Drawings for Sewer and Water

advertisement
STANDARD CONTRACT DOCUMENTS
FOR MUNICIPAL CONSTRUCTION
PROJECTS
SUPPLEMENTAL STANDARDS FOR SEWER
AND WATER
2014 EDITION
STANDARD DRAWINGS FOR SEWER AND WATER
Volume 3 of the Ontario Provincial Standard Drawings (OPSD), and the current City of London Standard
Drawings, are amended as follows:
SUPERSEDED/DELETED
(REMOVE)
OPSD
CITY OF
LONDON
AMENDED/NEW/CURRENT
(INSERT)
TITLE OF
DRAWING
DATED
CITY OF
LONDON
TITLE OF
DRAWING
DATED
-
SW-1
2000-02-29
Bedding Standard For
Gravity And Pressure
Pipe
SW-1.0
2013-08-15
Bedding Standard For Gravity
And Pressure Pipe
-
-
-
-
SW-1.1
1996-03-15
Concrete Bedding For Rigid
Pipe
1003.01
-
1988-12-01
Manhole Drop
Structure - Tee
-
-
-
1003.02
-
1988-12-01
Manhole Drop
Structure Wye
-
-
-
-
SW-2.0
1998-03-01
Manhole Drop
Structure - Wye
SW-2.0
2004-11-01
Maintenance Drop Structure
Wye
SW-2.5
1999-01-30
Safety Platform Aluminium
-
SW-3.0
2000-02-29
600X840 Precast
Concrete Curb Inlet
Catch Basin
SW-3.0
2012-11-12
600X840 Precast Concrete
Curb Inlet Catchbasin
SW-3.1
2012-11-12
Catchbasin Pipe
Subdrain Detail
SW-3.1
2013-11-01
Catch Basin Pipe Subdrain
Detail
-
SW-4.0
1998-03-01
Precast Concrete
Catch Basin in
Manhole
SW-4.0
2002-03-20
Precast Concrete Catch Basin
Maintenance Hole
-
SW-5.0
1998-03-01
Manhole Adjustment
Unit Detail
SW-5.0
2013-08-15
Maintenance Hole Adjustment
Unit Detail
707.010
-
1996-09-15
Precast Concrete
Maintenance Hole Tee
SW-5.1
2003-01-17
SW-5.2
2000-02-29
SW-5.3
2000-02-29
Precast Concrete Maintenance
Hole Tee
Steps in Maintenance Hole
Benching
Maintenance Hole Cast Iron
Watertight Liner
SW-5.4
2012-09-14
Sanitary Sewer Dog-House
Maintenance Hole
SW-5.5
2012-11-12
Catch Basin Frame and Grate
“Fish Grate”
City of London |2014 Edition
SW-57
STANDARD CONTRACT DOCUMENTS
FOR MUNICIPAL CONSTRUCTION
PROJECTS
SUPPLEMENTAL STANDARDS FOR SEWER
AND WATER
2014 EDITION
SUPERSEDED/DELETED
(REMOVE)
OPSD
CITY OF
LONDON
DATED
1006.01
-
1988-12-01
1006.02
-
1988-12-01
-
SW-6.0
-
TITLE OF
DRAWING
Sewer Service
Connections for Rigid
Pipe
AMENDED/NEW/CURRENT
(INSERT)
CITY OF
LONDON
TITLE OF
DRAWING
DATED
-
-
-
Sewer Service
Connections for Rigid
Pipe
-
-
-
2008-10-28
Private Drain
Connection
SW-6.0
2013-11-01
Private Drain Connection
SW-6.1
2004-11-01
PDC Riser Type I
SW-6.1
2008-10-28
PDC Riser Type I
-
SW-6.2
2008-10-27
PDC Riser Type II
SW-6.2
SW 6.3
2009-10-26
2013-08-15
PDC Riser Type II
PDC Vertical Riser Installation
-
SW-6.3
2012-11-12
SW6.4
2013-08-15
Private Drain Cleanout
SW-7.0
1997-02-15
Private Drain Cleanout
Standard Servicing
Locations for Single
Family And SemiDetached Lots
SW-7.0
1998-03-01
Standard Servicing Locations
for Single Family And SemiDetached Lots
UCC-1M
2002-05-23
(Removed
Included in
the UCC
Manual)
Standard Utility
Locations For All Streets
W-CS-1
2009-10-26
Standard Hydrant And Valve
Installation
W-CS-5
2006-11-06
W-CS-5
Sheet 2
W-CS-5
Sheet 3
2012-01-26
Standard 50mm Blow Off
Installation
Metered Automatic Flushing
Device
9800 Automatic Flushing
Device Detail
-
W-CS-1
2006-11-06
W-CS-5
1999-01-31
Standard Hydrant and
Valve Installation
Standard 50mm Blow
Off Installation
2012-01-26
W-CS-6
1999-01-31
Standard Valve Rod
Extension for 40mm and
Larger Valves
W-CS-6
2006-11-06
Standard Valve Rod Extension
Piece For 40mm And Larger
Valves
W-CS-7
2000-02-29
Standard Installation of
16mm Water Meter
W-CS-7
2004-11-01
Standard Installation Of 16mm
Water Meter
W-CS-8
2007-10-16
Standard Installation Of
20mm And 25mm Water
Service (Sht 1)
W-CS-8
Sheet 1
2009-10-26
Standard Installation Of 20mm
& 25mm Water Service (Sht 1)
W-CS-8
Sheet 2
1999-01-30
Standard Installation Of 20mm
& 25mm Water Service (Sht 2)
W-CS-8
Sheet 3
1999-01-30
Bottom Board For Standard
Installation Of 20mm & 25mm
Water Service (Sht 3)
W-CS-8
2008-10-28
Zinc Anode Installation on all
Copper Water Service Tubing
(Sht 4)
W-CS-8
2007-11-30
Zinc Anode Installation
on all Copper Water
Service Tubing (Sht 4)
City of London |2014 Edition
SW-58
STANDARD CONTRACT DOCUMENTS
FOR MUNICIPAL CONSTRUCTION
PROJECTS
SUPPLEMENTAL STANDARDS FOR SEWER
AND WATER
2014 EDITION
SUPERSEDED/DELETED
(REMOVE)
OPSD
CITY OF
LONDON
W-CS-12
W-CS-22
DATED
2000-02-29
1991-01-30
TITLE OF
DRAWING
Standard Mechanical
Joint Offset Installation
Using Tiebolt Couplings
Standard Installation of
40mm & 50mm Water
Service
W-CS-31
1999-01-30
Schematic Layout of
100mm and Larger
Service
W-CS-43
Sheet 1
2004-11-01
Typical Thrust Blocks for
Watermains (sht 1)
W-CS-43
Sheet 2
2004-11-01
Typical Vertical Thrust
Blocks For Watermains
(sht 2)
W-CS-43
Sheet 3
2004-11-01
Typical Thrust Blocks for
Watermains (sht 3)
AMENDED/NEW/CURRENT
(INSERT)
CITY OF
LONDON
DATED
TITLE OF
