KUWAIT TRADE CENTRE ILLUSTRATED LIGHTING SPECIFICATION, 100% design, Exterior, Interior public area, Shopping mall REVISION B Specification No 0429-. 4 baltic street, edinburgh, eh6 7bw, scotland phone: +44(0) 131 555 5553 fax: +44(0) 131 555 5559 email:office@kevan-shaw.com elucidation(2000)ltd. incorporated in scotland no. sc213106 registered office as above h t t p : / / w w w. k e v a n - s h a w. c o m CONTENTS 1. GENERAL 2. 2.1 2.2 2.3 2.4 EQUIPMENT General Light fittings Lamps Control Gear 3. FOCUSING AND COMMISSIONING 4. HAND OVER 5. 5.1 LUMINAIRE ILLUSTRATED SPECIFICATION Lighting Equipment Schedule (Summarised) 6. 6.1 6.2 ARCHITECTURAL LIGHTING CONTROL Lighting Control strategy Circuit Schedule 7. LIST OF SPECIFIED MANUFACTURERS AND SUPPLIERS LIGHTING SPECIFICATION KEY Prefix F - FREESTANDING P - PENDANT/SUSPENDED R - RECESSED S - SURFACE MOUNTED T - TRACK MOUNTED W - WALKOVER G - GEAR EXAMPLE: TYPE - P4e is suspended luminaire wired to central battery KEVAN SHAW LIGHTING DESIGN GENERAL SPECIFICATION 1 General 1.1 The contractor shall be responsible for the correct supply, installation, wiring, etc., in conformance with relevant regulations and codes of practice including B.S.7671: 2001, of the lighting equipment described in this specification and lighting drawings and schedules prepared by the electrical engineer. The specification is only concerned with the specific requirements of the client and is not intended to, or should be understood to free the contractor from statutory obligations with regard to electrical wiring and safety or any relevant British Standards, legislation, or code of practice. 1.2 The contractor shall ensure that the work is completed in a timely and satisfactory manner and appropriately coordinated with other trades working on the site. 1.3 The contractor shall ensure that the site is left in a clean and tidy state and shall dispose of all waste as laid down in “Environmental Policy” and shall retain copies of all waste transfer notes for inspection by the client’s site agents. 1.4 The contractor shall ensure work is carried out in a safe manner and shall be responsible for ensuring conformance with H. & S.E. guidelines and conform to requirements of C.O.S.H.E. regulations. 2 Equipment 2.1 General 2.1.1 Equipment shall be as described in the illustrated schedule attached. The contractor shall obtain all equipment as specified from the indicated manufacturer. The contractor shall ascertain lead times from suppliers for equipment as specified and shall ensure all orders are placed in time to allow for any delays in supply that may occur. 2.1.2 The contractor shall be responsible for any direct or consequential costs of delays in sourcing of equipment. The contractor shall inform the construction manager immediately if there is likely to be any late delivery of equipment that may cause any delay to the contract. 2.1.3 The contractor shall ensure that equipment as supplied conforms to relevant British Standards, requirements of licensing authorities and can be installed in accordance with B.S. 7671:2001 and any other relevant standards, legislation and approval . All fittings shall be C.E. Marked and Certificates of Conformity shall be provided. 2.2 Light Fittings 2.2.1The fittings shall be as defined in the attached schedule. 2.2.2 The contractor shall provide a working sample of each light fitting type for final approval prior to placing an order. Fittings shall be functionally checked for operation throughout the entire control range. Each sample shall be tested locally by the Lighting Control System Supplier to ensure correct operation with the Lighting Control System. Each sample shall be tagged and signed by the Lighting consultant, architect and project manager on acceptance and retained safely stored on site as a control sample until the completion and hand over of the project. Any fittings subsequently supplied that are judged by the design team not to match the approved control sample for quality of construction, operation or finish shall be rejected. 2.2.3 Fittings shall be installed according to the manufacturers instructions supplied and in accordance with details and instructions in the drawings and specifications, relevant codes of practice and legislation in force at the time of installation. 2.2.4 Fittings shall be handled with care to protect their finishes. The contractor shall be responsible for safe storage of fittings prior to erection and shall replace any fitting or part thereof damaged in handling or installation. 2.2.5 The contractor shall ensure that fittings and lamps are protected from contamination by dust, fumes, moisture or any other hazard common to building sites. Should contamination occur, fittings shall be cleaned carefully in accordance with manufacturers instructions. Care must be taken not to damage reflectors and lenses during cleaning, as this seriously degrades the performance of the fitting. 2.2.6 The contractor shall ensure that forming openings, installation of fittings, final finishes etc. are programmed so that none of these operations causes damage to works already complete and that paint plaster etc. cannot contaminate the finishes of fittings. 