Bulletin SP2009-02

advertisement

Standard Specifications Bulletin No. SP09-02

Architecture & Engineering

TO : S. Greenberger President & C.E.O.

L. Grillo

R. Holden

Executive Director, Chief of Staff

Vice President, General Counsel

G. Toma

C. Yee

B. DiTata

V. Castagnola

Vice President, Construction Management

Vice President, Project Services

Vice President and Inspector General

Vice President, Environmental & Regulatory Compliance

THROUGH:

M. Rebholz

A. Lempert

J. Shea

Director, Building Code Compliance

Director, Industrial and Environmental Hygiene

Chief Executive, Division of School Facilities, DOE

FROM:

DATE:

SUBJECT:

E. Bruce Barrett

Vice President

Architecture and Engineering

George Roussey

Director, Technical Standards & Support Studio

Architecture and Engineering

November 2, 2009

Revisions to the NYCSCA Standard Specifications

HVAC Sections

The following revisions were made to the Division 15h NYCSCA Standard Specifications. The remainder of the specifications generally being revised due to implementation of the new code will follow under future

Specification Bulletin SP09-03, which is to be released shortly.

Items denoted A# are applicable to all Capacity and CIP Projects.

Items denoted B# are applicable to all Capacity Projects but not to CIP Projects.

Items denoted C# are applicable to CIP Projects but not to Capacity Projects.

The Applicability Table at the end of this Bulletin indicates whether changes are applicable to all projects or just to those filed under the 2008 NYC Construction Codes.

Due to the complexity of many of the changes with the implementation of the 2008 NYC Mechanical Code and in order to assist in understanding of the changes, the descriptions are much more detailed than a typical

Bulletin and thus they are being presented in a separate Bulletin. Most projects affected by many of the changes are in design since mandatory implementation only went into affect in July 2009. If there are projects that are beyond the design/bid phase, Bulletins should be issued for items not addressed independently of the official specification changes that would otherwise lead to non-code compliant conditions. In addition, Bulletins should also be issued for non-code issues judged to be required for construction phase implementation as indicated in the Applicability Table at the end of this Bulletin.

1

Table of Contents

Changes due to deletions and title changes will be included in the SP09-03 Bulletin.

Section 15501 Basic Heating, Ventilating And Air Conditioning Requirements

A1. The Section was revised throughout to refer to the 2008 NYC Construction Codes: Building Code,

Mechanical Code and Fuel Gas Code.

A2. Section now refers to the Office of Technical Certification and Research (OTCR).

A3. The reference for compliance with the seismic requirements was changed to NYC Building Code

BC Table 1604.5.

A4. The list of Special Inspections was added per the NYC Building Code.

A5. References were added for the tests of mechanical systems according to the NYC Mechanical Code.

A6. The access and service space requirements were defined according to the NYC Mechanical Code

MC 306.1.

Section 15502 HVAC Identification

A1. The Section was revised to define the nameplate identification requirements per the NYC Mechanical

Code MC 301.6.

Section 15503 Vibration Isolation and Seismic Controls, HVAC Systems

A1. The Section was revised to specify that schools filed under the 2008 Code shall be Seismic Use

Group II with a corresponding Occupancy Category III “Structures that represent a substantial hazard to human life in the event of failure” for seismic design as per NYC Building Code Table BC 1604.5.

Seismic Design Category shall be indicated on the Structural Drawings. Component Importance

Factor (Ip) shall be indicated on the HVAC Drawings. For Seismic Design Category C and D, all mechanical and electrical components shall be designed and constructed to seismic requirements.

Also, new guidelines were added to which the seismic engineer hired by the Contractor must adhere to when designing seismic bracing for HVAC systems.

Section 15504 Vibration Isolation

A1. Added references to the NYC Mechanical Code MC 908.4, MC 926.2.3, MC 926.2.4, MC 926.2.5,

MC 926.2.6 and MC 926.2.9 which govern vibration control for cooling towers, evaporative condensers, fluid coolers, air-cooled condensers, piping and attached equipment, fans, pumps, compressors and duct connections.

Section 15510 HVAC Piping

A1. Deleted references to sprinkler piping, since all fire protection piping and equipment is covered under the new Fire Protection Sections (Division 15f).

A2. Piping shall be supported at distances not exceeding the spacing specified in the NYC Mechanical Code

MC Table 305.4 or in accordance with the referenced MSS standards.

A3. Refrigerant lines may be other than the former sole standard (ACR tube per ASTM B280). Other refrigerant pipe and tubing options are as defined in the NYC Mechanical Code MC 1107.4.

A4. Oil lines other than steel may now be provided for lines not associated with a transfer pump to equipment at levels above the lowest floor (which must remain as steel pipe per ASTM A 53 or ASTM A 106 Grade B seamless schedule 40). As applicable, oil lines shall be in accordance with NYC Mechanical Code MC

Table 1302.3. If oil tubing is provided, oil copper or copper-alloy tubing shall be Type K per ASTM B75,

ASTM B88 or ASTM B280 and shall utilize brazed Type K fittings.

A5. Added Tyco Grinnell as approved manufacturers of fittings.

A6. Hydronic fittings for hot water piping and chilled water piping may now be press fittings by Viega ProPress

(or approved equal) up to and including 4 inches in diameter in lieu of soldering.

A7. According to the NYC Mechanical Code MC 1107.4.4, tubing joints used in refrigerating systems containing Group A2, A3, B1, B2, or B3 refrigerants shall be brazed, but Group A1 refrigerating systems

2

may be soldered. Former standard required brazed fittings for all refrigerant lines. SCA approved refrigerants are all A1 refrigerants.

A8. Mechanical joints utilizing an elastomeric compression seal are not permitted for oil joints and connections per NYC Mechanical Code MC 1303.3.2.

A9. Added O.C. Keckly Company as approved manufacturers of strainers.

A10. Per NYC Mechanical Code MC 1203.1.1 and 1303.1.1, joints between different metallic piping materials shall be made with approved dielectric fittings or brass converter fittings. The usage of brass converter fittings is a new option.

A11. Per NYC Mechanical Code 1303.1, joints and connections shall be approved and of a type approved for fuel-oil and diesel oil piping systems. All threaded joints and connections shall be made tight with suitable lubricant or pipe compound. Pipe joint compounds and thread seal tape that utilize Teflon

(PTFE) shall be approved for usage on fuel oil and diesel oil lines.

C1. A drain pipe shall be installed at the base of shafts enclosing the supply and overflow piping. The pipe shall lead to a dedicated sump or minimum 55 gallon container with a leak detection alarm, arranged so as to sound an alarm and stop the transfer pump. The alarm shall be connected to a local audible alarm and to a remote alarm located at a supervising station. The provision of the leak detection alarm system to stop the transfer pump is a new NYC Mechanical Code requirement. (Refer to MC 1305.9.4).

Section 15511 Valves (HVAC)

A1. Added Bonney Forge Corporation as an approved valve manufacturer.

A2. Defined where shut-off valves must be provided per the NYC Mechanical Code MC 1205.

Section 15512 Piping Insulation (HVAC)

A1. Deleted the former option of using calcium silicate to insulate the exhaust pipe of the emergency generator. Material Safety Data Sheets (MSDS) indicate that calcium silicate is not “Classifiable as a

Human Carcinogen” per ACGIH. However, the MSDS notes that, “This product is an article and under normal conditions of use, this product is not expected to create any unusual emergency hazards.

However, cutting, sawing, or abrading may increase the risk of personnel exposure. Inhalation of excessive amounts of dust created when fabricating, cutting, or other mechanical alterations of the product may cause temporary upper respiratory irritation and/or congestion ”. In place of the calcium silicate insulation, a new insulating material was added to the Section for the insulation of emergency generator exhaust pipe: fibrous glass mineral fiber block or board insulation, density 18.5 pcf per ASTM

C612, Type V suitable for temperatures up to 1800 degrees F, thermal conductivity of 0.46 at 400 degrees

F. The usage of rigid fiberglass block or board in lieu of calcium silicate is the New York State Office of

General Services standard for the insulation of smoke breeching and smoke flue pipes. In addition,

Contractors have reported that calcium silicate insulation stock is not readily available since it is being phased out in preference of other types of insulation.

A2. Added Thermafiber as an approved insulation manufacturer.

Section 15513 Equipment Insulation (HVAC)

A1. Deleted the former option of using calcium silicate to insulate equipment and boiler breeching per the rationale as described above in the description of Section 15512 changes. Equipment shall be insulated with Type IA or IB rigid fiberglass block or board. Boiler smoke breeching shall be insulated with Type V rigid fiberglass block or board.

A2. Added Thermafiber as an approved insulation manufacturer.

Section 15514 Ductwork Insulation

A1. CMS wool wrap blanket insulation shall have NYC Office of Technical Certification and Research (OTCR) approval or Omega Point Labs (OPL) or UL listing in accordance with ASTM E 2336 or applicable legacy

MEA calendar number. ASTM E 2336 reference is per the 2006 version of the International Mechanical

Code (IMC).

3

A2. Insulation may be omitted on ductwork where the design temperature difference between interior and exterior of duct does not exceed 15 degrees F (such as in return air plenums) per the 2007 New York

State Energy Conservation Construction Code (NYSECCC) Article E803.2.8. This lack of need to insulate is also being implemented as a result of a Value Engineering study.

A3. A continuous fire-rated shaft shall still enclose the vertical insulated Kitchen exhaust duct riser unless insulation system is approved by OTCR for installation without the vertical fire rated shaft. For horizontal exhaust duct where no shaft enclosure is provided, CMS wool blankets may be wrapped around the

Kitchen exhaust duct in two layers installed in accordance with manufacturer’s ASTM E 2336 listing or with NYC OTCR approval or applicable legacy MEA approval.

Section 15515 Hydronic Specialties

A1. Added Armstrong Pumps, O.C. Keckley Company and Grinnell Mechanical Products by Tyco as approved manufacturers.

Section 15516 Water Treatment for Steam Boilers

C1.

Aqua Testing Inc. changed their name to Acqua Treat Limited. They remain as an approved water treatment firm.

Section 15525 Steam and Condensate Specialties

C1.

Removed Trane from the list of approved specialty manufacturers as they no longer make steam and condensate specialties.

Section 15540 HVAC Pumps

A1. Added Armstrong Pumps as an approved manufacturer.

A2. Memorializes previous requirement issued in February 2008 in Section S01650 that training is to be digitally recorded in lieu of the former videotaping requirement.

Section 15555 Fire-Tube Boilers (Steam)

C1. Added DEP Bureau of Air Resources and DOB submittal requirements. Added the requirement for the

Contractor to submit factory certified prototype test reports for combustion efficiency to verify compliance with BTS-2000, DOE 10 CFR Part 430 or ASME PTC-4.1 as applicable depending on nature of the fuel

(gas or oil) and input fuel ratings. Combustion efficiency documentation must be submitted to verify compliance with the 2007 NYS Energy Conservation Construction Code and ASHRAE 90.1-2004.

C2. UL listings for the following must be submitted by the Contractor: UL 726 listing for oil burning boilers, UL

795 listing for gas burning boilers, UL 726 and UL 795 listings for boilers with dual fuel burners.

C3. An affidavit must be submitted whether or not the boiler-burner combination is marketed as an assembly.

The UL-A or ETL listing for the burner must be submitted. The UL-B or UL-C listing (if required) for boilers must be submitted as defined in the Supplemental Quality Assurance article 1.04.

C4. A Certificate of Compliance must now be submitted in lieu of the former Equipment Use Permit.

C5. In the event that factory prototype testing has not been completed prior to submittal of boiler shop drawings, the boiler submittal may be granted "conditional" approval after verifying that all other aspects of the submittal comply with the basis of design, subject to subsequent Factory or Field prototype testing as defined in the Section.

C6. Design shall show the platforms/ladders in order to grant access to safety valves in accordance with NYC

Mechanical Code MC 1004.3.1.

Section 15556 Cast-Iron Boilers

Same changes were made to the Section as described above in the Section 15555 changes.

Section 15557 Fire-Tube Boilers (Hot Water)

Same changes were made to the Section as described above in the Section 15555 changes.

4

Section 15559 Flexible Water-Tube Boilers (Steam)

Same changes were made to the Section as described above in the Section 15555 changes.

Section 15560 Flexible Water-Tube Boilers (Hot Water)

Same changes were made to the Section as described above in the Section 15555 changes.

Section 15565 Hot Water Condensing Boilers

B1. Added DOB submittal requirements. Added the requirement for the Contractor to submit factory certified prototype test reports for combustion efficiency to verify compliance with BTS-2000, DOE 10 CFR Part

430 or ASME PTC-4.1 as applicable depending on input fuel ratings. Combustion efficiency documentation must be submitted to verify compliance with the 2007 NYS Energy Conservation

Construction Code and ASHRAE 90.1-2004.

B2. UL 795 listing for gas burning boilers must be submitted by the Contractor.

B3. A Certificate of Compliance must now be submitted in lieu of the former Equipment Use Permit.

B4. In the event that factory prototype testing has not been completed prior to submittal of boiler shop drawings, the boiler submittal may be granted "conditional" approval after verifying that all other aspects of the submittal comply with the basis of design, subject to subsequent Factory or Field prototype testing as defined in the Section.

B5. Design shall show the platforms/ladders in order to grant access to safety valves in accordance with NYC

Mechanical Code MC 1004.3.1.

