POWER TRANSFORMER SENSIBLE MAINTENANCE PLANNING BASED ON FIELD TESTING AND FAILURE ANALYSIS Waleed Abdullah Al-Saadi ¹ * and Mukhtar Ahmed Fazal Karim ² * Saudi Electricity Company (SEC) Kingdom Of Saudi Arabia changer operation, load profile, environmental conditions and its location criticality. SUMMARY The paper discusses the concepts of sensible maintenance planning focused on diagnostic electrical testing for power transformers selected on the bases of certain risk factors like age, load, and environments in SEC-COA Transmission network. Various scenarios of transformer failures are presented here based on the testing analysis of the large power transformers. Using the experience gained through investigation, the paper attempts to address the problem areas assessed in previous failures and tries to put recommendation to improve the existing maintenance planning effective and result oriented towards continuous improvement. Samples from groups containing identical transformers are selected as study cases to find transformer deterioration trends. Proposals for advance testing with diagnostic tools are furnished. Maintenance procedures based on diagnostic testing to address the problem areas of power transformer such as tap change maintenance, bushing change and oil reprocessing. Comprehensive life extension program with the goal to guarantee a reliable and prolonged service. Proposing maintenance steps through extensive diagnostic testing on sample transformer selected in a group of identical characteristics. COMPLEX PROBLEMS TO BE ADDRESSED How to deal with particular equipment showing a symptom of abnormality? How to assess transformers? How to prevent sudden failures particularly catastrophic ones? The goal of this paper is to reply on abovementioned questions and set the maintenance policy directions to achieve best results. KEYWORDS Sensible Management Planning, Diagnostic Testing, Transformer Structure, Frequency Response Test, Recovery Voltage Method, Polarization Spectrum, Dynamic Impedance Test. Data Management System, Data Analyzing Tools 1. INTRODUCTION The existing maintenance policy for HV power apparatus in SEC-network is time based executed during winter season from October to April every year. The existing maintenance policy shall be impressed further based on following concepts for life management of power transformers. Time based management based on condition of transformers such as age, load tap *¹΄² 2. and extend the life of TRANSFORMER LIFE CYCLE CONDITION Four key properties determine the transformer functional serviceability. Ability to transfer energy at specified condition including permissible over voltage and over loaded conditions with out over heating, over Saudi Electricity Company - Protection and Testing Division – Central, P. O. Box 57- Riyadh - 11411, KSA losses, gassing, over vibrations and sound levels. Gas generation. Ability to carry load current without developing hot spots such as high resistance and over heating of current path like bushings, windings, neutral path, selector switch & diverter switch contacts etc. PD activity. Oil deterioration. Increase in sound level and vibration. Ability to withstand strength of insulating materials such as oil, paper, pressboards and core and winding clamps against high voltages high temperature stresses. Increase of no load losses and magnetizing current. Increase in tap changer contact resistance causing local over heating, oil breakdown and gas generation. Oil over heating, oil break down, bubble formation, gas generation. Surface contamination with conducting particles and oil aging products leading to flashover. Formation of sludge in oil shows trend of accelerated degradations. Loosening of clamping, distortion of winding geometry, further deformation by switching surge and through fault current leading to ultimate failure Ability to maintain mechanical integrity under the influence of through fault current, without winding displacements and disturbance of internal components physical geometry. If any one of the above-mentioned conditions is exceeded, the transformer tends to fail or shorten its life span. 3. TRANSFORMER STRUCTURE Transformer is considered to have following structural components. Electro-magnetic circuit. Current carrying path. Insulation boards). Mechanical tap selection system What to do if transformer is gassing in service? Cooling system. Bushings and internal connecting leads. What to do if transformer has low insulation resistance and low polarization index (PI) value from its reference value found during maintenance test? Tap changer leads. Oil preservation and expansion system. What to do if transformer has high dissipation factor (%PF)? Protection and monitoring system. system (Oil, Paper, Press 5. ANALYSIS TO TRANSFORMERS HAVING PROBLEMS (HISTORY CASES) What to do if transformer has high ratio error? Any defect in all above-mentioned structures can affect the functional serviceability of transformer. What to do if transformer has high winding resistance? 