2.2.7 The contractor shall ensure that any fixings taken are suitable for the intended design load. The contractor shall confirm suitability of locations of fixings and imposed loads with the architect or structural engineer. Fixings for lighting track, suspensions, cantilevers, brackets etc. shall be dead weight tested to 2 times their maximum rated load prior to erection of track or fittings 2.3 Lamps 2.3.1 Low voltage reflector lamps shall be supplied with a glass front providing protection against non-passive failure of the capsule and to reduce the emission of UV rays to a negligible level. The lamps shall be precisely as specified in the attached schedules and specification. Please note exact specification of lamp type and rating to ensure that correct fitting performance is obtained and that the lamp is suitable for the fitting in which it is installed. Any lamps that do not conform to this specification will be rejected 2.3.2 Low Voltage capsule lamps shall be precisely as specified in the attached schedules and specification and shall conform to the type specification as indicated with regard to construction, light output and operating life. Any lamps that do not conform to this specification will be rejected. 2.3.3 Mains voltage and discharge lamps shall be precisely as specified in the attached schedules and specification. All lamps shall be rated suitably and intended for use in the UK. Lamps sourced internationally may be incorrectly rated and will not achieve correct operating life. 2.3.4 Fluorescent lamps are to be precisely as specified in the attached schedules and specification. Where a manufacturer, colour or tube type are shown in the specification these are to be supplied exactly, substitution is not acceptable without prior written instruction. Any lamps that do not conform to this specification will be rejected. 2.3.5 Cold Cathode lamps shall be manufactured and installed by an approved supplier. The supplier shall provide operating samples of tube to determine colour and surface illuminance for approval by the construction manager prior to manufacture. 2.3.6 The contractor shall ensure that all lamps installed at hand over meet the manufacturer’s published performance criteria for light output, colour rendition and photometric performance. Noticeable variations in colour output between lamps will not be accepted neither will noticeable variation of light output from similar lamps. 2.3.7 The contractor shall be responsible for replacement of all lamps judged to have failed prematurely according to the manufacturer’s stated life of that lamp, as timed from date of hand over. 2.4 Control Gear 2.4.1 Control gear including low voltage transformers is to be supplied as indicated in the drawings and schedules. 2.4.2. Where there is any discrepancy in part number, rating or performance due to manufacturers change of design, part numbers, advised substitution or error the construction manager and client’s consultant are to be informed immediately and prior to the contractor placing the order for such equipment. 2.4.3 Where any piece of lighting control gear has a tapping or adjustment for mains input voltage the contractor is to measure the voltage at the fitting at time of switch on and ensure the connections are made according to the measured voltage. Where fittings are installed and made operational prior to the full building load being applied to the substation the contractor shall re-measure and re-tap the control gear as necessary when the full load has been applied to the substation and subsequent to the final voltage settings being made at the substation. 3 Focusing and Commissioning 3.1 The client’s lighting consultant will require to supervise focusing of all adjustable light fittings. The contractor will advise the client’s consultant of suitable times The contractor shall allow not less than 21 days, not necessarily continuous or sequential, attendance in respect of this requirement. It shall be noted that a considerable amount of time will be required out with normal working hours and at weekends to accommodate focussing and adjustment during hours of darkness and at times when switching lighting on and off shall not inconvenience or compromise safety of other contractors working on the site. Some final adjustments may be required subsequent to client occupation of the building. 3.2 The contractor shall provide sufficient access and safety equipment for focusing of fittings at high level. The contractor shall ensure the full, exclusive and unhindered use of any such equipment for the entirety of any focusing session by the consultant and shall ensure that suitably trained and certificated operatives are present for the duration of the use of such equipment within their normal allowance of working hours. 3.3 The contractor shall ensure that all fittings to be focused in any session shall be fully working and correctly lamped prior to the commencement of the focusing session. 3.4 The contractor shall supply at least two competent electricians one of which must be the foreman or charge hand for the installation and fully familiar with the layout of wiring and switching and control system, as installed , for the period of any focusing or commissioning session. 