SECTION [26 12 19] [16271]
PAD-MOUNTED, LIQUID-FILLED, MEDIUM-VOLTAGE TRANSFORMER
PART 1 - GENERAL
1.1
SCOPE
A.
1.2
This specification covers the electrical and mechanical characteristics of 45-10,000 kVA ThreePhase Step-Down Pad-Mounted Distribution Transformers. KVA ratings for transformers with
secondary voltages not exceeding 700V are 45-3,750 kVA, while KVA ratings for transformers
with secondary voltages greater than 700V are 1,000-10,000 kVA. .
RELATED DOCUMENTS
A.
1.3
[Related Sections included the following:
1.
Section [26 01 26] [16xxx] – Maintenance and Testing of Electrical Systems]
SUBMITTALS
A.
1.4
The following data shall be submitted with the proposal:
1.
[Core losses] [DO NOT REQUEST IF JOB IS UNEVALUATED]
2.
[Winding losses] [DO NOT REQUEST IF JOB IS UNEVALUATED]
3.
Percent Impedance
4.
Typical record drawings
5.
Approval drawings (furnished at time of order)
6.
Final record drawings (furnished at time of shipment)
RELATED STANDARDS
A.
1.5
All characteristics, definitions, and terminology, except as specifically covered in this
specification, shall be in accordance with the latest revision of the following ANSI and NEMA
standards.
1.
C57.12.00 -IEEE Standard General Requirements for Liquid-Immersed Distribution,
Power, and Regulating Transformers.
2.
C57.12.26 - IEEE Standard for Pad-Mounted, Compartmental-Type, Self-Cooled, ThreePhase Distribution Transformers for Use with Separable Insulated High-Voltage
Connectors (34500GrdY/19920 Volts and Below; 2500 kVA and Smaller).
3.
C57.12.28 - Pad-Mounted Equipment - Enclosure Integrity.
4.
C57.12.34 - IEEE Standard Requirements for Pad-Mounted, Compartmental-Type, SelfCooled, Three-Phase Distribution Transformers (2500 kVA and Smaller) - High Voltage:
34500GrdY/19920 Volts and Below; Low-Voltage: 480 Volt 2500 kVA and Smaller.
(issued in March 2005 - combines C57.12.22 and C57.12.26)
5.
C57.12.90 - IEEE Standard Test Code for Liquid-Immersed Distribution, Power, and
Regulating Transformers and IEEE Guide for Short-Circuit Testing of Distribution and
Power Transformers.
6.
C57.91 - Guide for Loading Mineral-Oil-Immersed Transformers.
7.
This specification covers only the general requirements of the transformer.
QUALITY ASSURANCE
A.
The manufacturer shall have specialized in the design, manufacture and assembly of liquid filled
padmounted tamper-resistant transformers for a minimum of 10 years.
B.
The manufacturer shall have a well documented quality assurance program, which includes
procedures for all activities in order entry, design, material procurement, manufacturing
processes, testing, shipping and post shipment product follow.
C.
The manufacturer’s test floor shall have a documented calibration program. All equipment shall
receive regular calibrations. Calibration standards shall be traceable to National Bureau of
Standards.
March 7, 2016
Padmounted Transformers
[Project Name]
[26 12 19] [16271]-1
D.
1.6
The transformers shall be manufactured by a company which is certified to ISO 9001:2000. A
copy of the certificate of Compliance to this requirement is available upon request.
DELIVERY, STORAGE AND HANDLING
A.
Handle and store equipment in accordance with manufacturer’s Installation and Maintenance
Manuals. One (1) copy of this document to be provided with the equipment at time of shipment.
PART 2 - PRODUCTS
2.1
MANUFACTURERS
A.
2.2
The padmounted distribution transformer shall be provided by Siemens or pre-approved
equal. Approved manufacturers are as follows:
1.
SIEMENS Industry
2.
COOPER POWER SYSTEMS
3.
.]
TECHNICAL REQUIREMENTS
A.