DRAWING
Standard Mechanical Joint
Offset Installation Using
Tiebolt Couplings
W-CS-12
2012-01-26
W-CS-12
Sht 2
2000-02-29
Grip Ring Restrainer
Assembly
W-CS-12
Sht 3
2006-11-06
Typical Restraint Details
W-CS-22
2007-10-16
Standard Installation of
40mm & 50mm Water
Service
W-CS-24
2000-02-29
Cathodic Protection
Assemblies for 20mm to
50mm Water Service
W-CS-25
1999-01-30
Cathotic Protection for
100mm and Larger Water
Services
W-CS-30
Sht 1
1991-01-30
Typical Installation for
20mm, 40mm, and 50mm
Disc Type Water
Meter(Sheet 1)
W-CS-30
Sht 2
1999-01-30
Typical Turbine Water Meter
Installation for 75mm to
200mm
W-CS-31
Sht 1
2004-11-01
Schematic Layout of 100mm
and Larger Service
W-CS-45
1999-01-30
Standard Location for Water
Valves at Intersections With
9.0m and 10.5m Curb Radii
W-CS-51
1999-01-30
Standard City of London
737mm Frame and Cover
W-CS-60
1999-01-30
Sterilizing Mains
City of London |2014 Edition
SW-59
STANDARD CONTRACT DOCUMENTS
FOR MUNICIPAL CONSTRUCTION
PROJECTS
SUPPLEMENTAL STANDARDS FOR SEWER
AND WATER
2014 EDITION
SUPERSEDED/DELETED
(REMOVE)
OPSD
CITY OF
LONDON
DATED
TITLE OF
DRAWING
AMENDED/NEW/CURRENT
(INSERT)
CITY OF
LONDON
DATED
TITLE OF
DRAWING
W-CS-66
2004-11-01
Typical Service Entrances
100mm to 200mm
W-CS-67
1985-03-07
Remote Water Meter
Register Installation
W-CS-67
1999-01-30
Remote Water Meter
Register Installation
W-CS-68
2002-03-20
Insulation of Shallow
Mains and Offsets
W-CS-68
2012-01-26
Insulation of Shallow
Mains and Offsets
2003-09-16
450mm and Up Typical
Watermain Support
Detail for Utility
Crossings Using Open
Cut Construction
W-CS-69
Sheet 1
2012-10-01
450mm and Up Typical
Watermain Support Detail
for Utility Crossings Using
Open Cut Construction
2003-09-16
Typical Reinstatement /
Bedding Details for
450mm and Up
Watermain Support
W-CS-69
Sheet 2
2012-10-01
Typical Reinstatement /
Bedding Details for 450mm
and Up Watermain
Support
2003-09-16
General Submission and
Design Requirements for
Watermain Support and
Bedding / Reinstatement
W-CS-69
Sheet 3
2010-10-01
General Submission and
Design Requirements for
Watermain Support and
Bedding / Reinstatement
W-CS-70
2009-11-20
Valve Box on Chambers
W-CS-71
2012-01-26
Metered Irrigation System
and Backflow Prevention
Assembly
W-CS-69
Sheet 1
W-CS-69
Sheet 2
W-CS-69
Sheet 3
City of London |2014 Edition
SW-60
.COarse sand
Plein or reinforced
concrete_
to be 15 MPA before
backf;lling
- Formed
1/40. D.
b40.D. (100 Min,)
1
Crushed stone
Max. size 19mm
Formed or poured
CLASS
A-1
CONCRETE
CRADLEBEDDING
Coarse sGnd
Plain or reinforced
concrete
tobe 15 MPA before
backfilling
- Formed
Crushed stone
Max. size 19ram
NOTES:
1.
’W’ = O..D. + 200mmfor pipe sizes up to
and including
600mm in dia. and 1-1/40.D.
for pipe sizes greater than 60On, n;
2. ’P’ is the ratio of area of steel to the
Grea of concrete at the crown for
concrete oroh. and at the invert for
, concrete cradle.
3. All b~dding materials to be mechanically
compacted in Occordence with City of London
Standurd Contract Documents
a. When reinforcing steel is required to
obtaih ~ specifio load factor, design detail
shall be submitted to the Contract
Administrtotorfor epprov~l.
A. ALL DIMENSIONS.AREIN MILLIMETERS
UNLESSOTHERWISESHOWN
Load Factors:
~ 2.8 for plain concrete
= 3.4 for reinforced concrete
wi.th p =.0,4%
= 4.8 f.or reinforced
with p = 1,0%
concrete
CiTY OF LONDON STANDARD DRAWING
.>~LASS A-1 CONCRETECRADLEBEDDING AND CLASS A-2
CONCRETEARCH BEDDING FOR RIGID PIPE
1996 05 15
crfY
ENGINEER
A. ALL DIMENSIONS ARE IN MILLIMETERS
UNLESS OTHERWISE SHOWN
~
,
~"-’~~
/ .~-J-’---’~-L~
/
"~
~
~
"
/
/
~
[
~
~
~
~
"
~
I. Drop structure to be completely
encased In a minimum 150m o4 20
MPa concrete and secured to the
marnfenance hole wlfh 450mmlong,
13rl~ d I a threaded rods and
iI
I
~V
~~
~
I
i
i I
! ~
V
I
I~
both ~Ide~ Of
~
I
I
~
I
I
I
~
.........
OUIL~I ff~ff~
6
P~N
,~
~
,
~
z
~"
I’’~
~
,
.....
~" ,~
~
50
o
~
r~
’ , ,
~
,~~
", ~’,--
~ .....~ "-" ’
’
.- ~
~
n
~
)
~
SECTION
,.
’ ’ ’
be located ~0 avoid confllo~ wlfh
,,,,.
Aooess fo ~infenonoe hal
be above the benchlng pl
’
90
A-A
CITY
.......
2.. For plpe sewer slzes 200~
~o 4SO~ (inslde pipe
dlc~fer) DI = D2 . For pipe
sewer slzes equal fo
greater than 525~ DIQ.
D2 = 450~ D)
3. Drop ~@ruoture~ ~hell be
oon~fruofeQ ~en the
In Invert elevQflon~between the
upBTreQmQnd out let ~ewerB in
the ~ImfenQnoe hol
greaeer @han BOOmfor sanlfary,
~ewers and 900~ ~or storm
sewers.
4. When ~he difference
In elevation
between the upstream t nver$ and
the top oP the benching exceeds
1.50m, an addif!onal
se~ O~ sfep~
~ are required adjaoen~
/ /
/ /
/ /
/"
/
~/ /
/
Bend
PO
OF LONDON
STANDARD DRAWING
MAINTENANCE
’ DROP STRUCTURE
....................