3.5 The contractor shall make all reasonable facilities available to any supplier of light fittings for inspection, commissioning, installation or remedial work required on site. 4 Hand Over 4.1 The contractor shall ensure all light fittings, reflectors and lamps have been cleaned and are all operating correctly in accordance with drawings, focus instructions, site instructions etc. 4.2 The contractor shall hand over to the client any unused or surplus fittings and control gear, in a clean and reusable condition preferably in their original packing, otherwise adequately packed for storage. KSLD 5. LUMINAIRE ILLUSTRATED SPECIFICATION kevan shaw lighting design 4 baltic street, edinburgh, eh6 7bw, scotland phone: +44(0) 131 555 5553 fax: +44(0) 131 555 5559 email:office@kevan-shaw.com Illustrated Specification KUWAIT TRADE CENTER KSLD Schedule Reference F01 DESCRIPTION: Free standing indirect pole type luminaire with HIT 70w lamp. Constructed with Mica DB 701finish steel pole, base to be either flange or root mount, exact mounting method to be developed. Light fitting made of natural anodised aluminium with Borosilicate glass lamp cover and aluminium light shade/reflector. Fitting height 3180mm. Integral control gear. LUMINAIRE Manufacturer Hess LAMP Manufacturer Osram Accessories Catalogue No. LPH 2730:12.01111.2730 Catalogue No. HCI-TC 70/WDL Notes Wattage 70W Fitting Dimensions Notes Architect to confirm type of mounting required before ordering. Illustration issue date November PAGE: 8 kevan shaw lighting design 4 baltic street, edinburgh, eh6 7bw, scotland phone: +44(0) 131 555 5553 fax: +44(0) 131 555 5559 email:office@kevan-shaw.com Illustrated Specification KUWAIT TRADE CENTER KSLD Schedule Reference F02 DESCRIPTION: Free standing floor washlinght luminaire with 35w CDM lamp to IP55 protection and integral gear. Fitting constructed from anti-corrosion aluminium with double powder coating and stainless steel lens cover. Optics are to consist of asymmetric silver anodised reflector with anti-glare lamp cap and reeded glass sculpture lens with no direct light emission and a cut off below horizontal. fitting to allow mounting options of root or base plate, Architect to confirm mounting before ordering LUMINAIRE Manufacturer Erco Catalogue No. 33314.006 Notes LAMP Manufacturer Osram Catalogue No. HCI-TC-35/WDL Wattage 35W Accessories Fitting Dimensions Notes Architect to confirm type of mounting required before ordering. Illustration issue date November PAGE: 9 kevan shaw lighting design 4 baltic street, edinburgh, eh6 7bw, scotland phone: +44(0) 131 555 5553 fax: +44(0) 131 555 5559 email:office@kevan-shaw.com Illustrated Specification KUWAIT TRADE CENTER KSLD Schedule Reference R01 DESCRIPTION: Recessed IP65 exterior CDM downlight constructed from cast aluminium with powder coat finish where required. Fitting to have a cast aluminium housing/heat sink for operation of 70w CDM lamp with integral control gear. Fitting to have 40 degree cut-off and frosted glass lamp cover/diffuser. Note ftg type to be confirmed as canopy integration detail is confirmed, lights must not be ordered without architects approval. LUMINAIRE Manufacturer Erco Catalogue No. 81050.006 Notes LAMP Manufacturer Osram Catalogue No. HCI-T70/WDL Wattage 70W Accessories Fitting Dimensions Notes Illustration issue date November PAGE: 10 kevan shaw lighting design 4 baltic street, edinburgh, eh6 7bw, scotland phone: +44(0) 131 555 5553 fax: +44(0) 131 555 5559 email:office@kevan-shaw.com Illustrated Specification KUWAIT TRADE CENTER KSLD Schedule Reference R02 DESCRIPTION: Recessed CDM downlight constructed from cast aluminium with powder coat finish where required. Fitting to have a cast aluminium housing/heat sink for operation of 35w CDM lamp with remote control gear. Fitting to have 40 degree cut-off and frosted glass lamp cover/diffuser. LUMINAIRE Manufacturer Erco Catalogue No. 81636 + 83670 Notes LAMP Manufacturer Osram Catalogue No. HCI-35/WDL Wattage 35W Accessories Fitting Dimensions Remote control gear 83670.006 Notes Illustration issue date November PAGE: 11 kevan shaw lighting design 4 baltic street, edinburgh, eh6 7bw, scotland phone: +44(0) 131 555 5553 fax: +44(0) 131 555 5559 email:office@kevan-shaw.com Illustrated Specification KUWAIT TRADE CENTER KSLD Schedule Reference R03 DESCRIPTION: Recessed fluorescent Washlight for 26w fluorescent lamp. Fitting to have a cast aluminium housing/heat sink for operation of 26w fluorescent lamp with integral electronic control gear. 40 degree cut-off and translucent plastic lamp cover/diffuser. Reflector to have washlight optic. Dimmable gear to be provided. LUMINAIRE Manufacturer Erco Catalogue No. 22277 Notes LAMP Manufacturer Osram Catalogue No. Dulux T/E 26 W/840 Wattage 26W Accessories Fitting Dimensions Dimmable gear Notes Illustration issue date November PAGE: 12 kevan shaw lighting design 4 baltic street, edinburgh, eh6 7bw, scotland phone: +44(0) 131 555 5553 fax: +44(0) 131 555 5559 email:office@kevan-shaw.com Illustrated Specification KUWAIT TRADE CENTER KSLD Schedule Reference R04 DESCRIPTION: Recessed fluorescent Downlight for 26w fluorescent lamp. Fitting to have a cast aluminium housing/ heat sink for operation of 26w fluorescent lamp with integral electronic control gear. 40 degree cut-off and translucent plastic lamp cover/diffuser. Reflector to have beam angle of approx 100 degrees. Dimmable gear to be provided. LUMINAIRE Manufacturer Erco Catalogue No. 22237 Notes LAMP Manufacturer Osram Catalogue No. Dulux T/E 26 W/840 Wattage 26W Accessories Fitting Dimensions Dimmable gear Notes Illustration issue date November PAGE: 13 kevan shaw lighting design 4 baltic street, edinburgh, eh6 7bw, scotland phone: +44(0) 131 555 5553 fax: +44(0) 131 555 5559 email:office@kevan-shaw.com Illustrated Specification KUWAIT TRADE CENTER KSLD Schedule Reference R05 DESCRIPTION: Recessed fluorescent wallwasher. Fitting to be constructed with BLACK steel powder coated housing with white powder coated cast aluminium mounting ring. Darklight plastic reflector with vapourised mirror finish aluminium giving wallwash photometrics and 40 degree cut off away from wall side. Integral dimmable electronic control gear and 2x26w compact fluorescent lamps. LUMINAIRE Manufacturer Erco Catalogue No. 82512 Notes LAMP Manufacturer Osram Catalogue No. 2 x DULUX D/E 26W/840 Wattage 26W Accessories Fitting Dimensions Notes Illustration issue date November