4. What to do if transformer has high magnetizing current? What to do if transformer has high winding and oil temperature? POSSIBLE DEFECTS/FAULTS IN THE TRANSFORMER STRUCTURAL COMPONENTS Rise of temperature. What to do if transformer has high vibration and sound level? In reply to above-mentioned questions few study cases are presented below showing actual measurements and real defects found. 5.1 STUDY CASE NO 1 IN SERVICE GAS ALARM WHEN TRANSFORMER LOAD INCREASES . A three-phase generator transformer (GT31) at power plant # 5 in Riyadh with rating 69MVA, 132000/13800, Ynd1, was in the service since 1978. ON 13 April 2004 gas relay alarm operated. Gas relay was found full of gas. Transformer was shut down and thorough investigation launched by on site testing. Winding resistance test at LV side winding revealed the actual defect shown in table 1. Measure ments Between phases R-Y R-B Y-B Measured values (m Ω at 35ºC ambient temperature 7.76 7.75 9.45 5.2 STUDY CASE NO 2 TRANSFORMER FAILED DUE TO REPEATED SWITCHING ON FAULTY DISTRIBUTION CABLE FOR LOCALIZATION OF FAULTY SECTION A three-phase distribution transformer (T12) at substation # 7119 in Riyadh with rating 20MVA, 33000/13800, Ynyn0, was in the service since 1983. ON 27 December 2004 transformer tripped when distribution staff was localizing the faulty section of one of the 13.8kV under ground cable feeder being fed by this transformer by live switch on to fault. Site tests were performed and the analysis results are as under Readings after Time Elapsed HV To Ground LV To Ground HV To LV 1 Minute 1.0 G Ώ 150 K Ώ 10 Minute 1.5 G Ώ 100 K Ώ 1.5 G Ώ PI value 1.5 0.67 1.5 1.0 G Ώ Remarks Normal Normal High resistance in current path Table 1: LV Winding Resistance Measurements by Transformer Ohmmeter. Exciting current HV side (mA) R Y B Ph Ph Ph Measured ratio Table 3: Ratio and Exciting Current Test Results Winding under test mA Watts C (pF) % POWER FACTOR LV to HV+ Ground 108 1002 10814 246 Table 4: Power Factor Test at 5kV ac From the table 3 and 4, it is clear from the test results that the winding displacement has occurred resulting drastic changes in internal geometry of physical components. 6.91 6.82 2.3902 B Ph 287 Y Ph 2.3902 R Ph 2.4274 The reason of Gassing transformer in service was due to dangerous overheating of the contact of interconnecting lead between Y-B of LV windings at higher loads. This problem was revealed by precision winding resistance test TAP NO Computed Ratio 2.3913 5.1.1 ANALYSIS REMARKS LV side defective Table 2: Polarization Index (PI) Test Results 5 All other tests like turns ratio, insulation resistance, magnetizing current, dissipation factor were found normal. Gas was released and transformer energized again. When load reached 50MW, gas alarm initiated again confirming the loose joint. It was decided to carry out inspections after untanking the windings. A clear burnt-joint was found in the LV side Y-B interconnecting lead. Burnt contact was properly repaired and tested. Transformer was re-energized after reassembling without any further problem. Remarks 5.2.1 ANALYSIS REMARKS Loosening its clamping system has caused winding displacement. Loosening of clamping can’t happen suddenly. It is a slow process in stages developed by mechanical forces due to through fault currents passing repetitively. Voltage ratio, magnetizing and Cap & DF measurement tests are important for predictive maintenance. In order to prevent sudden failures, a predictive approach can be developed by maintaining the history record of all above-mentioned test results. Once a method is adopted with certain test equipment the same shall be repeated for next planned maintenance turn. Any change in ratio, magnetizing current and capacitance will indicate winding movement. Once the movement is detected, steps could be taken prevent it by particular service arrangements. Instructions were issued to use alternate methods for fault isolation instead of live switch on to faulty cable. 5.3 CASE STUDY NO 3 POLARIZATION INDEX (PI) VALUE FOUND LOW WHEN MEASURED DURING INVESTIGATION TESTS AFTER TRIPPING. A three-phase generator transformer (GTR 5) at power plant 7 Riyadh with ratings 125MVA 132kV/13.1kV/13.1kV, Ynd1d1 was in service since 1978. On 18 December 2004, the transformer tripped on differential protection operated. After necessary isolation the transformer was thoroughly checked and tested with following predictive test results. Reading After Time Elapsed 1 minute 10 minutes PI value Insulation resistance (IR)----M Ώ HVLV1LV2Ground Ground Ground 960 332 2800 2160 308 5700 2.25 0.927 2.037 Remarks LV1 is suspected Table 5: Insulation Resistance Test with (PI) Measurement by 5kv Tester It was decided to isolate LV1 bushings from its windings. After isolation, the same PI test was repeated on LV1 windings and bushings separately with results indicated in table 5 analyzed as above. LV1 windings found normal. LV1 red and yellow phase bushings found normal with PI value >2. LV1 blue phase bushing found abnormal with PI value< 1 Blue phase bushing was replaced with new one and same test repeated with good results. Transformer was put back into service without any further problem. 