Electrical Characteristics
1.
The transformer shall be designed in accordance with this specification and the kVA
rating shall be [45] [75] [112.5] [150] [225] [300] [500] [750] [1000] [1500] [2000] [2500]
[3000] [3750] [5000] [7500] [10,000] [Range may also be specified].
2.
Frequency: [60] [50] Hertz
3.
Primary Voltage:
a.
The primary voltage, configuration, and the basic lightning impulse insulation level
(BIL) shall be:
1.)
[2400 Delta, 60 kV BIL]
2.)
[4160 Delta, 60 kV BIL]
3.)
[4800 Delta, 60 kV BIL]
4.)
[7200 Delta, 75 kV BIL]
5.)
[12000 Delta, 95 kV BIL]
6.)
[12470 Delta, 95 kV BIL]
7.)
[13200 Delta, 95 kV BIL]
8.)
[13800 Delta, 95 kV BIL]
9.)
[14400 Delta, 95 kV BIL]
10.) [16430 Delta, 125 kV BIL]
11.) [34500 Delta, 150 kV BIL]
12.) [43800 Delta, 250 kV BIL]
13.) [4160GrdY/2400, 60 kV BIL]
14.) [8320GrdY/4800, 75 kV BIL]
15.) [12470GrdY/7200, 95 kV BIL]
16.) [13200GrdY/7620, 95 kV BIL]
17.) [13800GrdY/7970, 95 kV BIL]
18.) [22860GrdY/13200, 125 kV BIL]
19.) [23900GrdY/13800, 125 kV BIL]
20.) [24940GrdY/14400, 125 kV BIL]
21.) [34500GrdY/19920, 150 kV BIL]
22.) [43800GrdY/25300, 250 kV BIL]
b.
The secondary voltage, configuration, and the basic lightning impulse insulation
level (BIL) shall be:
1.)
[208Y/120, 30 kV BIL]
2.)
[480Y/277, 30 kV BIL]
3.)
[575Y/332, 30 kV BIL]
4.)
[600Y/347, 30 kV BIL]
5.)
[690Y/398, 30 kV BIL]
6.)
[240 Delta, 30 kV BIL]
March 7, 2016
Padmounted Transformers
[Project Name]
[26 12 19] [16271]-2
c.
d.
e.
4.
5.
6.
B.
7.)
[480 Delta, 30 kV BIL]
8.)
[240 Delta with 120 Mid-Tap, 30 kV BIL]
9.)
[480 Delta with 240 Mid-Tap, 30 kV BIL]
10.) [2400 Delta, 60 kV BIL]
11.) [4160 Delta, 60 kV BIL]
12.) [4800 Delta, 60 kV BIL]
13.) [7200 Delta, 75 kV BIL]
14.) [12000 Delta, 95 kV BIL]
15.) [12470 Delta, 95 kV BIL]
16.) [13200 Delta, 95 kV BIL]
17.) [13800 Delta, 95 kV BIL]
18.) [14400 Delta, 95 kV BIL]
19.) [4160GrdY/2400, 60 kV BIL]
20.) [8320GrdY/4800, 75 kV BIL]
21.) [12470GrdY/7200, 95 kV BIL]
22.) [13200GrdY/7620, 95 kV BIL]
23.) [13800GrdY/7970, 95 kV BIL]
[For complete connector rating, see ANSI/IEEE 386.]
Transformers are suitable for connectors with phase-to-ground or phase-toground/phase-to-phase high-voltage ratings as listed.
Arrester coordination may require higher BIL on multiple connections than
indicated to achieve a minimum protection level of 20%.
Taps
a.
The transformer shall be furnished with full capacity high-voltage taps. The taps
shall be +/- 2 – [2½% above and below nominal voltage] [4 – 2 ½% below
nominal voltage].
b.
