01/29/16 DESIGN NO. _____ SECTION 15510 HVAC PIPING PART 1 - GENERAL 1.01 DESCRIPTION OF WORK A. 1.02 Provide pipes, pipe fittings, pipe specialties, and pipe supports as shown on the Drawings, and as needed for a complete and proper installation. Product specific requirements are contained herein; Section 15501, General Provisions for Heating, Ventilating and Air Conditioning Work, shall be referred to for general requirements. DESIGN AND PERFORMANCE REQUIREMENTS A. B. Steam and Condensate Piping System High Press. Operating Pressure Over 16 psig Over 251oF. 212oF to 250oF Design Code (ANSI) B31.1 B31.9 Heating Hot Water Piping 125 psig 40o - 60oF B31.9 Condenser Water Piping Operating Pressure Operating Temperature Design Code (ANSI) NYCSCA 125 psig 150o - 250oF B31.9 Chilled Water Piping Operating Pressure Operating Temperature Design code (ANSI) D. 0-15 psig Operating Temp. Operating Pressure Operating Temperature Design Code (ANSI) C. Low Press.& Pumped Cond. 125 psig 80o - 110oF B31.9 HVAC PIPING 15510 - 1 01/29/16 E. DESIGN NO. _____ Dual Temperature Water Piping Operating Pressure Operating Temperature Design Code (ANSI) F. Refrigerant Piping Operating Pressure Operating Temperature Design Code (ANSI) G. 1 1.04 30 - 38 141.8 - 137.0 D396-86 RELATED SECTIONS A. Division 2 Sections B. Division 3 Sections E. Division 4 Sections D. Division 5 Sections E. Division 7 Sections F. Division 8 Sections G. Division 9 Sections H. Division 15 Sections SUPPLEMENTAL SUBMITTALS A. Shop Drawings: Submit schedule showing pipe or tube weight, fitting and joint type for each piping system; size, location and feature for each piping specialty, expansion compensation, hanger and support. 1. NYCSCA 150 psig 40o - 120oF B31.5 Fuel Oil Piping Grade 2 (Distillate) Gravity (API) Heating Value (MBTU/gal) Design Code (ASTM) 1.03 125 psig 40o - 250oF B31.9 Grooved joint coupling and fitting product submittals shall be specifically identified with the applicable manufacturer’s style or series number. HVAC PIPING 15510 - 2 01/29/16 B. 1.05 2. Submit the underground oil piping protection system design (cathodic protection by sacrificial anodes or impressed current) for approval. 3. Provide shop drawings of condensate lines showing all diameters, pitch, cleanouts, traps, routing and terminations. Certifications 1. Welding Certifications: Submit reports as required for piping work. 2. Brazing Certifications: Submit reports as required for piping work. 3. For expansion bolts installed in concrete, submit ICC certification for use in cracked concrete. SUPPLEMENTAL QUALITY ASSURANCE A. NYCSCA DESIGN NO. _____ Codes and Standards 1. Welding: Qualify welding procedures, welders and operators in accordance with ASME B31.1, or ASME B31.9, as applicable, for shop and project site welding of piping work and ASME Boiler and Pressure Vessel Code, Section IX, Part QW Welding or in accordance with AWS B2.1 Specifications for Welding Procedure and Performance Qualification per Section MC 1203.3.6 of the 2014 NYC Mechanical Code. 2. Certify welding of piping work using Standard Procedure Specifications by, and welders tested under supervision of, National Certified Pipe Welding Bureau (NCPWB). 3. Brazing: Certify brazing procedures, brazers, and operations in accordance with ASME Boiler and Pressure Vessel Code, Section IX, Part QB Brazing for shop and job-site brazing of piping work or in accordance with AWS B2.2 standard for Brazing Procedure and Performance Qualification per Section MC 1203.3.1. 4. Fluid Control Institute (FCI) Compliance: Test and rate "Y" type strainers in accordance with FCI 73-1: Pressure Rating Standard for "Y" Type Strainers. Test and rate other type strainers in HVAC PIPING 15510 - 3 01/29/16 DESIGN NO. _____ accordance with FCI 78-1: Pressure Rating Standard for Pipeline Strainers Other than "Y" Type. NYCSCA 5. EJMA Compliance: Construct expansion compensation products in accordance with standards of the Expansion Joint Manufacturer's Association (EJMA). 6. Manufacturers Standardization Society of The Valve and Fittings Industry (MSS) Compliance: Comply with: MSS SP-58 Pipe Hangers and Supports - Materials, Design and Manufacture MSS SP-69 Pipe Hangers and Supports - Selection and Application MSS SP-89 Pipe Hangers and Supports - Fabrication and Installation Practices Piping shall be supported at distances not exceeding the spacing specified in MC Table 305.4 or in accordance with the above MSS standards. 7. Comply with ANSI B31.1A, ASME Code for pressure Piping, and ASHRAE Equipment Guide. 8. New York City Construction Codes: Comply with the 2014 New York City Building Code, Mechanical Code, Fuel Gas Code, Plumbing Code and Fire Code. 9. Testing of material shall be in accordance with Section §28-113 of the NYC Administrative Code (reference Section MC 301.5). Whenever the NYC Construction Codes or the Rules of the Department of Buildings requires that material be listed or labeled and material proposed to be used is not so listed or labeled, the use of such material shall be subject to prior approval by the Commissioner (Office of Technical Certification and Research OTCR) and such material shall be used only to the extent set forth in such approval. Materials that were previously approved by the Board of Standards and Appeal (BSA) or by the Department (MEA) before the effective date of the NYC Construction Codes may continue to be used, but only to the extent set forth in such approval, and only if such approval is not specifically amended or repealed by the Commissioner. HVAC PIPING 15510 - 4 01/29/16 DESIGN NO. _____ PART 2 - PRODUCTS 2.01 PIPES A. Pipe used shall be free from scale or rust. Each length of pipe shall be properly marked at the mill for proper identification with name or symbol of manufacturer. Dimensions for steel pipe shall be in accordance with the ANSI B36.10. Dimensions for red brass pipe shall be in accordance with ASTM B251. B. Steel Pipe 1. 2. Black or Galvanized; Standard Weight: Schedule 40 or Extra Heavy Weight: Schedule 80; ASTM A135 or ASTM A53 or ASTM A106, however fuel oil lines and diesel oil lines for equipment or tanks above the level of the lowest floor shall only be seamless black steel pipe ASTM A53 Grade B, Type S or ASTM A106, Grade B, Schedule 40 with welded connections up to the oil tank or equipment except that fittings at the tank or equipment, shut-off valves and other fuel oil flow and control devices may be screwed or flanged per Section MC 1305.9.5. a. Steel Pipe for Threading: ASTM A53 Type F, Type E or S; ASTM A135 or A106. b. Flanging: ASTM A53, Type E or S; ASTM A135 or ASTM A106. (Type F not permitted for flanging). c. Bending and Coiling: ASTM A53, Type F, Type E or S; ASTM A135 or ASTM A106. d. Grooved End Type: Schedule 40, ASTM A53, Type F, Type E or S; or ASTM A135 or ASTM A106. Steel pipe shall be manufactured by: Koppel Steel Corp. North Star Steel Co. Sawhill Tubular Co. Sharon Tube Co. U.S. Steel Co. Wheatland Tube Company NYCSCA HVAC PIPING 15510 - 5 01/29/16 C. DESIGN NO. _____ Brass Pipe 1. Semi-annealed seamless drawn; ASTM B43; 84 and 86% copper. 2. Brass pipe shall be manufactured by: Anvil International Mueller Industries Phelps-Dodge Copper Products Corp. Revere Copper & Brass, Inc. Merit Brass Company. Trenton Pipe Nipple Company D. Copper Tubing 1. Hard-Drawn Temper; Water tubes shall be Type L or K per ASTM B88; Refrigerant lines shall be ACR tube per ASTM B280. Other refrigerant pipe and tubing options are as defined in Section MC 1107.5. Oil lines other than steel may be provided. If provided, lines shall be in accordance with MC Table 1302.3. Oil copper or copper-alloy tubing shall be Type K or Type L PVC Coated per ASTM B75; ASTM B88; ASTM B280. 2. Copper tubing shall be manufactured by: Mueller Industries NIBCO Inc. Phelps-Dodge Copper Products Corp. Revere Copper and Brass Inc. E. Ductile Iron Pipe 1. Ductile iron pipe shall have an outer coating of coal tar and shall comply with the requirements of the latest Standard Specifications of ANSI A21.51 and AWWA C151; AWWA C115. a. Thickness class of pipe shall be as follows: Water Service piping: thickness class 52 for 3” & 4” diameter pipe and thickness class 56 for pipe size greater than 4”. b. Ductile iron pipe shall also comply with the following requirements: 1) NYCSCA Marking: the weight and class and other designated markings required by ANSI HVAC PIPING 15510 - 6 01/29/16 DESIGN NO. _____ specifications shall be stenciled at the foundry on all ductile iron pipe, fittings and specials. Markings shall be painted conspicuously in white on the outside of each pipe length, fitting and special casting after the shop coat has hardened. 2) 2. Cement Lining: Pipe shall be cement lined in accordance with ANSI, Standard A21.24, with thickness of lining to be 1/8" minimum. A plus tolerance of 1/8" shall be permitted on all sizes of pipe. Manufacturers U.S.Pipe and Foundry American Cast Iron Foundry Amstead Industries 2.02 FITTINGS A. NYCSCA Steel, Malleable/Cast Iron 1. Steel Fittings, except couplings and unions, 21/2" and less: Threaded pattern, standard weight, black cast iron, suitable for a working steam pressure of 125 psi, except as otherwise specified below. 2. Flanges, Welding Neck Type, Same Pressure Rating as Adjoining Pipe: ANSI/ASME B16.5. Welding flanges shall be socket type. 3. Weld Fittings, Carbon Steel: Butt Welding Type: ANSI/ASME B16.9: Allied Piping Products Co., Inc.’s Branchlets, Type 1 or 2 or Bonney Forge Corp.’s Weldolets; Socket Welding Type: ANSI/ASME B16.11 Allied Piping Products Co., Inc.’s Branchlets, Type 1 or 2 or Bonney Forge Corp.’s Thredolets or Sockolets. 4. Grooved End Type: Steel ASTM A53 Grade B or Ductile iron ASTM A536 Grade 65-45-12; with factory grooved ends designed to accept manufacturer’s couplings. 5. Malleable Iron, Steam Pattern Threaded: ANSI/ASME B16.3 for 150 lb Class and 300 lb Class. HVAC PIPING 15510 - 7 01/29/16 DESIGN NO. _____ 6. Cast Iron, Steam Pattern Threaded: ANSI/ASME B16.4, Flanged Fittings and Threaded Flanges: ANSI/ASME B16.1 for standard weight pipe: Class 125 and for extra heavy weight pipe: Class 250. Gray iron shall be in accordance with ASTM A126 per MC Table 1202.5. 7. Steel and malleable/cast iron pipe fittings shall be manufactured by: Anvil International CIFUNSA Marketing, Inc. Smith-Cooper International Tube-Line Victaulic Co. of America Ward Manufacturing Weldbend Corporation TYCO Grinnell Mechanical Products Shurjoint Piping Products The Viking Corporation B. Brass 1. Malleable brass, threaded pattern; flanges, brass for use in brass pipe or copper tubing systems: Flanges shall conform to the Standards for fittings used in the systems. Brazing Flanges, With or Without Pre-inserted Rings of Brazing Alloy: ASME B16.15, with hubs modified for brazing ends. Brass fittings shall conform to ASTM F1974 per MC Table 1202.5. 2. Brass Fitting shall be manufactured by: Anvil International Elkhart Products Corp. Lee Brass/S. G. Flagg Co. Mueller Industries NIBCO Inc. Smith-Cooper International C. Unions class, bronze joint, rating 1. NYCSCA 3" Size and Under: Steel: malleable iron, 300 lb with brass to iron or brass to brass seats and to bronze, bronze to iron, or brass to iron ground except as otherwise specified. The pressure shall be indicated on the union. Unions for Use in Brass Pipe or Copper Tubing Systems, 2" and under: Cast bronze, 150 lb Class, HVAC PIPING 15510 - 8 01/29/16 DESIGN NO. _____ with bronze to bronze seats; with screw, brazing or solder ends, or with adapters as required. 2. Union shall be manufactured by: Anvil International E.M. Dart Co. NIBCO Inc. Smith-Cooper International Weldbend Corporation Ward Manufacturing LLC The Viking Corporation D. Fittings for Type "L" copper tubing 1. NYCSCA Fittings shall be wrought copper solder joint fittings suitable for brazing and shall be in accordance with ANSI B16.22. Type "L" fittings shall have a minimum working water pressure of 150 p.s.i. a. Flux for brazing Type L shall be equal to "Handy Flux" and shall comply with Navy Dept. Spec. 51F 4a. b. The silver brazing alloy for brazed Type L joints shall be similar to Handy & Harmon SilFos brazing alloy having a silver content of not less than 15% and a flow point of 1300oF. 2. Alternately, fittings for Type "L" copper tubing may be cast bronze threaded fittings, Class 125 working steam pressure, conforming to ASTM B62 and ASME B16.24. 3. Grooved end fittings for Type “L” copper tube: ASME B16.22 wrought copper or ASME B16.18 bronze casting; dimensioned grooved ends designed to accept manufacturer’s couplings. 