Corporate Fire Protection Marriott Drive, Dept.52/924.36 Washington, D.C. 20058 Tel: (301) 380-7502 Fax: (301) 380-6681 LOW RISE BUILDING* Fire Protection Systems Final Acceptance Test Criteria and Checklist Property Brand________________ Address_________________________________ City_________________________ State____________ Zip____________________ Contact Person_________________________________________________________ Phone__________________ Email____________________ Fax_________________ Under Marriott Corporate guidelines, all fire protection systems and life safety features of the building are required to be fully operational, comply with specifications, and be fully tested and accepted by Marriott Corporate Fire Protection prior to admitting Marriott operations personnel or general public to the building. The final testing will include the sprinkler system, fire alarm system, emergency power and kitchen hood suppression system where applicable. It is necessary that the installation of these systems is complete, has received prior testing or adjustment, and is ready for full operational use, prior to the witnessing of the final acceptance tests. Testing will require the presence of representatives from the sprinkler and fire alarm companies. Please have two fully charged portable radios available for use on site during test. The final test will include the following: Automatic Sprinkler System System shall be flushed and pressure tested by contractor prior to Marriott testing. All sprinkler devices connected to the fire alarm system will be tested. These devices include water flow switches, tamper switches, and pressure switches/gauges (if installed) on all zones. The fire pump (if installed) must be tested and approved by the authority having jurisdiction prior to Marriott testing. A representative of the sprinkler contractor shall be present and prepared to test system. Fire Alarm System The fire alarm system shall be clear from all troubles on the FACP and pre-tested by the contractor prior to Marriott testing. Marriott will test all devices and ensure proper zone/device indications and function on the alarm panel. A representative of the fire alarm contractor shall be present and prepared to test system (including canned smoke and pull station keys). Emergency Power System All power to the building will be turned off to test the emergency power system. Emergency lighting illuminating the exit path, exit signs and lighting of the exit discharge to the public way will be checked as well as certain other public and back of house areas. Diesel driven generator (if installed) must automatically activate upon loss of power to operate all emergency systems as specified in the Marriott International Design Guide. Page 1 of 9 Kitchen Suppression System (if applicable ) Kitchen hood is protected by an “Ansul PIRANHA” system that has been tested and approved by the authority having jurisdiction prior to Marriott testing. A certified Piranha installer must be present at the Marriott testing. The system will not be expelled however the manual pull station test, shunt test for gas and electric under the hood, fire alarm interface and the detection test from the farthest link under the hood will be tested. Note: The above systems represent only a portion of Marriott International's Life Safety Standards which must be implemented in accordance with the Marriott Hotel Design Guide. Local codes will be enforced if more stringent than Marriott requirements. LOCAL FIRE INSPECTIONS MUST BE COMPLETE WITH ALL DESCREPANCIES CORRECTED BEFORE INSPECTION BY MARRIOTT FIRE PROTECTION. Attach and fax. LOW RISE ACCEPTANCE CHECKLIST Sprinkler System: 1. System is zoned by floor. Each floor zone has a control valve assembly with a tamper switch and a flow switch on every floor. YES NO 2. The inspector test assemblies are located at the most remote end (opposite of feed end) of each zone (each floor) with a sight glass and hard piped drain to the exterior. Test valve cannot be located in a guest room. YES NO 3. The sprinkler flow switches are set to activate the general alarm within 30 to 60 seconds after water flow. YES NO 4. All sprinkler heads in occupied areas are recessed or semi recessed fast response type 3mm bulb (no concealed heads). and 155 to 165 F. YES NO 5. The entire building is protected with an automatic sprinkler system, including the attic, all mechanical and electrical rooms, as well as all public and back of house storage closets. YES NO 6. All occupied areas are protected with a wet sprinkler system. NO GUESTROOM IS PROTECTED BY A DRY SPRINKLER SYSTEM. YES NO 7. All unheated areas (less than 40F) and or subject to freezing are protected with a dry sprinkler system (attic, combustible canopies, etc.). YES NO N/A Page 2 of 9 8. The entire dry sprinkler system piping is installed with galvanized piping. YES NO N/A 9. The air compressor for the dry system is tank mounted type and permanently wired to house current. YES NO N/A 10. The dry system delivers water to the remote inspector test discharge within 60 seconds of activation of the inspector test