Compressor of a conventional air conditioner is replaced by 4 units (generator, heat exchanger, expansion valve and absorber) in an absorption chiller. A schematic diagram of solar absorption chiller with its major components is shown in figure 1. Fig. 1 Schematic diagram of solar powered vapour absorption chiller Generator which is the main electricity consumer is powered by solar energy. Type of solar collector is one of major design consideration parameter in this conditioning unit. Kalogirou (2004) elaborates about different 3 types of solar collectors available for commercial use, which includes Flat plate collector (FPC), Evacuated tube collector (ETC) and Parabolic through collector (PTC) etc., all of them have different operating temperature range and perform equally well under particular conditions. 2) Materials and Methods 2.1) Design of absorption chiller Selection of proposed substitute of conventional air conditioning unit with solar absorption chiller involves two major components. Selection of Solar Collector Selection of absorption chiller Where required operating temperature is 80-100 Co Evacuated Tube Collector (ETC) are used whereas Flat Plate Collectors (FPC) are used where temperature less than 80 Co is required (kalogoriou, 2009). List of solar collector properties is shown in table Table 1 Working range of collectors (kalogoriou, 2009) Type of Solar Collector Operating Temperature Range (c ) FPC 30-80 ETC 50-200 Absorption chillers are commercially available in a very wide variety. Several companies like Yazaki Energy Inc., Thermax D. Ltd. etc. offer absorption chillers ranging from 5 to 500 RT capacities which are compatible with solar panels. 2.2) Experimental Section Experimental evaluation has been carried out in two phases. In phase-1 actual cooling load required for existing conditions has been re-evaluated by using HAP. In phase-2 comparison was carried out between operating cost of conventional and solar powered vapour absorption chiller. 2.3) Cooling load calculation (Phase-1) HAP 4.3.4 requires three types of detail for its cooling load calculation process for any area. I. Weather (Region, location, longitude, summer design DB, winter design WB etc.) 4 II. III. Spaces (Floor area, ceiling height, walls, windows, doors, infiltration etc.) Systems (air system type, system components etc.) Summary of all three parameters where cooling load has been calculated are as listed in table 2, 3 & 4 Table2 Weather input in HAP Weather Region Middle East Location Pakistan City Lahore/Sheikhupura Latitude 32 Degree Longitude 74 Degree Elevation 712 Ft Summer Design Db 46 C Winter Design Db -5 C Table 3 Spaces input in HAP Spaces Floor Area 5504 Sq ft Ceiling Height 13 ft Main Doors Area (qty:02) 51.8 Sq ft Emergency Doors Area (qty: 04) 21.73 Sq ft Windows Glass Area (qty:16) 52.5 Sq ft Wall Thickness 9 in Occupants 75 Energy Savers 396 (20 watts each) Total Glass Area on Doors 24 ft 9 in Table 4 Systems input in HAP Systems Air System – Name/Type Air Handling Unit (AHU) / TECO/ 4,60,000 BTU/hr qty:02 Equipment Type Chilled water air handling units Air System Type Constant Air Volume(CAV) SINGLE ZONE 5 3 Results and Discussions 3.1 HAP Report Three required parameters (Weather, Space & Systems) were given to HAP software as explained above and an Air System Sizing Summary was generated which is given below. Air System Sizing Summary Air System Information Air System Name ......................................................... AHU Equipment Class .................................................. CW AHU Air System Type ..................................................... SZCAV Number of zones .................................................................... 1 Floor Area ...................................................................... 5504.0 ft² Location .............................................. sheikhupura, Pakistan Sizing Calculation Information Zone and Space Sizing Method: Zone CFM ................................. Sum of space airflow rates Space CFM ............................ Individual peak space loads Calculation Months ................................................. Jan to Dec Sizing Data ............................................................. Calculated Central Cooling Coil Sizing Data Total coil load ..................................... 36.0 Tons Total coil load .............................................................. 432.2 Sensible coil load ......................................................... 323.4 Coil CFM at Jul 1500 .................................................. 13826 Max block CFM .......................................................... 13826 Sum of peak zone CFM ............................................... 13826 Sensible heat ratio ........................................................ 0.748 ft²/Ton .......................................................................... 152.8 BTU/(hr-ft²) ................................................................... 