4. Alternately, hydronic fittings for cold and hot water piping and chilled water piping may be press fittings (press fit - pressure-sealed joints) by Viega ProPress, Elkhart Xpress, NIBCO Press System, Grinnell G-Press (or approved equal) up to and including 4” in diameter. O-rings: EPDM; Special Tools recommended and approved by the Manufacturer. HVAC PIPING 15510 - 9 01/29/16 DESIGN NO. _____ 5. Type "L" fittings shall be manufactured by: Elkhart Products Corp. Mueller Industries NIBCO Inc. Smith-Cooper International Viega ProPress Victaulic Co. Anvil International TYCO Grinnell Mechanical Products Shurjoint Piping Products Oil lines other than steel may be provided. If provided, lines shall be in accordance with MC Table 1302.3. Copper tubing joints used in refrigerating systems containing Group A2, A3, B1, B2, or B3 refrigerants shall be brazed. Soldered joints shall not be used in such refrigerating systems according to Section MC 1107.5.4. E. NYCSCA Fittings for Ductile Iron Pipe 1. Mechanical joints consisting of bell end with cast flange, cast iron gland, rubber gasket and necessary bolts and nuts shall conform to AWWA C110 and C153. Bolts shall be high-strength, low-alloy steel with minimum 45,000 psi yield strength and comply with AWWA C110 and C153. Unless otherwise specified, gasket material shall be rubber. 2. Fittings and accessories for ductile iron pipe shall comply with the requirements of the latest Standard Specifications of ANSI A21.10 and ANSI A21.11. Mechanical joints shall be similar to Tyton Joint by U.S.Pipe. F. Mechanically formed tee-branch outlets (refer to Section MC 1203.3.8) may be used on aboveground copper tubing. The mechanically formed outlet shall be by T-Drill Industries, Inc. or approved equal. All joints formed in this manner shall be brazed in compliance with Section MC 1203.3.8.2 and manufacturer’s recommendations. Soft soldered joints shall not be permitted. G. Couplings: Same material and pressure rating as adjoining pipe, conforming to standards for fittings in such pipe. Use taper tapped threaded type in screwed pipe systems operating in excess of 15 psig. H. Grooved Joints - for Steel Piping: Rolled or cut grooves, Pipe: Carbon Steel, ASTM A53, or ASTM A106, EPDM gaskets; HVAC PIPING 15510 - 10 01/29/16 DESIGN NO. _____ Housing: Ductile Iron. System shall be designed for flexible or rigid installation. Welded flanges shall be used at equipment connections, and for maintenance removal sections. Manufacturers: Victaulic, Anvil International Inc, TYCO Grinnell Mechanical Products or Shurjoint Piping Products 1. 2. Rigid Type: Housings shall be cast with offsetting, angle-pattern bolt pads or recessed tongue and grooves to provide system rigidity and support and hanging in accordance with ASME B31.1 and B31.9. a) 2” through 8”: Rigid coupling designed for direct installation onto grooved end pipe without prior field disassembly and no loose parts. Gasket shall be Grade “E” EPDM suitable for hot water up to 230°F. Victaulic Style 107 QuickVic, Anvil GRUVLOK Fig. 7401 Rigidlok, TYCO Grinnell Figure 772, Shurjoint Models Z07/7771 or approved equal. b) 10” and 12”: Standard rigid coupling with Grade “E” EPDM gasket suitable for hot water up to 230°F. Victaulic Style 07 Zero-Flex, Anvil GRUVLOK Fig. 7401 Rigidlok, TYCO Grinnell Figure 772, Shurjoint Models Z07/7771 or approved equal. c) 14” to 60”: Two ductile iron housing segments with flat bolt pads for metal-to-metal contact with wedge-shaped key profile. Grade “E” EPDM FlushSeal gasket suitable for hot water up to 230°F. Victaulic Style W07, Anvil GRUVLOK Fig. 7401, TYCO Grinnell Figure 772, Shurjoint Models Z07/771/7707L or approved equal. Flexible Type: Use in locations where isolation and stress relief are required. couplings may be used in lieu of connectors for vibration isolation at connections. Three couplings for each shall be placed in close proximity to the vibration. a) NYCSCA vibration Flexible flexible equipment connector source of 2” through 6”: Flexible coupling designed for direct installation onto grooved end pipe without prior field disassembly and no loose parts. Gasket shall be Grade “E” EPDM suitable for hot water up to 230oF. Victaulic Style 177 HVAC PIPING 15510 - 11 01/29/16 DESIGN NO. _____ QuickVic, Anvil GRUVLOK Fig. 7001, TYCO Grinnell Figure 705, Shurjoint Models 7707/7705 or approved equal. I. 2.03 c) 14” to 60”: Two ductile iron housing segments with flat bolt pads for metal-to-metal contact with wedge-shaped key profile. Grade “E” EPDM FlushSeal gasket suitable for hot water up to 230°F. Victaulic Style W77, TYCO Grinnell Figure 707 Shurjoint Models 7707/7707L or approved equal. 2” through 8”: Coupling designed for direct installation onto roll grooved copper tube without prior field disassembly and no loose parts. Gasket shall be Grade “E” EPDM suitable for hot water and glycol system up to 230°F. Victaulic Style 607 QuickVic, Anvil GRUVLOK CTS Fig. 6400, TYCO Grinnell Figure 640 or 672, Shurjoint Model C305 or approved equal. Nipples: same material and strength as adjoining pipe, except nipples having a length of less than 1" between threads shall be extra heavy. Manufacturer: Allied Piping Products, Babcock & Wilcox, Crane Co., Tube Turns and Smith-Cooper International. FLEXIBLE CONNECTIONS A. NYCSCA 8” through 12”: Standard flexible coupling with Grade “E” EPDM gasket suitable for hot water up to 230°F. Victaulic Style 77, Anvil GRUVLOK Fig. 7001, TYCO Grinnell Figure 705, Shurjoint Models 7707/7705 or approved equal. Grooved Joints - for Copper Piping: Rolled grooves, EPDM center legged gaskets, Ductile Iron housing, wrought copper or cast bronze fittings, rated for 300 psi working pressure. System shall be designed for rigid installation. Brazed flanges must be used at equipment connections, and for maintenance removal sections. Manufacturers: Victaulic, Anvil International Inc/Gruvlok, TYCO Grinnell Mechanical Products or Shurjoint Piping Products. 1. J. b) Corrugated inner tube and outer shield of wire braid: Stainless steel. Maximum working pressure at room temperature: 850oF and pressure safety factor of 4:1 HVAC PIPING 15510 - 12 01/29/16 DESIGN NO. _____ B. Corrugated inner tube and outer shield of wire braid: Bronze. Maximum working pressure at room temperature up to 150oF. Manufacturer: Metraflex Co. or Flex-Hose Co., Inc. C. Flexible metal connectors and hoses used in fuel oil system where rigid connections are impractical or to reduce the effect of jarring and vibration shall be listed and labeled in accordance with UL 536 and shall be installed in compliance with its label and the manufacturer’s installation instructions and shall not exceed 18”. Connectors made from combustible materials shall not be used inside buildings or above ground outside of buildings. (Refer to Section MC 1302.8). D. Anvil GRUVLOK Fig. 7001, TYCO Grinnell Figure 705, 707, Victaulic Style 177, 77 or W77, Shurjoint Models 7707/ 7705 flexible couplings (or approved equal) may be used in lieu of flexible connectors for vibration isolation at equipment connections. Three couplings, for each connector, shall be placed in close proximity to the source of vibration. E. Flexible Hose/Connections, manufactured by: stainless steel shall be Allied Metal Hose Inc. Flexaust Co. Flex-Hose Co., Inc. Mason Industries (Type BSS) Metraflex Co. Wheatley Pump & Valve Inc. 2.04 GALVANIZING A. 2.05 Galvanizing Pipe and Fittings: hot dip process, inside and out in accordance with ASTM or other nationally recognized specifications to which pipe and fittings conform. Galvanize before threading. JOINING AND SEALANT MATERIALS A. Solder: solid wire type conforming to type 2: 95-5 B. Gasket Material 1. NYCSCA For Use with Cold Water or Chilled Water: 1/16" thick rubber. HVAC PIPING 15510 - 13 01/29/16 DESIGN NO. _____ 2. For Use with Hot Water, Air or Steam or Oil: Waterproofed non-asbestos mineral, or ceramic fiber, or spirally wound stainless steel V-shaped strip with non-asbestos filler and an outer steel compression ring, designed for the temperatures and pressures of the piping systems. Mechanical joints utilizing an elastomeric and/or compression seal are not permitted per Section MC 1303.3.2. Fuel oil piping flanged joints requiring gaskets or packing shall be equipped with gaskets rated for a minimum of 750°F per Section MC 1303.1. C. Bolts and Nuts: heat treated carbon steel, ASTM A183 minimum tensile 110,000 psi. D. Per Section MC 1303.3, joints and connections shall be approved and of a type approved for fuel-oil and diesel oil piping systems as follows: 1. Brazed in accordance with ASME Boiler and Pressure Vessel Code, Section IX Welding and Brazing Qualifications or in accordance with American Welding Society AWS B2.2 Standard for Brazing Procedure and Performance Qualification or 2. Threaded in accordance with ASME B1.20.1 or 3. Welded in accordance with ASME Boiler Pressure Vessel Code, Section IX Welding Brazing Qualifications or in accordance with B2.1 Specifications for Welding Procedure Performance Qualification or 4. Flanged with gaskets rated for a minimum of 750°F per Section MC 1303.1 and and AWS and All threaded joints and connections shall be made tight with suitable lubricant or pipe compound. Pipe joint compounds and thread seal tape that utilize Teflon (PTFE) shall be approved for usage on fuel oil and diesel oil lines. 2.06 PIPING SPECIALTIES A. NYCSCA Provide factory-fabricated piping specialties recommended by manufacturer for use in service indicated. HVAC PIPING 15510 - 14 01/29/16 B. DESIGN NO. _____ Pipe Escutcheons 1. 2. C. a. Pipe Escutcheons for Moist Areas: For waterproof floors and areas, where water and condensation can be expected to accumulate, provide cast brass or sheet brass escutcheons, solid or split hinged. If exposed to view, escutcheon shall be solid type. b. Pipe Escutcheons for Dry Areas: Provide sheet steel escutcheons, solid or split hinged. If exposed to view, escutcheon shall be solid type. Manufacturers Zurn Industries, Inc. McGuire Mfg. Co. Strainers: Low Pressure Y-Type Pipeline Strainers: 1. NYCSCA Provide pipe escutcheons as specified herein with inside diameter closely fitting pipe outside diameter or outside of pipe insulation where pipe is insulated. Select outside diameter of escutcheon to completely cover pipe penetration hole in floors, walls, or ceilings; and pipe sleeve extension, if any. Provide pipe escutcheons with nickel or chrome finish for occupied areas, prime paint finish for unoccupied areas. Provide strainers full line size of connecting piping with ends matching piping system materials. Select strainers for 125 psi working pressure with perforated stainless-steel basket with 50 percent free area. Perforation or mesh size shall depend on strainer size and/or material being strained. a. Threaded Ends, 21/2" and Smaller: Bronze or Cast-iron body, screwed screen retainer with centered blow down fitted with pipe plug. b. Flanged Ends, 3" and Larger: Cast-iron body, bolted screen retainer with off-center blow down fitted with pipe plug. c. Butt Welded Ends, 3" and Larger: Schedule 40 cast carbon steel body, bolted screen retainer with off-center blow down fitted with pipe plug. HVAC PIPING 15510 - 15 01/29/16 DESIGN NO. _____ d. 2. Grooved Ends, 2" and Larger: Tee or Wye Type, ductile-iron or carbon steel body and access end cap, access coupling with EDPM gasket. Tee type shall be Anvil GRUVLOK Fig. 7260, TYCO Grinnell Figure S855, Victaulic Series 730 or W730, Shurjoint Model 728 or approved equal. Include wye type with off-center blow down port fitted with pipe plug, Anvil GRUVLOK Fig. 758G and 768G, TYCO Grinnell Figure S855, Victaulic Style 732 or W732 Shurjoint Model 726 or approved equal. Manufacturers Anvil International Armstrong Machine Works. Conbraco Industries, Inc.; Apollo Valves Hoffman Specialty ITT; Fluid Handling Div O.C. Keckley Company Metraflex Co. Victaulic Co. of America TYCO Grinnell Mechanical Products Shurjoint Piping Products Spirax Sarco Mueller Steam Specialty D. Dielectric Unions 1. Provide products which effectively isolate ferrous from non-ferrous piping (electrical conductance), prevent galvanic action, and stop corrosion. Per Sections MC 1203.1.1 and 1303.1.1 joints between different metallic piping materials shall be made with approved dielectric fittings or brass converter fittings. 2. Manufacturers Mueller Industries Capitol Mfg. Co.; Div. of Harsco Corp. Eclipse, Inc. Epco Sales, Inc. Perfection Corp. E. Pipe Sleeves: Provide pipe sleeves of one of the following. Pipe sleeve must be appropriate type and thickness for the UL firestopping assembly selected: 1. NYCSCA Sheet-Metal: Fabricate from galvanized sheet metal; round tube closed with snaplock joint, welded HVAC PIPING 15510 - 16 01/29/16 DESIGN NO. _____ spiral seams, or welded longitudinal joint. Fabricate from the following gauges: 3" and smaller, 20 gage minimum; 4" to 6", 16 gage; over 6", 14 gage minimum. F. NYCSCA 2. Steel-Pipe: Fabricate from Schedule 40 galvanized steel pipe; remove burrs. 