WYE
DWG
SW-2.0
DATE
2004 11 01 , /CITY EN.GINEER,,
d(.4~
0
t
a,
-
Q)
n
a
ul
0
O
1
.m
4
4'
C
.-
r
Y
8
-
I
y.
.,
4
4
0.
D
4
4
4
4
D
4
a>
v)
oLloooooooo
3 s
w *-
-2
tOQ)
>
OQ)
CJ
t
La
I
00
CL
00
/
I
a
a
z
0
Y
-J
U
a
IW
f3
I
m
Q
W
-I
U
00
cn
)
I:
(0
)
.-.-
L OQ)
c>
LLQ)Q)
O O t L
Q)
Q)OCO
+
+
v
0
m
-
00
(c
0
m
u)
0
u)
M
00
0
M
M
a,
N
c
)
-
-
v
c
C
3
0
S
Q)
v)
L
v)
.-3
0
c
v)
v)
Q)
J
-
oc
E
Q)
t
L
a,
v)
a,
E
L
0
t
Q)
L
v)
C
N
*
IC
v
0
U
3
I
-Q)C
L O U
a
t m t
cn
o wa
Q)c
WE%
t u )
c t o
I
'c)
.E
Q)
M C O L C
u
Q)rroLo E
-- O L
ac
.-
8
OnwLLu
ooc---v)-xu--- 0aaana
or
cv+ 3 0 O U
i:Z';a,->c.-
+ a L Em0
. O 9) * Q) O J O * L Wo
0
EQ
C )C*C- - ov)c
*+UEt
atov)v)
ant 0- u t o
+
wtoscn
E L cv) v)
ala
a 0 oao*03tQ)ow
at n - C Q )
QQ)
-cno+
0
0-
-0.-t
-LoQ ) OQUI
Em.-LMcn-
O O O C I IC-
W E 0.-
t
Lo
* L
u-
Q
o
0-
t
Q)
a
ma
-v)
t
Q)
a
-
t
IW
9)
n
-a
v
.-0c
f3
.
.a
1
Y
a
v,
n
IW
o
I-
W
v,
z a
W
IO
t+,.r.
|
I
-/
1
50 over lop
115
ffi
I l*o
I
PLAN
m
,ffi
115
600
ffi
Note
1
/
115
I
1070
|
840
115
ìll
l=
"'t,ll
lFË
IJK
Ël
|]'f;\ |[1 :*"*"'
q||]E
lll
tlt /
ffi+
sEc¡oN;
NOI"ES:
1.
200mm
dîo.
knockout
fo
B_B
A. ALL DIMENS]ONS ARE IN MILLlMETTRS
UNLESS OTHERW]5I
SHOWN
4.
Gronulor bocKfi I I to Þe ploced cnd compccfed
to o min. thicKness of 300nm ol I oround
5. Adjustment un¡ts shcl I be instol led
cs per 0PSD-704.010. Minimum of 1 unit
and o moximum of 300nm.
6. Closs of concrete: 30 MPo ot 28 doys
7, Refer fo 0PSD-400.09 for cafch bosîn
cost iron curb înlel overflow plote detoi ls.
I
occonrnodole
subdroin. Knockout to be holf wol
thickness from the outsÌde.
2. Ouflet hole size 400mm dio. locofion
I
os required.
3.
SECTION
Al I reÌnforcing sfeel bors To be 15.
Reinforcíng steel shol I hove 50rnm
cover
ctry OF LONDON STANDARD
DRAWING
ti00 x 840
PRECAST CONCRETE CURB INLET CATCHBASIN
DWG
DATE
sw-3,0
APPHOVED
2012 11
12
ctw
BY
Et.lelrurrn /d.
t)ã4
P/L
Varies
1
-
PLAN
- -P/L
NOTES:
1 . O u t l e t h o l e diameter = 400m.
located as required.
2. Adjustment u r l l t s and components
s h a l l be i n s t a l l e d as Der OPSD
701.030 and C i t y o f
London Standard Drawi ng SW-5 0
3. Class o f concrete 30 MPA
a t 28 days
4 . Refer t o OPSD 400.02 f o r
CATCH BASIN, CAST IRON FRAME
AND FLAT SQUARE GRATE
5. A l l catchbasin maintenance h o l e leads
and g r a t e s a r e t o be located a minimum
o f 0.6m from the P/L.
100m d i a . d r a i n t i l e
used i n permeable so
19rm crushed stone bedding
15Omm m i n . depth
A.
SECTION A-A
ALL DIMENSIONS ARE IN MILLIMETRES
UNLESS OTHERWISE SHOWN.
CITY OF LONDON
DWG
sw-4.0
DATE
APPROVED
2002 03 20
STANDARD
BY
CITY ENGINEER
DRAWING
g
&
I
kl 2 O O m d i a4
i
n
Balance of maintenance hole
according to OPSD-701.010
I
SECTION B
SECTION A - A
-B
Reinforcing 50mn min
lap weld and connection
grouted with non-shrink
mrtar
Spacing of mointenance hole steps to be 3 0 0 m c/c.
NoTES:2 Sewer pipe accdording to CAN/CSA A-257.2. class to match that of higher class adjcent pipe,
3 Steps are required to within 450mn above the invert for storm sewers only.
4 No connections are to be constructed into maintenance hole tee's ( ie sewers. C . B . ' s
and POC's 1.
A Bedding for MH tee similar to pipe bedding either slde of tee.
B Tee section bell or spigot as required.
C Granular backfill to be placed to a minimum thickness of 300mn all around the maintenance
hole tee.
D Minirmm s t e e l in connection must equal1 area of steel in pipe.
E Sanitary maintenance hole tees require a safety landing within 1.5m of crown for testing.
and maintenance operations.
F The minimum clearance between the safety landing [ within 1.5M of crown 1 and the first
safety landing above is a minimum 2.0m.
G A l l dimensions are nominal.
H A l l dimensions are in millimetres or metres unless otherwise shown.
1
DWG
SW-5.1
DATE
2003 01 17
APPROVED BY
CITY ENGINEER
ye"
-
KJd-
Handhold construction
shall
comply
with OPSD405.010
Section A - A
o
~
Steps to comply
with OPSD405,010
and 405.020
,,
~
300
14 ~ 2L%00
F --~
DETAIL A
Handhold
See Detail
SHOWN-1800mm
PIPE
BENCHED ~ CROWN.
Max
height
.....
.--~~
/
_
4so
~.............. ,.71~ .....
~
HDLE~
FACEVIEW
1. Step8 are required fn benching for pipe diameter8
a ) Greater than 900rrrn - benching to springl Inc,
b ) Greater than or equal to 450mm- benching to crown,
2, Handholds 8hall be constructed in accordance with
3, Handholds are required ~or pipe diameters greater
to 1500mmdie when benching to crown.