B6. A UL listed valve proving system may be substituted for the normally open vent valve. Approved valve proving system manufacturers were defined as follows: Karl Dungs, Siemens and Honeywell.

B7. Utility approved “ventless” gas pressure switch manufacturers were defined as follows: Antunes,

Honeywell, Karl Dungs and Siemens.

B8. The venting of the regulators was defined to be consistent with the NYC Fuel Gas Code FGC 410.3 and utility requirements. On elevated pressure systems of over 14"w.c., all regulators must be vented outside to the atmosphere. On services supplying 14"w.c. and less, regulators with valve bodies 1-1/4" and larger shall be vented outside to the atmosphere. Regulators with valve bodies smaller than 11/4” and those inst alled on services supplying 14”w.c. and less may be equipped with approved appliance vent limiters in lieu of outside venting. The Siemens SKP series of combination valve/regulator (with integral vent limiter) or approved equal may be utilized for their rated pressures and body sizes without outside venting.

B9. Per NYC Fuel Gas Code 403.9.3, joints and connections shall be approved and of a type approved for natural gas piping systems. All threaded joints and connections shall be made tight with suitable lubricant or pipe compound. Pipe joint compounds and thread seal tape that utilize Teflon (PTFE) shall be approved for usage on natural gas lines.

Section 15575 Breeching, Chimney and Stacks

A1. Added references to the required smoke test and Special Inspection as follows: A smoke test shall be performed in accordance with the New York City Building Code Section BC 1704.24. Chimney Connectors

(breeching) shall be subject to Special Inspection per New York City Building Code Section BC 1704.23.

Chimneys shall be subject to Special Inspection per New York City Building Code Section BC 1704.24.

B1. Per the NYC Fuel Gas Code, prefabricated double wall metal vents for gas-fired condensing boilers shall be listed to UL 173893, “Venting Systems for Gas-Fired Appliances, Categories II, III and IV with

Revisions through December 2000” for up to 550°F for use with low heat appliances burning natural gas.

B2. Added Simpson Dura-Vent as an approved manufacturer for the prefabricated double wall metal vents for gas-fired condensing boilers.

5

Section 15580 Feedwater Equipment

C1. Added the requirement per NYC Mechanical Code MC 1004.3 that clearances shall be maintained around heaters and tanks and related equipment and appliances so as to permit inspection, servicing, repair, replacement and visibility of all gauges. Passageways around all sides of equipment shall have an unobstructed width as required by the manufacturer and in no case less than 18 inches, unless otherwise approved by the DOB Commissioner.

C2. Memorializes previous requirement issued in February 2008 in Section S01650 that training is to be digitally recorded in lieu of the former videotaping requirement.

Section 15590 Emergency Generator System - Accessories

A1. Memorializes previous requirement issued in February 2008 in Section S01650 that training is to be digitally recorded in lieu of the former videotaping requirement.

A2. Day tank capacity was defined to be a maximum of 330 gallons per NYC Mechanical Code MC

1305.11.1.3.

A3. Day tanks shall be minimum 10 gauge steel for tanks less than or equal to 275 gallons and minimum 14 gauge steel for storage tanks of 60 gallon capacity or less per NYC Mechanical Code MC 1305.14.4 or shall be constructed according to MC 1305.12.2 (per UL 80 or UL 142 or ASME Boiler and Pressure

Vessel Code, Section VIII, Division 1 or 2).

A4. Normal and emergency vents shall be combined into one vent.

A5. Added O.C. Keckley as an approved manufacturer of diesel fuel oil pump strainers and relief valves.

A6. Diesel oil storage tank (275 gallon located above ground on the lowest floor inside a building) may be constructed according to MC 1305.12.2 requirements (in accordance with UL 80 or UL 142 or ASME

Boiler and Pressure Vessel Code, Section VIII, Division 1 or 2) or minimum 10 gauge Class A steel plates per MC 1305.14.4.

A7. Diesel oil storage tank identification shall be per MC 1305.14.1.5.

A8. Per NYC Mechanical Code MC 1305.13.2, tanks located above ground on the lowest floor inside a building that have a capacity exceeding 660 gallons storage, shall be provided with secondary containment intended to capture any leakage of fuel oil from the tank. The capacity of the containment need only equal the capacity of the tank served. 275 gallon tanks located above ground on the lowest floor inside a building, do not require secondary containment.

A9. Per NYC Mechanical Code MC 1305.3.4, appropriate safeties shall be provided so that the detection of heat within the generator or equipment room shall prevent additional fuel oil from being pumped into the piping system within such room. Fusible link operated link lever gate valves in the supply pipe at the wall of the generator room must be provided. In addition, per MC 1305.13.3.3, rooms above the lowest floors containing fuel oil tanks shall be provided with automatic smoke detectors. Fuel oil burning equipment rooms shall be equipped with automatic heat detection in accordance with NYC Building Code BC 907.

Div 16 Contractor shall wire heat detectors to Fire Alarm Panel to automatically shut-down the transfer pumps if excessive heat is detected.

A10. Per NYC Mechanical Code MC 1305.8.3 for tanks installed inside of buildings above the lowest floor, the combination normal and emergency vent piping shall be piped into the vent or top of the tank of the lowest floor storage tank that supplies the fuel to such tank.

A11. Per NYC Mechanical Code MC 1305.9.4, a drain pipe shall be installed at the base of shafts enclosing the supply and overflow piping. The pipe shall lead to a dedicated sump or minimum 55 gallon container with a leak detection alarm, arranged so as to sound an alarm and stop the transfer pump. The requirement to stop the transfer pump is a new 2008 NYC Mechanical Code requirement.

Section 15592 Fuel Burning/Pumping Equipment (for Steam Boilers)

C1. Section was modified to reflect DEP Bureau of Air Resources requirements. The burners may be listed per ETL or UL-A.

6

C2. A Certificate of Compliance must now be submitted in lieu of the former Equipment Use Permit.

C3. Utility approved “ventless” gas pressure switch manufacturers were defined as follows: Antunes,

Honeywell, Karl Dungs and Siemens.

C4. The venting of the regulators was defined to be consistent with the NYC Fuel Gas Code FGC 410.3 and utility requirements. On elevated pressure systems of over 14"w.c., all regulators must be vented outside to the atmosphere. On services supplying 14"w.c. and less, regulators with valve bodies 1-1/4" and larger shall be vented outside to the atmosphere. Regulators with valve bodies smaller than 11/4” and those installed on services supplying 14”w.c. and less may be equipped with approved appliance vent limiters in lieu of outside venting. The Siemens SKP series of combination valve/regulator (with integral vent limiter) or approved equal may be utilized for their rated pressures and body sizes without outside venting.

C5. Section was revised to require that the burner control cabinet have a relay coil wired in parallel with the alarm horn which will close a set of dry contacts when the alarm horn annunciates. Dry contacts must be wired to low voltage field wiring strip terminals by original equipment manufacturer. (Subsequent AWG 16 twisted pair connection to field wiring strip shall be by Div 16 Contractor to the intrusion alarm auto-dialer).

C6. Section was revised to reflect NYC Mechanical Code MC 1305.3.4 whereby appropriate safeties must be provided so that the detection of heat within the boiler equipment room shall prevent additional fuel oil from being pumped into the piping system within such room. Contractor to provide fusible link operated lever gate valve in the supply pipe at the wall of the boiler room. Also per MC 1305.13.3.3, rooms above the lowest floor containing fuel oil tanks shall be equipped with automatic smoke detection. Fuel oil burning equipment rooms shall be equipped with automatic heat detection in accordance with NYC

Building Code BC 907. Div 16 Contractor (as defined in Section 16720) shall wire heat detectors to Fire

Alarm Panel to automatically shut-down the transfer pumps if excessive heat is detected.

C7. Per NYC Mechanical Code MC 1305.9.4, a drain pipe shall be installed at the base of shafts enclosing the supply and overflow piping. The pipe shall lead to a dedicated sump or minimum 55 gallon container with a leak detection alarm, arranged so as to sound an alarm and stop the transfer pump. The requirement to stop the transfer pump is a new 2008 NYC Mechanical Code requirement.

C8. Added the requirement per NYC Mechanical Code MC 1004.3 that clearances shall be maintained around equipment and appliances so as to permit inspection, servicing, repair, replacement and visibility of all gauges. Passageways around all sides of equipment shall have an unobstructed width as required by the manufacturer and in no case less than 18 inches, unless otherwise approved by the DOB Commissioner.

C9. Added a Note to Specifier that the Designer shall show on the Electrical Drawing Set the required wiring

(twisted pair, AWG#16) from the boiler control panels to the Intrusion Alarm digital communicator (autodialer) per Electrical Design Requirement 7.3.14.

C10. A UL listed valve proving system may be substituted for the normally open vent valve. Approved valve proving system manufacturers were defined as follows: Karl Dungs, Siemens and Honeywell.

C11. Added O.C. Keckley as an approved manufacturer of fuel oil strainers.

C12. Per NYC Mechanical Code 1303.1, joints and connections shall be approved and of a type approved for fuel-oil piping systems. All threaded joints and connections shall be made tight with suitable lubricant or pipe compound. Pipe joint compounds and thread seal tape that utilize Teflon (PTFE) shall be approved for usage on fuel oil lines.

Per NYC Fuel Gas Code 403.9.3, joints and connections shall be approved and of a type approved for natural gas piping systems. All threaded joints and connections shall be made tight with suitable lubricant or pipe compound. Pipe joint compounds and thread seal tape that utilize Teflon (PTFE) shall be approved for usage on natural gas lines.

Section 15593 Fuel Burning/Pumping Equipment (for Hot Water Boilers)

Same changes were made to the Section as described above in the Section 15592 changes.

7

Section 15594 Fuel Storage Equipment

C1. Memorializes previous requirement issued in February 2008 in Section S01650 that training is to be digitally recorded in lieu of the former videotaping requirement.

C2. Fuel-oil storage and piping systems shall comply with the requirements of Chapter 13 of the NYC

Mechanical Code and to the extent not otherwise provided for in the NYC Mechanical Code shall comply with the requirements of NFPA 31-2001.

C3. Tanks located above ground, inside or outside of buildings, shall comply with any one of the following design standards:

1.

2.

3.

UL 80; such tanks shall be listed and labeled.

UL 142; such tanks shall be listed and labeled; or

ASME Boiler and Pressure Vessel Code, Section VIII, Division 1 or 2; such tanks shall be listed or labeled; or

4. Alternate tank design and construction standards per NYC Mechanical Code

MC 1305.14.

Note that the former standards only allowed tanks constructed per the equivalent of MC 1305.14.

Items 1, 2 and 3 now offer options on the nature of construction of the tanks.

C4. The use of a self-closing manway cover, a manway cover provided with long bolts that permit the cover to lift under internal pressure, or other type emergency relief vent device, shall be prohibited per NYC

Mechanical Code MC 1305.8.1. Former tank design under the 1968 Code allowed manway covers with long bolts that lifted under internal pressure that occurs during emergency venting. A tank’s emergency relief vent piping and normal vent piping shall now be combined. The installation of the combined normal and emergency relief vent shall be in accordance with NYC Mechanical Code MC 1305.7 and

MC 1305.8.1 through MC 1305.8.4.

C5. Spill containment is now only required for fill pipes serving tanks greater than 660 gallons per NYC

Mechanical Code MC 1305.6.6. Former SCA Standard required spill containment for tanks with less than

660 gallons.

C6. Per NYC Mechanical Code MC 1305.9.4, oil transfer pumps shall be shutdown upon a detection of a leak at any sumps or containers at the base of shafts that contain oil risers. This shutting down of the transfer pumps due to a sensed leak at the base of the oil riser shafts is a new NYC Mechanical Code requirement.

C7. Tanks shall be installed in accordance with the provisions of NYC Mechanical Code sections

MC 1305.13.1 through MC 1305.13.4. Tanks located above ground, on the lowest floor inside of buildings, shall comply with the following requirements:

1. Containment: Fuel-oil tanks having a capacity of more than 660 gallons storage shall be provided with secondary containment intended to capture any leakage of fuel oil from the tank. The capacity of the containment shall equal or exceed the capacity of the tank served. Typically this has been achieved by a concrete vault with epoxy coating. The epoxy need only be provided to provide equal tank capacity containment at a minimum.

2. Special limitations near subways: Regardless of capacity, fuel-oil tanks located within the outer lines of the subway or within 20 feet of the outside line of a subway wall shall be placed within a welded steel oil tight pan of not less than No. 18 Gage metal suitably reinforced and of capacity to contain the contents of the tank. For the purpose of the foregoing requirement, a subway shall be deemed to include any subsurface railroad or rapid transit roadbed.

8

C8. Per NYC Mechanical Code MC 1305.13.3.1, fuel-oil tanks and fuel-oil-burning equipment above the lowest floor inside a building shall be located in a dedicated room or enclosure, having a fire resistance rating of at least 2 hours. Rooftop tanks need not be enclosed provided that all exterior walls and roof surfaces within 10 feet horizontally and 20 feet vertically have a fire resistance rating of at least 2 hours.

C9. Smoke detection: Rooms containing fuel-oil tanks above the lowest floor inside a building shall be equipped with automatic smoke detection in accordance with Division 16, NYC Mechanical Code

MC 1305.13.3.3 and NYC Building Code BC 907.