valve. YES NO N/A 11. The inspector test for the dry system is located at the most remote end. Inspector test valve must not be located within a guestroom or attic space. YES NO N/A 12. Sprinkler heads are installed in laundry chute above the top opening, above the bottom opening, and at alternating levels. YES NO N/A 13. Sprinkler heads in pool/whirlpool rooms and pool equipment rooms are corrosion resistant type. YES NO N/A 14. Sprinkler heads are located in guest bathrooms containing a combustible (flame spread rating of 25 or more, i.e. fiberglass, etc.) bath tubs, surrounds, whirlpool or the room is greater than 55 sq.ft. YES NO N/A 15. All wet sprinkler pipe is located in heated space. Routing pipe through the attic and covering pipe with insulation or heat tape is not acceptable. YES NO N/A 16. All sprinkler control valves, drain valves and test valves are marked with permanent weatherproof metal or rigid plastic identification signs. Signs indicate the specific portion of the building controlled by the valve. YES NO 17. The electric fire pump annunciates the conditions “run”, “phase reversal” and “off line” at the fire alarm control panel. YES NO N/A 18. There are no lightning or electrical ground bonds on the wet or dry sprinkler pipe. YES NO 19. All combustible and limited combustible structures closer than 30 feet to any portion of the hotel or any significant outbuilding are protected with a sprinkler system. (In most locations this will mean a dry sprinkler system since antifreeze systems (liquid) are not permitted). YES NO Page 3 of 9 20. Porte cochere is protected by an automatic sprinkler system unless the exceptions delineated in NFPA 13, chapter 8.15.7.2, 8.15.7.3, 8.15.7.4 are met in the table below: EIFS is a limited combustible YES NO N/A Fire Alarm System: 1. The fire alarm system is a fully point addressable by a Marriott approved manufacturer. YES NO 2. Guestroom smoke detectors (sensors) are photoelectric type rather than ionization and have a sounder base. YES NO 3. Guestroom system type smoke detectors will sound a local alarm within each guestroom, display an audible/visual alarm at the FACP, as well as display the guestroom number at the FACP. YES NO Page 4 of 9 4. Multiple smoke detectors within a guestroom suite are interconnected. For example, if the smoke detector sounds within the living area, the smoke detector located in the bedroom(s) must also sound. YES NO N/A 5. Fire alarm mini-horns are installed in all sleeping areas within a typical guestroom. Smoke detector sounder bases may be used in lieu of fire alarm mini-horns as long as the sounder bases can be used for the local alarm as well as the notification appliance in the guestroom on building general alarm. YES NO 6. A fire alarm strobe is located in the sleeping area, bathroom, and living area (if separated) in all accessible and hearing impaired guestrooms. Check height of strobe for proper candela rating. YES NO 7. The fire alarm strobes within the accessible and hearing-impaired guestrooms will activate upon a local alarm (guestroom smoke detector activation) as well as upon a general alarm (sprinkler water flow alarm, pull station etc.) YES NO 8. The fire alarm tone consists of a three-pulse temporal pattern rather than a constant tone. This includes the general and local guestroom alarm. YES NO 9. Carbon monoxide (CO) detectors are installed in ALL rooms containing fuel burning equipment, appliances or fireplaces. CO detectors must provide a local alarm within the room and a supervisory alarm at the fire alarm control panel. YES NO N/A 10. Removal of a guest room smoke or carbon monoxide detector will initiate a trouble signal at the fire alarm control panel. YES NO 11. All guest elevators are equipped with elevator recall. Ensure 1st floor elevator lobby smoke detector will recall the elevators to an alternate level. YES NO Page 5 of 9 FAILURE TO PROVIDE THE FOLLOWING WILL DICTATE A RETURN TRIP, TOTAL FIRE ALARM RE-TEST AND A POSSIBLE DELAYED OPENING. 12. The FACP must disable audible appliances, visual strobes, and auxiliary function points for testing purposes with the use of disconnect switches or single function key pads. One switch/key should silence horns and strobes for general alarm. WHILE DISABLED, The guestroom smoke alarms must sound as usual on local alarm and ADA/hearing impaired rooms must have visible and audible on local alarm , One switch/key should bypass elevator recall, One should bypass fans 2000cfm or greater, smoke evacuation and stairwell pressurization, One should bypass magnetic door release mechanisms. THIS IS NOT A WALK TEST BUTTON The intent is to allow an occupied hotel to be inspected without bothering the guests, yet keep the system live in the guestroom for other actual alarms. At some point in the inspection the aux. function switches can be put back in, one at a time, for actual full scale audible/visual testing. FACP General Alarm Bypass Disabling Switch Matrix Switch Device Public Spaces/Corridor ADA & Hearing Impaired Guestrooms Back of House Stairwells Disable on GEN alarm Active on LOCAL alarm Disable Disable Disable Disable #1 Horns and Strobes Disable #2 Magnetic Door Hold-Open Disable #3 Smoke Evacuation & Stairwell Pressurization Fans Disable #4 Elevator Recall Disable Disable Disable *Please Note: 1) ADA/Hearing Impaired Guestroom Horns and Strobes will remain active for local activation during testing. 