BENCHING
SECTION
DETAIL ’A’,
than or equal to
4, Additional
handholds
be required for pipe diameters
Greater than 1950mm- benching to crown,
5, Step dimensions are typical
6.
Maintenance hole 8tap8 shall be Ioaated to ~vo[d
conflict
with an Inlettfng
or out tatting
sewer pipe,
Access to maintenance hole must be above benching pie+form,
A. All dl~ensions are in millfmetree
unless otherwise shown,
CITY
I
I ILl
OF
LONDONSTANDARD DRAWING
r I I I II j I I
i ,
] , ,,[ ........
],
, ....... ~1
ii
~1iiiii : ...... ........ ..................................
STEPS IN MAINTENANCEHOLE BENCHING
DWG
8W-&2
DATE
..........
2000
02
29
~PPRovED ’BY ............
pITY
ENGINEER
~:::
................
..../~
.
.
.... / .... ....................
................
800
8
-R
= 150m
tYP
f
4
c
18 mn d i a h o l e f o r
16 m brass o r
s t a i n l e s s s t e e l cap
screw
2 lugs ( o p t i o n a l )
typ i ca I
/
0
0
-
27
f
FRAME PLAN
I,
633
38 m d i a X
1 4 mn deep
624
13mn d i a
bar handle
cast i n
PIAN VIEW
51
6
I I*
575
M
4
667
800
-
L f+R=l9
r
SECTION C
-C
’
2 m rubber
gasket
SECTION B
CITY OF
SECTION D
-D
A l l dimensions a r e i n millimetres
o r metres un I ess otherwise shown.
-B
LONDON
NOTE :
STANDARD
DRAWING
P
I
CAST
DWG
AND SQUARE FRAME.
DATE
m
-A
4 - 1 6 m d i a brass or
s t a i n l e s s s t e e l cap
x 57 long
-
216
4
L
SECTION A
Rubber
washer
287
APPROVED
BY
SOUARE FORMED CONCRETE COLLAR
Ex+end ouf 300nm olong existing sewer
oncl 225nm oround borrel orch open¡ng
o-SeeNofes4&8
DOG HOUSE
MA I NTENANCE
HOLE
STRUCTURE
BARREL
I
I
CONCRE TE
I
I
COLLAR
c0L
I
A
I
I
t..
:{l
FLOW->
l"i
,lt
l-.'
I
FLOW
lp'
CHANNEL
,¡L
EXISTING
Exìsting sewer Íust be
cut of the sÞring-l ine
ocross ful I înternol
B
w¡drh or structure
SECTION
HOLE PROFILE
BASE
SEWER
'DOG
A
t- Þ'"
l-i iË'
Þ¡
FLOVJ
I
HOUSE" MAINTENANCE
1
200rm
'A_A'
MIN
CONCRETE
COLLAR
REMOVE TOP HALF OF EX. PIPE AFTER
MAINTENANCE HOLE IS CONSTRUCTED
OR FORM NEAT CI{ANNEL AS SPECIFIED
FLOW+
SIZE OF OPENING TO FIT
EXISTING SEYIER PLUS 75nm
REINFORC¡NG
SPEC IF IED
AS
I 50Ím
MI
z
19rm
CRUSHED STONE
BEDDING. MIN 150rm
=
POURED
IN PLACE CONCRETE
BASE
PRECAST CONCRETE BASE
tt-t
ùtrt/ I ll.Jl\ 'B-B'
SECTION
NoTES
'l . The doghouse rnoinlenonce hole Íìoy only be usecl for plocing o new rnointenonce hole on on exísf ing
sonifory or storm line when instollotion of o s+ondord rno¡ntenonce hole is not Þroc+icol.
2. All mo¡ntenonce hole coñponents ore +o rnee+ oPSD 70'l .
3. Al I benching ¡s fo meet 0PSD 701.21.
4. Al I poured ¡n ploce concrefe to be 30 MPo.
5. Concre+e bond¡ng ogen+ mrs+ be opÞlied +o oll in+erfoces of precost to cost-¡n-Þloce concrete.
6. Full +¡me inspec+ion sholl be provided by +he consul+ing eng¡neer during insfollo+ion of
this s+ruc+ure ond +he consultonf sholl provicle written cer+ifÌcofion of ¡ns+ollot¡on to the
City of London. The strucfure rrust no+ be bockf ¡lled for minirnrm 24 hr ofter consfruc+ion to
ol low for secondory inspec+¡on os required
7. The top of +he existing nrcinline sewer rrusf be fully removed from springline ocross
the ful I ïn+ernol wï<lth of the structure.
8. A curved ïn+ernol orch form rrus+ be used during collor concre+e fill. No brÎcK. mor+or or
debris is to be used in ploce of consol ¡doted concrete oround the Þipe or in the col lor.
The col lor. under pípe f¡ I I ond benching rrusf be construc+ed in one continuous pour.
'DOG
SANITARY SEWER
HOUSE' MAINTENANCE HOLE
2snm
xlctt LÈrrentt'lo
-
-l*l-,r* 1-"J
SECTION IAI-IA'
-ffi\
NË
I
/
25lfm HIGII LETTERING
( TYP ICAL )
-Krlt!ry&N3
SECTION 'B'-'B'
81
9ø HINGE PIN
i
rAnAr
t*l
DETAIL A
DETAIL B
CIry OF LONDON
r*
SECTION 'C'-'C'
A.
12
"-l H l'ë
SECTION 'D'_'D'
ALL DII/ENSIONS ARE 1N lvllLLIlvlETERS
UNLISS OTHERW]St SHOWN
STANDARD DRAWING
CATCH BASIN FRAME AND GRATE
,FISH GRATE'
2012 11
*ffi
|
C/L LOT
Note 2
Note 2
Note 2
I
,.!
I
C/L OF
BUILDING AREA
Building Area
Note 1
¯
.I "
STREET
STREET
I
SINGLE CORNERLOT
SINGLE
C/L COMMON
PARTYWALL
No~e 2Lguilding Area
C/L COMMON
PARTYWALL
Note2 I..Bu i I d i ng Area
Note 2
I
-DwelIing Dwel Iing
Unit
Unit
! Dwell~ng Dwelling
Unit
!I Uni
3.0
3.4 3.4 3.0.
2.5;
..... .’:..::
:$EM!~D,._ETACHED
’
NOTES:
1. External bul I d ing setbacks to ref I cot
current
appI i cabI e zoni ng by-Iaws
setbacks to reflect
2. Internal buildi.ng
current applicable
zoning by-laws
If
the
building
area
is located on the opposite
3.
side of zero lot line lot, then show the
services in reversed location (ie S~nitary
and Storm)
4. Storm PB.C’s are required except where exempt
by the dPalnage by-law
A~
2.5
0.9
STREET
STREET¯
o
Note I
C/L ~ LOT
Note 1 & 21. Buiidlng
Note
ol
STM. P.D.C. - storm Private Drain Connection
SAN. P.D.C. - Sanitary Private Drain Connection
W.S. - Water Service
ALL DIMENSIONS ARE IN METERS
UNLESS OTHERWISESHOWN.