5.3.1 ANALYSIS REMARKS Polarization index (PI) i.e. [10 minute IR value/1 minutes IR value] is an important predictive test as experienced above. It can assess the degree of deterioration. PI value less than 1 indicates serious problem. Timely change of defective parts like bushings can save the transformer from total failure in future. 6. MAINTENANCE PLANNING STRATEGY Before proceeding to transformer maintenance planning, one should understand following points. What are the factors affecting the transformer life? What are the steps for planning focused maintenance How to manage electrical testing to predict future failures? How to make decisions for preventive actions? 7. FACTORS AFFECTING TRANSFORMER LIFE a. Voltage Transients b. Heat and overloading c. Moisture and dirt. d. Insulating oil Decay e. External Short Circuits. f. Poor manufacturing 9. Figure 1: Transformer Life Cycle Stress levels 8. PLANNING FOCUSED TRANSFORMER MAINTENANCE When setting up a maintenance program the key is to get the most efficient use of your maintenance resources based on the risk factors and importance of the transformer. Therefore planning a maintenance program consideration should be given to the following key questions. How important is this transformer in its present location and what is affected if it is lost? If a transformer has sensitive location feeding important consumers and directly affects a key process and has no backup available then it should be considered a high priority How old is the transformer? Old transformers are more subject to failures of external components and gaskets because of their age. What is the shape of the load profile? If the load is steady state, then there will be less internal mechanical stresses. A load profile that has drastic fluctuations will cause heavy mechanical stress on the coil assembly. . What is the surrounding environment like? Units that operate inside closed transformer bay tend to suffer more from overheating because of poor airflow. They may also be exposed to harsh environments depending of the process being operated at the facility. Outdoor units tend to be less sensitive to the environment but are more at risk because of things like vandalism and weather conditions. Start the planning stage by identifying the most important transformers in the network system. These transformers will be easy to find since they are the ones that if lost, will cause the greatest effect on consumer on going process. TRANSFORMER SELECTION CRITERIA FOR STUDY CASES SEC-COA existing maintenance policy should be impressed further to include study cases in order to diagnose trends towards deteriorations through electrical testing. Certain selection criteria are needed to choose such samples. To find such study samples groups containing transformers with same manufacturer and ratings are separated. Out of these groups, transformers as study case are selected based on following risk factors. Importance Age Loading Environment 10. MAINTENANCE ACTION PLANS Maintenance plan consists of four key actions [4] Outline Inspections Preventive Actions Predictive Actions Corrective Actions 10.1 OUTLINE INSPECTIONS 10.1.1 VISUAL INSPECTION IN SERVICE THROUGH SPECIFIED CHECKLIST SUMMARIZED AS UNDER. Abnormal Sound levels in transformer bay Winding and oil temperature On line DGA device readings. HV bushing pressure gauge readings Oil level gauge readings. Oil and Gas sampling device checking for any gas present. Oil leakages Discoloring of transformer tank surface. Visual inspection in service should be performed every month for all transformers especially during the peak load season. and Recovery Voltage Measurement test (RVM) [2] 10.1.2 DETAILED INSPECTIONS & TESTS DURING OUTAGE PERIOD WITHOUT DISMANTLING ANY EQUIPMENT Windings and bushings insulation resistance test with polarization index (PI) measurements Dielectric loss (Tan-Delta Test) measurement on HV bushings through test tap Winding resistance test on all taps and on all windings Voltage ratio and magnetizing current measurement test. Tap changer motor input current measurement during tap change cycle [1] Detailed inspections should be performed every 5th year for all transformers. 