The tap changer switch shall be an externally operated switch with a hotstickoperable handle. The tap changer shall be clearly labeled to reflect that the
transformer must be de-energized before operating the tap changer as required in
Section 3.3 of ANSI C57.12.26. Taps shall be provided on the higher voltage of
dual voltage primary units.
Winding Temperature
a.
The average winding temperature rise above ambient temperature, when tested at
the transformer rating, [shall not exceed 65 deg C] [shall not exceed 55 deg C]
[at the base transformer rating, shall not exceed 55 deg C, and when tested
at 112% of the base rating, shall not exceed 65 deg C].
Impedance
a.
The percent impedance voltage, as measured on the rated voltage connection,
shall be as follows:
1.)
[[Low Voltage < 700V]
a.)
[At 75 kVa, 1.10 to 5.75% Impedance]
b.)
[At 112.5 to 300 kVa, 1.40 to 5.75% Impedance]
c.)
[At 500 kVa, 1.70 to 5.75% Impedance]
d.)
[At 750 to 3750 kVa, 5.75% Impedance nominal]]
2.)
[[Low Voltage >700V]
a.)
[At 1000 to 5000 kVA, < 150kV BIL, 5.75% Impedance]
b.)
[At 1000 to 5000 kVA, 200 kV BIL, 7.00% Impedance]
c.)
[At 1000 to 5000 kVA, 250 kV BIL, 7.50% Impedance]
d.)
[At 7500 to 10000 kVA, < 150kV BIL, 6.50% Impedance]
e.)
[At 7500 to 10000 kVA, 200 kV BIL, 7.00% Impedance]
f.)
[At 7500 to 10000 kVA, 250 kV BIL, 7.50% Impedance]]
b.
For target impedances, the tolerance on the impedance shall be +/- 7.5% of
nominal value for impedance values greater than 2.5%. The tolerance on the
impedance shall be +/- 10.0% for impedance values less than or equal to 2.5%.
High Voltage Bushings And Terminals
March 7, 2016
Padmounted Transformers
[Project Name]
[26 12 19] [16271]-3
1.
2.
C.
Bushing Style: [Select one of the following 5, delete the other 4]
a.
[15/25 KV Deadfront, For Currents below 200 Amps: The high voltage
bushings shall be 15/25 kV 200A bushing wells with bushing well inserts
installed. The bushings shall be externally removable and be supplied with a
removable stud. ]
b.
[35 KV Deadfront, For Currents below 200 Amps: The high voltage bushing
shall be a one-piece, 150 kV, 200-amp large interface load-break bushing.]
c.
[15/25/35 KV Deadfront, For Currents Above 200 Amps: The high voltage
bushing shall be a 600A Deadbreak Primary One-Piece Bushing externally
removable, 3ø rated, integral design. 900 A can also be achieved using
copper conductors.]
d.
[UP TO 46 KV (250 KV BIL) Deadfront Applications: The high voltage bushing
shall be a CONNEX Plug-in Cable Termination System, size 3S. The male and
female portions of the bushing shall be supplied with the transformer. This
is only available in radial feed.]
e.
[15/25/35 KV Livefront, 200 KV BIL Max: The high voltage bushing shall be a
porcelain bushing with a two, four, or six-hole spade or an eyebolt
connector.]
Bushing Configuration - [Select one of the following 7, delete the other 6]
a.
[15/25 KV Radial Feed Deadfront: The transformer shall be provided with
three (3) high voltage bushings in accordance with Figure 1 minimum
dimensions (Figure 4a specific dimensions also available) of ANSI C57.12.34
for radial feed configurations. The bushing heights shall be in accordance
with Figure 3 minimum dimensions (Figure 6 specific dimensions also
available) of ANSI C57.12.34.]
b.
[15/25 KV Loop Feed Deadfront: The transformer shall be provided with six
(6) high voltage bushings in accordance Figure 2 minimum dimensions
(Figure 5a specific dimensions also available) of ANSI C57.12.34 for loop
feed configurations. The bushing heights shall be in accordance with Figure
3 minimum dimensions (Figure 6 specific dimensions also available) of ANSI
C57.12.34.]
c.