CITY
OF
Area
SINGLE ZERO LOTLINE
LONDONSTANDARD DRAWING
STANDARDSERVICING .LOCATIONS FOR
SINGLE ,FAMILY ANDSEMI/q~~TACHED
LOTS.
~I DW~
SW-7.0
. IDAT
e
1998
03
APPROVED
BYe.
O~I CITY ENGINEI~
~ <
/
//~_~~~
’
}WAY
75mm
HYDRANI
TO ì50ññ FROM
TO CENTRE
FINISHED GRADE
OF BREAK FLANGE
tl|
.
{
È
c¡¡
i
o
È
o
G
È
CIJT AWAY
TO SHOW VAI.VE
ÐcENDED TO WTHTN t50
BETOW FIML GRADE
ROD
fO
300
o
é
AT LEÆT 900x900x450 DEEP
FROM I5O ÆOVE WÆTE
OPENING TO BOTTOM OF
SEE
DETAIL OF
N
MECHANICAI TTHRUST RESTRAINT
TIE RODS AND BOI.TS COVERED
DRAINAGE PIT
SHATL NOT BE CONNECTED
I,ATÊRAT PIPE.
TO
W_CSJ FOR
VALVE ROD
=
o
o
AND 20mm
WTH DENSO
TAPE
SEWER
1.9m ON ST/NDARD
STREEI
rrolES:
D,I. PIPE, WRAP IN P,E. ENCASEMENT
AS PER SPECIFICATION.
ì.
2
AII
3.
HYDRÂNI I.OCATIONS
DIMENSIONS ÆE
DIffiNSIONS
GMN
IN NN UNIff OTHERWSE SHOWN
TO SNDA¡D I#IN LOATþN
ÆPLY
PER
MUS BE MROVED BY FIft DEPffiMTM
AND DUNAGE DMSION
DUWNG UCè] ND UCCjM
ilVRONMENTI
ND
SEMCES WANR, SEWER
MECHANICAT
RODS
AND
IHRUST
AND 20mm TIE
WTH DENSO TAPE
RESTRAINT
BOTTS COVERED
4, HYoMNT TO 8E lsæññ M¡n FROM À DRMWAY AND PruFEMßtY lN THE MlOotE
OF Â LOT fRONTAGE
5, AL JOII.TIS TO BE MECHÁNICAII.Y THRUST RESTRAINED.
ó. POI-YEftÍY|.ENE BOND EREAÆR TO 8E Ij5ED BNWEEN CRUsHED STONE ANO FIMNGS
7, lN CÀtES WHERE THE DEm OF ffE WATERI#IN lS GMTE¡ lN I 9ñ,8ENN mY
0E usED
ST
Nm
8. IHE
I'6
CITY
OF
LONDON
USE
10 OFFSfl üE mRANT LATERAJ, {PAST IIiE GAIE VAwq fO
IHE
^CHIEIESTnvlCES DSAtrMENTl
Frtr ttrDßANT BOOÍ DEml hS APPROWO ry frE ENVRONMENTAT
OF A 300mm (Ma) Fttr mMNT MRE| gfiENStON lllAy AISO BE USEo.
ÆPROVED
il
THE ENVRONMEÑIA
STANDARD DRAWING
HYDRANT AND VALVE INSTALLATION
...\standardsVT.dgn 2010-10-19 I 1:34:17 AM
SEMCES DEPAflTMEI{ÍI.
G.I. P~ug or Cep
(;rode
0. I. Coupling
G.I. Stand Pipe
BWG. W-CS-22 for Service Rod & Porte
Curb Velve - With inlet cnd Butlet
inside I,P. Threod
M.
Jo
Flat
Cap
(Drilled
end Tepped 50)~
I. Elbow
50 G.I. Pipe
50 Bress Nipple
Main
Board
See Dwg. W-CS-8 Sht. 5
100 Min. Bedding
NOTES :
1. All dimensions are in millimeters unless otherwise shown.
2. All concrete to be min. 20mpo. compressive strength.
3~ Polyethylene Bond Breaker to be used between concrete end fittings.
4. Mechenical thrust restroint required os per section 701.07.21
CITY
OF LONDON STANDARD DRAWING
STANDARD 50mm BLOW OFF INSTALLATION
DWG:
W-CS-5
I
DATE
2006 11 06
APPROVED BY
CITY ENGINEER:
I
NTS
HYDRANTS 98OO ECL IPSE
AUTOMAT I C
FLUSHING DEVICE
FORD TYPE "W" WABASH DOUBLE
LfD COVER (OR EOUIVÄLENT)
EXISTING
GRADE
22.5'
AS
sorÏm CURB
OR 45"
REOUIREO
VALVE
AND SERVICE
BOX
150rfm DR28
PVC PDC
5OÍm PEX SERVICE
(MIN. }
CORE IIOLE
TO ACCEPT
AT SPRINGLINE
1sorrn PIPE
EX.
X.
WAÏERMAIN
300Ín 0F lgrrm
METERED AUTOMATIC FLUSHING DEVICE
FORD PVC CYLINDER
(OR EOUIVALENT}
WAIEBMAIN AND WATERMAIN NETWORKS SHALL BE DESIGNED SO THAT WATER
SHALL NOT REMAIN UNUSED IN THE WAIERMAIN FOR MORE THAN THRÊÊ (3)
DAYS UNDER AVERAGE DAY DEMAND.THE CITY OF LONDON HAS PRIMARY
TO ENSURE THAT THE MINIMUM CHLORINE RESIDUALS AFE
MAINTAINED IN THE DISTRIBUTION SYSTEM AND THEREFOBE RESERVES'IHE
RESPONSIBILIIY
RIGHT
TO
REQUIRE WATERMAIN LOOPING AND,/OR AUTOMATIC FLUSHING
DEVICES AND,/OR BLOW-OFFS TO FACILITATE THË MAINTENANCE OF THE
300Ím OF 19rm SToNE AND
2ooffm AROI,JND METER PIT
CHLORINE BESIDUAL
TO BE IN ACCORDANCE WITH THE SECTION 441.05,æ
OF ÏHE CI'I'Y OF LONDON STANDAFD CONTRACT DOCUMENIS FOR ¡'UNICIPAL
CONSTRUCTION PROJECTS AND THE MANUFACTUBER'S RECOMMENDATIONS.