3. Iron-Pipe: Fabricate from cast-iron or ductile-iron pipe; remove burrs. 4. Plastic-Pipe: Fabricate from plastic pipe; remove burrs. 5. Firestop penetration materials for sealing sleeves shall be listed by Underwriters Laboratories and if not listed have MEA or OTCR approval. The materials shall be as specified in Section 07270. For pipes passing through fire-rated floor, cast-in place firestop device with Underwriters Laboratories listing, and if not listed have MEA or OTCR approval, is permitted as an acceptable sleeve alternative to a metallic sleeve with firestopping material. The cast-in place device is a one-step firestopping process that does not require additional firestop penetration materials for sealing the sleeves. The device shall be installed where required for sleeving purposes. The cast-in place firestop device shall not be used for wall applications. 6. Materials for sealing space between each pipe and sleeve through non-rated interior walls shall consist of mineral wool and sealant. Schedule 80 PVC Mechanical Sleeve Seals 1. Modular mechanical type consisting of interlocking synthetic rubber links shaped to continuously fill annular space between pipe and sleeve, connected with bolts and pressure plates which cause rubber sealing elements to expand when tightened, providing watertight seal and electrical insulation 2. Provide mechanical sleeve seals for sleeves located in foundation walls below grade, or in exterior walls. HVAC PIPING 15510 - 17 01/29/16 DESIGN NO. _____ 3. Manufacturers Thunderline Corp.; Link Seal Type "C" Metraflex Co; MetraSeal. G. 2.07 Drip Pans: Fabricated from corrosion-resistant sheet metal with watertight joints, and with edges turned up 21/2". Reinforce top, either by structural angles or by rolling top over 1/4" steel rod. Provide hole, gasket, and flange at low point for watertight joint and 1" drain line connection. EXPANSION COMPENSATION A. Provide packless expansion joints where indicated on the Drawings and required for piping systems, with materials and pressure/temperature ratings selected to suit intended service. Select packless expansion joints to provide 200% absorption capacity of piping expansion between anchors. B. Expansion Compensators 1. 2. Pressure rated for 60 psi for low pressure systems, 175 psi for high pressure systems. Multiple phosphor bronze bellows, brass shrouds and end fittings for copper piping systems, or multiple stainless steel bellows, carbon steel shrouds and end fittings for steel piping systems. Provide internal guides and anti-torque device, and removable end clip for proper positioning. a. Joints for water systems shall be reinforced rubber corrugations secured by steel flanges. The number of corrugations shall be determined by the amount of movement required. b. Joints for steam or higher temperature fluids shall be composed of multiple layers of thin stainless steel, corrugated and mounted between flanges. The number of corrugations shall be selected for the movement involved. Manufacturer Flex-Hose Co., Inc. Flexonics Div.; UOP, Inc. Mason Industries Metraflex Co. Victaulic Co. of America NYCSCA HVAC PIPING 15510 - 18 01/29/16 DESIGN NO. _____ Vibration Mountings and Controls, Inc. C. Rubber Expansion Joints 1. Construct of butyl rubber with full-faced integral flanges, internally reinforced with steel retaining rings. Provide steel retaining rings over entire surface of flanges, drilled to match flange bolt holes, and provide external control rods. 2. Manufacturer Garlock; Mechanical Packing Div. Metraflex Co. Vibration Mountings and Controls, Inc. D. 2.08 Expansion joints provided in grooved end steel piping water systems shall be packless, gasketed, slip-type with grooved end telescoping slip-pipe section providing up to 3” axial end movement. Install expansion joints adjacent to an anchor or between guides. Shurjoint Models 650/651, Anvil GRUVLOK Fig. 7240, Victaulic Style 150, Tyco Grinnell Figure 7550 (or approved equal) or Victaulic Style 155 expansion joints (or approved equal) consisting of a combination of flexible couplings and grooved end nipples joined in tandem to provide increased expansion. Provide in water systems to 250°F in accordance with manufacturer’s recommendations for expansion compensation. SLIP JOINTS A. Provide slip joints where indicated on the Drawings and required for piping systems, with materials and pressure/ temperature ratings selected to suit intended service. Select slip joints to provide 200% absorption capacity of piping expansion between anchors. Slip shall be the type designed for repacking under pressure, with drip connections for steam piping systems and ends to mate with piping system. B. Manufacturer Flex-Hose Co., Inc. Flexonics Div; UOP, Inc. Metraflex Co. NYCSCA HVAC PIPING 15510 - 19 01/29/16 2.09 DESIGN NO. _____ PIPE ALIGNMENT GUIDES A. Provide pipe alignment guides on both sides of loops, elsewhere as required and as indicated on the Drawings. Construct with 4 fingers spider traveling inside guiding sleeve with provision for anchoring sleeve to structural steel. The pipe alignment guide spider, housing, and base must be constructed of carbon steel (painted for rust protection). B. Manufacturer Anvil International Flex-Hose Co., Inc. Hyspan Precision Products, Inc. Metraflex Co. 2.10 HANGERS AND SUPPORTS A. NYCSCA General 1. Insulated Piping: Each pipe hanger supporting insulated piping shall be provided with a pipe covering protection shield. 2. Hangers for pipes smaller than 5" shall be forged or malleable iron ring type or steel clevis type supported by a solid steel rod. 3. Hangers for pipes 5" and larger shall be formed of a section of steel angle having 3/4" diameter steel rod, threaded at both ends, run through a drilled hole near each end of the angle. Secure two nuts at the bottom end of the rod. Refer to Details Drawings. 4. Sockets used on upper ends of rods at beam clamps and on lower ends of rods for single hangers shall be malleable or forged steel with standard machine threads. 5. Supports for vertical piping shall be double bolt riser clamps, Anvil International MSS SP 69 Type 8 with each end having equal bearing on the building structure located as hereinafter specified. If piping is insulated, riser clamp shall be placed under insulation. 6. Trapeze type hangers shall be made of 2"x2"x1/4" carbon steel angle iron with drilled holes and 1/2" HVAC PIPING 15510 - 20 01/29/16 DESIGN NO. _____ hanger rods. In lieu of an angle iron, a strut assembly may also be used for the trapeze style hanger supports. B. Pipe hangers shall be manufactured by: Anvil International Cooper B-Line, Inc. Carpenter & Paterson, Inc. F.& S. Central Mfg. Co. Grabler Mfg. Co. Empire Industries, Inc. 2.11 INSERTS AND EXPANSION BOLTS A. Inserts for use in new conventional reinforced poured concrete slabs shall be as follows: Carpenter & Paterson Inc. No. 650; Anvil International Fig. 281; C. H. Leibfried Mfg. Corp. No. 100; Cooper B-Line, Inc. B2500 & N2500 Series. B. Inserts for new composite metal decks shall be Powers Fasteners “Bang-It” or Hilti, Inc. Cast-In Anchor HCI-WF (or approved equal). Steel deck insert shall be used to attach hanger rods. C. Expansion bolts for use in new and existing reinforced concrete slabs and concrete deck shall be wedge-type zinc-coated fastener with pull-out, tension, and shear capacities appropriate for supported loads and building materials where used: ITW Ramset/Red Head “Trubolt+”; Hilti, Inc “Kwik Bolt 3”, Powers Fasteners, Inc. “Power Stud+ SD2” or approved equal. Expansion Bolts installed in concrete shall be in accordance with Appendix D of ACI 318 as modified by Sections 1908.1.9 and 1908.1.10 as per Section BC 1912 of the 2014 NYC Building Code. 6 2.12 SADDLES AND SHIELDS A. Except as otherwise indicated on the Drawings, provide saddles or shields under piping hangers and supports, factory-fabricated, for all insulated piping. Size saddles and shields for exact fit to mate with pipe insulation. 1. NYCSCA Protection Saddles: MSS Type 39; fill interior voids with segments of insulation matching adjoining insulation. HVAC PIPING 15510 - 21 01/29/16 B. DESIGN NO. _____ 2. Protection Shields: MSS Type 40; of length recommended by the manufacturer to prevent crushing of insulation. 3. Thermal Hanger Shields: Constructed of 360o insert of high density, 100 psi, waterproofed calcium silicate, encased in 360o sheet metal shield. Provide assembly of same thickness as adjoining insulation. Manufacturers: Elcen Metal Products Co. Pipe Shields, Inc. Value Engineered Products, Inc. PART 3 - EXECUTION 3.01 3.02 NYCSCA INSPECTION A. Perform flexibility analysis of the final piping configuration as required by ANSI B31.1. Insure that the resultant stresses are within the limits for the respective pipe materials and that the resultant forces and moments imposed on the anchors and guides do not exceed the Joist and Truss Manufacturers stated limitations. B. Upon completion of the flexibility analysis, notify the Authority of additional loops, anchors or guides required to adequately protect the piping system. C. Examine areas and conditions under which all products are to be installed. Do not proceed with work until unsatisfactory conditions have been corrected in manner acceptable to the Authority. PREPARATION A. Proceed with installation of hangers, supports anchors only after required building structural work been completed. Correct inadequacies including (but limited to) proper placement of inserts, anchors other building structural attachments. and has not and B. Prior to installation of hangers, supports, anchors and associated work, Contractor shall meet at project site with testing agency representatives (if any), other trades requiring coordination, the Project Architect, HVAC PIPING 15510 - 22 01/29/16 DESIGN NO. _____ Project Engineer and the Authority Representative for purpose of reviewing material selections and procedures. 3.03 5 NYCSCA PIPE INSTALLATION A. Install pipes in accordance with recognized industry practices which will achieve permanently-leakproof piping systems, capable of performing each indicated service without piping failure. Align piping accurately at connections, within 1/16" misalignment tolerance. Comply with ANSI B31 Code for Pressure Piping. B. Locate piping runs, except as otherwise indicated, vertically and horizontally (pitched to drain) and avoid diagonal runs wherever possible. Orient horizontal runs parallel with walls and column lines. Locate runs as shown or described by diagrams, details and notations. Run piping in shortest route which does not obstruct usable space or block access for servicing building and its equipment. Hold piping close to walls, overhead construction, columns and other structural and permanentenclosure elements of building; limit clearance to 1/2" where furring is shown for enclosure or concealment of piping, but allow for insulation thickness, if any. Where possible, locate insulated piping for 1" clearance outside insulation. All piping in finished and occupied spaces shall be concealed from view by locating piping in column enclosures, in hollow wall construction or above suspended ceilings; do not encase horizontal runs in solid partitions, except as indicated on the Drawings. C. Do not run piping through transformer vaults and other electrical or electronic equipment spaces and enclosures unless unavoidable. Install drip pan under piping that must be run through electrical spaces. Do not run piping in stairwells or elevator equipment rooms except for systems serving those spaces. D. In the outlet from pan, provide a tee facilitate cleaning single "P" trap for E. Riser Casings: Unless otherwise indicated on the Drawings, all exposed risers, including the drop risers, shall be enclosed in casings extending from floor to a height of 7'-6" above floor. Riser casings shall be installed after the pipe insulation work is completed, inspected and approved. Casings shall be made of 24-gage galvanized sheet steel, with the upper end wired with each cooling coil condensate drain with a brass plug at one end to of drain. Additionally, provide a proper operation of the unit. HVAC PIPING 15510 - 23 01/29/16 DESIGN NO. _____ 1/8" half hard wire. Each casing shall be fastened to the wall at the upper end with a metal band and round head screws. Seams shall be located at the rear of the casing. 