C10. Per NYC Mechanical Code MC 1305.13.3.4, rooms above the lowest floor inside a building containing fuel-oil tanks shall be ventilated to limit the concentration of vapors within the room at or below 25% of the Lower Flammable Limit (LFL) of the fuel oil being used.

C11. Fill and vent piping: Fill piping shall comply with the requirements of NYC Mechanical Code MC 1305.6 and vent piping shall comply with MC 1305.7.

C12. For tanks installed above the lowest floor, the normal vent shall be piped, in an approved manner, into the vent or top of tank of the lowest floor storage tank that supplies the fuel to such tank.

Section 15595 Natural Gas/Carbon Monoxide Leak Detection Equipment

C1. Memorializes previous requirement issued in February 2008 in Section S01650 that training is to be digitally recorded in lieu of the former videotaping requirement.

C2. Section was modified to require that all outputs from the natural gas/carbon monoxide leak detection panel be dry contacts. Equipment power shall not flow through the dry contacts. This applies to all equipment that is to be shut down upon the detection of natural gas or carbon monoxide including but not limited to boilers, gas booster pumps and safety shut-off valves (Maxon valves). It also applies to energizing gas meter room exhaust fan.

Section 15596 Natural Gas Leak Detection Equipment

A1. New Section was created. Section describes gas monitoring system that only monitors natural gas and not carbon monoxide. This section is applicable to New Schools, Leased Buildings, Major Modernizations,

Additions, and those schools undergoing CIP Heating Plant Upgrade/Boiler Conversion projects with a concurrent fire alarm system replacement or concurrent extension to existing fire alarm system where the existing fire alarm system can be extended to include carbon monoxide detectors. For the above cases, the Electrical Fire Alarm system will monitor carbon monoxide.

Section 15610 Gas-Fired Duct Heaters

C1. Memorializes previous requirement issued in February 2008 in Section S01650 that training is to be digitally recorded in lieu of the former videotaping requirement.

C2. Added the fact that a Certificate of Compliance is now required in lieu of the former Equipment Use

Permit.

C3. Per the NYC Fuel Gas Code FGC 610, a listing according to UL 795-1999 is now required.

Section 15650 Split Air Cooled Chillers

C1. Memorializes previous requirement issued in February 2008 in Section S01650 that training is to be digitally recorded in lieu of the former videotaping requirement.

C2. Refrigeration system shall be constructed in accordance with ASHRAE 15-2001: Safety Standard for

Refrigeration Systems as modified by NYC Mechanical Code Chapter 11.

C3. Air Cooled Condensers shall meet or exceed the minimum COP/Efficiency levels as prescribed in the

2007 New York State Energy Conservation Construction Code and ASHRAE 90.1-2004.

C4. Refrigeration equipment such as chillers, condensers and condensing units shall be listed and labeled to

UL 1995-1998 per the NYC Mechanical Code. UL listing shall be indicated on the Shop Drawings.

9

C5. Signs, nameplates, and operation and emergency shutdown instructions for refrigeration systems shall comply with the requirements of MC 1101.11 and ASHRAE 15-2001.

Section 15660 Packaged Modular Outdoor Chillers

A1. Memorializes previous requirement issued in February 2008 in Section S01650 that training is to be digitally recorded in lieu of the former videotaping requirement.

A2. Refrigeration system shall be constructed in accordance with ASHRAE 15-2001: Safety Standard for

Refrigeration Systems as modified by NYC Mechanical Code Chapter 11.

A3. Packaged air cooled modular chiller shall meet or exceed the minimum COP/Efficiency levels as prescribed in the 2007 New York State Energy Conservation Construction Code and ASHRAE 90.1-2004.

A4. Refrigeration equipment such as chillers shall be listed and labeled to UL 1995-1998. UL listing shall be indicated on the Shop Drawings.

A5. Signs, nameplates, and operation and emergency shutdown instructions for refrigeration systems shall comply with the requirements of NYC Mechanical Code MC 1101.11 and ASHRAE 15-2001.

Section 15670 Plate Heat Exchangers

A1. Memorializes previous requirement issued in February 2008 in Section S01650 that training is to be digitally recorded in lieu of the former videotaping requirement.

A2. Per NYC Mechanical Code MC 1003.1, all pressure vessels shall bear the label of an approved agency and shall be installed in accordance with the manufacturer’s installation instructions. The requirements for unfired pressure vessels shall be the same as required for boilers designed for the same operating temperatures.

A3. Per NYC Mechanical Code MC 1003.3, welding on pressure vessels shall be performed by approved certified welders in compliance with nationally recognized standards, ASME Boiler Pressure Vessel Code

Sections VIII and IX, 12 NYCRR 4-6.2 and 12 NYCRR 14-3.3 through 14-3.18.

Section 15756 Converters

C1. Memorializes previous requirement issued in February 2008 in Section S01650 that training is to be digitally recorded in lieu of the former videotaping requirement.

C2. Per NYC Mechanical Code MC 1003.1, all pressure vessels shall bear the label of an approved agency and shall be installed in accordance with the manufacturer’s installation instructions. The requirements for unfired pressure vessels shall be the same as required for boilers designed for the same operating temperatures.

C3. Per NYC Mechanical Code MC 1003.3, welding on pressure vessels shall be performed by approved certified welders in compliance with nationally recognized standards, ASME Boiler Pressure Vessel Code

Sections VIII and IX, 12 NYCRR 4-6.2 and 12 NYCRR 14-3.3 through 14-3.18.

C4. Added Armstrong Pumps as an approved manufacturer.

Section 15781 Packaged Heating and Cooling Units

A1. Memorializes previous requirement issued in February 2008 in Section S01650 that training is to be digitally recorded in lieu of the former videotaping requirement.

A2. Refrigeration system shall be constructed in accordance with ASHRAE 15-2001: Safety Standard for

Refrigeration Systems as modified by NYC Mechanical Code Chapter 11.

A3. Heating and cooling units shall comply with the EER requirements of the 2007 Edition of the New York

State Energy Conservation Construction Code and ASHRAE 90.1-2004.

A4. Refrigeration equipment shall be listed and labeled to UL 1995-1998. UL listing shall be indicated on the

Shop Drawings.

10

A5. Signs, nameplates, and operation and emergency shutdown instructions for refrigeration systems shall comply with the requirements of NYC Mechanical Code MC 1105.10 and ASHRAE 15-2001.

Section 15783 Split Heat Pump System

A1. Memorializes previous requirement issued in February 2008 in Section S01650 that training is to be digitally recorded in lieu of the former videotaping requirement.

A2. Split air cooled heat pump units shall comply with the EER requirements of the 2007 edition of the New

York State Energy Conservation Construction Code and ASHRAE 90.1-2004.

A3. Refrigeration equipment shall be listed and labeled to UL 1995-1998. UL listing shall be indicated on the

Shop Drawings.

A4. Refrigeration system shall be constructed in accordance with ASHRAE 15-2001: Safety Standard for

Refrigeration Systems as modified by NYC Mechanical Code Chapter 11.

A5. For ceiling hung units, per NYC Mechanical Code MC 307.2.3, Mechanical Contractor shall provide a primary pan overflow drain line or auxiliary drain pan and associated drain line for each cooling or evaporator coil to avoid damage to any building component as a result of overflow from the primary equipment drain pan or stoppage in the primary condensate drain piping. An alternate acceptable installation shall be identified in the bid package whereby the Mechanical Contractor must coordinate with the sheet metal subcontractor to provide an auxiliary drain pan without a separate drain line under the coils on which condensate will occur. Mechanical Contractor must coordinate with the Temperature

Controls subcontractor to provide a hard-wired water-level detection device for the auxiliary pan that will shut off the equipment served prior to overflow of the auxiliary pan. Designer shall select either option of a primary pan overflow drain line or auxiliary drain pan and associated drain line and show same in the bid set.

A6. Per NYC Mechanical Code MC 1107.2, rigid or flexible metal enclosures or pipe ducts shall only be provided for soft annealed copper tubing used for refrigerant piping erected on the premises and containing other than Group A1 refrigerants.

A7. Signs, nameplates, and operation and emergency shutdown instructions for refrigeration systems shall comply with the requirements of NYC Mechanical Code MC 1101.11 and ASHRAE 15-2001.

Section 15835 Convectors

A1. Removed dampers from the section since they are an additional cost item and are not required.

Historically, the units have been provided without adjustable dampers.

A2. Removed the insulation requirements from the section as the units are typically provided without internal backing insulation since there is only limited internal room. Also, removed the former requirement to provide ½” rigid fiberglass board insulation to the back of the convector cabinets. ½” rigid fiberglass board is not available and only foam type insulation is available at this thickness. There is no significant advantage to using the ½” foam type insulation. Insulation requirements for all convectors will be achieved via the standard wall insulation.

Section 15836 Unit Heaters/Cabinet Heaters

A1. Whenever the NYC Construction Codes or the Rules of the Department of Buildings require that material be listed or labeled and material proposed to be used is not so listed or labeled, the use of such material shall be subject to prior approval by the Commissioner (Office of Technical Certification and Research

OTCR) and such material shall be used only to the extent set forth in such approval. The above text was added to the section since the section requires that electrical unit heaters and electrical cabinet heaters be

UL listed. Obtaining approval from OTCR is an approved option in lieu of UL listing.

Section 15838 Fan Coil Units

A1. For ceiling hung units, per NYC Mechanical Code MC 307.2.3, Mechanical Contractor shall provide a primary pan overflow drain line or auxiliary drain pan and associated drain line for each cooling or evaporator coil to avoid damage to any building component as a result of overflow from the primary equipment drain pan or stoppage in the primary condensate drain piping. An alternate acceptable installation shall be identified in the bid package whereby the Mechanical Contractor must coordinate with

11

the sheet metal subcontractor to provide an auxiliary drain pan without a separate drain line under the coils on which condensate will occur. Mechanical Contractor must coordinate with the Temperature

Controls subcontractor to provide a hard-wired water-level detection device for the auxiliary pan that will shut off the equipment served prior to overflow of the auxiliary pan. Designer shall select either option of a primary pan overflow drain line or auxiliary drain pan and associated drain line and show same in the bid set.

Section 15852 Air Handling Units

A1. Memorializes previous requirement issued in February 2008 in Section S01650 that training is to be digitally recorded in lieu of the former videotaping requirement.

A2. Per NYC Mechanical Code MC 513.10 equipment utilized in Smoke Control systems such as fans and automatic dampers shall be suitable for their intended use, suitable for the probable exposure temperatures and shall be as approved by the Commissioner. Fans shall be rated and certified by the manufacturer for the probable temperature rise to which the components will be exposed. Per NYC

Building Code BC 909.4.6, all portions of active smoke control systems shall be capable of continued operation after detection of the fire event for not less than 20 minutes. The above text is applicable if the air handling unit is used for Smoke Control.

A3. If the Temperature Controls Contractor (TCC) furnishes their controllers to the Original Equipment

Manufacturer (OEM), the TCC shall furnish their controllers and related devices mounted on a back-plate and wired to a terminal strip. This is being implemented to facilitate the coordination process so the OEM knows how much space must be reserved for the TCC furnished controls.

Section 15853 Custom Packaged Rooftop Heating and Cooling Units (Variable Air Volume System)

A1. If the Temperature Controls Contractor (TCC) furnishes their controllers to the Original Equipment

Manufacturer (OEM), the TCC shall furnish their controllers and related devices mounted on a back-plate and wired to a terminal strip. This is being implemented to facilitate the coordination process so the OEM knows how much space must be reserved for the TCC furnished controls.

A2. Refrigeration system shall be constructed in accordance with ASHRAE 15-2001: Safety Standard for

Refrigeration Systems as modified by NYC Mechanical Code Chapter 11.

A3. Refrigeration equipment shall be listed and labeled to UL 1995-1998. UL listing shall be indicated on the

Shop Drawings.

A4. Per NYC Mechanical Code MC 513.10 equipment utilized in Smoke Control systems such as fans and automatic dampers shall be suitable for their intended use, suitable for the probable exposure temperatures and shall be as approved by the Commissioner. Fans shall be rated and certified by the manufacturer for the probable temperature rise to which the components will be exposed. Per NYC

Building Code BC 909.4.6, all portions of active smoke control systems shall be capable of continued operation after detection of the fire event for not less than 20 minutes. The above text is applicable if the rooftop unit is used for Smoke Control.

A5. All induced draft type burners shall be equipped with flame rollout switch.

A6. Provide manual reset high and low gas pressure switches.

A7. Shop fabrication drawings of gas train shall be submitted.

A8. “Ventless” gas pressure switches may be used alleviating the requirement for outside venting; however, pressure switches in this category shall be UL353 listed and shall be equipped with an integral vent limiter in lieu of the requirement for outside venting. The utilities have accepted the following pressure switches or their equal as being “Ventless”: a. Antunes series LGP-G, HGP-G b. Honeywell series C6097 c. Karl Dungs series GMH, GML d. Siemens series QPH, QPL

12

A9. On services supplying 14"w.c. and less, regulators with valve bodies 1-1/4" and larger shall be vented outside to the atmosphere. Regulators with valve bodies smaller than 11/4” and those installed on services supplying 14”w.c. and less may be equipped with approved appliance vent limiters in lieu of outside venting. The Siemens SKP series of combination valve/regulator (with integral vent limiter) or approved equal may be utilized for their rated pressures and body sizes without outside venting. Per NYC

Fuel Gas Code FGC 410.3: A vent to the outside is not required for regulators less than 1-1/4 inches NPS equipped with and labeled for utilization with approved vent-limiting devices installed in accordance with the manufacturer’s instructions.