[35 KV Radial Feed Deadfront: The transformer shall be provided with three
(3) high voltage bushings in accordance with Figure 4b specific dimensions
of ANSI C57.12.34 for radial feed configurations. The bushing heights shall
be in accordance with Figure 6 specific dimensions of ANSI C57.12.34.]
d.
[35 KV Loop Feed Deadfront: The transformer shall be provided with six (6)
high voltage bushings in accordance with Figure 5c specific dimensions of
ANSI C57.12.34 for loop feed configurations. The bushing heights shall be in
accordance with Figure 6 specific dimensions of ANSI C57.12.34.]
e.
[250 KV BIL Deadfront: The transformer shall be provided with 3 bushings
mounted 45° down from the horizontal, 60” from the ground, and 12” apart
from each other.]
f.
[15/25/35 KV Livefront, 150 KV BIL MAX: The transformer shall be provided
with three (3) bushings in accordance with Figure 9 of ANSI C57.12.34 for
radial feed configurations. The bushing heights shall be in accordance with
Figure 10 of ANSI C57.12.34.]
g.
[200 KV BIL Livefront: The transformer shall be provided with 3 bushings
with phase-to-phase and phase-to-ground clearances adequate for 200 kV
BIL.]
Secondary Voltage Bushings And Terminals
1.
Bushing Style:
a.
For Voltages less than 700 Volts:
1.)
The transformer shall be provided with tin-plated spade-type bushings for.
The spacing of the connection holes shall be 1.75” on center, per ANSI
March 7, 2016
Padmounted Transformers
[Project Name]
[26 12 19] [16271]-4
C57.12.34 figure 13. The quantity of connection holes shall be [4] [6] [8]
[10] [12] [16] [20] holes. [Delete table, below, after using.]
2.)
Standard/Possible Bushing Hole Quantities
KVA
45-300
500
750-1500
2000-3750
208Y/120
4 standard, 16 possible
6 standard, 12 possible
10 standard, 20 possible
Out of product scope
480Y/277 and up
4 standard, 16 possible
4 standard, 16 possible
6 standard, 12 possible
10 standard, 20 possible
3.)
2.
D.
Bushing supports shall be provided for units requiring 10 or more connection
holes. Bushing supports shall be attached to the cabinet sidewalls; tankmounted support mountings are not acceptable.
b.
For Voltages greater than 700 Volts:
1.)
Refer to Section 2.2.B for the bushing type. Secondary arrangements are
available in radial live front and loop or radial deadfront with a porcelain X0
bushing.
Bushing Configuration:
a.
The transformer shall be provided with bushings in a staggered arrangement in
accordance with Figure 11a minimum dimensions (Figure 12a specific dimensions
also available) of ANSI C57.12.34.
Transformer Protection And Switching
1.
Overcurrent Protection:
a.
Bayonet [with] [without] current limiting fuses: [Available up to 130 amps of
full-load transformer current, up to 34.5 kV grounded wye, or 17.1 kV delta].
[The high-voltage overcurrent protection scheme provided with the transformer
shall be an externally removable loadbreak expulsion Bay-O-Net fuse assembly
with a flapper valve to minimize oil spillage. [The bayonet fuses shall be in
series with ELSP under-oil partial-range current-limiting back-up fuses with
an interrupting rating of 50,000 A.]] [For voltages 23000GY and above and a
delta connected secondary, bayonet fuses are not available.]
b.
[An interlock shall be required between the load-break switch scheme
specified and the bayonet fuses, such that the fuses may not be removed
unless the transformer has been de-energized via the load-break switch
scheme.]
c.
[Magnex® Interrupter: [Available up to 42 amps of full-load transformer
current, up to 35 kV]
1.)
[The high-voltage overcurrent protection scheme provided with the
transformer shall be a three-phase trip Magnex® Interrupter. This
externally resettable device may also be used as an on-off switch. The
three-phase Magnex® Interrupter shall be in series with ELSP under-oil
partial-range current-limiting back-up fuses with an interrupting rating
of 50,000 A.]]
d.