2 2 F. Casing for pipe at or near floors: Where pipes at or near floors are indicated on the Drawings to be encased, pipes shall be supported, insulated, and then enclosed in a casing of No. 20-gage galvanized sheet steel. G. Protection of Refrigerant Piping Located Inside Buildings: As per Section MC 1107.1.1, all refrigerant piping and fittings installed at a height less than 7’-3” above the floor shall be concealed or otherwise protected from mechanical damage except at the point of connection to terminal equipment. H. Per Section MC 1107.2, refrigerant piping that crosses an open space that affords passageway in any building shall be not less than 7’-3” above the floor unless the piping is located against the ceiling of such space. Refrigerant piping shall not be placed in any elevator, dumbwaiter or other shaft containing a moving object or in any shaft that has openings to means of egress. Refrigerant piping shall not be installed in an enclosed public stairway, stair landing or an exit. I. Per Section MC 1107.2.1, refrigerant piping shall not be installed in public corridors. Exception: Refrigerant piping in public corridors that complies with all of the following conditions: NYCSCA 1. The refrigeration system to which the piping is associated utilizes a Group A-1 refrigerant and contains not more than 10 pounds of refrigerant per system, and there is not more than one system’s refrigerant piping per tenant per public corridor; and 2. A complete discharge of any one refrigerant system’s charge into the volume of the public corridor would be insufficient to achieve 50% of the allowable refrigerant densities set forth in MC Table 1103.1; and 3. Refrigerant piping and fittings within a public corridor are installed with brazed joints or the refrigerant equipment manufacturer provided precharged tubing systems installed in accordance with HVAC PIPING 15510 - 24 01/29/16 DESIGN NO. _____ the refrigerant equipment manufacturers instructions. Refrigerant piping and fittings shall be concealed or otherwise protected from mechanical damage. 2 2 J. Refrigerant Piping in Concrete Floors: As per Section MC 1107.2.2, refrigerant piping installed in concrete floors shall be encased in pipe ducts. The piping shall be isolated and supported to prevent damaging vibration, stress and corrosion. K. Refrigerant Piping Penetrations: As per Section MC 1107.2.3, refrigerant piping shall not penetrate floors, ceilings or roofs. Exceptions: 7 3.04 NYCSCA 1. Penetrations connecting the basement and the first floor 2. Penetrations connecting the top floor machinery penthouse or roof installation 4. Penetrations connecting adjacent floors served by the refrigeration system 5. Penetrations by piping enclosed by gas-tight, fire resistive duct or shaft as shown on the Drawings. and a INSTALLATION OF PIPE SYSTEM JOINTS A. Provide joint of type indicated in each piping system. B. Thread pipe in accordance with ASME B1.20.1; cut threads full and clean using sharp dies. Ream threaded ends to remove burrs and restore full inside diameter. Apply pipe joint compound, or pipe joint tape where recommended by pipe/fitting manufacturer, on male threads at each joint and tighten joint to leave not more than three threads exposed. C. Weld pipe joints in accordance with recognized industry practice and as follows: 1. Weld pipe joints only when ambient temperature is above 0oF where possible. 2. Bevel pipe ends at a 37.5o angle where possible, smooth rough cuts, and clean to remove slag, metal particles and dirt. HVAC PIPING 15510 - 25 01/29/16 NYCSCA DESIGN NO. _____ 3. Use pipe clamps or tack-weld joints with 1" long welds, 4 welds for pipe sizes to 10", 8 welds for pipe sizes 12" to 20". 4. Build up welds with stringer-bead pass, followed by hot pass, followed by cover or filler pass. Eliminate valleys at center and edges of each weld. Weld by procedures which will ensure elimination of unsound or unfused metal, cracks, oxidation, blowholes and non-metallic inclusions. 5. Do not weld-out piping system imperfections by tack-welding procedures; refabricate to comply with requirements. 6. Weld high-pressure piping under Special Inspection as required by the NYC Construction Code. D. Brazed Joints: Joints in refrigerant piping shall be brazed in Groups A2, A3, B1, B2, or B3 refrigerants. Oil lines shall use brazed Type K fittings. The outside of the copper tube and the inside of the fitting where solder will be applied, shall be cleaned and burnished with fine crocus cloth until all dirt and oxide is removed. A light coat of non-corrosive brazing flux shall be applied to both pipe and fittings (Acid flux shall not be used). Joint shall be uniformly heated to proper brazing temperature and the brazing material shall be fed to the joint until a uniform line of brazing material appears around the pipe at the end of the fitting. Brazing shall be done only by mechanics that are qualified for brazing refrigerant piping. E. Fittings for copper tubing for refrigerant use shall be wrought copper with solder type ends as applicable. Forged brass fittings are also acceptable for this purpose. Fittings shall be suitable for working water pressure up to 250 psi. The use of cast brass fittings for this service will not be approved F. Solder copper tube-and-fitting joints in accordance with recognized industry practice. Cut tube ends squarely, ream to full inside diameter, and clean outside of tube ends and inside of fittings. Apply solder flux to joint areas of both tubes and fittings. Insert tube full depth into fitting, and solder in manner that will draw solder full depth and circumference of joint. Wipe excess solder from joint before it hardens. HVAC PIPING 15510 - 26 01/29/16 NYCSCA DESIGN NO. _____ G. The use of mechanical formed outlets on copper tubing instead of soldered joints is acceptable. (Refer to Section MC 1203.3.8).The maximum diameter of branches shall be 21/8”. Use appropriate tool designed for mechanical formed outlets on copper tubes. All mechanical formed tee fittings shall be brazed in accordance with the Copper Development Associations Copper Tube Handbook Using BCuP series filler metal. All mechanical formed branch collars shall be listed by UPC, and Underwriters Laboratory. They shall comply with ASME Code for pressure piping ANSI B31.5c. H. Offsets in piping shall be accomplished by means of standard fittings; pipe bends shall not be used for this purpose unless shown on the Drawings or unless permission is obtained from the Authority to use pipe bends. I. Flanged Joints: match flanges within piping system, and at connections with valves and equipment. Clean flange faces and install gaskets. Tighten bolts to provide uniform compression of gaskets. J. The "Y" fitting in the vacuum pump discharge piping and all fittings in the fuel oil piping within the building shall be of malleable iron. K. Eccentric Fittings: reductions in sizes of steam mains and hot and/or chilled water mains shall be made with eccentric fittings. To avoid trapping of condensate or air in mains at eccentric reducers, install steam piping eccentric reducers with the offset to the bottom of the run, and install water piping eccentric reducers with the offset to the top of the run. L. Reducing Fittings: except for welded piping, no fittings shall be taped for drip except in boss provided for that purpose. Reducing fittings shall be used where drips are required. M. Unions shall be used in piping only adjacent to units of equipment such as pumps, oil burners, compressors, heating coils, cooling coils and all other items and accessories, or in other locations where specified, where shown on the Drawings, or where written permission is granted prior to installation. N. Mechanical Couplings Type Fittings: The use of mechanical coupling type fittings on hot and cold water piping in lieu of threaded or flanged fittings is acceptable in sizes 2" to 8" inclusive. The mechanical couplings shall HVAC PIPING 15510 - 27 01/29/16 DESIGN NO. _____ be self-centering and shall engage and lock the grooved pipe and/or fittings in a positive couple while allowing for some degree of angular pipe deflection, contraction and expansion. Entire coupling installation including pipe grooving shall be performed in accordance with the manufacturer's instructions. Mechanical Products couplings together with their respective grooved end pipe fittings are acceptable. NYCSCA 1. The gasket style and elastomeric material (grade) shall be verified as suitable for the intended service as specified. 2. Grooved end shall be clean and free from indentations, projections, and roll marks in the area from pipe end to groove for proper gasket sealing. 3. A manufacturer factory-trained field representative shall provide on-site training for contractor's field personnel in the proper use of grooving tools and installation of grooved piping products. Factory-trained representative shall periodically review the product installation. Contractor shall remove and replace any improperly installed products. O. Grooved Copper coupling may be used in lieu of soldering joints on 2" and up Type L copper tubing; on water services from -30oF to +250oF within the manufacturer rated working pressures. Tubing shall be roll grooved as per manufacturer. P. Pressed Connect Fit (Pressure Seal - Press Fit) Fittings: All the connections shall be made in accordance with the manufacturer’s installation instructions. Copper tubing shall be cut at right angles using displacement type cutter or fine-toothed saw. Burrs shall be removed from inside and outside of tubing to prevent cutting sealing element. Mark insertion depth according to manufacturer’s insertion depth chart. Seals and grip ring shall be checked for correct fit. Only the manufacturer’s sealing elements shall be used. Press fitting shall be slid onto tubing while turning slightly to the marked depth. Oils or lubricants shall not be used. Fitting connections shall be made with the tool provided by manufacturer. Manufacturer’s assembly tool shall be used to perform the pressing process. HVAC PIPING 15510 - 28 01/29/16 DESIGN NO. _____ For locations where there is insufficient access to accommodate the pressing tool, this type of joint is not allowed. Sufficient clearance must be left around each joint to allow room for the pressing tool and jaw to be attached without interference when repairing the system in the future. 3.05 INSTALLATION OF FLEXIBLE CONNECTIONS A. 3.06 3.07 PIPING TESTS A. For operational and hydrostatic tests, refer to Section 15992: Cleaning and Testing. B. Where piping installed under this project is connected to any existing system, such installed piping shall be isolated from the existing system during the performance of the required tests. INSTALLATION OF PIPING SPECIALTIES A. Pipe Escutcheons: Install pipe escutcheons on each pipe penetration through floors, walls, partitions, and ceilings where penetration is exposed to view; and on exterior of building. Secure escutcheon to pipe or insulation so escutcheon covers penetration hole, and is flush with adjoining surface. B. Strainers 8 NYCSCA Install stainless steel type on the water line at the circulating pumps and on the chilled water lines; and bronze type on the refrigerant line. Pipe system must be properly supported so as not to impose weight on the connectors which would compress the hose and relax the braid tension. Avoid torque. Do not twist the hose assembly during installation when aligning bolt holes in a flange or in mating-up the pipe threads. 1. Provide pipe nipple and shutoff valve in strainer blow down connection, full size of connection, except for strainers 2" and smaller installed ahead of control valves feeding individual terminals. Where indicated, provide drain line from shutoff valve to plumbing drain, full size of blow down connection. 2. Provide strainers in supply line ahead of the following equipment and elsewhere as indicated (if control valve selected comes with an integral HVAC PIPING 15510 - 29 01/29/16 DESIGN NO. _____ strainer in the assembly, a separate strainer does not need to be installed): Pumps Steam traps serving steam main drips Temperature control valves Pressure reducing valves Temperature or pressure regulating valves C. Dielectric Unions: Per Sections MC 1203.1.1 and 1303.1.1, joints between different ferrous and non-ferrous metallic piping materials shall be made with approved dielectric fittings or brass converter fittings. D. Pipe Sleeves 1. 