PAGE: 14 kevan shaw lighting design 4 baltic street, edinburgh, eh6 7bw, scotland phone: +44(0) 131 555 5553 fax: +44(0) 131 555 5559 email:office@kevan-shaw.com Illustrated Specification KUWAIT TRADE CENTER KSLD Schedule Reference R06 DESCRIPTION: Recessed wall mounted IP65 low voltage tungsten floorwash luminaire Fitting constructed from anticorrosion aluminium with double powder coating and stainless steel lens cover. Optics are to consist of asymmetric silver anodised reflector with anti-glare lamp cap and reeded glass sculpture lens with no direct light emission and a cut off below horizontal. Integral transformer. LUMINAIRE Manufacturer Erco Catalogue No. 33300.000 Notes LAMP Manufacturer Osram Catalogue No. 464405S Wattage 20W Accessories Fitting Dimensions Mounting accessories as required to manufacturers recommendations Notes Illustration issue date November PAGE: 15 kevan shaw lighting design 4 baltic street, edinburgh, eh6 7bw, scotland phone: +44(0) 131 555 5553 fax: +44(0) 131 555 5559 email:office@kevan-shaw.com Illustrated Specification KUWAIT TRADE CENTER KSLD Schedule Reference R07 DESCRIPTION: Recessed low voltage underwater pool light to safety class 3 and IP68. constructed from Stainless steel to take PAR 56 lamp. 3m of HO7RN-F waterproof cable to be provided, remote 300vA transformer required. LUMINAIRE Manufacturer Bega Catalogue No. 9912 + 484 Notes LAMP Manufacturer Osram(Europe) Catalogue No. Halopar 56 12V WFL Wattage 300W Accessories Fitting Dimensions Pool specialsit to confirm mounting requirements before ordering. Notes Remote transformer ref. 484 Illustration issue date November PAGE: 16 kevan shaw lighting design 4 baltic street, edinburgh, eh6 7bw, scotland phone: +44(0) 131 555 5553 fax: +44(0) 131 555 5559 email:office@kevan-shaw.com Illustrated Specification KUWAIT TRADE CENTER KSLD Schedule Reference R08 DESCRIPTION: Recessed low voltage directional downlight to allow 0-30 degree tilt, 360degree rotation. fitting constructed from cast aluminium for lamp holder/heat sink, white plastic mounting ring and vapourised aluminium/plastic reflector with cut off angle of 30 degrees. Remote transformer to be provided LUMINAIRE Manufacturer Erco Catalogue No. 22407 + 83831.006 Notes LAMP Manufacturer Osram Catalogue No. 48865F Wattage 35W Accessories Fitting Dimensions Trailing edge transformer Mode ET105-Puma Notes Illustration issue date November PAGE: 17 kevan shaw lighting design 4 baltic street, edinburgh, eh6 7bw, scotland phone: +44(0) 131 555 5553 fax: +44(0) 131 555 5559 email:office@kevan-shaw.com Illustrated Specification KUWAIT TRADE CENTER KSLD Schedule Reference R09 DESCRIPTION: Recessed CDM downlight constructed from cast aluminium with powder coat finish where required. Fitting to have a cast aluminium housing/heat sink for operation of 70w CDM lamp with remote control gear. Fitting to have 50 degree cut-off and frosted glass lamp cover/diffuser. Mounting ring to be provided to allow top relamping. LUMINAIRE Manufacturer Erco Catalogue No. 81641(70) + 83671 Notes LAMP Manufacturer Osram Catalogue No. HCI-70/WDL Wattage 70W Accessories Fitting Dimensions Remote control gear 83671 Notes Mounting ring for top relamping 83958 Illustration issue date November PAGE: 18 kevan shaw lighting design 4 baltic street, edinburgh, eh6 7bw, scotland phone: +44(0) 131 555 5553 fax: +44(0) 131 555 5559 email:office@kevan-shaw.com Illustrated Specification KUWAIT TRADE CENTER KSLD Schedule Reference R10 DESCRIPTION: Recessed miniture LED downlight with 1w cool white LUXEON LED. Fitting constructed from machined natural aluminium. Remote control gear to be provided to allow operation of multiple fittings. Note gear to go in ceiling void, access to gear through ceiling void. Cut-out=mm Overall dimaeter=38mm LUMINAIRE Manufacturer Mike Stoane Lighting LAMP Manufacturer Lumilux Accessories Remote control gear per 10 ftgs, Philips Xitanium 9137-05-18806 Catalogue No. E1581.star + E1581 power supply Notes Catalogue No. Wattage 1W Fitting Dimensions Diameter 38mm Cut-out 32mm Recess depth 40mm Notes Illustration issue date November PAGE: 19 kevan shaw lighting design 4 baltic street, edinburgh, eh6 7bw, scotland phone: +44(0) 131 555 5553 fax: +44(0) 131 555 5559 email:office@kevan-shaw.com Illustrated Specification KUWAIT TRADE CENTER KSLD Schedule Reference R11 DESCRIPTION: Recessed low voltage downlight. Fitting constructed from cast aluminium for lamp holder/heat sink, white plastic mounting ring and vapourised aluminium/plastic reflector with cut off angle of 30 degrees. Remote transformer to be provided LUMINAIRE Manufacturer Erco Catalogue No. 22405 + transformer Notes LAMP Manufacturer Osram Catalogue No. 48865SP Wattage 35W Accessories Fitting Dimensions Trailing edge transformer Mode ET105-Puma Notes Illustration issue date November PAGE: 20 kevan shaw lighting design 4 baltic street, edinburgh, eh6 7bw, scotland phone: +44(0) 131 555 5553 fax: +44(0) 131 555 5559 email:office@kevan-shaw.com Illustrated Specification KUWAIT TRADE CENTER KSLD Schedule Reference R12 DESCRIPTION: Recessed directional downlight . Fitting constructed from machined aluminium with 360 pan and 45 degree tilt with mechanical locking mechinism. Fitting to take louvres and lenses as required. Remote control gear required as recommended by manufacturer. LUMINAIRE Manufacturer Mike Stoane Lighting Catalogue No. ADL.CDMR111 Notes LAMP Manufacturer Philips Catalogue No. CDMR111, 10 degrees Wattage 35W Accessories Fitting Dimensions Remote control gear as recommended by manufacturer Notes Illustration issue date November PAGE: 21 kevan shaw lighting design 4 