INDUSTRIAL MEASUREMENT & CONTROL ST 3000® Gauge Pressure Transmitters For High Temperatures Field Instrument Solutions ST 3000® Transmitters for High Temperatures can withstand process temperatures in excess of 300 degrees Fahrenheit (150 degrees Celsius). Designed to measure pressure or the level of fluid in open or non-pressurized tanks, these unique transmitters can replace troublesome capillary-filled remote seal systems to yield better overall accuracy, much greater stability, and substantially reduced installation and maintenance costs. A patented sensor provides high-temperature performance and functionality. Features and Functions Versatile and Flexible Applications Capability ST 3000® Transmitters for High Temperatures Eliminating a remote-seal capillary High-temperature capabilities make address difficult applications in which system reduces errors due to changes this product the ideal choice when the high temperatures prohibit contact in ambient temperature and fill fluid process medium: between the transmitter and the process, densities. Because remote-seal transmitters • Is a slurry or has suspended solids that may clog the instrument line or where contact could contribute to eliminating unreliable, troublesome into a process, replacing them with a more • Might freeze or solidify due to ambient or process temperature changes reliable alternative is highly desirable. • Has a high temperature. measurement problems and numerous are notorious for being troublesome and often introduce problems of their own Also, replacing remote seals in sanitary applications minimizes downtime because there is no need to remove transmitters during Clean-In-Place and Sterilize-In-Place operations. Honeywell’s high-temperature capability ST 3000 ®s provide the right alternative, while offering the same high level of accuracy as all our highly respected These devices are well suited for a variety of industries such as power generation, clogging or contamination. In addition, remote seals prevents a multitude of field and maintenance difficulties. These effective, accurate transmitters: industrial energy management, pulp and • Withstand process temperatures in paper, hydrocarbon processing, oil and gas, excess of 300 degrees Fahrenheit and chemicals. A small flange-mount model with piping sizes as small as one inch reduces associated piping, plumbing, and equipment costs. ST 3000® transmitters. (150 degrees Celsius) • Replace remote seals in many applications • Feature a robust Honeywell- Sanitary Applications patented sensor that provides greater Two sanitary models, designed for performance and functionality than any food and pharmaceutical applications, are suitable for Clean-In-Place and comparable product on the market • Offer small, flange-mount models Sterilize-In-Place installations and meet with piping sizes down to one inch to 3A requirements for non-contamination reduce associated piping, plumbing, of the process. The sanitary connection and equipment costs. avoids the cavities and dead volume that often contribute to contamination. To learn more about the ST 3000 ® ST 3000® For High Temperatures Specification Summary* Upper Range Limit Minimum Span psig (bar) psig (bar) Gauge Pressure Transmitters and other 300 (21) 15 (0.35) Honeywell field instrument solutions, Turndown Ratio 20:1 Zero Elevation and Suppression No limit except minimum span from absolute zero to 100% of URL Accuracy (Reference) ±0.075% of calibrated span or upper range value (URV), whichever is greater Process Head: 1/ 2-inch NPT. Process Connections contact your local Honeywell representative, or visit our Web site at www.honeywell.com/imc. Sanitary: 2-inch Sanitary Tri-Clamp Flange: 3- or 4-inch Class 150 or 300 ANSI; DN80-PN40 or DN100-PN40 DIN flange. 2", 4", or 6" extension 1/ 2", 1", 11/ 2", and 2" flange Sanitary Flange Mount: 4-inch sanitary tank spud with Ladish 4-inch WARRANTY/REMEDY Honeywell warrants goods of its manufacture as being free of defective material and faulty workmanship. Contact your local sales office for warranty information. If warranted goods are returned to Honeywell during that period of coverage, Honeywell will repair or Tri-Clamp. See Specification 23-ST-03-26. replace without charge those items it finds defective. Diaphragm Materials (wetted) 316L Stainless Steel, Hastelloy C The foregoing is Buyer’s sole remedy and is in lieu Gasket Ring Materials (wetted) 316L Stainless Steel, Hastelloy C of all other warranties, expressed or implied, Mounting Flange (non-wetted) Zinc: Chromate-plated Carbon Steel, 304 SS, or 316 SS. including those of merchantability and fitness for a particular purpose. Sanitary Design: 316SS Fill Fluid Silicone (DC 200), CTFE (Chlorotrifluoroethylene) Electronic Housing Epoxy-polyester hybrid paint. Low copper-aluminum alloy. Meets NEMA 4X (watertight) and NEMA 7 (explosion proof). IP 66/67 Ambient Temperature °F / °C Process Interface Temp. Humidity °F / °C 77±2 / 25±1 -40 to 185 / -40 to 85 77±2 / 25±1 -40 to 302 / -40 to 150 10 to 55 0 to 100 0/0 0/0 265 / 18 690 / 48 %RH Flange Rating ANSI Class 150 psi/bar ANSI Class 300 psi/bar Supply Voltage, Current, and Load Resistance While we provide application assistance, personally, through our literature and the Honeywell Web site, it is up to the customer to determine the suitability of the product in the application. Specifications may change at any time without notice. The information we supply is believed to be accurate and reliable as of this printing. However, we assume no responsibility for its use. ST 3000 ® is a registered trademark of Honeywell International Inc. Voltage Range: 10.8 to 42.4 Vdc at terminals Current Range: 3.8 to 21.8 mA Load Resistance: 0 to 1440 ohms Output (two-wire) Analog 4 to 20 mA or digital communications DE mode Supply Voltage Effect ±0.005% span per volt. Damping Time Constant Adjustable from 0 to 32 seconds digital dumping RFI Protection (Standard) Negligible (20 to 1000 MHz at 30 volts per meter) CE Conformity (Europe) 89/336/EEC, Electromagnetic Compatibility (EMC) Directive *See specification 34-ST-03-70 for complete product specifications. U.S.A.: Honeywell Industrial Measurement and Control, 16404 North Black Canyon Hwy., Phoenix, AZ 85053 • Canada: The Honeywell Centre, 155 Gordon Baker Rd., North York, Ontario M2H 3N7 Latin America: Honeywell Inc., 480 Sawgrass Corporate Parkway, Suite 200, Sunrise, Florida 33325 • Japan: Honeywell K.K., 14-6 Shibaura 1-chome, Minato-ku, Tokyo, Japan 105-0023 Asia: Honeywell Pte Ltd., Honeywell Building, 17 Changi Business Park Central 1, Singapore 486073, Republic of Singapore • Pacific Division: Honeywell Pty Ltd., 5 Thomas Holt Drive, North Ryde NSW Australia 2113 • Europe and Africa: Honeywell S. A., Avenue du Bourget 3, 1140 Brussels, Belgium • Eastern Europe: Honeywell Praha, s.r.o. Budejovicka 1, 140 21 Prague 4, Czech Republic Middle East: Honeywell Middle East Ltd., Technology Park, Cert Complex, Block Q, Muroor Rd., Abu Dhabi, U.A.E. Industrial Measurement and Control www.honeywell.com/imc SL-53-550 (5M) Rev. 6/02 ©Honeywell International Inc. Printed in U.S.A