[Integral Vacuum Fault Interrupter (VFI): [Available from 13 amps up to 712
amps of full-load transformer current, up to 34.5 kV, grounded wye or delta]
1.)
[The high-voltage or low-voltage overcurrent protection scheme
provided with the transformer shall be an integral Vacuum Fault
Interrupter (VFI). The VFI shall have a maximum interrupting rating of
12000A RMS symmetrical with resettable fault protection up through
35kV. The VFI shall also include a Tri-Phase electronic breaker control
with over 100 minimum trip settings and 5 selectable time current
curves. The minimum trip setting shall be XX amps, and curve profile
shall be the EF, KF, TF, F, or H.]]
e.
[VFI Accessories:
March 7, 2016
Padmounted Transformers
[Project Name]
[26 12 19] [16271]-5
1.)
SCADA board; Secondary ground fault protection; Motor operator
assembly; visible break window.]
E.
Overvoltage Protection:
1.
The overvoltage protection scheme provided with the transformer shall protect the [high
voltage] [low voltage] winding.
2.
[[With DEADFRONT bushings: 150 kV BIL, for voltages up to 22 kV delta and 35 kV
grounded wye.] [Externally mounted, Distribution Class M.O.V.E. Deadfront elbow
arresters shall be supplied.]
3.
[UNDER OIL: For voltages up to 35 kV.] [Internally mounted, Distribution Class
MOV under-oil surge arresters shall be supplied.]
a.
[Three (3) disconnect switches shall be included to disconnect the under-oil
arresters from ground for transformer testing.]]
4.
[With LIVEFRONT bushings: Up to 200 KV BIL.] [Intermediate class] [Distribution
Class] [Heavy Duty] [Medium Duty] [Riser Pole Duty] arresters shall be supplied
beneath the high-voltage livefront bushings.]]
F.
Switching:
1.
The primary switching scheme provided with the transformer shall be [one] [for radial
feed one is the only available option] [two] [three on/off] [one four-position Vblade] [one four-position T-blade loadbreak switch].
a.
[Make-before-break option for four-position, sectionalizing switch:
1.)
The switch shall eliminating momentary interruptions during switching
operations by utilizing a make before break operation.]
2.3
GENERAL DESIGN
A.
Core and coil
1.
The core and coil shall be vacuum processed to ensure maximum penetration of
insulating fluid into the coil insulation system. While under vacuum, the windings will be
energized to heat the coils and drive out moisture, and the transformer will be filled with
preheated filtered degassed insulating fluid. The core shall be manufactured from burrfree, grain-oriented silicon steel and shall be precisely stacked to eliminate gaps in the
corner joints. The coil shall be insulated with B-stage, epoxy coated, diamond pattern,
insulating paper, which shall be thermally cured under pressure to ensure proper bonding
of conductor and paper.
B.
Dielectric fluid
1.
The dielectric coolant shall be
a.
[listed less-flammable fluid meeting the requirements of National Electrical
Code® Section 450-23 and the requirements of the National Electrical Safety
Code (IEEE C2-1997), Section 15. The dielectric coolant shall be readily and
completely biodegradable per EPA OPPTS 835.3100. The base fluid shall be
100% derived from edible seed oils with performance enhancing additives.
The fluid shall result in zero mortality when tested on trout fry per OECD G.L.
203 and be non-bioaccumulating. The fluid shall be published under US EPA
Environmental Technology Verification (ETV) requirements, and tested for
compatibility with transformer components. The fluid shall be Factory Mutual
Approved, UL® Classified Dielectric Medium (UL-EOUV) and UL Classified
Transformer Fluid (UL-EOVK), Envirotemp® FR3® fluid.] [The dielectric
coolant in the transformer must be highly refined Type II inhibited new
mineral oil and meet the minimum requirements as specified in Table 1,
“Functional Property Requirements,” of ASTM D3487 and ANSI C57.106.]