A10. Normally open vent valves, if required by the GE GAP Guidelines, shall be piped separately and directly to the outside of the enclosure. A UL listed valve proving system may be substituted for the normally open vent valve (when a normally open vent valve is otherwise required by the GE GAP

Guidelines). The valve proving system shall be wired to operate on a call for startup locking out the burner prior to pilot ignition and/or after burner shutdown if an internal gas valve leak is detected.

Wiring diagrams of the valve proving system shall be included with the burner submittal package.

A11. The following valve proving systems may be utilized which are approved by the local utility:

Karl Dungs model# VDK 200a/CM100 pressure module and control relay

Siemens model# LDU11, LMV,WFM, LFL/LAL/LFE/LME valve pressure proving systems

Honeywell RM7800L, RM7840L integral valve pressure proving system

A12. Contractor shall provide label in compressor section indicating rated horsepower and kilowatt equivalent for each compressor.

A13. Contractor shall provide a furnace control Hand-OffAuto toggle selector switch. In the “Auto” position, the furnace shall be controlled as defined in Section 15985 Sequence of Operation. In the “Off” position, the furnace shall be disabled. In the “Hand” position, the units’ DDC furnace operating controls shall be overridden and the furnace started and modulated to maintain a manually set discharge temperature.

A14. For curb mounted units, per NYC Mechanical Code MC 307.2.3, Mechanical Contractor shall provide a primary pan overflow drain line or auxiliary drain pan and associated drain line for each DX evaporator coil

(when the unit is curb mounted, not dunnage mounted) to avoid damage to any building component as a result of overflow from the primary equipment drain pan or stoppage in the primary condensate drain piping. An alternate acceptable installation shall be identified in the bid package whereby the Mechanical

Contractor must coordinate with the sheet metal subcontractor to provide an auxiliary drain pan without a separate drain line under the coils on which condensate will occur. Mechanical Contractor must coordinate with the Temperature Controls subcontractor to provide a hard-wired water-level detection device for the auxiliary pan that will shut off the equipment served prior to overflow of the auxiliary pan.

Designer shall select either option of a primary pan overflow drain line or auxiliary drain pan and associated drain line and show same in the bid set.

A15. Signs, nameplates, and operation and emergency shutdown instructions for refrigeration systems shall comply with the requirements of NYC Mechanical Code MC 1101.11 and ASHRAE 15-2001.

A16. Per NYC Fuel Gas Code 403.9.3, joints and connections shall be approved and of a type approved for natural gas piping systems. All threaded joints and connections shall be made tight with suitable lubricant or pipe compound. Pipe joint compounds and thread seal tape that utilize Teflon (PTFE) shall be approved for usage on natural gas lines.

A17. Added the following text: “The number of circuits that connect to the reheat coil shall be as shown on the HVAC equipment schedule Drawings. The capacity of the reheat coil as shown on the HVAC equipment schedule Drawings shall be such that the total maximum unit flow can be reheated to a minimum of 65 degrees F. At least 50% of the compressor circuits shall be connected to the reheat coil for redundancy purposes ”.

13

Section 15854 Custom Packaged Rooftop Heating and Cooling Units (Constant Volume System)

Same changes were made to the Section as described above in the Section 15853 changes.

Section 15855 Commercial Packaged Rooftop Heating and Cooling Units

C1. If the Temperature Controls Contractor (TCC) furnishes their controllers to the Original Equipment

Manufacturer (OEM), the TCC shall furnish their controllers and related devices mounted on a back-plate and wired to a terminal strip. This is being implemented to facilitate the coordination process so the OEM knows how much space must be reserved for the TCC furnished controls.

C2. Refrigeration system shall be constructed in accordance with ASHRAE 15-2001: Safety Standard for

Refrigeration Systems as modified by NYC Mechanical Code Chapter 11.

C3. Refrigeration equipment shall be listed and labeled to UL 1995-1998. UL listing shall be indicated on the

Shop Drawings.

C4. Per NYC Mechanical Code MC 513.10, equipment utilized in Smoke Control systems such as fans and automatic dampers shall be suitable for their intended use, suitable for the probable exposure temperatures and shall be as approved by the Commissioner. Fans shall be rated and certified by the manufacturer for the probable temperature rise to which the components will be exposed. Per NYC

Building Code BC 909.4.6, all portions of active smoke control systems shall be capable of continued operation after detection of the fire event for not less than 20 minutes. The above text is applicable if the rooftop unit is used for Smoke Control.

C5. Memorializes previous requirement issued in February 2008 in Section S01650 that training is to be digitally recorded in lieu of the former videotaping requirement.

C6. Contractor shall provide manual reset high and low gas pressure switches.

C7. Shop fabrication drawings of gas train shall be submitted.

C8. “Ventless” gas pressure switches may be used alleviating the requirement for outside venting; however, pressure switches in this category shall be UL353 listed and shall be equipped with an integral vent limiter in lieu of the requirement for outside venting. The utilities have accepted the following pressure switches or their equal as being “Ventless”: a. Antunes series LGP-G, HGP-G b. Honeywell series C6097 c. Karl Dungs series GMH, GML d. Siemens series QPH, QPL

C9. On services supplying 14"w.c. and less, regulators with valve bodies 1-1/4" and larger shall be vented outside to the atmosphere. Regulators with valve bodies smaller than 11/4” and those installed on services supplying 14”w.c. and less may be equipped with approved appliance vent limiters in lieu of outside venting. The Siemens SKP series of combination valve/regulator (with integral vent limiter) or approved equal may be utilized for their rated pressures and body sizes without outside venting. Per NYC

Fuel Gas Code FGC 410.3: A vent to the outside is not required for regulators less than 1-1/4 inches NPS equipped with and labeled for utilization with approved vent-limiting devices installed in accordance with the manufacturer’s instructions.

C10. Normally open vent valves, if required by the GE GAP Guidelines, shall be piped separately and directly to the outside of the enclosure. A UL listed valve proving system may be substituted for the normally open vent valve (when a normally open vent valve is otherwise required by the GE GAP

Guidelines). The valve proving system shall be wired to operate on a call for startup locking out the burner prior to pilot ignition and/or after burner shutdown if an internal gas valve leak is detected.

Wiring diagrams of the valve proving system shall be included with the burner submittal package.

C11. The following valve proving systems may be utilized which are approved by the local utility:

Karl Dungs model# VDK 200a/CM100 pressure module and control relay

14

C12. Contractor shall provide label in compressor section indicating rated horsepower and kilowatt equivalent for each compressor.

Siemens model# LDU11, LMV,WFM, LFL/LAL/LFE/LME valve pressure proving systems

Honeywell RM7800L, RM7840L integral valve pressure proving system

C13. Temperature Controls Contractor (TCC) shall provide a field installed furnace control Hand-Off-Auto

(HOA) toggle selector switch. In the “Auto” position, the furnace shall be controlled as defined in

Section 15985 Sequence of Operation. In the “Off” position, the furnace shall be disabled. In the

“Hand” position, the units’ DDC furnace operating controls shall be overridden and the furnace started and ramped up to the full heat output capacity. In all modes, the furnace operation shall be subject to all safety devices including but not limited to the manufacturer's high temperature cut-out safety and a unit airflow proving switch. Manufacturer’s authorized field representative shall verify that the HOA selector switch is properly field installed such that the manufacturer’s furnace heat exchanger warranty and the labeling and listing requirements remain in effect.

C14. For curb mounted units, per NYC Mechanical Code MC 307.2.3, Mechanical Contractor shall provide a primary pan overflow drain line or auxiliary drain pan and associated drain line for each DX evaporator coil

(when the unit is curb mounted, not dunnage mounted) to avoid damage to any building component as a result of overflow from the primary equipment drain pan or stoppage in the primary condensate drain piping. An alternate acceptable installation shall be identified in the bid package whereby the Mechanical

Contractor must coordinate with the sheet metal subcontractor to provide an auxiliary drain pan without a separate drain line under the coils on which condensate will occur. Mechanical Contractor must coordinate with the Temperature Controls subcontractor to provide a hard-wired water-level detection device for the auxiliary pan that will shut off the equipment served prior to overflow of the auxiliary pan.

Designer shall select either option of a primary pan overflow drain line or auxiliary drain pan and associated drain line and show same in the bid set.

C15. Signs, nameplates, and operation and emergency shutdown instructions for refrigeration systems shall comply with the requirements of MC 1101.11 and ASHRAE 15-2001.

C16. Per NYC Fuel Gas Code 403.9.3, joints and connections shall be approved and of a type approved for natural gas piping systems. All threaded joints and connections shall be made tight with suitable lubricant or pipe compound. Pipe joint compounds and thread seal tape that utilize Teflon (PTFE) shall be approved for usage on natural gas lines.

Section 15857 Unit Ventilators

A1. For ceiling hung units, per NYC Mechanical Code MC 307.2.3, Mechanical Contractor shall provide a primary pan overflow drain line or auxiliary drain pan and associated drain line for each cooling coil to avoid damage to any building component as a result of overflow from the primary equipment drain pan or stoppage in the primary condensate drain piping. An alternate acceptable installation shall be identified in the bid package whereby the Mechanical Contractor must coordinate with the sheet metal subcontractor to provide an auxiliary drain pan without a separate drain line under the coils on which condensate will occur. Mechanical Contractor must coordinate with the Temperature Controls subcontractor to provide a hard-wired water-level detection device for the auxiliary pan that will shut off the equipment served prior to overflow of the auxiliary pan. Designer shall select either option of a primary pan overflow drain line or auxiliary drain pan and associated drain line and show same in the bid set.

Section 15858 Window Air Conditioners

C1. Equipment shall be listed and labeled to UL 1995-1998. UL listing shall be indicated on the Shop

Drawings.

C2. Units shall comply with the EER requirements of the 2007 Edition of the New York State Energy

Conservation Construction Code and ASHRAE 90.1-2004.

15

Section 15860 Centrifugal Fans

A1. Per NYC Mechanical Code MC 513.10 equipment utilized in Smoke Control systems such as fans and automatic dampers shall be suitable for their intended use, suitable for the probable exposure temperatures and shall be as approved by the Commissioner. Fans shall be rated and certified by the manufacturer for the probable temperature rise to which the components will be exposed. Per

BC 909.4.6, all portions of active smoke control systems shall be capable of continued operation after detection of the fire event for not less than 20 minutes. The above text is applicable if the centrifugal fans are used for Smoke Control.

A2. Per NYC Mechanical Code MC 513.10.5 for smoke control fans: Belt-driven fans shall have 1.5 times the number of belts required for the design duty with the minimum number of belts being two. Fans shall be supported and restrained by noncombustible devices in accordance with the structural design requirements of the New York City Building Code. Motors driving fans shall not be operating beyond their nameplate horsepower (kilowatts) as determined from measurement of actual current draw.

Motors driving fans shall have a minimum service factor of 1.15.

A3. Contractor shall provide high energy efficient motors that meet the requirements of the 2007 New York

State Energy Conservation Construction Code and ASHRAE 90.1-2004.

A4. Per ASHRAE 90.1-2004 Article 6.4.3.4.3, systems shall be equipped with motorized dampers that will automatically shut when the systems or spaces served are not in use. Gravity (non-motorized) dampers are acceptable in buildings less than three stories in height. Gravity (non-motorized) dampers are acceptable in systems with a design exhaust capacity of 300 cfm or less.

A5. Added PennBarry as an approved manufacturer of centrifugal fans.

A6. Kitchen exhaust fans shall be listed and labeled to UL 762-99 for grease duct use.

A7. Duct to Kitchen Exhaust Fan Connections: Contractor shall provide flexible connections on inlet and outlet duct connections (comply with NYC Mechanical Code MC 506.3.2.3 for Kitchen Exhaust Fans).

MC 506.3.2.3 requires that duct-to-exhaust fan connections be flanged and gasketed at the base of the fan for vertical discharge fans; be flanged, gasketed and bolted to the inlet of the fan for side-inlet utility fans; and be flanged, gasketed and bolted to the inlet and outlet of the fan for in-line fans.

Approved flexible connectors may be provided.

Section 15864 Propeller Fans

A1. Per ASHRAE 90.1-2004 Article 6.4.3.4.3, systems shall be equipped with motorized dampers that will automatically shut when the systems or spaces served are not in use. Gravity (non-motorized) dampers are acceptable in buildings less than three stories in height. Gravity (non-motorized) dampers are acceptable in systems with a design exhaust capacity of 300 cfm or less.

A2. Per NYC Mechanical Code MC 513.10 equipment utilized in Smoke Control systems such as fans and automatic dampers shall be suitable for their intended use, suitable for the probable exposure temperatures and shall be as approved by the Commissioner. Fans shall be rated and certified by the manufacturer for the probable temperature rise to which the components will be exposed. Per NYC

Building Code BC 909.4.6, all portions of active smoke control systems shall be capable of continued operation after detection of the fire event for not less than 20 minutes. The above text is applicable if the propeller fans are used for Smoke Control.