WATER MFTEF PITS ARE
TO BE IN ACCORDANCE WTH THE SECTON
OF THÊ CITY OF LONDON STANDARD CONTRACT DOCUMENTS FOR
MUNICIPAL CONSTRUCTION PROJECTS AND THE MANUFAC'IURER'S RECOMMENDAÍIONS
AUTOMATIC FLUSHING DEVICES ARE
44'I.05.1S
STANDARD
DRAWING
METERED AUTOMATIC FLUSHING DEVICE
DWG
STORM SEWER
50nm PEX CoNNECTI0N
w-cs-s
2
'HEET
2012-03-29 9:09:42 AM
PIT
SETTER
CLEAR SToNE
SYiEEPS
50mm PVC BALL VALVE
SAMPL
SUPPORT ROD AND CLAMP
ING PO]NT
50rm
ACCESS PLATE
UV RESISTANT
- 90" BEND
BOX
WITH LOCKING LID
LOCK
100mm
ING DEVICE
AIR
GAP
EXISTING
BRASS
LL
fL
o
F-
-
E
F Ot
ù
t¡J
o o
F
tL
BASE
o
UN ] T
LLI
IPE
RISER
É.
=
dl
P
E
F-
CONTROLLER
CONNECT I ON
150mm SEWER PIPE
AUÏOMAT I C
DRAIN
AUTOMAT I
VAL VE
C
75mm FIP
o_
v)
O-R I NG
TO STORM
SDR
35
DTBRIS PLATE
5Omm MIPX COMPRESS I ON
ADAPTER
CITY
OF LONDON STANDARD
5OrnrniBRASS
300mm
0F 19nm
FIP
INLET
CLEAR STONE
DRAWING
98OO AUTOMATIC FLUSHING DEVICE DETAIL
2012-08-30 11:36:03 AM
GRADE
SEWER
PVC PIPE
63
I-- 60 LI--
VARIES - LONG ENOUGH TO EXTEND WITHIN 150 ~1~
120
TO 300 FROM VALVE BOX COVERI
31301
T
40 I.D.
STANDARD BLACK PIPE
AVAILABLE FROM CITY
SQUARE~
TOP VIEW
END VIEW
VALVE ROD FOR 40mm VALVES AND LARGER
NOTES
ALL DIMENSIONS ARE IN mm UNLESS OTHERWISE SHOWN.
~--~OPERATING NUT TO REMAIN
SECURED TO VALVE
DETAIL - OPERATING NUT
TYPICAL SECTION
CITY
2
CUSTOMER CAN PICK UP COMPLETED EXTENSION RODS
FROM THE CITY STORES DEPARTMENT.
3
RODS WILL BE PROVIDED IN 150 INCREMENTS FROM
600mm TO 1200~a’n.
OF LONDON STANDARD DRAWING
STANDARD VALVE ROD EXTENSION PIECE
FOR 40mm & LARGER VALVES
DWG:
W-CS-6
DATE
2006 11 06
CITY ENGINEER:
I
NTS
NOTE:
1. REFERTO W-CS-67 FOR DETAILS
OF REMOTEWATERMETER
REGISTER INSTALLATION.
VALVE
2. NO GROUNDING ALLOWED
ON WATER METER
BY OWNER---.m
,
~
~.~..~
METER
SEAL.~~~~_
F~.~----16rnrnWATER METER
~
~
|
BRASS NUT AND
I
ANGLE METERVALVE STOP
SUPPLIED BY CITY ~
/
IN
¯
OU~kll~J~-~-l-r’~
~
:
=,,.,
WATER PIPE OR
APPROVED SERVICE
MATERIAL
m
~
CITY
,
,
,,
,
OF LONDON
,
STANDARD DRAWING
,
,
STANDARDINSTALLATION OF 16mm WATERMETER
DWG:
W-CS-7
DATE
2004 11 01
APPROVED BY
CITY ENGINEER:
NTS
REV200402 25
/’
~
SERVICEBOX
(C,I,) 1400 TO 1700
.,,
I,,,SER, VICEBOX
BASE
ADJUST TO GRADE USING
25 BLACKIRON NIPPLEAVAILABLE
IN VARIOUSLENGTHS
--~
SERVICEBOX- AS ABOVEWITH EXTENSION
COVER (C;I,)~
Z----BRAS
S
PLUG
25 BLACK IRON COUPLINGf
COTTER PIN - BRASS
SERVICER~)D - STAINLESSSTEEL
/
NOTES.I, ALLDIMENSIONS
ARE IN mmUNLESSOTHERWISE
SHOWN,
2, CURBBOX MUSTBE INSTALLED SQUARELYOVERCURBSTOPAND
BOTTOMBOARD,
3, SERVICEROD MUSTBE AT LEAST 300mmBELOWGRADEAND NO MORETHAN
900mmBELOWGRADEAND MUSTBE OPERABLEWITH A 1400 KEY-WHEN
INSTALLAT.IONOFSERVlCE
PIECE IS COMPLETED,
. BOXANDEXTENSION
¯
BRASS PLUG - WITH 20ram PENTAOON
HEAD
CITY OF LONDON STANDARD DRAWING
STANDARD INSTALLATIONOF 20mm
lllIl
II
I
I
DWG: W-CS-8
)
SHT.
II
II
! i.
I
,
i
AND 25mm
2
1999 01 30
.
CITY ENGINEER:
I
WATER SERVICES
I
II
I
NTS
184
BOTTOMBOARDCONSTRUCTED
FROM
38mmx 184mrn CEDARAND16rrrn-x 38rrrn
~SPRUCE INSTALLED AS A BASE FOR
CURB STOPSAND SERVICE BOXESAS PER
W~CS-8, SHT, 1 & W-CS-5,
O
O
A
A
75mmDIA, FOR25mrn SERVICE
POSITIONF.OR 64rrrn DIA, FOR
20mm SERVICE
20mmDIA.
PLAN VIEW
NOTE
: ALL..D. !MENS
IONSAREI N..!tin
UNLESSOTHERWISE
NOTED,
SECTION"A-A"
CITY
OF LONDON. S"FANDARDDRAWING
BOTTOM BOARDFOR STANDARDINSTALLATION
OF 20mm. & 25mm WATER SERVICES
DATE
[DWG:
W-CS-8
SHT.
31
NTS
1999 01 30
UNIFLANGE SERIES
E
I3OO-C RESTRAINER
SPECIAL LONG
RESTRAINER ASSEMBLY
o
FOR P.V.C. PIPE
@m
ROD ASSEMBLY
c\^ó
FOR D.I. AND P.V.C. PIPE
TIEBOL
TIE ROD ASSEMBLY USING
CLAMP
FOR D.I. PIPE
T JOINT
RES T RAINER
MINIMUM CLEARANCE AS
PERCOFLDESIGN
SPECTFtCATT0NS
&
7.4.7.2.
M.O.E. PROCEDURE
SEWER OR OTHER
OBSTRUCTION
LEGEND:
A
B
C
D
E
F
G
H
NOTES:
I.