78.5 Water flow @ 10.0 °F rise ........................................... 86.50 MBH MBH CFM CFM CFM gpm Load occurs at ............................................................ Jul 1500 OA DB / WB .......................................................... 115.0 / 84.0 Entering DB / WB .................................................... 81.7 / 68.2 Leaving DB / WB ..................................................... 59.4 / 58.2 Coil ADP ............................................................................ 57.0 Bypass Factor ................................................................... 0.100 Resulting RH ........................................................................ 55 Design supply temp. ........................................................... 57.0 Zone T-stat Check ........................................................... 1 of 1 Max zone temperature deviation ......................................... 0.0 °F °F °F °F % °F OK °F Central Heating Coil Sizing Data Max coil load ............................................................... 155.5 Coil CFM at Des Htg .................................................. 13826 Max coil CFM ............................................................. 13826 Water flow @ 20.0 °F drop .......................................... 15.56 MBH CFM CFM gpm Load occurs at ............................................................. Des Htg BTU/(hr-ft²) ........................................................................ 28.2 Ent. DB / Lvg DB ..................................................... 69.1 / 79.8 °F Supply Fan Sizing Data Actual max CFM ......................................................... 13826 CFM Standard CFM ............................................................. 13474 CFM Actual max CFM/ft² ....................................................... 2.51 CFM/ft² Fan motor BHP .................................................................. 6.21 BHP Fan motor kW .................................................................... 4.63 kW Fan static ............................................................................ 2.00 in wg Outdoor Ventilation Air Data Design airflow CFM ..................................................... 1400 CFM CFM/ft² .......................................................................... 0.25 CFM/ft² CFM/person ..................................................................... 20.00 CFM/pers 6 It is evident from central cooling coil sizing data that cooling load on coil is 36 Ton which is almost 2 times less than installed capacity. Installed capacity of conventional air conditioners as mentioned before is 76 ton (two units of 38 ton each): additional installed capacity has been developed to ensure production don’t stop in case of mechanical breakdown of any one of the two air conditioning units and to compensate for de-rating factor of air conditioners. Thus 36 ton is taken as theoretical required cooling load for the area under discussion. 3.2 KW annual Energy consumption and operating cost of Conventional Units Energy consumption and operational cost of one conventional unit over period of one year is estimated. Annual workings days were calculated by excluding gazetted holidays. Air conditioner will be operated from April to October. AC operating hours during one day work from 08 45 AM to 03 00 AM were calculated to be equal to 17 hours/day (excluding work breaks) Rest of the data is as below Table 5 Energy consumption and operating cost of Conventional unit Total working days 296 Ac operating days 192 (April to October) Ac operating hours/day 17 Annual ac operating hours 17x192= 3264 Annual Energy consumption *35KWx3264= 1,14,240 KWh Annual operating cost **20x 114240 = 2,284,800PKR Annual maintenance cost ***150,000PKR Total operating cost 2,434,800 PKR * 35KW is the input consumed by TECO (Dong Guang) Air conditioning Equipment Co. Ltd. Model: LP40M1MAR **Industrial electricity unit rate is 12-15 PKR /KWh during off peak loads and 20-24 PKR / KWh during Peak loads, calculation has been carried out at a mid value of 20PKR/KWh. *** Tentative cost of annual maintenance (de scaling & over hauling) 7 Ambient Temperature( C) Cooling Load (RT) 3.3 Ambient Temperature and Cooling load Fig. 2 Graphical comparison between cooling load and temp 36 ton load has been calculated theoretical cooling load at ambient temperature of 46◦C as shown in state 3 in graph. Required cooling load depletes as ambient temperature decreases. In state 2 cooling load comes down 19% for a 10◦C fall in temperature and further drops 65% at 26◦C (cooling load calculated from HAP). Thus it is concluded that at higher temperature proposal for using solar powered cooling technology will be supported since more sun shine hours will be available at higher temperature. KW INPUT Comp AMP 3.4 Compressor amperes and KW Input from system Fig. 3 Graphical Comparison between comp amp and KW input 8 Each of conventional air conditioning unit consists of three compressors. KW input drawn and was recorded from system by operating each of them one after another. It is clear from graph that when all three compressors are in use max KW input are being utilized from system(state 1) and decreases when compressors are turned off one by one in state 2 and state 3. Thus if compressors which are the main electricity consumers in complete system are substituted by a source of same cooling capacity with minimum electricity consumption, a huge amount of saving in terms of cost and energy can be achieved. 