Section 15865 Axial Flow Fans

A1. Per NYC Mechanical Code MC 513.10 equipment utilized in Smoke Control systems such as fans and automatic dampers shall be suitable for their intended use, suitable for the probable exposure temperatures and shall be as approved by the Commissioner. Fans shall be rated and certified by the manufacturer for the probable temperature rise to which the components will be exposed. Per NYC

Building Code BC 909.4.6, all portions of active smoke control systems shall be capable of continued operation after detection of the fire event for not less than 20 minutes. The above text is applicable if the axial flow fans are used for Smoke Control.

A2. Per NYC Mechanical Code MC 513.10.5 for smoke control fans: Belt-driven fans shall have 1.5 times the number of belts required for the design duty with the minimum number of belts being two. Motors

16

driving fans shall not be operating beyond their nameplate horsepower (kilowatts) as determined from measurement of actual current draw. Motors driving fans shall have a minimum service factor of 1.15.

Section 15872 Gravity Roof Ventilator

A1. Added PennBarry as an approved manufacturer of gravity roof ventilators.

A2. Per ASHRAE 90.1-2004 Article 6.4.3.4.3, systems shall be equipped with motorized dampers that will automatically shut when the systems or spaces served are not in use. Gravity (non-motorized) dampers are acceptable in buildings less than three stories in height. Gravity (non-motorized) dampers are acceptable in systems with a design spill/relief exhaust capacity of 300 cfm or less.

Section 15885 Air Filters

A1. Air filers must be labeled and listed to UL 900-1994 (Refer to MC 605.2).

Section 15891 Metal Ductwork

A1. Per NYC Mechanical Code MC 513.10, equipment utilized in Smoke Control systems such as ductwork shall be suitable for their intended use, suitable for the probable exposure temperatures and shall be as approved by the Commissioner. Components shall suitable for the probable temperature rise to which the components will be exposed. Per MC 513.10.2, duct materials and joints shall be capable of withstanding the defined probable temperatures and pressures to which they are exposed. Smoke Control ductwork shall be leak tested to 1.5 times the maximum design operating pressure. Measured leakage shall not exceed 5% of design flow. Ducts shall be supported directly from the fire resistance rated structural elements of the building by substantial non-combustible supports.

A2. Contractor shall fabricate kitchen hood exhaust ducts and supports of carbon steel sheets complying with

ASTM A 1008/A 1008M according to the following per NYC Mechanical Code MC 506.3.1.1:

Ducts with cross sectional area up to and including 155 square inches shall be constructed of

0.0598” (No. 16 gage steel)

Ducts with cross sectional area over 155 square inches but not more than 200 square inches shall be constructed of 0.074” (No. 14 gage steel)

Ducts with a cross sectional area equal to or more than 200 square inches shall be constructed of 0.1046” (No. 12 gage steel)

Exception per MC 506.3.1.1: Listed and labeled factory-built commercial kitchen grease ducts shall be installed as required by the terms of their approval, in accordance with the conditions of the listing, the manufacturer’s installation instructions and the NYC Construction Codes and shall be approved by the

Commissioner.

Note that formerly Kitchen exhaust ducts were constructed of 10 gage black sheet steel. Black steel was changed to carbon steel sheets to be consistent with NFPA 96 and AIA Master Specifications.

A3. Per NYC Mechanical Code MC 506.2 Corrosion protection: Kitchen exhaust ducts exposed to the outside atmosphere or subject to a corrosive environment shall be protected against corrosion in an approved manner. All exterior ducts shall be constructed of stainless steel not less than 0.043 inch

(No. 18 Gage) in thickness. At the base of each duct and at its termination point a clearly identifiable permanent sign shall be installed identifying the facility from which the duct originates. Exception:

Listed and labeled factory-built commercial kitchen grease ducts may be used when installed in accordance with NYC Mechanical Code MC 304.1.

A4. Contractor shall fabricate joints with continuous welds or braze (or as specified in the listing) per NYC

Mechanical Code MC 506.3.2 for watertight construction. Former standards only allowed welding. Brazing is now an additional option.

A5. Leakage Tests: Contractor shall perf orm leakage tests on ductwork operating in excess of 3”w.c. and on all ductwork upstream of the VAV boxes (regardless of the operating pressure) for all variable volume systems in accordance with SMACNA HVAC Air Duct Leakage Test Manual, 1st Edition-1985 and in accordance with the 2007 Edition of the New York State Energy Conservation Construction Code and

17

ASHRAE 90.1-2004. All rectangular ductwork upstream of the VAV boxes shall be sealed according to minimum Seal Class B, Construction Class 3” wc or higher (equipment external static pressure) or as indicated on the drawings and shall have Leakage Class 12. All rectangular ductwork upstream of the

VAV boxes shall be leak tested at equipment external static pressure but in no case less than 3” wc testing pressure. The requirements to leak test ductwork upstream of the VAV boxes is being implemented for Quality Control.

Section 15910 Ductwork Accessories

A1. Per NYC Mechanical Code MC 606.2.3, where return air risers serve two or more stories and serve any portion of a return air system having a design capacity greater than 15,000 cfm, smoke detectors shall be installed on each story. Such smoke detectors shall be located upstream of the connection between the return air riser and any air ducts or plenums.

Section 15915 Dampers

A1. Per NYC Mechanical Code MC 513.10, equipment utilized in Smoke Control systems such as automatic dampers and balance dampers shall be suitable for their intended use, suitable for the probable exposure temperatures and shall be as approved by the Commissioner. Components shall suitable for the probable temperature rise to which the components will be exposed. Per MC 513.10.4, automatic dampers, regardless of the purpose for which they are installed within the smoke control system, shall be listed and conform to the requirements of approved recognized standards. Per NYC Building Code BC 909.5.2.1, ducts and air transfer openings are required to be protected with a minimum Class II, 250ºF smoke damper complying with BC 716 when used as part of smoke control systems.

A2. Noted that Staefa Control Systems was purchased by Siemens Building Technologies, Inc. - Talon

Controls. Siemens (through the Staefa line) is still an approved manufacturer of damper actuators.

A3. Per NYC Mechanical Code MC 607.3.1.1.2, the fire damper operating temperature shall not be more than

286°F where located in a smoke control system complying with NYC Mechanical Code MC 513.

A4. Distinguished between “testing” airflow and “rated” airflow per UL standards. Smoke dampers and combination fire/smoke dampers must close and open within 75 seconds after 15-minute exposure to minimum 250°F elevated temperature at a “testing” airflow of 2400 fpm, 4.5 inches wc. Dampers shall

"rated" at 2,000 fpm at 4.0" wc. Dampers shall include and bear a UL label in accordance with established UL labeling procedures.

Section 15930 Variable Air Terminals

A1. Memorializes previous requirement issued in February 2008 in Section S01650 that training is to be digitally recorded in lieu of the former videotaping requirement.

A2. Added Note 11 to Specifier that all ductwork upstream of the VAV boxes is to be tested regardless of operating pressure. Designer shall show magnitude of leak testing pressure on the ductwork drawings.

Section 15931 Fan - Powered Variable Air Volume (VAV) Terminal Units

A1. Memorializes previous requirement issued in February 2008 in Section S01650 that training is to be digitally recorded in lieu of the former videotaping requirement.

A2. Added Note 10 to Specifier that all ductwork upstream of the VAV boxes is to be tested regardless of operating pressure. Designer shall show magnitude of leak testing pressure on the ductwork drawings.

Section 15940 Air Outlets and Inlets

A1. Air Outlets and Inlets shall be in accordance with NYC Mechanical Code MC 608. Any wall mounted outlets and inlets shall be at least 3” from the floor. Grilles may be located in floors provided they are installed so that they may be removed for cleaning purposes.

Section 15970 Temperature Control System (LonWorks BMS/DDC With School Operating Console)

B1. For rooftop units and air handling units, if the Temperature Controls Contractor (TCC) furnishes their controllers to the Original Equipment Manufacturer (OEM), the TCC shall furnish their controllers and related devices mounted on a back-plate and wired to a terminal strip. This is being implemented to facilitate the coordination process so the OEM knows how much space must be reserved for the TCC furnished controls.

18

B2. For ceiling hung fan coil units, ceiling hung unit ventilator units and curb mounted rooftop units, per NYC

Mechanical Code MC 307.2.3, where the primary drain pan is not provided with auxiliary drain line or an auxiliary drain pan is not provided with an auxiliary drain line, Temperature Control Contractor shall provide a condensate water level detection device in the auxiliary drain pan. Water level detection device shall be hard-wired and shall shut off the equipment served prior to overflow of the auxiliary pan.

B3. Per NYC Mechanical Code MC 1305.9.4, the Mechanical Contractor shall install sumps or containers at the base of any shaft containing diesel oil risers for any generators located on higher elevation floors or on the roof. The Mechanical Contractor shall also provide leak sensors in the sumps or containers that report to the leak detection panel provided by the Mechanical Contractor per Section

15590. The Temperature Controls Contractor (TCC) shall interface the diesel oil leak detection panel to the diesel oil transfer pumps such that when a leak is detected at the sumps or containers at the base of the shaft containing the diesel oil risers and the diesel oil leak detection panel goes into the alarm mode, the diesel oil transfer pumps will be shut down. TCC shall run control wiring from the diesel oil leak detection panel to the diesel oil transfer pump starters to enable this shutdown. If dry contacts are not available at the diesel oil leak detection panel, the TCC shall provide a relay in parallel with the diesel oil leak detection panel alarm horn. This relay shall close a set of TCC provided dry contacts which in turn will be utilized in the wiring from the diesel oil leak detection panel to the diesel oil transfer pump starters.

B4. The LNS/WEB Server hardware requirements were revised to require the following at a minimum:

CPU: Intel Core 2 Duo E6305, 1.86 GHz, 2MB Cache, 1066 MHz FSB

Hard Drive: Two (250 GB or larger) 7200 rpm SATA Hard Drives

Video Display: 19” LCD Monitor, capable of viewing up to 1600 X 1200 @ 32 bit depth mode @75

Hz in 16 X 9 format with a Video Display Adapter equipped with video graphics card capable of displaying up to 1600 X 1200 resolution @ 32 bits, video memory minimum of 128 Meg of RAM.

B5. In addition to 40 hours of instruction, additional training shall be repeated quarterly during the warranty period. A minimum of 8 hours of instruction shall be provided for each quarterly training period.

B6. Added Note 15 to Specifier stating that “Designer shall show the required wiring (twisted pair,

AWG#16) from the iLon100 to the Intrusion Alarm digital communicator (auto-dialer) on the Electrical

Drawing set. Refer to Electrical Design Requirement 7.3.14

”.

Section 15971 Temperature Control System LonWorks DDC-Only Without Network

C1. For rooftop units and air handling units, if the Temperature Controls Contractor (TCC) furnishes their controllers to the Original Equipment Manufacturer (OEM), the TCC shall furnish their controllers and related devices mounted on a back-plate and wired to a terminal strip. This is being implemented to facilitate the coordination process so the OEM knows how much space must be reserved for the TCC furnished controls.

C2. For ceiling hung fan coil units, ceiling hung unit ventilator units and curb mounted rooftop units, per NYC

Mechanical Code MC 307.2.3, where the primary drain pan is not provided with auxiliary drain line or an auxiliary drain pan is not provided with an auxiliary drain line, Temperature Control Contractor shall provide a condensate water level detection device in the auxiliary drain pan. Water level detection device shall be hard-wired and shall shut off the equipment served prior to overflow of the auxiliary pan.

C3. Per NYC Mechanical Code MC 1305.9.4, the Mechanical Contractor shall install sumps or containers at the base of any shaft containing diesel oil risers for any generators located on higher elevation floors or on the roof. The Mechanical Contractor shall also provide leak sensors in the sumps or containers that report to the leak detection panel provided by the Mechanical Contractor per Section

15590. The Temperature Controls Contractor (TCC) shall interface the diesel oil leak detection panel to the diesel oil transfer pumps such that when a leak is detected at the sumps or containers at the base of the shaft containing the diesel oil risers and the diesel oil leak detection panel goes into the

19

alarm mode, the diesel oil transfer pumps will be shut down. TCC shall run control wiring from the diesel oil leak detection panel to the diesel oil transfer pump starters to enable this shutdown. If dry contacts are not available at the diesel oil leak detection panel, the TCC shall provide a relay in parallel with the diesel oil leak detection panel alarm horn. This relay shall close a set of TCC provided dry contacts which in turn will be utilized in the wiring from the diesel oil leak detection panel to the diesel oil transfer pump starters.

C4. Temperature Controls Contractor (TCC) shall provide a field installed furnace control Hand-Off-Auto

(HOA) toggle selector switch for the commercial and semi-custom units. (HOA selector switch will be factory installed for the custom rooftop units). In the “Auto” position, the furnace shall be controlled as defined in Section 15985 Sequence of Operation. In the “Off” position, the furnace shall be disabled. In the “Hand” position, the units’ DDC furnace operating controls shall be overridden and the furnace started and ramped up to the full heat output capacity. In all modes, the furnace operation shall be subject to all safety devices including but not limited to the manufacturer's high temperature cut-out safety and a unit airflow proving switch. For the commercial and semi-custom units, manufacturer’s authorized field representative shall verify that the HOA selector switch is properly field installed such that the manufacturer’s furnace heat exchanger warranty and the labeling and listing requirements remain in effect.

Section 15972 Temperature Control System (Pneumatic)

C1. Memorializes previous requirement issued in February 2008 in Section S01650 that training is to be digitally recorded in lieu of the former videotaping requirement.