2. NYCSCA Install pipe sleeves where piping passes through walls, floors, ceilings, and roofs. Do not install sleeves through structural members of work, except as detailed on the Drawings or as reviewed by the Project Architect. Install sleeves accurately centered on pipe runs. Size sleeves so that piping and insulation (if any) will have free movement in sleeve, including allowance for thermal expansion; but not less than 2 pipe sizes larger than piping run. Where insulation includes vapor-barrier jacket, provide sleeve with sufficient clearance for installation. Install length of sleeve equal to thickness of construction penetrated, and finish flush to surface; except floor sleeves. Extend floor sleeves 1/4" above level floor finish, and 3/4" above floor finish sloped to drain. a. Install sheet-metal sleeves at interior partitions and ceilings other than suspended ceilings. b. Install iron-pipe sleeves at exterior penetrations, both above and below grade. c. Install steel-pipe or plastic-pipe where indicated on the Drawings. sleeves Sleeves for floors, walls and other masonry work shall be set in place before the slabs or walls are constructed. In buildings having floor slab of composite metal deck construction, Contractor shall be responsible for cutting holes in the steel deck. Where drilled openings are in terra cotta arch, exposed hollow core of the blocks shall be HVAC PIPING 15510 - 30 01/29/16 DESIGN NO. _____ completely filled with non-shrink grout and prepacked to achieve firm bearing on the entire perimeter of the structural steel sleeve. Where corrugated sheet metal is encountered, it shall be cut by the rotary drill used to cut the arch. For location of sleeve, Contractor is to coordinate with new and existing Drawings (Structural steel beams are shown on original Drawings). Openings in arch must be located to miss existing structural steel. Openings in existing arch are to be made by rotary core drill only. Hammering of any type is not permitted. The size of the opening in arch may not exceed the requirement shown on the Details Drawings. The mix for non-shrink grout shall be in accordance with the manufacturer's recommendations. The non-shrink grout shall be compacted to provide firm bearing between the structural steel sleeve or sleeves and the existing arch. Additionally, where there are two sleeves, provide compacted non-shrink grout between the sleeves. E. Mechanical Sleeve Seals: Mechanical modular seals may be used in lieu of packing and sealant for sleeves and core drilled holes. Loosely assemble rubber links around pipe with bolts and pressure plates located under each bolt head and nut. Push into sleeve and center. Tighten bolts until links have expanded to form watertight seal. Use fire protective seals where required. Size annular space as required for seal installation. F. Fire Barrier Penetration Seals: refer to Section 07270 Firestopping. G. Drip Pans: locate drip pans under piping passing over or within 3 feet of electrical equipment, and elsewhere as indicated. Hang from structure with rods and building attachments, weld rods to side of drip pan. Brace to prevent sagging or swaying. Connect 1" drain line to drain connection, and run to nearest plumbing drain or elsewhere as indicated on Drawings. 3.08 INSTALLATION OF EXPANSION COMPENSATION A. NYCSCA Expansion joints: Install expansion joint as determined for adequate expansion of installed piping system. Provide pipe anchors and pipe alignment guides in accordance with manufacturer's recommendations. Align units properly to avoid end loading and torsional stress. HVAC PIPING 15510 - 31 01/29/16 3.09 3.10 NYCSCA DESIGN NO. _____ B. Expansion loops: Fabricate expansion loops as determined for adequate expansion of installed piping system. Subject loop to cold spring that will absorb 50% of total expansion between hot and cold conditions. Provide pipe anchors and pipe alignment guides as determined to properly anchor piping in relationship to expansion loops. C. Expansion compensation for risers and terminals: If not indicated on the Drawings, install connection between piping mains and risers with at least 5 pipe fittings including tee in main, install connections between piping risers and terminal units with at least 4 pipe fittings including tee in riser. MISCELLANEOUS CONNECTIONS A. For steel piping runouts not detailed on the Drawings, use three elbow connections between runouts and mains. B. Connections to Equipment: provide three elbow runouts to all rotating equipment such as pumps and chillers. Provide swing connections for boilers. Provide two elbow connections to fuel oil tanks. C. Connections to Building Structure: connect to trusses and joints at panel points. Provide supplementary steel framing at panel points to transfer loads to framing. D. Connection to domestic water system shall be protected by reduced pressure principal backflow preventer. INSTALLATION OF SUPPORTS AND ANCHORS A. Provide all necessary pipe hanger material needed to safely and securely support or hang all piping. Pipe hanger loads shall be determined by accurate weight balance calculations to prevent transferring loads and forces to any equipment and terminal connections. Per Section MC 305.4, piping shall be supported at distances not exceeding the spacing specified in MC Table 305.4 or in accordance with MSS SP-69. B. Install building attachments at required locations within concrete or on structural steel for proper piping support. Hangers and anchors shall be attached to building structure per Section MC 305.3. Space attachments within maximum piping span length indicated in MSS SP-69 and MSS SP-89 and MC Table 305.4. Install additional concentrated loads at valves, flanges, guides, HVAC PIPING 15510 - 32 01/29/16 DESIGN NO. _____ strainers, expansion joints, and changes in direction of piping. Install concrete inserts before concrete is poured; fasten insert securely to forms. Where concrete with compressive strength less than 2500 psi is indicated, install reinforcing bars through openings at top of inserts. For composite metal decks, inserts shall be of the type that is supported entirely by the concrete slab, not by the metal deck. Install expansion bolts after erection of the metal deck, after concrete is placed and completely cured in accordance with the bolts manufacturer's written installation instructions. Expansion bolts shall be installed so that the load acts on the bolts in shear and withdrawal. Expansion bolts shall be carefully located in order to eliminate the risk of damage to concrete, steel reinforcement, electrical conduits and any other embedded items. C. Install hangers, supports, clamps and attachments to support piping properly from building structure per Section MC 305.3. Arrange for grouping of parallel runs of horizontal piping to be supported together on trapeze type hangers where possible. Install supports with maximum spacings complying with MSS SP-69 and MSS SP-89 and MC Table 305.4. Where piping of various sizes is to be supported together by trapeze hangers, space hangers for smallest pipe size or install intermediate supports for smaller diameter pipe. Do not use wire or perforated metal to support piping, and do not support piping from other piping. D. Install hangers and supports complete with necessary inserts, bolts, rods, nuts, washers and all other items and accessories. Except as otherwise indicated for exposed continuous pipe runs, install hangers and supports of same type and style as installed for adjacent similar piping. E. Prevent electrolysis in support of copper tubing by use of hangers and supports which are copper plated or by other recognized industry methods. F. Provisions for Movement 1. NYCSCA Install hangers and supports to allow controlled movement of piping systems, to permit freedom of movement between pipe anchors and to facilitate action of expansion joints, expansion loops, expansion bends and similar units. HVAC PIPING 15510 - 33 01/29/16 G. H. NYCSCA DESIGN NO. _____ 2. Load Distribution: Install hangers and supports so that piping live and dead loading and stresses from movement will not be transmitted to connected equipment. 3. Pipe Slopes: Install hangers and supports to provide indicated pipe slopes and so that maximum pipe deflections allowed by ANSI B31 Pressure Piping Codes are not exceeded. Pipe Supports 1. Mains located near floors shall be supported on roller type pipe stands bedded in cement base. When mains are installed before concrete floor is laid, the mains shall be supported from overhead construction until the pipe stands can be put in place. 2. Horizontal piping connections (near floor) to convectors and all other items and accessories located more than 4' from risers shall be supported on adjustable iron pipe stands. Pipe stand shall consist of a split ring extension hanger mounted on a hanger flange, which shall be secured to the floor. Insulated Piping: Comply with the following installation requirements. 1. Clamps: Attach clamps, including spacers (if any), to piping with clamps projecting through insulation; do not exceed pipe stresses allowed by ANSI B31. 2. Shields: Where low-compressive-strength insulation or vapor barriers are indicated on chilled water piping, install coated protective shields. For pipe 8" and over, install wood insulation saddles. 3. Saddles: Where insulation without vapor barrier is indicated, install protection saddles. 4. Insulation Saddle System, the equal of Anvil Fig 260 ISS can be used instead of shields and/or saddles when proper insulating techniques are employed including the use of mastic and caulk on all insulation edges and final taping. Position the pipe on the saddle, notch section of the insulation to fit around the saddle, square cut the HVAC PIPING 15510 - 34 01/29/16 DESIGN NO. _____ adjoining insulation section and butt the mating end to the notched section, finish taping according to standard methods, no metal shield is required between the hanger and pipe insulation. 3.11 I. Install anchors at proper locations to prevent stresses from exceeding those permitted by ANSI B31 and to prevent transfer of loading and stresses to connected equipment. J. Fabricate and install anchor by welding steel shapes plates and bars to piping and to structure. Comply with AWS standards. K. Where expansion compensators are indicated, install anchors in accordance with expansion unit manufacturer's written instructions and to limit movement of piping and forces to maximum recommended by manufacturer for each unit. L. Anchor Spacings: where not otherwise indicated, install anchors at ends of principal pipe-runs, at intermediate points in pipe-runs between expansion loops and bends. Make provisions for preset of anchors as required to accommodate both expansion and contraction of piping. M. Piping passing under concrete areas shall be supported by hangers secured by means of beam clamps fastened to the beams. Where pipe support spacing is excessive between steel, beam clamps shall be fastened to structural members that are approved by the Authority. Removed fireproofing around beams shall be replaced to original condition. No hangers or supports shall be attached to hung ceilings, concrete, ductwork or work of other trades. N. The refrigerant piping above the roof slab shall be supported in a galvanized sheet steel enclosure constructed in accordance with the Detail shown on the Drawings. The cover of the enclosure shall be held in place with stainless steel sheet metal screws on 18" centers. The base of the enclosure shall be secured to the angle uprights with 1/4" bolts, washers and nuts. O. Hangers and supports for refrigerant piping shall be copper plated, malleable iron or carbon steel. CLEANING, FLUSHING, INSPECTING A. NYCSCA Clean exterior surfaces of superfluous materials, and prepare for application of specified coatings (if any). HVAC PIPING 15510 - 35 01/29/16 DESIGN NO. _____ Flush out piping systems with clean water before proceeding with required tests. Inspect each run of each system for completion of joints, supports and accessory items. Inspect pressure piping in accordance with procedures of ASME B31. 3.12 B. Hanger Adjustments: adjust hangers so as to distribute loads equally on attachments. C. Support Adjustment: provide grout under supports so as to bring piping and equipment to proper level and elevations. PAINTING A. 3.13 PIPE APPLICATION A. B. NYCSCA Upon completion of the installation, remove all protecting materials, all scale and grease and leave in a clean condition for painting. Boiler Piping 1. Each boiler shall be connected with steam, feed water, city water (quick fill), blow-off, water equalizing, trimming, and accessories piping as shown on the Drawings and as specified. Refer to the Drawings Details. The steam header may be made with screwed fittings or fabricated by welding at the shop with welding fittings. 