10.2 OLTC Dynamic Resistance Measurement test [1] Voltage ratio and magnetizing current measurement test Short circuit impedance measurement tests Tap changer driving motor input power measurement test during tap change cycle [1] Sweep Frequency Response Analysis test (SFRA) [3] PREVENTIVE ACTIONS DGA for Insulating oil samples performed on regular bases Repair or replacement of aged parts, assessed from outline inspections mentioned above, as leading to future troubles 10.3 PREDICTIVE ACTIONS FOR STUDY CASES For thorough investigation on a particular transformer selected as study case or bad history of alarms or trips initiated in service, following diagnostic tests are recommended. Suitable planned outages shall be arranged for suspected equipment based on above mentioned inspections and previous history of gas alarm generation Certain part like cables, jumpers should be dismantled. Only transformer with its bushings left for detailed tests. Detailed testing is performed as under Windings and bushings insulation resistance test with Polarization Index (PI) Core and core clamp insulation resistance test. Dielectric loss (Tan-Delta Test) measurement for windings and HV bushings through test tap. Winding resistance test on all taps and on all windings with assessment of diverter switch condition during tap change operation. 10.4. CORRECTIVE ACTIONS Decision should be taken by well-experienced senior engineers on the bases of abovementioned test record and its evaluation to perform internal inspections through inspection holes. Major overhaul should be launched in case of the defects are repairable. 11. DATA MANAGEMENT SYSTEM [6] Gathering correct data from field-testing and maintaining records in a proper way is key to successful diagnosing problem much earlier than it becomes a disaster for the transformer. Field-testing without comparison to previous records has no meaning but wastage of time and money. In order to manage records of field tests, keep all test records in the database especially available with special test equipments listed in appendix 3 for particular transformers under maintenance. Three steps are explained as under: Data Management Test Conditions Analysis Techniques 11.1 DATA MANAGEMENT 12. TEST CONDITIONS All modern test equipments listed in appendix 3 have their-own data management and analyzing software, which can be efficiently used to diagnose faults. If the test equipment is not associated by any data handling software then data can be arranged in normal MS Excel Spreadsheets as Sheet 1 as transformer identity and name plate data Sheet 2 as Visual inspection in service through specified checklist. Sheet 3 as Windings and bushings insulation resistance test with Polarization Index (PI) and Recovery Voltage Measurement test (RVM) Sheet 4 as Core and core clamp insulation resistance test. Measurements are sensitive to ambient conditions such as temperature humidity etc. Transformer maintenance shall be planned at same date and time when it was tested in previous maintenance turn so that the ambient conditions do not vary too much. Note down all test conditions in the test data sheet with date and time. Transformer condition should be same as tested before such as cables and jumpers removed. Only transformer own bushings shall be used as test points. Try to use the same test equipment as used before in previous tests on the same transformer under study. Use latest model test equipment listed in appendix 3 with data management and analysis software. Sheet 5 as Dielectric loss (Tan-Delta Test) measurement on HV bushings through test tap Sheet 6 as Winding resistance test on all taps and on all windings with assessment of diverter switch condition during tap change operation Sheet 7 as OLTC Dynamic Resistance Measurement test Sheet 8 as Voltage ratio and magnetizing current measurement test. Sheet 9 as Short circuit impedance measurement tests Sheet 10 as Tap changer driving motor input power measurement test during tap change cycle. Sheet 11 as Sweep Frequency Response Analysis test (SFRA) Sheet 12 as Transformer problems and corrective measures history record Rename all sheets with suitable names. 13. DATA ANALYZING TECHNIQUES Two analyzing techniques are used for the purpose of graphical interpretation. The methods are signature and comparison. 