ALL
DIMENSIONS ARE
IN mm UNLESS
OTHERWISE SHOWN.
2. THIS DETAIL TO BE USED FOR OFFSETS ON
2OO DIA. MAINS. OFFSETS ON LARGER MAINS
IOO,
I5O
&
REOUIRE
INDIVIDUAL APPROVAL.
EXISTING WATERMAIN
ÂPPROVED CLAMP
REOUIRED M.J. BEND
FILLER
F-6-I
PIECE
(THREADED COR-TEN STEEL)
APPROVED TIEROD
M.J. SLEEVE
APPROVED TIEBOLT JOINT RESTRAINER
APPROVED TIENUT
3. IF OFFSET IS INSTALLED IN HORIZONTAL OR INVERTED
POSIÏION, MINIMUM COVER TO BE DECIDED BY ENGINEER.
4. ONE PAIR 0F 20mm DlA. RODS FOR 100, 150 & 200 DtA.
5. COVER TIEBOLT ASSEMBLY WITH DENSO PASTE MASTIC
AND TAPE ALL TO MANUFACTURER'S SPECIFICATIONS.
6. ALL
RESTRAINERS MUST BE APPROVED
BY THE CITY
OF
LONDON.
CITY OF LONDON STANDARD
DRAWING
STANDARD MECHANICAL JOINT OFFSET INSTALI-ATION USING TIEBOLT COUPLINGS
...\standardsW.dgn 2012-03-28 2:23:25 PM
P|PE.
DUCTILEIRON
OR PVC PIPE
GRIPRiNG
~.
GLAND
T-BOLT
GRIP RING RESTRAINER ASSEMBLY
FORD.IANDPVCPIPE
M,J. BELL
PIPE
GASKET.
GRIPRING
,,,
GRIP RING DETAIL
CITY
OF
LONDONSTANDARD.DRAWING
¯
If
,lJIIIII I
I I
I
I.. I Jlllll
~11
I
.I I
L JJ III I
II . II|l.
~111
II
Illl
I IIII I
.................................
GRIP
....RING."~ESTRAiNER
ASSEMBLY
..I
¯
_HI
,~,
Ill I Ill ,
,11,
, " jl, ,
DWG:
W--CS--12 SliT.
2
,1,I
,,
,. J,
I1,,
IIIII I
..FOR DI & PVCPIPE
JIll 1, ,
DATE 2000 02 29
CITY ENGINEER:
NTS
~E CUT TO PLACE VALVE IN PROPER LOCATION (TYP.)
/
A) VALVES UP TO 300ram (IN LINE)
I_
ALL VALVES MUST BE
(~
RESTRAINED AS NOTED
~ INCLUDING ANY JOINTS
6m
(~)~~
250mm TO 3OOmm = 30.Om
100mm TO 200ram = 20.0m
I
250ram TO 300ram = 30.Ore
lOOmm TO 200ram = 20.Ore
B) DEAD ENDS UP TO 300mm
250mm TO 300ram = 30.Om
_
INDICATED.
! WTHIN
THE DISTANCE
ALL DEAD ENDS MUST BE
RESTRAINED AS NOTED
INCLUDING ANY JOINTS
WTHIN THE DISTANCE
~’INDICATED.
lOOmm TO 200ram =/20.Ore
C) BENDS UP TO 300mm
4.Ore
6m
ANY JOINT WITHIN 4.0m
OF THE BEND SHALL BE
RESTRAINED.
6m
4.Ore
~]
6m
D) ALL FITTINGS UP TO 300ram
6m
Com
6m
4.0m
ALL FITTINGS MUST BE
RESTRAINED INCLUDING
ANY JOINTS WITHIN 4.0m.
~~
(~ = RESTRAINT
CITY OF
LONDON
STANDARD
DRAWING
TYPICAL RESTRAINT DETAILS
DWG: W-CS-12 Sheet 3
2006 11 06
CITY ENGINEER:
NTS
NOTES:
I. ALL DIMESIONS ARE IN mm UNLESS OTHERWISE SHOWN.
2. MAIN STOPS SHALL BE SPACED ON MAIN NOT CLOSER
THAN ~50.. IF MAIN IS PVC TAPS SHALL NOT BE ON A
COMMON LINE PARALLEL TO THE AXIS OF THE PIPE AND
NO CLOSER THAN 450 FROM THE SPIGOT END OF PIPE.
3. A~V JOINT MADE IN SERVICE PIPE SHALL BE MADE WITH
APPROVED COUPLINGS.
4. NO JOINTS SHALL BE MADE UNDER PAVEMENT.
5. APPROVED SERVICE SADDLES MUST BE USED TO
TAP ALb 40rnm & 50mm MAIN STOPS INTO ALL
TYPES OF PIPE.
NOTE: SERVICE PLATE TO BE INSTALLED ON
BLDG. SHOWING MEASUREMENT TO VALVE
4.6m
VAR I E S
w~s-6 SHT. 2
~
SEE
.,~_ ~
_,~
I
SEE DETAIL ’C’
DN W-CS-B SHT. 1
~
SEE SECTION ’A-A’
5.SKo ZINC ANODE
SEE W-CS-8 SHT. 4
SECTION VIEW
¯I
WATER MAIN
DDUBLE STRAP (SHOWN)
OR BROAD BAND SERVICE
SADDLE WITH 40 OR 50rrm
40 OR 50mmFLARED (SHOWN)
OR COMPRESSION OUTLET
MAIN STOP /
~~
TYPE ’K’ COPPER TUBING
CURB STOPOR BALL VALVE
COMPRESSION
OR FLARED (SHOWN)
INLET AND OUTLET,
BRASS COTTER PIN
TYPE ’K’
COPPER TUBING
PLAN
THREAD
TO BE VERY
WELL COMPACTED
SECTION ’A-A’
SEE W-CS-8 SHT. 3
DETAIL ’D’
CiTY OF LONDON STANDARD DRAWING
STANDARD INSTALLATION OF 40mm AND 50mm WATER SERVICES
DWG:
W-CS-22
IDA~
200Y-10-16
APPROVED BY
CITY ENGINEER:
NTS
d
O
z
I-
I
,
I
I
I
I
I
I
>
J W
VIJ
,&I
a
4
ou
a
on
a
LIZ
0-
V I 3
--I
0
zn
-I
aa
VIW
WI-
-0
VI
i-tZ J
I I
I
iI
0
n
W
I
I
Ia- m
o
a
W
z
E
W
W
z
0
P
I
I-
%
2
0
-I
w
2
I
p
.
W
W
c
>-
I
I I
I
I
LL
f,
I
-v iw-
.
I
MIN, CLEARANCE TO WALL.