C.
Tank and Cabinet Enclosure
1.
The tank and Cabinet enclosure shall meet the following requirements.
a.
The high-voltage and low-voltage compartments, separated by a metal barrier,
shall be located side-by-side on one side of the transformer tank. When viewed
from the front, the low-voltage compartment shall be on the right. Each
March 7, 2016
Padmounted Transformers
[Project Name]
[26 12 19] [16271]-6
b.
c.
d.
e.
f.
g.
h.
i.
2.4
compartment shall have a door that is constructed so as to provide access to the
high-voltage compartment only after the door to the low-voltage compartment has
been opened. There shall be one or more additional fastening devices that must
be removed before the high-voltage door can be opened. Where the low-voltage
compartment door is of a flat panel design, the compartment door shall have threepoint latching with a handle provided for a locking device. Hinge pins and
associated barrels shall be constructed of corrosion-resistant material, passivated
AISI Type 304 or the equivalent.
A recessed, captive, [penta-head] [hex-head] bolt that meets the dimensions per
ANSI C57.12.28 shall secure all access doors.
The enclosure integrity of the tank and cabinet shall meet the requirements for
tamper resistance set forth in ANSI C57.12.28 including but not limited to the pry
test, pull test, and wire probe test.
The compartment depth shall be in accordance with C57.12.34, unless additional
depth is specified.
The tank base must be designed to allow skidding or rolling in any direction. Lifting
provisions shall consist of four lifting lugs welded to the tank.
The tank shall be constructed to withstand 7 psi without permanent deformation,
and 15 psi without rupture. The tank shall include a 15 psig pressure relief valve
with a minimum flow rate of 35 SCFM.
The tank and cabinet coating shall meet all the requirements of ANSI C57.12.28
including:
1.)
Salt Spray Test
2.)
Crosshatch Adhesion Test
3.)
Humidity Test
4.)
Impact Test
5.)
Oil Resistance Test
6.)
Ultraviolet Accelerated Weathering Test
7.)
Abrasion Resistance - Taber Abraser
The exterior of the unit shall be painted [Munsell 7GY3.29/1.5 green] [ANSI 70
gray] [ANSI 61 gray] color. The cabinet interior and tank face shall be painted
gray for ease of viewing the inside the compartment.
The tank shall be complete with an anodized aluminum laser engraved nameplate.
This nameplate shall meet Nameplate B per ANSI C57.12.00.
FEATURES
A.
2.5
The following features shall be provided:
1.
Bolted main tank cover (1000 kVA & below)
2.
Welded main tank cover with bolted handhole (1500 kVA & above)
3.
1.0” upper fill plug
4.
1.0” drain plug in LV compartment (500 kVA & below)
5.
1.0” drain valve w/ sampling device in LV compartment (750 kVA & above)
6.
Automatic pressure relief valve
7.
Metal drip shield (when bayonets specified)
8.
20” deep cabinet (2500 kVA & below)
9.
24” deep cabinet (3000 kVA & above)
10.
Ground provisions per C57.12.34 section 9.11.
11.
Meet NEMA TR-1 sound levels
ACCESSORIES
A.
The following accessories shall be provided
1.
[Liquid level gauge]
2.
[Dial-type thermometer gauge]
3.
[Pressure vacuum gauge]
4.
[1.0” drain valve w/ sampling device in (LV or HV) compartment (500 kVA & below)]
5.
[Upper fill valve]
March 7, 2016
Padmounted Transformers
[Project Name]
[26 12 19] [16271]-7
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
25.
26.
27.
28.
29.
30.
31.
32.
33.
34.
35.
36.
37.