2. Provide water supply to fill the boilers with City water as shown on the Drawings. Mains 1. Steam Mains: Pitch horizontal steam piping in the direction of steam flow, excepting the runouts to risers and other piping which the Drawings indicate is to be pitched against the flow. Piping shall be hung at the elevations given on the Drawings. Where the elevations are not indicated, install piping approximately 12" below the overhead beams. In boiler, fan and equipment rooms, provide piping so as to give easy access to valves. 2. Return Mains: Return mains shall be run in the locations shown on the Drawings. Return mains on floors or in trenches shall not be installed until floors have been laid, unless otherwise directed. HVAC PIPING 15510 - 36 01/29/16 DESIGN NO. _____ Such return piping shall be painted immediately after erection. Outlets of return piping in trenches, and at or near floor shall be plugged or capped until connecting piping has been installed. C. D. NYCSCA 3. Low Points: Low points of each seal or pocket in piping shall be provided with a 1/2" (minimum size) gate valve arranged to empty the line. 4. Water Piping: Piping shall be installed at the elevations and locations indicated on the Drawings. It shall be so supported as to avoid the trapping of air. However, where trapping of air cannot be avoided, provision shall be made for manual venting of piping in such locations. Each low point in a main shall be provided with a 1" bronze hose gate valve, having a bronze cap and chain on the outlet. 5. Condensate Drain Piping: Condensate drain piping from cooling coil drain pans shall be pitched at not less than one-eighth unit vertical in 12 units horizontal (1-percent slope) in the direction of discharge per Section MC 307.2.1. Runouts 1. Runouts from steam mains for risers, convectors, and all other items and accessories shall be taken from top of steam main on a rise of 45o and shall be pitched toward the main, unless otherwise shown on the Drawings. 2. Runouts from return mains for risers, convectors, and all other items and accessories shall be taken from the side of horizontal return main and shall be pitched toward the main, unless otherwise shown on the Drawings. Risers: Steam and return risers shall be installed in the locations indicated on the Drawings. They shall be of the sizes marked on the Riser Schedule or Sheet. Where the distance between fittings is less than 18', no couplings shall be used in the riser. Risers shall be supported and anchored at the first floor of a 3-story building, and at the second floor of a 4-story building. Risers, connections to convectors, traps, and all other items and accessories shall be neatly arranged and shall allow for expansion. HVAC PIPING 15510 - 37 01/29/16 E. F. NYCSCA DESIGN NO. _____ Drips, Test Connections 1. Drips shall be provided to keep horizontal steam piping free of condensation. They shall be connected from steam mains, branches at locations indicated on the Drawings, through traps to return mains as per Drawings Details. Each trap in a steam main drip shall have a strainer and a full size valved by-pass. Drips not shown on the Drawings, but made necessary by job conditions, shall be provided as directed, as part of the Contract. 2. Provide plugged tees for steam pressure and vacuum test connections in the locations indicated on the Drawings. Test connections shall be as shown in the Drawings Details. Vacuum Heating Pump Connections 1. Condensate return piping from direct radiation, heating coils, drips, and all other items and accessories shall be connected into a vacuum heating pump suction header, unless otherwise shown on the Drawings. Suction header shall be constructed of pipe, flanges, welding fittings in accordance with the Drawings Details. 2. Vacuum pump respects. arranged so duties when installation shall be complete in all Piping, valves, connections shall be that the pumping units will perform the operating simultaneously or separately. G. Steam Convector Connections: Provide schedule 40 black steel pipe connection to steam convectors. Supply shall be provided with a gate valve, and a pneumatic steam control valve and return with a thermostatic trap, three elbow swing joint, and gate valve. Refer to the Standard Details. H. Piping for Oil Burning Equipment 1. Pipe shall be pitched in the direction indicated on the Drawings, at least 1" in 10', unless otherwise shown. 2. Fill Pipe: Provide fill pipe, of size shown on Drawings for each tank (for No.2 oil, fill piping shall be a minimum of 2” in diameter per Section MC 1305.6.1). Fill pipes shall pitch toward tanks, HVAC PIPING 15510 - 38 01/29/16 DESIGN NO. _____ shall be connected into tapping on tanks, and shall be extended to fill pipe terminals near the sidewalk curb, or otherwise shown on the Drawings. A fill pipe shall terminate outside of a building at or above grade at a point at least two feet from any building opening and 5 feet away from any subway grating at the same or lower level per Section MC 1305.6.2. NYCSCA 3. Vent Pipe: A vent pipe of size indicated on the Drawings shall be connected to the vent pipe tapping on each tank and extended to a vent head. Vent pipe shall pitch toward tank and shall be supported as indicated on the Drawings. 4. Suction Lines: Suction lines shall be connected to the tappings provided on top of the tanks and extended into the tanks as shown on the Drawings. Overhead lines shall be pitched toward the tanks. 5. Pump Connections: Provide suction piping connections to the pump as indicated on the Drawings. Include an OS&Y valve in each suction line. 6. Fuel Oil Piping from transfer pump to equipment or to storage tanks above the lowest floor (Refer to Section MC 1305.9). a. Fuel Oil Piping shall be enclosed in a shaft constructed of 4” concrete or masonry having a 4” clearance from all pipe or pipe covering, except that no such enclosures shall be required within the room containing the pump, tank, or equipment where such room is itself enclosed with construction and materials having at least a two hour fire resistance rating. Provisions shall be made for expansion in piping without the use of expansion joints (Refer to Section MC 1305.9.6). b. Where it is necessary to make horizontal offsets in the supply piping, overflow/return piping and pipe shafts including the lowest level such piping shall be enclosed in a sleeve of other piping of at least no. 10 U.S. standard gage steel, two sizes larger and arranged to drain into the shaft. Horizontal piping offsets shall be further enclosed in HVAC PIPING 15510 - 39 01/29/16 DESIGN NO. _____ construction having a two hour fire resistance rating, except that no such enclosure or pipe sleeve shall be required for the pipes serving the equipment within the room containing the pump, tank, or equipment where such room is itself enclosed with construction and materials having at lease a two hour fire resistance rating. Horizontal piping shall include all piping at or above the roof level. No 2-hour fire-resistance rated enclosure is required for horizontal piping offsets located outside the building. NYCSCA c. A drain pipe shall be installed at the base of shafts enclosing the supply and overflow/return piping. The pipe shall lead to a dedicated sump or minimum 55 gallon (208 L) container with a leak detection alarm, arranged so as to sound an alarm and stop the transfer pump. The alarm shall be connected to a local audible alarm and to a remote alarm located at a supervising station. The wiring shall comply with the New York City Electrical Code. (Refer to Section MC 1305.9.4). d. Oil lines for equipment or tanks above the level of the lowest floor shall be black steel pipe ASTM A53 or A106, Grade B seamless, schedule 40 with welded connections up to the oil tank or equipment, except that fittings at the tank or equipment, shut off valves and other fuel oil flow and control devices may be screwed or flanged. e. Pipe shafts shall not be penetrated by or contain other piping or ducts. (Refer to Section MC 1305.9.2). f. The piping shall be located and secured from movement so as to prevent undue stress on the piping and to isolate the piping from vibrations from any equipment. (Refer to Section MC 1305.9.7). g. Pipe connections to the main header (supply or return) shall be made from the top of the header, except for systems with equipment above the lowest floor where such equipment is designed to operate utilizing fuel pumped as HVAC PIPING 15510 - 40 01/29/16 DESIGN NO. _____ needed from the lowest floor and without utilizing fuel oil stored above the lowest floor. (Refer to Section MC 1305.9.8). NYCSCA h. In systems with equipment above the lowest floor where such equipment is designed to operate utilizing fuel stored above the lowest floor, piping diameters shall not exceed 4”. However, where the Engineer of Record requires a greater diameter to ensure the proper flow for the functioning of the system, such greater diameter may be permitted by NYCDOB. Piping shall not be used for fuel storage purposes. (Refer to Section MC 1305.9.11). i. Per Section MC 1305.9.12: In systems with equipment above the lowest floor, where such equipment is designed to operate utilizing fuel pumped as needed from the lowest floor and without utilizing fuel oil stored above the lowest floor, piping diameters throughout such systems shall not exceed the design flow (three times the maximum firing rate as calculated by the engineer or architect). However, piping diameters within rooms containing such equipment may exceed the calculated design flow pipe size to provide limited reservoir storage to prime equipment, provided such reservoir storage is counted toward the maximum permitted oil storage per story as provided for in Article 1305.11.1.3 of the NYCMC (330 gallons maximum fuel oil above the lowest floor inside of a building). j. All air vents and vacuum breakers shall be hard piped to a curb or pan as provided for in Section MC 1305.9.10. 7. Fuel Oil Gauge Piping shall be copper material, Type L, ASTM B88. Protective enclosure piping, if required for Fuel Oil Gauge Piping shall be black steel Schedule 40. 8. Gas Piping: Provide a gas supply service connection for burner ignition and pilot to each oil burner. All gas connections shall be installed by a Licensed Plumber. HVAC PIPING 15510 - 41 01/29/16 I. NYCSCA DESIGN NO. _____ Air Piping for Temperature Control 1. Provide piping required for the temperature control systems. Piping shall be concealed wherever practicable, supported and anchored to prevent vibration and damage. No air lines shall be hidden within insulation. Exposed piping passing through floors, walls and all other penetration shall have neatly fitted cast aluminum or cast brass escutcheon plates. Sizes given in the following paragraphs are for copper tubing and are the nominal minimum sizes acceptable. It shall be the responsibility of the temperature control manufacturer to size all piping (above the minimum sizes specified) to insure proper operation of the entire temperature control installation. The number of mains and risers installed shall be determined by the temperature control manufacturer and shall be governed by the configuration of the building. It is the intent to provide a temperature control system that divides the building into several areas of control which may be conveniently isolated for future maintenance and repair. All joints in copper tubing shall be soldered connections except for compression fittings where connecting to instruments and operators. 2. Air Distributing Header: Provide air distributing header in the vicinity of pressure reducing station. Header and piping of pressure reducing station shall be made of brass pipe nipples with brass fittings. The use of type K copper tubing with brass or copper solder joint fittings is also acceptable for this purpose. Outlets of header shall be connected with the air mains, each of which shall be provided with a valve (or plug cock) at this location. 3. Air Mains: Provide air mains near the ceiling of the basement (or cellar, pipe and duct space, and all other items and accessories). Mains shall be 1/2" nominal minimum size. Each main shall be provided with a drain cock at its low point. 4. Air Risers: Air risers shall not be run near heating risers. Each riser shall drain to the main and be provided with a valve and with a pressure gauge close to the main. Risers shall be 3/8" nominal minimum size, except that a riser serving a HVAC PIPING 15510 - 42 01/29/16 DESIGN NO. _____ fan or equipment room shall be 1/2" nominal minimum size. At least one riser shall be provided to serve each floor area. (e.g. A three story area shall have at least three risers). J. K. 5. Air piping (copper tubing) installed in finished spaces on partitions which do not have a plaster finish shall be enclosed in a surface metal raceway as defined in Section 16130, Raceways, Fittings, Supporting Devices, Boxes and Accessories. 