2) A "walk test" mode is not an option. YES NO Page 6 of 9 13. The guestroom smoke detectors DO NOT initiate the general fire alarm. YES NO 14. The fire alarm installer has completed and signed the NFPA 72 Fire Alarm System Record of Completion. ATTACH AND FAX. YES NO 15. Guest room smoke detectors are powered by the fire alarm control panel. A/C smoke detectors are not acceptable. YES NO 16. The fire alarm strobe in the ADA/Hearing impaired guestrooms is located in direct line-of-sight with the pillow. (NFPA 72 Chapter 7.6) YES NO N/A 17. The fire alarm system is arranged to transmit an alarm automatically to a listed central station. YES NO Emergency Power System: 1. Emergency lighting is installed throughout the entire hotel including; all back of house areas, laundry, fire alarm control panel area, public restrooms, engineer’s office, telephone equipment room, mechanical rooms, elevator room, fire pump and sprinkler room, administrative offices, meeting rooms, and on the exterior side of all marked exit discharges. YES NO 2. Exit signs are illuminated by emergency power. YES NO 3. Transfer to emergency generator power occurs within 10 seconds. YES NO 4. The emergency generator must annunciate the conditions “run” and “off line” at the fire alarm control panel. YES NO N/A Kitchen Hood System (if applicable): 1. The kitchen hood is protected with an Ansul “PIRANHA” suppression system. YES NO N/A Page 7 of 9 2. Activation of the hood system sends an alarm to the fire alarm control panel, drops an electric shunt tripping breakers for all electric current under the hood, as well as trips the gas solenoid for all gas fueled cooking appliances under the hood. The hood exhaust fan must start and continue to run after activation. YES NO N/A 3. The PIRANHA system was installed by an Ansul Piranha Certified Technician and tested in accordance with Ansul Piranha test procedures. AN ANSUL TECHNICIAN MUST BE ON SITE FOR MARRIOTT TESTING. SUPPLY WRITTEN TEST CERTIFICATION. YES NO N/A Life Safety: 1. Exit stairwell doors are not locked from the stairwell side (allowing re-entry back into the guestroom floor). However, the exit door at the bottom of the stairwell, which leads directly to the exterior, may be locked from the exterior side as long as the door is equipped with panic hardware. YES NO 2. Guestroom entrance doors are equipped with self closures. YES NO 3. All doors in the means of egress that serve an area with an occupant load of 50 or more persons must swing out in the direction of egress (toward the corridor/outside). Occupant load is computed by dividing the net floor area by 7 square feet per person. YES NO 4. A second remote exit is required for meeting room configurations where there are more than 50 occupants within an enclosed meeting space. A door in a partition leading to another room is not considered an exit. YES NO N/A 5. Panic hardware is required on assembly occupancy doors, and outdoor enclosed area gates, where occupant loads and exiting capacity from the building is greater than 100 persons. YES NO N/A 6. Sufficient “EXIT” signs are installed throughout the building so that 2 exits can be seen from all public spaces. YES NO 7. The linen chute extends through the roof at full diameter with sprinklers located at the top, bottom and alternate floors. The terminal end of the chute and all access doors must be fire rated doors. Chute must comply with NFPA 82. YES NO N/A 8. Corridor doors must have the appropriate UL fire rating and do not have louvers for make-up air or ventilation. YES NO Page 8 of 9 9. Guestroom windows have stops to prevent opening more than 4 inches. YES NO 10. There are no storage rooms or storage room doors located in the stairwell. If so, this will prevent the hotel from opening until it is corrected. YES NO 11. All marked exits discharge to an all weather walkway that leads to a publicway (parking lot or paved road). YES NO When all items are complete, sign and fax this entire document AND the required attachments to Marriott Fire Protection at 301 644 8765 to the attention of Rob Schmidt. To ensure receipt, contact Rob Schmidt at 301 380 5198 or 301 875 2786 *This checklist applies only to “low-rise” buildings (6 stories or less and less than 75 ft. from the lowest level of fire department access to the floor of the highest occupied level). I certify that the items above are complete, tested and ready for inspection by Marriott Fire Protection. Failure of the Marriott Fire and Life Safety inspection may cause a delayed opening and additional charges for re-inspection. ______________________________ Printed Name ______________________________ Signed _______________________________ Title ______________________________ Date _______________________________ Email ______________________________ Phone 19-4-13 Page 9 of 9