baltic street, edinburgh, eh6 7bw, scotland phone: +44(0) 131 555 5553 fax: +44(0) 131 555 5559 email:office@kevan-shaw.com Illustrated Specification KUWAIT TRADE CENTER KSLD Schedule Reference R13 DESCRIPTION: Recessed low voltage downlight to allow. Fitting constructed from cast aluminium for lamp holder/heat sink, white plastic mounting ring and vapourised aluminium/plastic reflector with cut off angle of 30 degrees. Remote transformer to be provided LUMINAIRE Manufacturer Erco Catalogue No. 22405 + transformer Notes LAMP Manufacturer Osram Catalogue No. 48870FL Wattage 50W Accessories Fitting Dimensions Trailing edge transformer Mode ET105-Puma Notes Illustration issue date November PAGE: 22 kevan shaw lighting design 4 baltic street, edinburgh, eh6 7bw, scotland phone: +44(0) 131 555 5553 fax: +44(0) 131 555 5559 email:office@kevan-shaw.com Illustrated Specification KUWAIT TRADE CENTER KSLD Schedule Reference R14 DESCRIPTION: Recessed CDM downlight constructed from cast aluminium for housing with powder coat finish cast aluminium mounting ring to allow mechanical screw fixing Fitting to have a cast aluminium housing/heat sink for operation of 70w CDM lamp with remote control gear and 500mm connecting cable. Fitting to have 40 degree cut-off and frosted glass lamp cover/diffuser. Relector to be bright anodised aluminium. LUMINAIRE Manufacturer Erco Catalogue No. 22680 + 83671 Notes LAMP Manufacturer Osram Catalogue No. HCI-T 70/WDL Wattage 70W Accessories Fitting Dimensions Remote control gear 83671 Notes Illustration issue date November PAGE: 23 kevan shaw lighting design 4 baltic street, edinburgh, eh6 7bw, scotland phone: +44(0) 131 555 5553 fax: +44(0) 131 555 5559 email:office@kevan-shaw.com Illustrated Specification KUWAIT TRADE CENTER KSLD Schedule Reference R15 DESCRIPTION: Recessed Tungsten Halogen low voltage downlight constructed with a cast aluminium housing/heatsink withRAL 9002 powder coat finish cast aluminium mounting ring to allow mechanical screw fixing Fitting to have a cast aluminium housing/heat sink for operation of 90w LVTH capsule lamp with remote transformer and 500mm connecting cable. Fitting to have 40 degree cut-off and frosted glass lamp cover/diffuser. Relector to be bright anodised aluminium. LUMINAIRE Manufacturer Erco Catalogue No. 22453 Notes LAMP Manufacturer Osram Catalogue No. 64458S Wattage 90W Accessories Fitting Dimensions Trailing edge transformer Mode ET105-Puma Notes Illustration issue date November PAGE: 24 kevan shaw lighting design 4 baltic street, edinburgh, eh6 7bw, scotland phone: +44(0) 131 555 5553 fax: +44(0) 131 555 5559 email:office@kevan-shaw.com Illustrated Specification KUWAIT TRADE CENTER KSLD Schedule Reference S01 DESCRIPTION: Surface mounted IP68 flexible linear xenon lighting. Fitting constructed from Polycarbonate with miniture Xenon lamps. Sectional size of fitting 12.8mm diameter, length as required from site measurments, with transformers as recommended by manufacturer. Lamp type to be 28v 40mA at with minimium of 25,000hr lamp life, transformer to supply 24v maximium. Lamp spacing to be 50mm. Fitting comes with 1 no. C128 tube clip per 500mm. LUMINAIRE Manufacturer Lightgraphix Catalogue No. Light tube LT12 + C128+ transformers Notes LAMP Manufacturer Catalogue No. Wattage Accessories Fitting Dimensions Remote transformer as supplied by manufacturer Notes Plastic surface mounting brackets as required to be provided Illustration issue date November Note dimensions show overall size of fitting with clear plastic mounting clip C128. PAGE: 25 kevan shaw lighting design 4 baltic street, edinburgh, eh6 7bw, scotland phone: +44(0) 131 555 5553 fax: +44(0) 131 555 5559 email:office@kevan-shaw.com Illustrated Specification KUWAIT TRADE CENTER KSLD Schedule Reference S02 DESCRIPTION: Surface mounted low voltage robotically manufacturered Cold Cathode to total length as shown on drawings, (Note exact length must be determined from site measurements). C/w remote control gear to allow dimming between 5% and 100% using 1-10Volt signal. LUMINAIRE Manufacturer AC/DC lighting Catalogue No. low voltage cold cathode, warm white LAMP Manufacturer Catalogue No. Masonlite no. 3 warm white 3000k tri-phosphor Accessories Notes Wattage Fitting Dimensions High frequency control gear to allow dimming between 5% and 100% Notes Illustration issue date November PAGE: 26 kevan shaw lighting design 4 baltic street, edinburgh, eh6 7bw, scotland phone: +44(0) 131 555 5553 fax: +44(0) 131 555 5559 email:office@kevan-shaw.com Illustrated Specification KUWAIT TRADE CENTER KSLD Schedule Reference S03 DESCRIPTION: Surface mounted 3 x 60lum. White LED adjustable fitting with surface mounting stirrup. Remote control gear is required to allow operation of up 8 no. fittings at 30m distance. Constructed from Silver anodised aluminium to IP67 protection. Note, cable length to be 4m. LUMINAIRE Manufacturer AC/DC lighting LAMP Manufacturer Luxeon Accessories Catalogue No. Artemis + ACDC1903 Notes Catalogue No. Wattage 3 x 1w Fitting Dimensions Control gear for up to 8 ftgs, ACDC 1903, 1 no. control gear per 6 ftgs to be provided Notes Illustration issue date November PAGE: 27 Illustrated Specification kevan shaw lighting design KUWAIT TRADE CENTER 4 baltic street, edinburgh, eh6 7bw, scotland phone: +44(0) 131 555 5553 fax: +44(0) 131 555 5559 email:office@kevan-shaw.com KSLD Schedule Reference S04 DESCRIPTION: Surface mounted IP65 exterior grade colour changing luminaire constructed from Extruded and machined Aluminium with natural colour anodising. Integral DMX controlled gear and colour changing unit using no more than 6 DMX channels with dimming mechanism. 