C2. Revised the compressor specifications to reflect state of the art technology to allow ductile iron crankshaft in addition to cast-iron. Compressor shall be provided with lap joint piston rings to limit oil carryover to 4 PPM maximum.

C3. Added Johnson Controls Inc. by Powerex as an approved compressor manufacturer.

Section 15973 Facility Management Systems Integration

B1. Noted that Staefa Control Systems was purchased by Siemens Building Technologies, Inc. - Talon

Controls. Siemens (through the Staefa line) is still an approved manufacturer of LonWorks controls.

B2. Formerly two RS-232 serial ports were required, now only one is required on the School Operating

Console PC.

Section 15985 Sequence of Operation

A1. Ceiling hung dual-temperature fan coil unit or unit ventilator control: Per NYC Mechanical Code

MC 307.2.3, where the primary drain pan is not provided with auxiliary drain line or an auxiliary drain pan is not provided with an auxiliary drain line, a hard-wired water-level detection device located in the auxiliary pan shall shut off the equipment served prior to overflow of the auxiliary pan.

A2. Fire Alarm Shutdown (reference NYC Mechanical Code MC 606.2.2): Fan powered boxes shall be shutdown during a fire condition when their associated RTU or air handling unit is commanded to shutdown by the building Fire Alarm Control Panel (FACP). Fan powered boxes shall be shutdown by the building Fire Alarm Control Panel (FACP).

A3. Added Note to Specifier (Note 38) which governs the control of the dampers in gravity ventilators. Per

ASHRAE 90.1-2004 Article 6.4.3.4.3, systems shall be equipped with motorized dampers that will automatically shut when the systems or spaces served are not in use. Gravity (non-motorized) dampers are acceptable in buildings less than three stories in height. Gravity (non-motorized) dampers are acceptable in systems with a design exhaust capacity of 300 cfm or less.

A4. Added text to the Section and corresponding Note 39 to Specifier regarding ventilation of the Hydraulic

Elevator Machine Room. Text added to the Section is as follows: “Elevator Machine Room exhaust fan shall run at constant speed to provide ventilation at all times. The exhaust fan run status shall be monitored, via a motor leg current switch. Failure of the exhaust fan to run shall be alarmed at the

School Operating Console (SOC) of the BMS system ”. Corresponding Note 39 that was added states

20

the following: “Edit as required. Hydraulic Elevator Machine Rooms and machinery spaces shall be vented to the outside air naturally or mechanically, as required by NYC Building Code Appendix K

Section 3.7 in order to minimize odors associated with hydraulic oil. If mechanical ventilation is elected, makeup air ventilation loads shall be considered when sizing the split system for the Hydraulic

Elevator Machine Room ”.

A5. Added text to the Section and corresponding Note 37 to Specifier regarding ventilation of rooms containing fuel oil tanks located above ground above the lowest floor of a building. Text added to the

Section is as follows: “Rooms containing fuel oil tanks located above ground above the lowest floor of a building shall be ventilated to limit the concentration of vapors in the room at or below 25% of the Lower

Flammability Limit (LFL) of the fuel oil being used per NYC Mechanical Code MC 1305.13.3.4. The combustible vapor sensor shall operate the exhaust fan and remote annunciation through the BMS when

25% LFL is exceeded. The exhaust fan run status shall be monitored, via a motor leg current switch.

Failure of the exhaust fan to run after being commanded to run by the combustible vapor sensor shall be alarmed at the School Operating Console (SOC) of the BMS system ”. Corresponding Note 37 that was added calls to edit as required.

A6. Added text to the Section that addresses the manual control of the gas fired furnace from the Hand-Off-

Automatic selector switch as covered above in the changes to Sections 15853 and 15854 Item A13 and

Section 15855 Item C13.

A7. Per NYC Mechanical Code MC 307.2.3, for curb mounted units (not applicable for dunnage mounted units) where the primary drain pan is not provided with auxiliary drain line or an auxiliary drain pan is not provided with an auxiliary drain line, a hard-wired water-level detection device located in the auxiliary pan shall shut off the equipment served prior to overflow of the auxiliary pan.

A8. Per NYC Mechanical Code MC 403.3.3, variable air volume systems other than those designed for 100% outdoor air, shall be provided with controls to regulate the flow of outdoor air. Such control systems shall be designed to maintain the minimum required flow of outdoor air over the entire range of supply air operating rates.

A9. The relative humidity levels in all occupied spaces shall be controlled to maintain 50% relative humidity per NYC Building Code BC 1204.2. This applies to both variable air volume and constant volume systems. Previously for constant volume systems serving one space, the relative humidity was controlled to 60% per the 2002 NYS Energy Conservation Construction Code (NYSECCC). The 2007 NYSECCC added exemptions to allow the relative humidity to be controlled below 60% if condenser waste heat is recovered. Condenser waste heat recovery is achieved by the rooftop units by the hot gas reheat coils.

A10. Carbon monoxide shut down: Boiler burner equipment shall be shut down by the fire alarm system on detection of high carbon monoxide levels.

A11. Fuel oil transfer pumps will be shut down by remote control from the fire alarm system upon detection of excess heat in the generator room.

A12. Added new Articles 3.24 and 3.25 to differentiate how make up air is to be provided for the post fire smoke purge systems for non-high rise buildings as compared to high rise buildings. For high rise buildings, added an option to use the supply fan as part of the post fire smoke purge system.

A13. Added Note 40 to Specifier to edit the Section if vents are designed for the elevator hoistway in accordance with Building Code BC 3004.6.1 in lieu of mechanical ventilation as defined in Building Code

BC 3004.6.2. If a mechanical ventilation system is designed, designer is directed to provide a smoke control sequence of operation in Section 16720, Fire Detection and Alarm system.

A14. Added Note 41 to Specifier to edit the Section if roof vents are designed for the stage in accordance with

Building Code BC 410.3.7.1 in lieu of mechanical ventilation as defined in Building Code BC 410.3.7.2. If a mechanical ventilation system is designed, designer is directed to provide a smoke control sequence of operation in Section 16720, Fire Detection and Alarm system.

21

A15. Added Note 43 to Specifier to edit the Section if smoke control is not required per Building Code

BC 404.4. If the Atrium floor openings meet the requirements of Building Code BC 707.2 Exceptions 2 and 8, a mechanical ventilation system as defined in Building Code BC 909.8 is not required. If the

Exceptions do not apply, a mechanical ventilation system shall be provided per Building Code BC 909.8 and a smoke control sequence of operation shall be included in Section 16720, Fire Detection and Alarm system.

Section 15992 Cleaning and Testing

A1. Added a new Article 3.02 stating, “The Contractor shall provide gas, refrigerant, energy, fuel, oil, water, air, light and electrical instruments as required for all testing, including testing associated with Special

Inspections (unless otherwise noted). Although the Authority will select Special Inspection Firms and pay for all Special Inspection services, the Contractor shall furnish labor, material, and instruments necessary to conduct all acceptance tests at no additional cost to the Authority including testing associated with

Special Inspections. Contractor shall provide access for Special Inspections and testing laboratory services ”.

A2. Revised the hydrostatic testing requirements to the following: Hydrostatic Tests: (Per NYC Mechanical

Code MC 1208.1) Low pressure steam piping, condensate return, hot and/or chilled water systems, including glycol systems, shall be tested at one and one half times the system design operating pressure, but not less than 100 pounds per square inch hydrostatic pressure maintained for at least 2 hours during the progress of installation. Former requirement was for 80 psi minimum for 4 hours.

A3. Added the hydrostatic testing criteria for pressure vessels.

A4. Revised the testing methodology for refrigeration systems to be compliant with NYC Mechanical Code

MC 1108. Every refrigerant-containing part of every system that is erected on the premises, except compressors, condensers, vessels, evaporators, safety devices, pressure gauges and control mechanisms that are listed and factory tested, shall be tested and proved tight after complete installation and before operation.

A5. Clarified that the field testing for fuel oil and diesel oil tanks (25 psi for minim um ½ hour) only applies to tank s of the “alternate” construction per NYC Mechanical Code MC 1308.2 and MC 1305.14.

A6. L isted fuel oil storage tanks 660 gallons or less in capacity, supplied with a label or manufacturer’s certification attesting that the tank was factory tested to NFPA 31 are not required to be field tested in accordance with NYC Building Code BC 1704.16. Per NYC Mechanical Code MC 1308.1, fuel-oil storage tanks, other than tanks complying with the alternate tank design and construction standards contained in

MC 1305.14, shall be factory tested in accordance with NFPA 31.

A7. The testing of the fuel oil lines was revised to comply with NYC Mechanical Code MC 1308.2 as follows:

After the fuel oil piping has been filled and all the air has been removed, the fuel oil piping shall be tested at 1.5 times the maximum working pressure applicable to that part of the piping system but at a pressure not less than the test pressure required for the storage tank. The hydrostatic pressure shall be maintained until all joints and connections have been visually inspected for leaks, but in no case for less than 1/2 hour. A Note to Specifier was added directing the designer to insert the applicable testing pressure based on the maximum operating pressure. Former standard required testing at 150 psi for one hour.

A8. The chimney and breeching smoke tests were revised to refer to the procedures defined in NYC

Mechanical Code MC 810, NYC Building Code BC 1704.23 and 1704.24. A pressure equivalent to 1/2inch (13 mm) column of water measured at the base of the stack remains as the magnitude of the testing pressure consistent with the former standard section requirement.

A9. Added the requirement to conduct leakage testing on all ductwork upstream of the VAV boxes (regardless of the operating pressure) for all variable volume systems. All rectangular ductwork upstream of the VAV boxes shall be sealed according to minimum Seal Class B, Construction Class 3” wc or higher (equal to equipment external static pressure) and shall have Leakage Class 12. All rectangular ductwork upstream of the VAV boxes shall be leak tested at equipment external static pressure but in no case less than 3” wc testing pressure.

22

A10. Per NYC Mechanical Code MC 513.10.2, Smoke Control duct materials and joints shall be capable of withstanding the defined probable temperatures and pressures to which they are exposed. Smoke Control ductwork shall be leak tested to 1.5 times the maximum design operating pressure. Measured leakage shall not exceed 5% of design flow.

A11. Article 3.11 was added to define the Special Inspections and associated Contractor test requirements for projects utilizing smoke control.

A12. Per NYC Mechanical Code, MC 507.16 Performance test: A performance test shall be conducted upon completion and witnessed by a representative of the Fire Department before final approval of the installation of a ventilation system serving commercial cooking appliances.

A13. Article 3.13 was added to define the DOB and DEP noise control requirements. Although the Authority will select the Acoustical Special Inspector to verify compliance with NYC Mechanical Code MC 926 and the

New York City Noise Control Code and pay for all Special Inspection services, the Contractor shall furnish labor and material necessary to conduct all acceptance tests at no additional cost to the Authority.

Contractor shall provide access for Special Inspections and testing laboratory services, including but not limited to providing the manpower to run the HVAC units while the Acoustical Special Inspector takes the necessary field measurements. For this Acoustical Special Inspection, the Special Inspector will provide all sound level measuring instruments.

A14. Article 3.14 was added to define the high pressure steam welding, radiographic inspection and hydrostatic testing requirements. Although the Authority will select the High Pressure Steam Piping Special Inspector to verify compliance with the requirements and pay for all Special Inspection services, the Contractor shall furnish labor and material necessary to conduct all acceptance tests at no additional cost to the Authority.

Contractor shall provide access for Special Inspections and testing laboratory services.

Section 15993 Balancing of Systems

A1. The testing, adjusting and balancing firm shall have a Professional Engineer registered in the State of NY

(on staff or a sub-consultant of the testing, adjusting and balancing firm) who shall sign and seal all the reports. The section was revised to add the allowable provision for the testing, adjusting and balancing firm to sub-consult to a Professional Engineer (i.e. need not necessarily be on the staff of the testing, adjusting and balancing firm).

A2. Firms performing the balancing work shall be on the “HVAC Certified Testing and Balancing Firms” list of the Authority’s Contractor Qualification Unit.

Notes : The revised Specification Sections are dated 11/02/09 .

Revisions are indicated in the body of the specification Sections by use of unless specifically indicated otherwise. bold type for text additions

At this time, revisions have been made only to the Bulletin set on A&E’s Standards Bulletins page at the following Internet address: http://schools.nyc.gov/Offices/SCA/DoingBusiness/AE/Bulletins/default.htm

. Click on the Bulletin

SP09-02 link to download. The information on the LAN in the "Apps1 on ’sca_appsl’(T:) sca_stds\std_spec directory and individually on the NYCSCA website will be updated simultaneously with the next bulletin within the next several weeks.

Applicability Table / Compliance Form

The revised Standard Specifications should be used for all projects requiring them, as indicated in the table on the following pages.

The table has been configured for use as the Standards Bulletin Compliance Form. The project design professional will complete Standards Bulletin Compliance Forms as appropriate for each of their active projects (in Scope through Construction). Refer to the AE Procedural Guideline PG 1.3.1 SCA Standards

Bulletins – Issuance and Compliance for additional information.

23

The A&E design project manager will provide each design professional with a customized Standards Bulletin

Compliance Summary to indicate compliance for each active project.

For each project that includes an item needing compliance, an individual Standards Bulletin Compliance

Form must be completed and transmitted by the design professional, along with the Summary, to the A&E design project manager.