6. Valve Tags: Each valve and plug cock shall be provided with a valve tag as specified in Section 15502: HVAC Identification. Steam Piping Systems 1. Install to permit complete drainage. 2. Pitch: Pitch horizontal steam mains, return mains and branches downward, 1/4" per 10' in direction of flow. b. Pitch steam runouts and connections to risers upward, 3/16" per foot in direction of flow. 3. Use eccentric reducers in horizontal piping. 4. Size short vertical supply and return connections, from horizontal runouts to radiator traps and valves, same size as trap or valve. Water and Propylene Glycol Piping Systems 1. Pitch: Pitch horizontal piping 1/8" per 10' direction indicated on Drawings. When direction flow is not indicated, pitch supply piping up direction of flow and return piping downward direction of flow. 2. Air Vents: Install air vents at locations indicated on the Drawings, and at each high point in system. Use manual air vents, unless otherwise indicated. 3. Drains: Provide drains at low points, consisting of a 1/2" valve with a hose bibb connection, and at the following locations and equipment: 3 NYCSCA a. in of in in HVAC PIPING 15510 - 43 01/29/16 DESIGN NO. _____ 4. NYCSCA a. In each section of piping separated by valves. b. For each riser, where riser or runout to riser has a valve installed. c. For each heating cooling unit, having valves in supply and return connections. d. In low point of piping to each down feed convector or radiator. Runouts: Connect runouts to upfeed risers to top of mains, and runouts to downfeed risers to bottom of mains. L. Fill and Make-Up Plumbing Work. Water M. Dissimilar Pipe Joints System to match connecting 1. Between Cast Iron and Threaded Pipe: Use a half coupling screwed onto the threaded pipe to form a spigot end and calk into the cast iron pipe. 2. Between Black Steel Pipe and copper pipe or tubing: Use a dielectric connector or brass converter fittings per Sections MC 1203.1 and MC 1303.1.1. 3. Between galvanized steel pipe and copper pipe or tubing: Use a dielectric connector or brass converter fittings per Sections MC 1203.1 and MC 1303.1.1. 4. Between Threaded Brass and Threadless Copper Pipe: Use a suitable brazing adapter. 5. Between Threaded Pipe and Types L Copper Tubing or Welded Brass: Water Tube: Use suitable cast bronze soldering adapter. 6. Between Cast Iron and Threadless Copper Pipe: Use an approved flanged adapter. 7. Between Cast Iron Soil Pipe and Type DWV Copper Tubing or Welded Brass: Drainage Tube: Use a suitable copper to soil pipe adapter and caulk into the cast iron pipe. HVAC PIPING 15510 - 44 01/29/16 NYCSCA DESIGN NO. _____ 8. Between Type DWV Copper Tubing or Welded Brass Drainage Tube and Threaded Outlets at Drains or Fixtures: Use a suitable cast bronze adapter. 9. Between Grooved End Steel Pipe and Other Types of Pipe Joints, Pipe Fittings and Pipe Materials: Use adapter fittings and grooved end coupling fittings, as manufactured by the grooved end pipe fitting manufacturer. 10. Between Hubless Cast Iron pipe and Other Types of Pipe Joints, Pipe Fittings and Pipe Materials: Use adapter fittings, hubless fittings and joint couplings, as furnished by manufacturer. 11. Between Cast Iron and Ductile Iron Pipe, with Rubber Ring Gasketed Joints, and Other Types of Pipe Joints, Fittings and Materials: Use adapter fittings of material and type as required for the particular application. 12. Dissimilar pipe joints in refrigerant piping, i.e., copper to steel, copper to bronze, all stainless steel; stainless steel to copper, brass or bronze: Use approved adapter fittings, with a cadmium free melting alloy. N. Piping for Water Heaters: Where Plumbing and Drainage furnishes a steam tube type water heater, provide steam and return piping, temperature regulating valve, hand valves, traps, and all other items and accessories as shown on the Drawings. O. Standard Weight Red Brass Pipe: Use for compressed air reducing station, piping between boiler and water column, between boiler and water feeder, between boiler and steam gauge, between boiler and secondary low water cut-off, and drip piping from water column, water feeder and secondary low water cut-off. P. Schedule 80 Black Steel Pipe: Use for steam heating return mains, return riser runouts, steam heating coil returns, drips, blow-offs, boiler feed pump discharge, boiler equalizer, steam vent lines, and for all fill and vent piping buried in the ground. Pipe buried in the ground shall be protected with heavy coat of black asphaltum paint. HVAC PIPING 15510 - 45 01/29/16 3.14 DESIGN NO. _____ PIPE AND FITTING SCHEDULE A. Bearing Coolant (Bearing Water Supply (BWS) and Bearing Water Return (BWR)) 125 psig & Less: Type L hard drawn copper tubing, with bronze or brass solder fittings. B. Boiler Blow Off (BO) and Surface Blow Down (CBD) 250 psig & Less: Extra Heavy Weight Black Steel pipe with Weld End Extra Heavy Weight Steel fittings. C. Boiler Feed Pump Discharge (BFD), Boiler Equalizer, and Vent lines: Extra Heavy Weight Black Steel pipe with Weld End Extra Heavy Weight Steel fittings. D. Boiler Feed Pump Suction (BFS) 125 psig & Less: E. 1. 21/2" and Less: Standard Weight Black Steel pipe, with Screwed End Standard Weight Cast-Iron fittings, or Weld End Standard Weight Steel fittings. 2. 3" and Up: Standard Weight Black Steel pipe with Weld End Standard Weight Steel fittings. Chemical Feed (CMF) 125 psig & Less: 1. 21/2" and Less: Standard Weight Black Steel pipe, with Screwed End Standard Weight Cast-Iron fittings, or Weld End Standard Weight Steel fittings. 2. 3" and Up: Standard Weight Black Steel pipe with Weld End Standard Weight Steel fittings. F. Chemical Feed (CMF) 126 to 250 psig: Extra Heavy Weight Black Steel pipe with Weld End Extra Heavy Weight Steel fittings. L. Chilled Water Supply and Return (CHWS & CHWR), and Dual Temperature Water Supply and Return (DTS & DTR), 125 psig and less: 1. NYCSCA 3” and Less: Standard weight black steel pipe with screwed ends standard weight cast-iron fittings; or Type L hard drawn copper tubing with wrought copper or cast copper alloy solder fittings and Type 3 solder (ASTM B32 Alloy Grade E, AC or HB) or mechanically extracted joints made up with brazing alloy or press fit or grooved end fittings. HVAC PIPING 15510 - 46 01/29/16 H. DESIGN NO. _____ 2. 4” size: Standard weight black steel pipe with screwed ends standard weight cast iron fittings or weld end standard weight steel fittings or grooved end fittings; or (press fit Type L hard drawn copper tubing) 3. 5” and Up: Standard weight black steel pipe with weld end standard weight steel fittings or grooved end fittings Chilled Water Supply and Return (CHWS & CHWR) 126 to 250 psig: Standard Weight Black Steel pipe with Weld End Standard Weight Steel fittings. Piping connections 1” in size and less may be made with Standard Weight Black Steel pipe with Screwed End. I. J. Cold Water Above Ground (CW) 125 psig and Less: 1. 4" and Less: Type "L" Copper tubing with soldered fittings or Grooved End Tubing with Grooved End fittings from 2” through 4”. 2. 41/2" and Up: Standard Weight Galvanized Steel pipe with Galvanized fittings or Galvanized Groove End fittings. Compressed Air (A) 125 psig and Less: 1. 21/2" and Less: Red Brass pipe with Malleable Brass threaded fittings. 2. Standard Weight Galvanized steel pipe with Galvanized fittings is only required for direct buried pipe. Pipe above ground shall be standard weight black steel pipe with threaded or grooved joints. K. Compressed Air (A) 126 psig to 250 psig: Standard Weight Black Steel pipe with Screwed End 300 lb Malleable Iron fittings or grooved end with grooved end fittings. L. Condenser Water: (CWS and CWR) 125 psig and Less: 1. NYCSCA 21/2" and Less: Standard Weight Black Steel pipe with Screwed End Standard Weight Cast-Iron fittings, or Weld End Standard Weight Steel fittings. HVAC PIPING 15510 - 47 01/29/16 DESIGN NO. _____ 2. M. N. NYCSCA 3" and Up: Standard Weight Black Steel pipe with Weld End Standard Weight Steel fittings or Grooved End and Grooved End fittings. Fuel Oil Pump Suction and Fuel Oil Return (FOPS and FOR) 125 psig and less: 1. 21/2" and Less: Standard Weight Black Steel pipe, with Screwed End Standard Weight Malleable Iron fittings and fuel resistant thread sealant, or Weld End Standard Weight Steel fittings. 2. 3" and Up: Standard Weight Black Steel pipe with Weld End Standard Weight Steel fittings. 3. Acceptable options are brass pipe, copper or copper-alloy pipe or Type K copper or copper alloy tubing per MC Table 1302.3 except above the lowest floor per Section MC 1305.9.5. Joints between brass pipe or fittings shall be brazed, mechanical, threaded or welded joints complying with Sections MC 1303.3 and MC 1303.4. Joints between copper or copper alloy pipe or fittings shall be brazed, mechanical, threaded or welded joints complying with Sections MC 1303.3 and MC 1303.6. Joints between copper or copper alloy tubing or fittings shall be brazed or mechanical joints complying with Sections MC 1303.3 or flared joints. Flared joints shall be made by a tool designed for that operation. (Refer to Section MC 1303.7). Fuel Oil Pump Discharge (FOPD) 126 to 300 psig: 1. 21/2"and Less: Extra Heavy Weight Black Steel pipe with Screwed End Malleable Iron fittings and fuel resistant thread sealant, or Weld End Extra Heavy Weight Steel fittings. For piping from transfer pumps to equipment or storage tanks above the lowest floor: Lines shall be ASTM A53 or ASTM A106, Grade B, seamless, with welded connections up to the oil tank or equipment, except that fittings at the tank or equipment, shut-off valves, and other fuel oil flow and control devices may be screwed or flanged. 2. 3" and Up: Extra Heavy Weight Black Steel pipe, with Weld End Extra Heavy Weight Steel fittings. For piping from transfer pumps to equipment or storage tanks above the lowest floor: Lines shall be ASTM A53 or ASTM A106, Grade B, seamless, with HVAC PIPING 15510 - 48 01/29/16 DESIGN NO. _____ welded connections up to the oil tank or equipment, except that fittings at the tank or equipment, shut-off valves, and other fuel oil flow and control devices may be screwed or flanged. O. Fuel Oil Fill and Fuel Oil Vent (FOF and FOV) 125 psig and Less: Not Directly Buried in the Ground: 1. 21/2" and Less: Standard Weight Black Steel pipe, with Screwed End Standard Weight Malleable Iron fittings and fuel resistant thread sealant, or Weld End Standard Weight Steel fittings. 2. 3" and Up: Standard Weight Black Steel pipe with Weld End Standard Weight Steel fittings. 3. Acceptable options are brass pipe, copper or copper-alloy pipe or Type K copper or copper alloy tubing per MC Table 1302.3. Joints between brass pipe or fittings shall be brazed, mechanical, threaded or welded joints complying with Sections MC 1303.3 and MC 1303.4. Joints between copper or copper alloy pipe or fittings shall be brazed, mechanical, threaded or welded joints complying with Sections MC 1303.3 and MC 1303.6. Joints between copper or copper alloy tubing or fittings shall be brazed or mechanical joints complying with Section MC 1303.3 or flared joints. Flared joints shall be made by a tool designed for that operation. (Refer to Section MC 1303.7). Directly buried in the Ground: 1. NYCSCA Option 1 (All Sizes): Extra Heavy Weight Black Steel pipe (Schedule 80) with Weld End Extra Heavy Weight Steel fittings with cathodic protection. Where sacrificial anodes or impressed current systems are used, monitors to check on the adequacy of the system shall be installed and kept in proper working condition. Except where cathodic protection is provided by impressed current, underground piping systems shall have dielectric bushings, washers, sleeves or gaskets installed at the end to electrically isolate the piping system from the tank. These dielectric connectors must be chemically compatible when exposed to petroleum, petroleum additives and corrosive soils. The corrosion protection system must be designed by the HVAC PIPING 15510 - 49 01/29/16 DESIGN NO. _____ Contractor’s qualified engineer or corrosion specialist and must be designed to provide a minimum of thirty (30) years of protection against external corrosion. Submit the underground oil piping protection system design (cathodic protection by sacrificial anodes or impressed current) for approval. 2. NYCSCA Option 2 (All Sizes): Double Wall Steel pipe; inner pipe: Extra Heavy Weight Black Steel pipe (Schedule 80) with Weld End Extra Heavy Weight Steel fittings; outer pipe: Standard Weight Black Steel pipe (Schedule 40) with Weld End Standard Weight Steel Fittings, primed with a factory-formulated galvanized metal primer for exterior application, then finish coated with black asphaltum. P. Fuel Oil Gauge: Type L copper tubing with wrought copper solder joint fittings and brazing alloy. Protective enclosure piping, if required Standard Weight Black Steel. Q. Diesel Fuel: 1. 