36 degree fresnel lens. Unit designed to EN50081/2-1 and US ANSI/UL 1573. LUMINAIRE Manufacturer Martin Catalogue No. Notes Exterior 200 90509000+91610022 fresnel lens LAMP Manufacturer Osram Catalogue No. HQI-T 150/NDL UVS Accessories Wattage 150w Fitting Dimensions C/W mounting stirrup and Fresnel lens to allow 36 degree beam angle. Notes Illustration WeightLengthwidthHeight- issue date November 15kg 301mm 306mm 422mm PAGE: 28 kevan shaw lighting design 4 baltic street, edinburgh, eh6 7bw, scotland phone: +44(0) 131 555 5553 fax: +44(0) 131 555 5559 email:office@kevan-shaw.com Illustrated Specification KUWAIT TRADE CENTER KSLD Schedule Reference S05 DESCRIPTION: Surface mounted three colour cold cathode colour changing unit mounted onto aluminium channel suitable for surface mounting. DMX or 1-10V control interface. Ftg length and configuration to be developed. Note length must be confirmed before ordering. C/w control gear as recommended by manufacturer. LUMINAIRE Manufacturer ACDC LAMP Manufacturer Masonlite Accessories Catalogue No. Colourise Notes Catalogue No. Wattage Fitting Dimensions Control gear as required to manufacturers recommenrdation Notes Illustration issue date November PAGE: 29 kevan shaw lighting design 4 baltic street, edinburgh, eh6 7bw, scotland phone: +44(0) 131 555 5553 fax: +44(0) 131 555 5559 email:office@kevan-shaw.com Illustrated Specification KUWAIT TRADE CENTER KSLD Schedule Reference S06 DESCRIPTION: Surface mounted linear colour changing LED luminaire. Constructed from silver powder coated extruded aluminium and stainless steel with clear cover. Nominal Length of unit 1200mm, remote control gear required for each unit. colour changing by DMX control. LUMINAIRE Manufacturer ACDC LAMP Manufacturer Luxeon Accessories Catalogue No. Lucinda Notes Catalogue No. Wattage 1w Fitting Dimensions Remote control gear ACDC1906 Notes Illustration issue date November PAGE: 30 kevan shaw lighting design 4 baltic street, edinburgh, eh6 7bw, scotland phone: +44(0) 131 555 5553 fax: +44(0) 131 555 5559 email:office@kevan-shaw.com Illustrated Specification KUWAIT TRADE CENTER KSLD Schedule Reference S07 DESCRIPTION: Weather resisitant Umbrela light, rechargable battery powered LED for 8 rib umbrella, total 64 lamps. Batteries and changer as optional extras. 30,000hr life expectancy. Cool white light, non insect attracting, c/w pole adaptor LUMINAIRE Manufacturer Dayva International Catalogue No. Night Lights LED Notes LAMP Manufacturer Catalogue No. Wattage Accessories Fitting Dimensions batteries and charger Notes Illustration issue date November PAGE: 31 kevan shaw lighting design 4 baltic street, edinburgh, eh6 7bw, scotland phone: +44(0) 131 555 5553 fax: +44(0) 131 555 5559 email:office@kevan-shaw.com Illustrated Specification KUWAIT TRADE CENTER KSLD Schedule Reference S08 DESCRIPTION: Surface mounted low voltage robotically manufacturered Cold Cathode to total length as shown on drawings, (Note exact length must be determined from site measurements). C/w remote control gear to allow dimming between 5% and 100% using 1-10Volt signal. LUMINAIRE Manufacturer AC/DC lighting Catalogue No. low voltage cold cathode, cool white LAMP Manufacturer Catalogue No. Masonlite no. 7 snow white 6500k tri-phosphor Accessories Notes Wattage Fitting Dimensions High frequency control gear to allow dimming between 5% and 100% Notes Illustration issue date November PAGE: 32 kevan shaw lighting design 4 baltic street, edinburgh, eh6 7bw, scotland phone: +44(0) 131 555 5553 fax: +44(0) 131 555 5559 email:office@kevan-shaw.com Illustrated Specification KUWAIT TRADE CENTER KSLD Schedule Reference T01 DESCRIPTION: Surface mounted 3 cct track to take fittings with Erco track adaptors. Length as required from site measurement. Construction of extruded aluminium, c/w live ends and dead ends as required. fixing to be as per manufacturers recommendation LUMINAIRE Manufacturer Erco Catalogue No. as required Notes LAMP Manufacturer Catalogue No. Wattage Accessories Fitting Dimensions Live ends, dead ends and connecting pieces as required Notes Illustration issue date November PAGE: 33 kevan shaw lighting design 4 baltic street, edinburgh, eh6 7bw, scotland phone: +44(0) 131 555 5553 fax: +44(0) 131 555 5559 email:office@kevan-shaw.com Illustrated Specification KUWAIT TRADE CENTER KSLD Schedule Reference T02 DESCRIPTION: Track mounted adjustable fitting with spread lens to fit Erco track. Constructed from natural brushed alumimium with plastic components and lampholder. Integral transformer, fitting to be fully lockable. LUMINAIRE Manufacturer Mike Stoane LIghting Catalogue No. MRX.MR16 Notes LAMP Manufacturer Osram Catalogue No. 48870SP Wattage 50W Accessories Fitting Dimensions Notes Illustration issue date November PAGE: 34 kevan shaw lighting design 4 baltic street, edinburgh, eh6 7bw, scotland phone: +44(0) 131 555 5553 fax: +44(0) 131 555 5559 email:office@kevan-shaw.com Illustrated Specification KUWAIT TRADE CENTER KSLD Schedule Reference T03 DESCRIPTION: Track mounted adjustable fitting with spread lens to fit Erco track. Constructed from natural brushed alumimium with plastic components and lampholder. Integral control gear, fitting to be fully lockable. LUMINAIRE Manufacturer Mike Stoane LIghting Catalogue No. MRX.BGT Notes LAMP Manufacturer Philps Catalogue No. CDMR111 35w 10 degree Wattage 35W Accessories Fitting Dimensions Notes Illustration issue date November PAGE: 35 kevan shaw lighting design 4 baltic street, edinburgh, eh6 7bw, scotland phone: +44(0) 131 555 5553 fax: +44(0) 131 555 5559 email:office@kevan-shaw.com Illustrated