13.1 SIGNATURE TECHNIQUE This technique takes the measurement from all the three phases of a transformer and creates a single value to represent the condition of the transformer at the testing time as under. Key equation: A = (R + Y +B) / 3 Where, R Ξ Red phase measurement value Y Ξ Yellow phase measurement value B Ξ Blue phase measurement value A Ξ Average value of red, yellow and blue phases for particular test. S = √ [(R – A) ² + (Y – A) ² + (B – A) ² 11.2 GRAPHICAL DISPLAY OF TEST RECORDS Where, All the test data should be kept in columns of spreadsheets. S Ξ Single value to represent transformer condition. MS Excel charts generate graphical displays of test records and comparing them with one another or with footprints will assess the transformer condition trends. S = Zero means all phases ideally identical. S > 0 indicates dissimilarity in phase’s condition. A single value created out of measured values from all the three phases to show the similarity of windings at the testing time. This technique requires transformer characteristics in healthy condition. Measurements acquired from factory can be regarded as footprint or reference value. How ever if factory test records are not available then historical test data can be considered as fingerprints. mentioned in this paper can diagnose failures of power transformers much before these actually happened. Though real testing at site is limited due time constraints. The schedules are being made very tight not enough time given for proper testing. This hasty test has no use. It is better to select a group of transformers with same characteristics and select one sample out of those to perform representative detailed study. Result can be applied to all. Sensible maintenance plans can save lot of time, money and enhance the efficient use of manpower. In order to promote result oriented and updated the maintenance testing techniques, this paper tries to introduce some of the dynamic testing techniques in addition to conventional test methods. Managing test data and then analyzing it for further preventive action is primary task of this paper. 13.2 COMPARISON TECHNIQUE This technique compares a reading from one phase of a transformer to a reference set of data. The difference between the two readings represents the condition of transformer winding as compared to reference. Reference data can be obtained from the healthy phase of the same transformer or the identical transformer near by in same location. It is to be highlighted here that the signature of the healthy reference phase must be obtained from the same winding that is either high voltage or low voltage as phase under study D = M – Ref Where REFERENCES M Ξ Measured value Ref Ξ Reference data [1] J.J. Smith+, “ Decision Making Experience With Maintenance Diagnosis Of High Voltage Equipment”, Kema T & D Power [2] Volker Karius +, “ Practical Foundation Of The Recovery Voltage Method (RVM)”, Hefley Trench AG Switzerland. [3] Muhammad Aziz Abdul Rahman, Halimatun, Ps Ghosh, “Frequency Response Analysis Of A Power Transformer” Universiti Tenaga Nasional. [4] M.H. Rahman, “ Maintenance Of Electrical Equipment” IEP-SAC Journal 2003-2004. [5] V.V Sokolov, “ Consideration On Power Transformer Condition Based Maintenance” EPRI Substation Equip Diagnostic Conference VIII Feb 20-23-2000, New Orleans, LA [6] Robert Houbaer+,’ Power Transformer Asset Management’ APWA International Public Works Congress, NRCC/CPWA Seminar Series 2000. D Ξ Difference between measured and reference data. D = Zero means all phases ideally identical. D > OR < 0 indicates dissimilarity in phases condition. This technique needs reference data. It will be very useful if historical data is available so that the difference can be analyzed. From the above analysis, ones the clear trend is established for particular test, and the trend line reach to unacceptable limits set by the appendix 1, the problem source can be identified explained in appendix 2 for further preventive or corrective measures. 14. CONCLUSIONS Power transformer is the heart of electrical utility. In order to insure it’s healthy operation, steps are required to take preventive and predictive measures. Diagnostic techniques APPENDIX 1 Test Criteria and Defect Analysis Type Of Tests Test Criteria and defect analysis Windings and bushings insulation resistance test with polarization index (PI) measurements PI <1-- Equipment defective 1 < PI > 1.5 --satisfactory 1.5 <PI >2.5 --good PI > 2.5 –excellent Recovery voltage test On polarization spectra curve less dominant time constant (Td) indicates more moisture contents. Curve peak shifting towards left side with steep rise indicates high moisture contents in the transformer. Refer to figure 3. Dielectric loss (Tan-Delta Test) measurement on HV bushings through test tap %DF (PF) at 20ºC 0.25 to 1 for new P/TFs 0.75 to 1.5 for 15 year old P/TFs More than 5.0 is problem for investigated Winding resistance test on all taps and on all windings. Condition of diverter switch for transition time between tap change process Resistance shall increase or decrease gradually. Any abrupt change from tap to tap indicate tap changer contacts bad condition. If the transformer ohmmeter trips during tap change operation then there is problem in diverter switch diverting resistances. OLTC Dynamic Resistance measurement test Magnitude of current transients captured on each tap change indicates the