2.6
[Pressure vacuum bleeder]
[24” deep cabinet]
[30” deep cabinet]
[36” deep cabinet]
[40” deep cabinet]
[Spare bayonet fusing]
[Fault indicator provisions]
[Ground connectors]
[Mr. Ouch warning & danger signs]
[Danger high voltage warning signs]
[Miscellaneous stenciling]
[Non-PCB decal]
[Touch-up paint]
[Interphase barriers (for live front primary units only)]
[Seismic zone 3 and 4 tank anchoring]
[Complete 304 stainless steel tank and cabinet]
[304 stainless steel tank base and cabinet sides & sill (partial)]
[Liquid level gauge with auxiliary contacts]
[Dial-type thermometer gauge with auxiliary contacts]
[Pressure vacuum gauge with auxiliary contacts]
[Current or potential transformers]
[Rapid rise relay with seal-in panel]
[Winding temperature indicator]
[Watt-hour meter package – includes GE kV Vector Meter (digital demand register).
Factory supplied wiring shall be internal to the cabinet, not in conduit.
Communication connection shall be the OPTOCOM port.]
[Harmonic resistant K-factor design, K-[4] [9] [13] [20]]
[Forced air (FA) rating]
[Future forced air (FFA) rating]
[Factory Mutual (FM) Approved transformer (for NEC Code-listed installations on,
near, or inside of buildings)]
[UL Listed and Classified transformer (for NEC Code-listed installations on, near,
or inside of buildings) per UL XPLH]
[UL Listed transformer (certifying compliance with ANSI standards only) per UL
XPLH]
[Increased efficiency criteria / evaluated losses:
a.
[Core loss evaluation (A-factor) ______$/watt]
b.
[Winding loss evaluation (B-factor)_________$/watt]]
[NEMA TP-1 Efficiency design (2500 kVA and below)]
SHIPPING
A.
2.7
Units 1000 kVA and below shall be palletized. Units 1500 kVA and larger shall be loaded and
unloaded with overhead cranes, so a pallet is not to be provided for these transformers.
TESTING & TOLERANCES
A.
All units shall be tested for the following:
1.
No-Load [85 deg C] [20 deg C] losses at rated current
2.
Total (85 deg C) losses at rated current
3.
Percent Impedance (85 deg C) at rated current
4.
Excitation current (100% voltage) test
5.
Winding resistance measurement tests
6.
Ratio tests using all tap settings
7.
Polarity and phase relation tests
8.
Induced potential tests
9.
Full wave and reduced wave impulse test
March 7, 2016
Padmounted Transformers
[Project Name]
[26 12 19] [16271]-8
B.
Cerification
1.
The manufacturer shall provide certification upon request for all design and other tests
listed in C57.12.00, including verification that the design has passed short circuit criteria
per ANSI C57.12.00 and C57.12.90.
C.
[Evaluted Losses
1.
The no-load losses of a transformer shall not exceed the specified no-load losses
by more than 10%, and the total losses of the transformer shall not exceed the
specified total losses by more than 6%.]
PART 3 - EXECUTION
3.1
INSTALLATION
A.
Install transformer as shown on Project Drawings and in accordance with manufacturer’s
Instruction/Installation Manual.
B.
Provide concrete pad with sufficient structural support and in accordance with local codes and
standards. Concrete pad requirements should be coordinated with transformer manufacturer.
C.
Grounding should be per Project Drawings and in accordance with local codes and standards
and in compliance with the NEC.
3.2
ADJUSTMENTS AND CLEANING
A.
Remove debris from job site and wipe dust and dirt from all components.
B.
Repaint marred and scratched surfaces with touch up paint to match original finish.
3.3
TESTING
A.
[Field-testing will be conducted at the expense of the Owner, if required for final
acceptance.]
B.
Refer to Section [26 xx xx] [16040], “Electrical Tests, Adjustments and Inspection.”
3.4
WARRANTY
A.
Equipment manufacturer warrants that all goods supplied are free of non-conformities in
workmanship and materials for one year from date of initial operation, but not more than
eighteen months from date of shipment.
END OF SECTION
March 7, 2016
Padmounted Transformers
[Project Name]
[26 12 19] [16271]-9