Specification KUWAIT TRADE CENTER KSLD Schedule ReferenceUW01A DESCRIPTION: Surface mounted IP68 linear colour changing LED luminaire. Constructed from T6050 grade aluminium or similiar non corrosive metal suitable for use in clorinated fountains. Fitting to have a cluster of 3 no. liquid lensed Luxeon RBG LEDs per 100mm, fitting to be IP68 to be encapsulated to prevent ingress of liquids up to 2m below water. Control by DMX, control unit to be able to mount 50m from fitting. All Luxeon LED's to be Bin matched for stability and colour intensity. Standard length of fitting to be 600mm length as required. LUMINAIRE Manufacturer Optino LAMP Manufacturer Luxeon Accessories Catalogue No. OPT-1053-A Notes Catalogue No. Wattage 1w Fitting Dimensions Remote control gear to allow DMX RGB control Notes Illustration issue date November PAGE: 36 kevan shaw lighting design 4 baltic street, edinburgh, eh6 7bw, scotland phone: +44(0) 131 555 5553 fax: +44(0) 131 555 5559 email:office@kevan-shaw.com Illustrated Specification KUWAIT TRADE CENTER KSLD Schedule ReferenceUW01B DESCRIPTION: Surface mounted IP68 linear colour changing LED luminaire. Constructed from T6050 grade aluminium or similiar non corrosive metal suitable for use in clorinated fountains. Fitting to have a cluster of 3 no. liquid lensed Luxeon RBG LEDs per 100mm, fitting to be IP68 to be encapsulated to prevent ingress of liquids up to 2m below water. Control by DMX, control unit to be able to mount 50m from fitting. All Luxeon LED's to be Bin matched for stability and colour intensity. Standard length of fitting to be 1200mm. LUMINAIRE Manufacturer Optino LAMP Manufacturer Luxeon Accessories Catalogue No. OPT-1053-A Notes Catalogue No. Wattage 1w Fitting Dimensions Remote control gear to allow DMX RGB control Notes Illustration issue date November PAGE: 37 kevan shaw lighting design 4 baltic street, edinburgh, eh6 7bw, scotland phone: +44(0) 131 555 5553 fax: +44(0) 131 555 5559 email:office@kevan-shaw.com Illustrated Specification KUWAIT TRADE CENTER KSLD Schedule Reference UW02 DESCRIPTION: Surface mounted IP68 underwater luminaire. Constructed from stainless steel with remote transformer. Note standard cable length 4m, longer can be supplied on request. Remote transformer required, exact confirguration of control gear to be confirmed LUMINAIRE Manufacturer Bega Catalogue No. 8509 Notes LAMP Manufacturer GE Catalogue No. 35PAR36/VNSP/H Wattage 35W Accessories Fitting Dimensions Remote transformer to manufacturers recommendation. Notes Cable length to be confirmed with engineer and water specialist Illustration issue date November PAGE: 38 kevan shaw lighting design 4 baltic street, edinburgh, eh6 7bw, scotland phone: +44(0) 131 555 5553 fax: +44(0) 131 555 5559 email:office@kevan-shaw.com Illustrated Specification KUWAIT TRADE CENTER KSLD Schedule Reference W01 DESCRIPTION: Recessed inground drive over IP68 adjustable uplight constructed from corrosion resistant cast aluminium, black double powder coated. Directional reflector and anti-dazzle cylinder with 40 degree cut-off to take 70w CDM lamp and integral control gear. LUMINAIRE Manufacturer Erco Catalogue No. 33726 Notes LAMP Manufacturer Osram Catalogue No. HCI-T 70/WDL Wattage 70W Accessories Fitting Dimensions Notes Illustration issue date November PAGE: 39 kevan shaw lighting design 4 baltic street, edinburgh, eh6 7bw, scotland phone: +44(0) 131 555 5553 fax: +44(0) 131 555 5559 email:office@kevan-shaw.com Illustrated Specification KUWAIT TRADE CENTER KSLD Schedule Reference W02 DESCRIPTION: Recessed blue linear luminaire to IP68 protection. Constructed from extruded aluminium with encapsulated LED unit with blue LED's and polycarbonate cover. Remote gear required at location to be confirmed. Load resistence to be 60J minimium, suitable for light vehicular traffic and pedestrian use. LUMINAIRE Manufacturer LEC LAMP Manufacturer na Accessories Catalogue No. Brunei, 5620 + control gear Notes Catalogue No. Wattage Fitting Dimensions Remote control gear Notes Cable length to be confirmed Illustration issue date November PAGE: 40 kevan shaw lighting design 4 baltic street, edinburgh, eh6 7bw, scotland phone: +44(0) 131 555 5553 fax: +44(0) 131 555 5559 email:office@kevan-shaw.com Illustrated Specification KUWAIT TRADE CENTER KSLD Schedule Reference W03 DESCRIPTION: Recessed inground drive over IP68 adjustable uplight constructed from corrosion resistant cast aluminium, black double powder coated. Directional reflector and anti-dazzle cylinder with 40 degree cut-off to take 35w CDM lamp and integral control gear. LUMINAIRE Manufacturer Erco Catalogue No. 33718 Notes LAMP Manufacturer Osram Catalogue No. HCI-T 35/WDL Wattage 35w Accessories Fitting Dimensions Notes Illustration issue date November PAGE: 41 kevan shaw lighting design 4 baltic street, edinburgh, eh6 7bw, scotland phone: +44(0) 131 555 5553 fax: +44(0) 131 555 5559 email:office@kevan-shaw.com Illustrated Specification KUWAIT TRADE CENTER KSLD Schedule Reference WU01 DESCRIPTION: Surface mounted Anemometer wind sensor utilising ultrsonic sensors. Sensor to come with 1.6m mast and RS232 cable suitable for PC serial port RS232, note extension cable may be required from converter(not supplied) to PC. Anemometer to allow for low start up speed(0.01 m/s) and 0-360 degree operation. 9v DC power imput required. LUMINAIRE Manufacturer Richard Paul Russell ltd LAMP Manufacturer na Accessories Catalogue No. System1 Notes Catalogue No. Wattage Fitting Dimensions 9v DC power to anemometer required Notes Illustration issue date November PAGE: 42 5.1 LIGHTING EQUIPMENT SCHEDULE (SUMMARISED) 6. ARCHITECTURAL LIGHTING CONTROL 6.1 Kuwait Trade Centre : Lighting Control Show Descriptions 1 System Description: The system shall be supplied as defined in the detailed performance specification. 