Attachment: Standards Bulletin Compliance Form cc: SCA A&E

SCA Construction Management

SCA Project Controls

SCA Environmental & Regulatory Compliance

SCA Facilities Inspection Division

SCA Contract Administration

SCA Furniture & Equipment

SCA Scheduling

SCA Industrial & Environmental Hygiene

SCA Commissioning Unit

SCA Change Order Unit

SCA Construction Services

SCA Close-Out Unit

SCA Project Services

DoED: V. Braren

24

STANDARDS BULLETIN COMPLIANCE FORM for Standard Specifications Bulletin No. SP09-02, November 2, 2009

The revised Standard Specifications should be used for all projects requiring them, as indicated in the table belo w. Apply Bulletin items to project phases marked by “A”, “B” or “C”. Items denoted A# are applicable to all

Capacity and CIP Projects. Items denoted B# are applicable to all Capacity Projects but not to CIP Projects.

Items denoted C# are applicable to CIP Projects but not to Capacity Projects. For those projects nearing turnover for the design phase or bid opening for the bid stage, the designers shall consult with the Design

Manager, Studio Director, and Technical Standards Studio to determine whether the document revision should be deferred and be issued as an Addendum or Change Order in order to maintain the project schedule. For projects in bid, add items as part of other required addenda, if possible.

This Compliance Form is to be completed by the project design professional for each project/design bundle for the applicable item. Highlight the column for the current phase of the project in yellow to facilitate input and review. For projects having an applicable item, complete the table below with method of compliance and, if beyond Design phase, with the forecast or actual date of compliance.

Fill in only those rows applicable to the current phase of the project. Include both Design number and LLW number(s) for CIP projects and LLW number for capacity projects.

Use these options when filling in the “Method and Date of Compliance” column:

Item is not applicable to project - “ n.a.

In Scope/Design – “ will comply at milestone” (insert QC, compliance, or turnover)

During Bid – “ Addendum to be issued on d ate” (insert forecast or actual date, indicated by F or

A)

Bids Opened (No NTP) – “ Bulletin to be issued on da te” (insert forecast or actual date, F or A)

In Construction (Post NTP) – “ Bulletin to be issued on date ” (insert forecast or actual date, F or

A)

Applicability Comments are provided to facilitate the compliance process. The design professional may also use this column, only as needed, to explain unique or irregular compliance, or reason for non-compliance.

Completed forms (delete the pages preceding) must be sent to the A&E design project manager in an organized set (Bulletin Compliance Summary and all applicable Compliance Forms) for all active projects.

SP09-02 11-02-09

25

School/Boro:

Project Description:

Current Project Phase:

Date:

SPEC SECTION

NUMBER,

DESCRIPTION

Section 15501 Basic

Heating, Ventilating And

Air Conditioning

Requirements

Section 15502 HVAC

Identification

Section 15503 Vibration

Isolation and Seismic

Controls, HVAC Systems

SCOPE/

DESIGN

A1 to A6

A1

A1

DURING

BID

A1 to A6

A1

A1

BIDS

OPENED

NO NTP

Building ID:

Design No.:

LLW No(s):

CONSTR

(Post

NTP)

METHOD AND

DATE OF

COMPLIANCE

A1 to A6 A1 to A6

A1

A1

A1

A1

Section 15504 Vibration

Isolation

Section 15510 HVAC

Piping

Section 15511 Valves

(HVAC)

Section 15512 Piping

Insulation (HVAC)

Section 15513

Equipment Insulation

(HVAC)

Section 15514 Ductwork

Insulation

A1

A1, A2

A1, A2

A1, A2

Section 15515 Hydronic

Specialties

A1, A2,

A3

A1

Section 15516 Water

Treatment for Steam

SP09-02 11-02-09

A1

A2

A1, A2

A1, A2

A1, A2,

A3

A1 A1

A1- A11,

C1

A1- A11,

C1

A2, A8, C1 A2, A8,

C1

A2

A1, A2

A1, A2

A2

A1, A2

A1, A2

Designer:

SCA DPM:

SCA DM:

APPLICABILITY COMMENTS

Applies to all projects filed under the

2008 Code.

Applies to all projects filed under the

2008 Code.

Applies to all projects filed under the

2008 Code. Use Section 15503 for projects that involve construction of a

New Building or Addition to building in

Seismic Design Category C or D.

Section 15503 is also to be utilized if project involves retrofit work in Existing

Buildings constructed after LL17/1995 went into effect for buildings in Seismic

Design Category C or D.

Applies to all projects with retrofit work in Existing Buildings that requires vibration isolation for all MEP work constructed prior to the effective date of

LL17/1995 and for new buildings in

Seismic Design Category B per the

2008 Code.

A1 applies to all Capacity projects and

CIP projects involving fire protection work filed under the 2008 Code using

15300 series specifications. A2 (per the 2008 Code) applies to all Capacity projects and CIP projects involving hanging new pipe. A3 applies to all projects with field assembled refrigerant piping. A4 applies to all

Capacity projects and CIP projects involving oil piping. A5, A6, A7, A8,

A9, A10 and A11 apply to all projects as applicable based on scope of work.

C1 (per the 2008 Code) applies to

CIP projects that utilize oil fired boilers and have the oil risers running up in a shaft. A8 (per the 2008 Code) applies to all projects with oil lines.

Applies to all projects filed under the

2008 Code.

Applies to all projects with emergency generators with exhausts that enter shafts.

Applies to all projects with steam or hot water boilers.

Applies to all projects filed under the

2008 Code.

Applies to all projects with hydronic systems. Changes are not Code related.

Applies to all projects with steam boilers. Changes are not Code

26

School/Boro:

Project Description:

Current Project Phase:

Date:

SPEC SECTION

NUMBER,

DESCRIPTION

Boilers

Section 15525 Steam and Condensate

Specialties

Section 15540 HVAC

Pumps

Section 15555 Fire-Tube

Boilers (Steam)

SCOPE/

DESIGN

DURING

BID

C1

C1

A1, A2

C1-C6 C1-C6

BIDS

OPENED

NO NTP

Building ID:

Design No.:

LLW No(s):

CONSTR

(Post

NTP)

METHOD AND

DATE OF

COMPLIANCE

C1-C6 C1-C6

Section 15556 Cast-Iron

Boilers

C1-C6

Section 15557 Fire-Tube

Boilers (Hot Water)

C1-C6

Section 15559 Flexible

Water-Tube Boilers

(Steam)

C1-C6

Section 15560 Flexible

Water-Tube Boilers (Hot

Water)

C1-C6

C1-C6

C1-C6

C1-C6

C1-C6

Section 15575

SP09-02

A1, B1,

11-02-09

A1, B1

C1-C6

C1-C6

C1-C6

C1-C6

Section 15565 Hot Water

Condensing Boilers

B1- B9 B1- B9 but without

B6

B1- B9 but without

B6

B1- B9 but without

B6

A1, B1

C1-C6

C1-C6

C1-C6

C1-C6

A1, B1

Designer:

SCA DPM:

SCA DM:

APPLICABILITY COMMENTS related.

Applies to CIP projects utilizing steam heating systems.

Applies to all projects with HVAC pumps. Changes are not Code related.

Applies to all CIP projects with firetube steam boiler replacements. C2,

C4 and C6 are required per the 2008

Code and apply to those projects filed under the 2008 Code. C1, C3 and C5 relate to complying with DEP BAR,

2007 NYSECCC and ASHRAE 90.1-

2004 requirements.

Applies to all CIP projects with castiron boiler replacements. C2, C4 and

C6 are required per the 2008 Code and apply to those projects filed under the 2008 Code. C1, C3 and C5 relate to complying with DEP BAR, 2007

NYSECCC and ASHRAE 90.1-2004 requirements.

Applies to all CIP projects with firetube hot water boiler replacements.

C2, C4 and C6 are required per the

2008 Code and apply to those projects filed under the 2008 Code.

C1, C3 and C5 relate to complying with DEP BAR, 2007 NYSECCC and

ASHRAE 90.1-2004 requirements.

Applies to all CIP projects with flexible water tube steam boiler replacements.

C2, C4 and C6 are required per the

2008 Code and apply to those projects filed under the 2008 Code.

C1, C3 and C5 relate to complying with DEP BAR, 2007 NYSECCC and

ASHRAE 90.1-2004 requirements.

Applies to all CIP projects with flexible water tube hot water boiler replacements. C2, C4 and C6 are required per the 2008 Code and apply to those projects filed under the 2008

Code. C1, C3 and C5 relate to complying with DEP BAR, 2007

NYSECCC and ASHRAE 90.1-2004 requirements.

Applies to all Capacity projects that utilize condensing boilers. B2, B3, B5 and B8 are per the 2008 Code and apply to those projects filed under the

2008 Code. B1, B4 and B7 relate to complying with, 2007 NYSECCC and

ASHRAE 90.1-2004 requirements. B9 is being implemented to alert all that

Teflon is allowed on gas train piping joints if the pipe joint compound or tape is approved for gas lines.

A1 applies to all projects filed under

27

School/Boro:

Project Description:

Current Project Phase:

Date:

SPEC SECTION

NUMBER,

DESCRIPTION

Breeching, Chimney and

Stacks

SCOPE/

DESIGN

DURING

BID

B2

BIDS

OPENED

NO NTP

Building ID:

Design No.:

LLW No(s):

CONSTR

(Post

NTP)

METHOD AND

DATE OF

COMPLIANCE

Section 15580

Feedwater Equipment

Section 15590

Emergency Generator

System - Accessories

C1, C2

A1, A2,

A3, A4,

A5, A6,

A7, A8,

A9, A10,

A11

C1

A3, A4,

A6, A7,

A8, A9,

A10, A11

C1

A3, A4,

A6, A7,

A8, A9,

A10, A11

C1

A3, A4,

A6, A7,

A8, A9,

A10, A11

Section 15592 Fuel

Burning/Pumping

Equipment (for Steam

Boilers)

Section 15593 Fuel

Burning/Pumping

Equipment (for Hot

Water Boilers)

C1-C9,

C10,

C11, C12

C1-C9,

C12

C1-C9,

C10,

C11, C12

C1-C9,

C12

C1-C9,

C12

C1-C9,

C12

C1-C9,

C12

C1-C9,

C12

Designer:

SCA DPM:

SCA DM:

APPLICABILITY COMMENTS the 2008 Code that utilize boilers. B1

(per 2008 Code) and B2 apply to all

Capacity projects that utilize condensing boilers.

Applies to all CIP projects filed under the 2008 Code that utilize steam feedwater equipment.

Applies to all projects filed under the

2008 Code that utilize emergency generators which get their fuel pumped from a remote storage tank.

The connection to the fire alarm system as described in A9 applies to all Capacity projects and to CIP emergency generator projects coupled with a fire alarm replacement or where the existing fire alarm system is expandable.

Applies to all CIP projects that utilize steam boilers. C2, C4, C6, C7and C8 are required per the 2008 Code and apply to those projects filed under the

2008 Code. C1 and C3 are required to comply with Utility and DEP BAR requirements. C5 and C9 are being implemented in Construction to provide remote notification of any boiler failures after normal school hours. C6 (per 2008 Code) requires that the fire alarm system shut down the transfer pumps upon a high heat condition. This is only applicable to

CIP projects utilizing new burners that are coupled with a fire alarm upgrade or where the existing fire alarm system is expandable. C12 is being implemented to alert all that Teflon is allowed on gas train and oil train piping joints if the pipe joint compound or tape is approved for such usage.

Applies to all CIP projects that utilize hot water boilers. C2, C4, C6, C7and

C8 are required per the 2008 Code and apply to those projects filed under the 2008 Code. C1 and C3 are required to comply with Utility and

DEP BAR requirements. C5 and C9 are being implemented in

Construction to provide remote notification of any boiler failures after normal school hours. C6 (per 2008

Code) requires that the fire alarm system shut down the transfer pumps upon a high heat condition. This is only applicable to CIP projects utilizing new burners that are coupled with a fire alarm upgrade or where the existing fire alarm system is expandable. C12 is being implemented to alert all that Teflon is allowed on gas train and oil train

SP09-02 11-02-09

28

School/Boro:

Project Description:

Current Project Phase:

Date:

SPEC SECTION

NUMBER,

DESCRIPTION

SCOPE/

DESIGN

DURING

BID

BIDS

OPENED

NO NTP

Building ID:

Design No.:

LLW No(s):

CONSTR

(Post

NTP)

METHOD AND

DATE OF

COMPLIANCE

Section 15594 Fuel

Storage Equipment

Section 15595 Natural

Gas/Carbon Monoxide

Leak Detection

Equipment

Section 15596 Natural

Gas Leak Detection

Equipment

Section 15610 Gas-Fired

Duct Heaters

Section 15650 Split Air

Cooled Chillers

Section 15660 Packaged

Modular Outdoor

Chillers

Section 15670 Plate Heat

Exchangers

Section 15756

Converters

Section 15781 Packaged

Heating and Cooling

Units

Section 15783 Split Heat

Pump System

Section 15835

Convectors

C1, C2 -

C12

C2-C12 C2-C12 but without

C5

C2-C12 but without

C5

C1, C2

A1

C1, C2,

C3

C1, C2-

C5

A1, A2-

A5

A1, A2,

A3

C1, C2,

C3, C4

A1, A2-

A5

A1, A2-

A7

A1, A2

Section 15836 Unit

Heaters/Cabinet Heaters

SP09-02 11-02-09

A1

C2

A1

C2, C3

C2-C5

A2-A5

A2, A3

C2, C3

A2-A5

A2-A7

C2

A1

C2, C3

C2-C5

A2-A5

A2, A3

C2, C3

A2-A5

A2-A7

C2

A1

C2, C3

C2-C5

A2-A5

A2, A3

C2, C3

A2-A5

A2-A7

Designer:

SCA DPM:

SCA DM:

APPLICABILITY COMMENTS piping joints if the pipe joint compound or tape is approved for such usage.