21/2" and Less: Standard Weight Black Steel pipe, with Screwed End Standard Weight Malleable Iron fittings and fuel resistant thread sealant, or Weld End Standard Weight Steel fittings. 2. 3" and Up: Standard Weight Black Steel pipe with Weld End Standard Weight Steel fittings. 3. Acceptable options are brass pipe, copper or copper-alloy pipe or Type K copper or copper alloy tubing per MC Table 1302.3. Joints between brass pipe or fittings shall be brazed, mechanical, threaded or welded joints complying with Sections MC 1303.3 and MC 1303.4. Joints between copper or copper alloy pipe or fittings shall be brazed, mechanical, threaded or welded joints complying with Sections MC 1303.3 and MC 1303.6. Joints between copper or copper alloy tubing or fittings shall be brazed or mechanical joints complying with Section MC 1303.3 or flared joints. Flared joints shall be made by a tool designed for that operation. (Refer to Section MC 1303.7). HVAC PIPING 15510 - 50 01/29/16 DESIGN NO. _____ 4. Vent and Vapor Recovery (Above Ground): 21/2" and Less: Standard Weight Black Steel pipe, with Screwed End Standard Weight Malleable Iron fittings and fuel resistant thread sealant, or Weld End Standard Weight Steel fittings. 3" and Up: Standard Weight Black Steel pipe with Weld End Standard Weight Steel fittings Acceptable options are brass pipe, copper or copper-alloy pipe or Type K copper or copper alloy tubing per MC Table 1302.3. Joints between brass pipe or fittings shall be brazed, mechanical, threaded or welded joints complying with Sections MC 1303.3 and MC 1303.4. Joints between copper or copper alloy pipe or fittings shall be brazed, mechanical, threaded or welded joints complying with Sections MC 1303.3 and MC 1303.6. Joints between copper or copper alloy tubing or fittings shall be brazed or mechanical joints complying with Section MC 1303.3 or flared joints. Flared joints shall be made by a tool designed for that operation. (Refer to Section MC 1303.7). 5. Fill and Gage (not directly buried in the ground): 21/2" and Less: Standard Weight Black Steel pipe, with Screwed End Standard Weight Malleable Iron fittings and fuel resistant thread sealant, or Weld End Standard Weight Steel fittings. 3" and Up: Standard Weight Black Steel pipe with Weld End Standard Weight Steel fittings. Acceptable options are brass pipe, copper or copper-alloy pipe or Type K copper or copper alloy tubing per MC Table 1302.3. Joints between brass pipe or fittings shall be brazed, mechanical, threaded or welded joints complying with Sections MC 1303.3 and MC 1303.4. Joints between copper or copper alloy pipe or fittings shall be brazed, mechanical, threaded or welded joints complying with Sections MC 1303.3 and MC 1303.6. Joints between copper or copper alloy tubing or fittings shall be brazed or mechanical joints complying with Section MC 1303.3 or flared joints. Flared joints shall be made by a tool designed for that operation. (Refer to Section MC 1303.7). NYCSCA HVAC PIPING 15510 - 51 01/29/16 DESIGN NO. _____ 6. Fill and Gage, and Vapor Recovery (buried in the ground from tank to manholes at grade): Option 1 (All Sizes): Extra Heavy Weight Black Steel pipe (Schedule 80) with Weld End Extra Heavy Weight Steel fittings with cathodic protection. Where sacrificial anodes or impressed current systems are used, monitors to check on the adequacy of the system shall be installed and kept in proper working condition. Except where cathodic protection is provided by impressed current, underground piping systems shall have dielectric bushings, washers, sleeves or gaskets installed at the end to electrically isolate the piping system from the tank. These dielectric connectors must be chemically compatible when exposed to petroleum, petroleum additives and corrosive soils. The corrosion protection system must be designed by the Contractor’s qualified engineer or corrosion specialist and must be designed to provide a minimum of thirty (30) years of protection against external corrosion. Submit the underground oil piping protection system design (cathodic protection by sacrificial anodes or impressed current) for approval. Option 2 (All Sizes): Double Wall Steel pipe; inner pipe: Extra Heavy Weight Black Steel pipe (Schedule 80) with Weld End and Extra Heavy Weight Steel fittings; outer pipe: Standard Weight Black Steel pipe (Schedule 40) with Weld End and Standard Weight Steel Fittings, primed with a factoryformulated galvanized metal primer for exterior application, then finish coated with black asphaltum. R. Fuel Oil and Diesel Oil Supply Piping from a transfer pump, Return piping, and Vent piping above the lowest floor: 4" and Less: Standard Weight Black Steel pipe with Weld End Standard Weight Steel fittings. Horizontal piping: double wall (pipe within a pipe) inner: Black Steel Schedule 40; outer: Black Steel Schedule 10 all welded construction. S. NYCSCA High Temperature Water Supply and Return (HTS and HTR) 250 psig and Less: Standard Weight Black Steel pipe with Weld End Standard Weight Steel fittings. HVAC PIPING 15510 - 52 01/29/16 DESIGN NO. _____ T. Instrument Air (IA) 60 psig and Less: Type L copper tubing, with copper or brass or bronze solder fittings. U. Steam (LPS and MPS) 125 psig and Less: 1. 21/2" and Less: Standard Weight Black Steel pipe, with Screwed End Standard Weight Cast-Iron fittings, or Weld End Standard Weight Steel fittings. 2. 3" and Up: Standard Weight Black Steel pipe with Weld End Standard Weight Steel fittings. V. Steam (HPS) 126 to 250 psig: Standard Weight Black Steel pipe with Weld End Standard Weight Steel fittings. W. Steam Condensate Returns, Risers Runouts, Drips: X. Y. 1. 21/2" and Less: Standard Weight Black Steel pipe, with Screwed End Standard Weight Cast-Iron fittings, or Weld End Standard Weight Steel fittings. 2. 3" and Up: Extra Heavy Weight Black Steel pipe (Schedule 80) with Weld End Extra Heavy Weight Steel fittings. Vents (V): 1. 21/2" and Less: Standard Weight Black Steel pipe, with Screwed End Standard Weight Cast-Iron fittings, or Weld End Standard Weight Steel fittings. 2. 3" and Up: Standard Weight Black Steel pipe with Weld End Standard Weight Steel fittings. Hot Water Supply and Return (HWS and HWR) 125 psig and less: 1. NYCSCA 3” and Less: Standard weight black steel pipe with screwed ends standard weight cast-iron fittings; or grooved end pipe with grooved end fittings; or Type L hard drawn copper tubing with wrought copper or cast copper alloy solder fittings and Type 3 solder (ASTM B32 Alloy Grade E, AC or HB) or mechanically extracted joints made up with brazing alloy or press fit or roll grooved copper tube with grooved end fittings. HVAC PIPING 15510 - 53 01/29/16 Z. DESIGN NO. _____ 2. 4” size: Standard weight black steel pipe with screwed ends standard weight cast iron fittings or weld end standard weight steel fittings or grooved end fittings; or (press fit Type L hard drawn copper tubing) 3. 5” and Up: Standard weight black steel pipe with weld end standard weight steel fittings or grooved end fittings 4. Acceptable option is to provide brass pipe, brass tubing, copper or copper-alloy pipe per MC Table 1202.4. Joints between brass pipe or fittings shall be brazed, mechanical, threaded or welded joints conforming to Sections MC 1203.3 and MC 1203.5. Joints between brass tubing or fittings shall be brazed, mechanical, or soldered joints conforming to Sections MC 1203.3 and MC 1203.6. Joints between copper or copper alloy pipe or fittings shall be brazed, mechanical, soldered, threaded or welded joints conforming to Sections MC 1203.3 and MC 1203.7. Refrigerants (RS, RL, RG and RD) 350 psig and Less: In accordance with Section MC 1107.4 AA. Secondary Water (SWS and SWR) 125 psig and Less: NYCSCA 1. 3” and Less: Standard weight black steel pipe with screwed ends standard weight cast-iron fittings; or grooved end pipe with grooved end fittings; or Type L hard drawn copper tubing with wrought copper or cast copper alloy solder fittings and Type 3 solder (ASTM B32 Alloy Grade E, AC or HB) or mechanically extracted joints made up with brazing alloy or press fit or roll grooved copper tube with grooved end fittings. 2. 4” size: Standard weight black steel pipe with screwed ends standard weight cast iron fittings or weld end standard weight steel fittings or grooved end fittings; or (press fit Type L hard drawn copper tubing) 3. 5” and Up: Standard weight black steel pipe with weld end standard weight steel fittings or grooved end fittings 4. Acceptable option is to provide brass pipe, brass tubing, copper or copper-alloy pipe per MC Table HVAC PIPING 15510 - 54 01/29/16 DESIGN NO. _____ 1202.4. Joints between brass pipe or fittings shall be brazed, mechanical, threaded or welded joints conforming to Sections MC 1203.3 and MC 1203.5. Joints between brass tubing or fittings shall be brazed, mechanical, or soldered joints conforming to Sections MC 1203.3 and MC 1203.6. Joints between copper or copper alloy pipe or fittings shall be brazed, mechanical, soldered, threaded or welded joints conforming to Sections MC 1203.3 and MC 1203.7. BB. Condensate Drain Piping: Connected to drip-lip pump bases; all drip piping from air handling units; all drains and overflow lines from heating and air conditioning systems, and all condensate piping systems connected to drain pans - All Sizes: Standard weight (Schedule 40) galvanized steel pipe; or Type L hard temper copper tubing and fittings. Minimum condensate drain line diameter shall be in accordance with MC Table 2 307.2.2. CC. Emergency/Standby Generator Exhaust: Standard Weight Black Steel Pipe with Welded Fittings or Double Wall Insulated Metal Chimney per Section 15575. END OF SECTION RM:JB:MM:BB 01/29/16 Notes to Specifier (Delete from Specifications) 1. Section 15503 is to be utilized if the project involves construction of a New Building or Addition to building in Seismic Design Category C or D. Section is also to be utilized if project involves retrofit work in Existing Buildings constructed after LL17/1995 went into effect in Seismic Design Category C or D. Use Section 15504, Vibration Isolation, (without seismic restraints) for retrofit work on Existing Buildings constructed prior to the effective date of LL17/1995 or New Buildings or Additions in Seismic Design Category B. 2. Ensure Contract Drawings are detailed such that they can meet these requirements. 3. Edit title as required; use in replacement projects only not in new schools. 4. All High Temperature pumps require bearing coolant. NYCSCA HVAC PIPING 15510 - 55 01/29/16 DESIGN NO. _____ 5. Designer shall show cleanouts, traps, routing and terminations (to floor drain, to roof, etc.) of condensate drainage lines on the Drawings. 6. Ensure that concrete anchor used as basis of design has ICC certification for cracked concrete in accordance with Appendix D of ACI 318. 7. Where the refrigerant quantity exceeds MC Table 1103.1 for the smallest space, penetrations for piping that connects separate pieces of equipment shall be either: a. Enclosed by an approved gas-tight, fire- resistive duct or shaft with openings to those floors served by the refrigeration system or b. Located on the exterior of the building where vented to the outdoors or to the space served by the system and not used as an air shaft, closed court or similar space. Designer must show appropriate details on the Drawings. 8. Designer is to show on the Drawing Details the required strainers for all devices (upstream of control valves for chilled beams, unit ventilators, fan coil units, cabinet unit heaters, etc.; pumps; reducing/regulating valves; steam traps serving steam main drips; etc.). Terminal strainers are to be provided even if the central combination air and dirt coalescing separators are provided according to Section 15515, Hydronic Specialties. * * * NYCSCA HVAC PIPING 15510 - 56 01/29/16 DESIGN NO. _____ LIST OF SUBMITTALS SUBMITTAL DATE SUBMITTED DATE APPROVED Product Data: ______________ ____________ ______________ ____________ ______________ ____________ 1. 2. 3. 4. Pipe & Fittings Piping Specialties Expansion Compensation Hangers & Supports Shop Drawings: Schedule: 1. 2. 3. 4. 5. Pipe & Fittings Piping Specialties Expansion Compensation Hangers & Supports Underground Piping Protection System Design 6. Shop Drawings of Condensate Lines Certifications: 1. Welders Qualification Data 2. Brazer Qualifications Data 3. Expansion bolts: ICC Certification * * * NYCSCA HVAC PIPING 15510 - 57