3.5 KW annual Energy consumption and operating cost without compressors of conventional units. Each 38 RT conventional air conditioner has 3 compressors and KW consumption of each of compressor motor is 9.75 KW. Specification of particular unit is as below Table 6 Input KW without compressor Capacity *134.8 KW / 460,000 Btu/h / 38 RT Compressor motor *9.75 x 3= 29.25 KW Input *35 KW Input without Compressor for Auxiliaries (Pumps, Evaporator-condenser fans, electrical panels etc.) 35-29.25= 5.75KW *Specification of Model: LP40M1MAR, TECO (Dong Guang) Air conditioning Equipment Co. Ltd. KW energy consumption in this case for annual ac operating hours is shown in table where as in place of compressors an equivalent capacity of solar powered vapour absorption chiller will be integrated. 9 Table7 KW Energy consumption without compressors Total working days 296 Ac operating days 192 Ac operating hours/day 17 Annual ac operating hours 17x 192 = 3264 Annual Energy consumption *5.75 x 3264 = 18768 KWh Annual operating cost 375,360PKR Annual maintenance cost *150,000PKR Total operating cost 5,25,360 PKR * as estimated in table 6 3.6 Comparative Analysis Table 8 Comparative analysis of Conventional Air Conditioner (CAC) & Solar powered Vapour Absorption Chiller (SVAC) Calculations CAC at full load(35KW) SVAC Total working days 296 296 - Ac operating days 192 192 - Ac operating hours/day 17 17 - Annual ac operating hours 3264 3264 - Annual Energy consumption 1,14,240 KWh 18768 KWh 95,481 KWh Annual operating cost 2,284,800PKR 375,360PKR 1,909,440 PKR Annual maintenance cost 150,000PKR 150,000PKR - Total operating cost 2,434,800 PKR 5,25,360 PKR 1,909,440 PKR (approx) (5.75 KW) Saving 10 4) Conclusions Ambient temperature conditions of Pakistan are best for utilization solar cooling technology. Implementation of this technology will help in Peak load / demand management since more solar radiation is available in summer and peak load is also during summer due to air conditioning. Substantial KW energy saving can be done as evident from comparative analysis summary. If KW energy saving is estimated as per concept explained in introduction i.e. 1KW energy saved at end user is equivalent to 5.5 KW of electricity generation at source then it can be concluded that 95,481KWh saving at end user means 530,450 KWh saving at generation source. (Operational efficiency 30% & distribution efficiency 60%) Usage of this technology can give the potential solutions to issues arising from climate changes like GWP and decrease emissions of GHGs. Ozone layer depletion by use of CFCs can also be controlled by use of solar cooling technology Energy security can be addressed by decrease in dependency of fossil fuel. Awareness about renewable energy potential Solar radiation data needs to be thoroughly reviewed and timely updated especially at major cities of country for better assessment about installation feasibility of solar cooling technology at a particular place. Renewable energy resource planning is required at governmental level especially during future planning to meet energy demands. Investor friendly policies need to be established by government to bring down initial capital cost of this technology. 11 References Baker, S.E., Parker, J.D., 2006. Use of Alternate Energy. In: Energy Management Handbook, W.C. Turner., S. Doty (ed), pp. 411-450, 7th edition, Fairmount / CRC, GA, USA. Gelman, R. 2012. Renewable Energy Data Book Washington (NREL), USA: National Renewable Energy Laboratory. Retrieved 2012 from http://www.nrel.gov/docs/fy14osti/60197.pdf Hwang, Y., Radermacher, R., Alili, A.A., Kubo, I. 2008. Review of Solar Cooling Technologies. HVAC & R Research, 14: 507-528. Kroll, M. 2013. The Monetary Cost of Non-use of Renewable Energies (WFC), Hamburg: World Future Council. Retrieved January, 2013 from http://www.worldfuturecouncil.org/fileadmin/user_upload/Climate_and_Energy/Cost_of_n on_use_of_RE.pdf Kalogirou, S. 2007. Recent patents in solar energy collectors and applications. Recent Patents on Engineering, 1, 23-33. Kalogirou, S. 2009. Solar Energy Engineering: Processes and Systems, 122pp. Elsevier / Academic Press, London, UK. Philibert, C. 2011. Solar Energy Perspectives Paris (IEA), France: International Energy Agency. Retrieved November, 2011 from https://www.iea.org/publications/freepublications/publication/Solar_Energy_Perspectives20 11.pdf Vaishnav, A. 2013. Energy Efficiency using Vapour Absorption Technology, India: Thermax Ltd., Retrieved April, 2013 from http://www.icci.com.tr/2013/sunumlar/OT25_Ashis_Vaishnav.pdf 12