condition of tap position. Comparing the transients captured on several tap positions it can be concluded as high resistance and action for further check up. Turns ratio and measurement test magnetizing current Measured turns ratio should be within 0.5% of computed value. Especially at principal tap, turns ratio outside this limit indicates winding defects. Any abrupt change in magnetizing current from tap to tap indicates turn-turn short. Tap changer motor input current measurement during tap change cycle. Power measured at the time of commissioning shall be taken as fingerprints. If new record shows any noticeable change then there could be mechanical problem in driving mechanism. Short circuit impedance measurement tests. Fingerprints shall be developed for short circuit impedance when transformer is new and normal. Noticeable change in impedance value when measured under same condition indicate mechanical distortion and dislocation of transformer windings due passage of fault currents. Sweep Frequency Response Analysis (SFRA) test Refer to figure 2 For a given transformer new frequency response plot is compared with previous records taken at different time during maintenance. Clear differences from previous records indicate core movement, winding deformation, faulty core grounds, partial winding collapse, broken or loosened clamping structures and short or open windings. Figure 2- Sample of Sweep Frequency Response (SFRA) Test Record Dominant time constant (Td) Figure 3: Sample Of Recovery Voltage Method (RVM) Test Record Newly energized After 15years In Service. Figure 4 - RVM Polarization Spectrum For Transformers Shifting of the curve peak (Td) towards right side indicates more moisture contents in transformer under test. APPENDIX 2 Power Transformer Component Defects [5] System, Components Defect Fault & Symptoms Electromagnetic Circuit Loose Clamping Short Circuit (Opencircuit) in grounding circuit Abnormal circulating current Floating potential Aging lamination Insulation degradation General overheating Localized hot spot Sparking/dischargers Gassing Winding strands, leads Poor joint Localized hot spot Connection, joins, contacts Poor contacts, Contact deterioration Open-circuit, Short-circuit Major insulation Excessive water, Oil contamination Destructive PD Minor insulation Surface contamination Localized tracking Leads insulation Abnormal aged oil Creeping discharge Electrostatic shields Abnormal cellulose ageing PD of low energy Excessive aged/overheated Cellulose Flashover Loose clamping Winding distortion Core Structure Insulation Clamping Structure Magnetic Shields Grounding Circuit Windings (Turns, parallels) Failure Current carrying circuit Dielectric system Mechanical Windings Clamping Radial buckling Leads support Axial Twisting Failure of insulation Cooling system Heat exchanger Contamination Cooling deficiency Pumps Wrong rotation, bearings General overheating Fans Overheating, failure, Malfunction Piping external and internal Poor oil flow Penetration of decay product Into oil Bushings Local defect: moisture, air Ionization Condenser core Overstressing, Dielectric overheating Ageing, oil instability Thermal run away Core surface, oil Conductor Over-saturation Moisture, Flashover Aging Explosion Poor contact, Overheating OLTC Motor driver, shaft Couplings, fixing Selector & reverser Diverter switch Mechanical damage Cooking Discharges Contacts overheating Malfunction Contamination Dielectric breakdown Contacts wearing out Contamination Mechanical deficiency Mal-function Oil preservation & expansion Tank, conservator, Low oil level Preserving components, Poor sealing Piping APPENDIX 3 Recommended Test Equipment For Power Transformer Diagnostic Testing. Diagnostic Test Suitable Test Equipment Windings and bushings insulation resistance test with Polarization Index (PI) and Recovery Voltage Measurement test (RVM) Recovery Voltage & Insulation Measuring Unit Type ETP-2 Recovery Voltage Meter type RVM 5462 Core and core clamp insulation resistance test. 5kv Insulation Tester Type BM21 Dielectric loss (Tan-Delta Test) measurement on HV bushings through test tap 10kv Automated Insulation Test Set Type Delta-2000 Winding resistance test on all taps and on all windings with assessment of diverter switch condition during tap change operation. Winding Resistance Measurement Unit Type ETP-3 OLTC Dynamic Resistance Measurement test. Transient Recorder Type IDMT1 Voltage ratio and magnetizing current measurement test. Transformer Turns Ratio Measurement Unit Type ETP-1 Short circuit impedance measurement tests. Short Circuit Impedance Measurement Unit Type ETP-4 Tap changer driving motor input power measurement test during tap change cycle. Power Multi-Meter Type PMM-1 VER 2.5 Frequency Response Analysis test (FRA) Sweep Frequency Response Analyzer type M5100,