Applies to all CIP projects filed under the 2008 Code that utilize oil tanks.

C10 refers to providing tank room ventilation which is only applicable when new tank rooms are constructed above the lowest floor. C9 refers to providing smoke detectors in fuel oil tank rooms. This is only applicable when new tank rooms are constructed above the lowest floor.

Applies to CIP Heating Plant

Upgrade/Boiler Conversion projects without a concurrent fire alarm system replacement or concurrent extension to existing fire alarm system.

Changes are not driven by Code but are being implemented for coordination purposes and to not overload the contacts in the gas leak panel.

Applies to New Schools, Leased

Buildings, Major Modernizations,

Additions, and those schools undergoing CIP Heating Plant

Upgrade/Boiler Conversion projects with a concurrent fire alarm system replacement or concurrent extension to existing fire alarm system where the existing fire alarm system can be extended to include carbon monoxide detectors. Change is driven by the

2008 Code requirements.

Applies to all CIP projects filed under the 2008 Code that utilize gas-fired duct heaters.

Applies to all CIP projects filed under the 2008 Code that utilize split air cooled chillers.

Applies to all Capacity and CIP projects filed under the 2008 Code that utilize packaged modular outdoor chillers.

Applies to all Capacity and CIP projects filed under the 2008 Code that utilize plate heat exchangers.

Applies to all CIP projects filed under the 2008 Code that utilize converters.

Applies to any project filed under the

2008 Code that uses packaged heating and cooling units

Applies to any project filed under the

2008 Code that uses split heat pump systems.

Applies to any project that uses convectors. Changes are not 2008

Code related.

Applies to any project that uses unit heaters or cabinet heaters.

29

School/Boro:

Project Description:

Current Project Phase:

Date:

SPEC SECTION

NUMBER,

DESCRIPTION

Section 15838 Fan Coil

Units

Section 15852 Air

Handling Units

SCOPE/

DESIGN

DURING

BID

A1

A1, A2,

A3

A1

A2, A3

BIDS

OPENED

NO NTP

Building ID:

Design No.:

LLW No(s):

CONSTR

(Post

NTP)

METHOD AND

DATE OF

COMPLIANCE

A1 A1

A2 A2

Section 15853 Custom

Packaged Rooftop

Heating and Cooling

Units (Variable Air

Volume System)

Section 15854 Custom

Packaged Rooftop

Heating and Cooling

Units (Constant Volume

System)

A1- A17 A2, A3,

A4, A7,

A8, A9,

A12,

A14,

A15, A16

A2, A3,

A4, A7,

A8, A9,

A12, A14,

A15, A16

A2, A3,

A4, A7,

A8, A9,

A12,

A14,

A15, A16

Section 15855

Commercial Packaged

Rooftop Heating and

Cooling Units

Section 15857 Unit

Ventilators

A1- A17 A2, A3,

A4, A7,

A8, A9,

A12,

A14,

A15, A16

A2, A3,

A4, A7,

A8, A9,

A12, A14,

A15, A16

A2, A3,

A4, A7,

A8, A9,

A12,

A14,

A15, A16

C1-C16 C2, C3,

C4, C7,

C8, C9,

C12,

C14, C15 and C16.

C2, C3,

C4, C7,

C8, C9,

C12, C14,

C15 and

C16.

C2, C3,

C4, C7,

C8, C9,

C12,

C14, C15 and C16.

A1 A1 A1 A1

Designer:

SCA DPM:

SCA DM:

APPLICABILITY COMMENTS

Applies to any project filed under the

2008 Code that uses fan coil units.

Applies to any project that uses air handling units. A2 change is per the

2008 Code and applies to those projects filed under the 2008 Code.

Applies to any project that uses custom packaged rooftop heating and cooling units (variable air volume systems). A2, A3, A4, A9, A12, A14 and A15 are per the 2008 Code and apply to those projects filed under the

2008 Code. A7 (the requirement to submit gas train shop fabrication drawing) is being implemented in construction to facilitate inspection.

A8 is being implemented in

Construction to comply with utility requirements. A16 is being implemented to alert all that Teflon is allowed on gas train piping joints if the pipe joint compound or tape is approved for gas lines.

Applies to any project that uses custom packaged rooftop heating and cooling units (constant volume systems). A2, A3, A4, A9, A12, A14 and A15 are per the 2008 Code and apply to those projects filed under the

2008 Code. A7 (the requirement to submit gas train shop fabrication drawing) is being implemented in construction to facilitate inspection.

A8 is being implemented in

Construction to comply with utility requirements. A16 is being implemented to alert all that Teflon is allowed on gas train piping joints if the pipe joint compound or tape is approved for gas lines.

Applies to any CIP project that uses commercial packaged rooftop heating and cooling units. C2, C3, C4, C9,

C12, C14 and C15 are per the 2008

Code and apply to those projects filed under the 2008 Code. C7 (the requirement to submit gas train shop fabrication drawing) is being implemented in construction to facilitate inspection. C8 is being implemented in Construction to comply with utility requirements. C16 is being implemented to alert all that

Teflon is allowed on gas train piping joints if the pipe joint compound or tape is approved for gas lines.

Applies to any CIP project that uses outside air intake unit ventilators and to Capacity projects that are decoupled and use recirculation only unit ventilators filed under the 2008

Code.

SP09-02 11-02-09

30

School/Boro:

Project Description:

Current Project Phase:

Date:

SPEC SECTION

NUMBER,

DESCRIPTION

Section 15858 Window

Air Conditioners

Section 15860

Centrifugal Fans

Section 15864 Propeller

Fans

Section 15865 Axial

Flow Fans

Section 15872 Gravity

Roof Ventilator

Section 15885 Air Filters

Section 15891 Metal

Ductwork

Section 15910 Ductwork

Accessories

Section 15915 Dampers

Section 15930 Variable

Air Terminals

SCOPE/

DESIGN

DURING

BID

C1, C2 C1, C2

A1-A7

A1-A2

A1-A2

A1, A2

A1

A1 - A4,

A5

A1

A1, A2,

A3, A4

A1, A2

A1-A7

A1-A2

A1-A2

A2

A1

A1 - A4

A1

BIDS

OPENED

NO NTP

C1, C2

A1-A7 but not A5

A1-A2

A1-A2

A2

A1

A1 - A4

A1

Building ID:

Design No.:

LLW No(s):

CONSTR

(Post

NTP)

METHOD AND

DATE OF

COMPLIANCE

C1, C2

A1-A7 but not

A5

A1-A2

A1-A2

A2

A1

A1 - A4

A1

A1, A3,

A4

A1, A3, A4 A1, A3,

A4

Section 15931 Fan -

Powered Variable Air

Volume (VAV) Terminal

Units

Section 15940 Air

Outlets and Inlets

Section 15970

Temperature Control

System (LonWorks

BMS/DDC With School

Operating Console)

B1-B6 B2, B3,

B4, B6

B2, B3,

B4, B6

B2, B3,

B4, B6

Section 15971

Temperature Control

System LonWorks DDC-

Only Without Network

Section 15972

Temperature Control

System (Pneumatic)

Section 15973 Facility

Management Systems

Integration

C1-C4

C1, C2,

C3

B1, B2

C2, C3

SP09-02

A1, A2

11-02-09

A1 A1 A1

C2, C3

A1

C2, C3

Designer:

SCA DPM:

SCA DM:

APPLICABILITY COMMENTS

Applies to any CIP project that uses window air conditioners filed under the 2008 Code.

Applies to any project that uses centrifugal fans projects filed under the 2008 Code.

Applies to any project that uses propeller fans filed under the 2008

Code.

Applies to any project that uses axial flow fans filed under the 2008 Code.

Applies to any project that uses gravity roof ventilators filed under the

2008 Code.

Applies to all projects utilizing filters filed under the 2008 Code.

Applies to all projects utilizing ductwork filed under the 2008 Code.

Applies to all projects utilizing ductwork filed under the 2008 Code.

Applies to all projects utilizing ductwork filed under the 2008 Code.

Applies to all projects utilizing standard variable air volume boxes.

Changes to this Section are not Code related and are being implemented due to Quality Control.

Applies to all projects utilizing fan powered variable air volume boxes.

Changes to this Section are not Code related and are being implemented due to Quality Control.

Applies to all projects utilizing lower elevation air outlets and inlets filed under the 2008 Code. This would only be for special cases.

Applies to all Capacity Projects which utilize a BMS/DDC network. B2 and

B3 are per the 2008 Code. B4 is required computer hardware changes.

B6 is being implemented in

Construction to provide remote notification of any network failures after normal school hours.

Applies to all CIP Projects that use non networked digital controls. C2 and C3 are per the 2008 Code and apply to those projects filed under the

2008 Code.

Applies to all CIP Projects that use pneumatic controls.

Applies to all Capacity Projects which utilize a BMS/DDC network. Changes do not affect Contractor’s work as the work scope defined in Section 15973 is performed by the Authority’s

Facilities Management Systems

Integrator (CTI). Section 15973 is included in the Contractor’s bidset for informational purposes only.

31

School/Boro:

Project Description:

Current Project Phase:

Date:

SPEC SECTION

NUMBER,

DESCRIPTION

SCOPE/

DESIGN

DURING

BID

BIDS

OPENED

NO NTP

Building ID:

Design No.:

LLW No(s):

CONSTR

(Post

NTP)

METHOD AND

DATE OF

COMPLIANCE

Designer:

SCA DPM:

SCA DM:

APPLICABILITY COMMENTS

Section 15985 Sequence of Operation

Section 15992 Cleaning and Testing

Section 15993 Balancing of Systems

A1 - A15 A1 - A15

A1 - A14 A1 - A14

A1, A2 A1, A2

A1 - A15 but without

A6

A1 - A14 without

A9

A1, A2

A1 - A15 but without

A6

A1 - A14 without

A9

A1, A2

All items apply to all Capacity and CIP projects with exception of A10. Boiler burners will be shut down by the fire alarm system for all Capacity projects.

For CIP projects, shut down will only occur if CIP project scope includes an upgrade to the existing fire alarm system or if the existing fire alarm system has the capability to do the shutdown.

Changes are per the 2008 Code. A1 applies to all projects. A2 applies to projects utilizing low pressure steam piping, condensate return, hot and/or chilled water systems. A3 applies to projects with pressure vessels

(converters, heat exchangers, etc.),

A4 applies to projects with split refrigeration systems. A5 applies to tanks of the alternate tank design. A6 applies to projects with listed fuel oil storage tanks 660 gallons or less in capacity. A7 applies to projects with field erected fuel oil lines. A8 applies to projects with chimneys/breeching.

A9 applies to projects with VAV boxes. A10 and A11 apply to projects with smoke control. A12 applies to projects utilizing a ventilation system serving commercial cooking appliances. A13 applies to all projects with exterior equipment subject to the noise control requirements. A14 applies to projects utilizing high pressure steam piping.

Applies to all projects where balancing of mechanical systems is required.

Table Notes:

Items denoted A# are applicable to all Capacity and CIP Projects.

Items denoted B# are applicable to all Capacity Projects but not to CIP Projects.

Items denoted C# are applicable to CIP Projects but not to Capacity Projects.

For those projects nearing turnover for the design phase or bid opening for the bid stage, the designers shall consult with the Design Manager, Studio Director, and Technical Standards Studio to determine whether the document revision should be deferred and be issued as an Addendum or Change Order in order to maintain the project schedule.

Projects in Design Phase:

SP09-02 11-02-09

32

The Project Design Professional shall use the revised specifications as required and include them in the project specifications.

Projects that are presently in Bid (prior to bid opening):

The Project Design Professional shall revise the Project Documents to include the revisions as required, and issue to the bidders as an Addendum through the Design Project Manager (DPM).

Projects that have Bids opened, but the Notice to Proceed has not yet been issued:

The Project Design Professional shall revise the Contract Documents to include the revisions as required, and issue as a Change Order Bulletin through the Project Officer as soon as the Notice to Proceed is issued if change requires such. As most projects affected by many of the changes are in design since mandatory implementation only went into affect in July 2009, if there are projects that are beyond the design/bid phase any Bulletins should only be issued if the item was not addressed independently of the official specification changes and will lead to a non-code compliant condition.

Projects where the Contract Notice to Proceed has been issued and the Project is in Construction:

The Project Design Professional shall revise the Contract Documents to include the revisions as required and issue as a Change Order Bulletin through the Project Officer if change requires such. As most projects affected by many of the changes are in design since mandatory implementation only went into affect in July

2009, if there are projects that are beyond the design/bid phase any Bulletins should only be issued if the item was not addressed independently of the official specification changes and will lead to a non-code compliant condition. For non-code related items, designer is to determine if work is installed before issuing.

* * *

SP09-02 11-02-09

33

Download