2 Show overview: 2.1 The lighting control system shall allow for programmable and variable lighting effects. This document provides a description of the initial shows required but shall not be construed as to limit the system capability to providing these shows only. 2.2 The daily show sequence will commence at a time determined by an astronomical time clock integral with the system, typically this will be 30 minutes before sunset. Shows will stop at an absolute time determined by the time clock, typically 01.00 hours. Thereafter an overnight static scene will be set that will be switched off at a time relative to sunrise, typically 30 minutes after sunrise. This setting will prevent operation of heat sensitive lighting components throughout the daylight hours. 2.3 Event shows shall be required to be initiated by time clock and calendar and by manual operation. These will similarly be limited to operating in the hours of darkness only. These shows will be variable year on year by selection of preprogrammed shows or by providing new programmes as and when required. 3 Daily Show: 3.1 The daily show will be initiated by time clock events and will consist of a sunset show, an evening show an overnight scene and a sunrise show. 3.2 The sunset show will typically consist of a white scene that fades up over 5 minutes at a given time then a subsequent fade of 20 minutes to a blue scene including set up of interior night scenes and water feature effects chases 3.3 The evening show shall consist of between 25 and 50 scenes that consecutively change colour floor by floor. These scenes shall be selected according to inputs from a roof mounted ultrasonic anemometer to indicate, by the number of floors in each colour the measured wind speed. The system shall be programmed with at least four alternate patterns that may be selected manually or by wind direction information from the anemometer. 3.4 Typically the anemometer shall provide an RS232 output as an ASCII string that shall include comma separated variables including the wind speed and the wind direction. Wind speed data will be used to select specific scenes, wind direction data may be used to determine the groups of scenes selected by the wind speed data. 3.5 Typically the scenes shall have a fade time of 3 to 5 seconds and a wait time of 5 to 10 seconds, these values will be finally determined during set up of the system. Scene selection shall be initiated by the last data received from the anemometer at the completion of the previous scene wait time. 3.6 Response to wind speed shall be non linear. Typically from 0m/s to 12m/s scenes are selected each 1m/s change in wind speed. Thereafter scenes shall be selected at 14m/s, 16m/s, 18m/s, 20m/s, 23m/s, 26m/s, 30m/s, 34m/s, 38m/s, 44m/s, 50m/s 58m/s, >66m/s . These values are based on average ground level data and shall be able to be reset as required based on actual performance of the anemometer on the building. Further information as to actual wind speeds shall be available in the course of construction. Final settings shall be determined during on site set up. 3.7 The overnight scene shall consist of all floors in a single colour. This scene shall be selected at a determined time that may be altered as required. At sunrise the show shall be the exact inverse of the sunset show. 4 Event Shows: 4.1 Event shows shall include sequences of colour change on tower and atrium lighting elements. These shall be sequences of 100 cues that loop and repeat or may alternitavely be similarly sized chase sequences. Chase patterns be established with the possibility of varying colours in the cue sequence on the fly using a separate sequence to determine order and change of the colours. Speed and timing of sequences shall be variable. It shall be possible to use input from the anemometer to determine speed and colour selection in the sequences from either wind speed or direction information. 4.2 Event shows shall typically replace the daily shows on given calendar days and by manual selection either on the day the effect is required or to interrupt and replace the daily show running. 5 Housekeeping Shows: 5.1 Housekeeping scenes and shows shall be provided for fault finding. These scenes shall be manually selected and password protected. 5.1 All Red, All Green and All Blue scenes shall be required. A red green blue chase of 1 second fade and 3 second with per scene shall be required. An All On scene shall be required. 5.2 Test scenes or other outputs shall be required to confirm the anemometer is functioning and is being correctly interpreted by the system for wind speed and direction. 6 Programming: 6.1 The system supplier shall provide all system elements and shall confirm compatibility and operation by off site tests and mock ups prior to shipping equipment to site 6.2 The system supplier shall work with the Lighting designer to prepare agreed formats for “story boards” covering daily shows and initial event shows. These shows shall be off-site programmed as will initial settings for other presets, effects and scenes as required. 6.3 On site programming will include initial system set up and testing, loading and testing of off-site programming. The programmer shall work with the lighting designer to fine tune shows to the satisfaction of the client’s representative. Kevan Shaw 9-12-04 6.2 CIRCUIT SCHEDULE 6.2 SCHEMATIC DMX CONTROL DIAGRAM 7. LIST OF SPECIFIED MANUFACTURERS AND SUPPLIERS