OR ANY IMMOVABLE OBJECT
TOP VIEW
:-’~-- BY-PASS VALVE
IN SHUT POSITION
¯ (SEALED BY CITY)
0
I. A,LL 40mm. METERS AND LARGER AND ANY METERS SUPPLYING MORE THAN
ONE CUSTOMER REOUIRE A BY-PASS UNLESS OTHERWISE APPROVED BY ENGINEERING;
UNLESS. THE CONDITIONS OUTLINED IN 4.6.1 EXIST, A 25mm METER INSTALLATION
DOES NOT REQUIRE A BY-PASS,
2, METER AND BY’-PAS~ PIPING TO BE EQUAL SIZE.
3. ALL DIMENSIONS ARE EXPRE.SSED IN mm UNLESS OTHERWISE NOTED.
4. SOLD~RED COPPER PIPE AND FITTINGS MAY BE USED.
LONDON STANDARD DRAWING
’TYPICAL INSTALLATION
l~0we: W-CS-30 sa-r.-~ I
DAYE
25mm, 40ram, & 50mm DISC TYPE WATER METER
APPROVED BY
19S9 O1 30
!
CITY’. , ENGINEER~__~____~.)
.
B
NoL__.II.",,
ALL
DIMENSIONS
ARE
INmmUNLESS
SHOWN
OTHERWISE.
’B
.....
~ E
F
COMPOUND
$~A~DAR~!~IREFLOWI
,
305
431
750
150
100
356
508
I000
200
150
458
610
229
200
508
NA
254
75"
,
FLANGED FITTINGS ARE REQUIRED FOR ALL METERS.
MINIMUM SIZE OF VALVING & BYPASS PIPING TO BE ’
EQUAL TO METER SIZE. ALL VALVES, PIPING, FITTINGS
& SUPPORTS TO BE SUPPLIED & AND INSTALLED. BY OWNER
ALL CHECKVALVES, BACKFLOWPREVENTION, PRESSURE
’.
REDUCINOVALVES~ ETC. RUST BE .INSTALLED AFTER THE
BY-PASSW, HEN F IREFLOWSARE METERED.
"
¯
:
ALL METERS ARE TO BE INSTALLED HORIZONTALLY UNLESS
APPROVED OTHERWI.SEBY ENOINEER,ING.
"
INSTALLATION¯INDICATES THE MIN. SPACE REQUIREMENTS:
IN A MECHANICALOR METEREDROOM. MIN. CLEARANCEFROM
683
1500
796
2000
300
400
’
BY-PASSVALVE
~
IN SHUTPOSITION
(SEALEDBY CITY}
x
’
-
"
.
’
’
"
’
~~
’
~,~ ~==~.
’
t
VI~TAULIC
OR fIN I-FLANGE
CONNECT
I ON
CITY
’
DWG:
OF LONDON
STANDARD
COUPLING~
-
FLOOR
DRAWING
TYPICAL TURBINE’ WATER.METER INSTALLATION" "
FOR 75mm TO 200mm
W-CS-30
. SHm.2
DATE
,,
1999 01 30
APPROVED BY
CITY ENGINEER:
"
NTS
TO STANDPIPE
AND/OR
TO STANDPIPEAND/OR
SEE NOTE3=
--
(M~
-z~/> ......
~,/~’~~
BLDG, WALL
-t-~/~--/>
VALVE-RISING
STEMPREFERRED
........
’ ....
BLDG, WALL
~>-- BLDG, WALL
-"--~
/
I
POSTINDICATORVALVE
IF REQ’DBY UNDERWRITERS
OROWNER,
ST. LINE
_~-I 300
co,
,N,EE
,/---T,,V
----
IF TS&V USED AT /
MAIN.)
/
DOMESTIC SERVICE
IF TS&V USED AT
MAIN.}
CO,
,N,EE
L’~
--
MAIN
_ _
MAIN
(SEE NOTE
DOMESTICSERVICE TAKEN OFF
STANDPIPE AND/ORSPR I NKLERSERV ICE
1. ALL DIMENSIONS
ARE IN mm UNLESSOTHERWISESHOWN,
5,
4.
5.
B.
?.
THE DOMESTICWATER MAY BE TAKEN FROM THE SPRINKLER
SERVICEAND/ORTHE STANDPIPESERVICEINSIDE THE BUILDING
IF APPROVEDBY FIRE UNDERWRITERS.IF NOT, THE DOMESTIC
SERVICESHALL BE INSTALLEDTO THE MAIN AS SHOWN WITH
A MINIMUMOF 500mmSEPARATION
FROM THE FIRE SERVICE.
DOMESTICVALVES,METER AND BY-PASS,IF BY-PASSIS REQUIRED,
SHALL BE IMMEDIATELYINSIDE THE STRUCTUREWALL. VALVES
ARE PREFERREDTO BE RISING STEM. SEE DWG. W-CS-50.
CONTROLAND CHECK VALVES DN FIRE SERVICESSHALL BE AS
REQUIREDBY ONTARIOBUILDINGCODE.
IF THE SERVICEIS OFF A SERVICEMAIN, A TAPPINGSLEEVE
AND VALVE OR A TEE AND VALVE SHALL BE INSTALLEDAT
THE SERVICEMAIN.
SEESHEET 2 FOR DETAILSDF SERVICE.
FOR BACKFLOWPREVENTERREQUIREMENTSREFER TO
ONTARIOPLUMBINGCODE.
CITY OF
,
LONDON
,,,
MAIN
LTS&VOR CUT IN TEE
STANDPIPE AND/OR SPRINKLER.SERVICE
NOTES:
2.
-
LINE
--v
_---T--x-~n--------ST.__L
ST. LINE
_ ~-I 300
IF TS&V USED AT /
MAIN.}
/
BACKFLOW
PREVENTER
SEE NOTE3_
-
B. FOR DuM~STIC SERVICE,THE BACKFLOW
PREVENTERSHALL BE INSTALLED
DOWNSTREAMOF THE METER/BYPASS
ASSEMBLY.
STANDARD DRAWING
, ,
,
,
SCHEMATICLAYOUTOF 100mm AND LARGERSERVICES
DWG: W-CS-31
SliT.
1
DATE
2004 11 01
CITY ENGINEER:
~
......
’
NTS
REV20O402 25
~POST INDICATOR VALVE
OR NO VALVEIF O. S. & Y,
VALVE USED"INSIDEBLDG.
SEE DWG NO. W-CS-BB
FOR ENTRANCEDETAI~S
M d TEE OB TAPPING
SLEEVE & VALVE
--~------M~IN OR
SERVICEMAIN
.
I
-
"
:
UNI-FLANGESMAY
BE USED INSIDE ONLY
T
VALVE
(NOT
REQ’D
IF
TAPPINGSLEEVE & VALVE
OR TEE & VALVE IS USED
AT MAIN)
~--THRUST
BLOCK
OTES
I
ALL DIMENSIONSARE IN n-rn UNLESSSHOWNOTHERWISE
SEE SHEET I FOR TYPICALSERVICELAYOUTS
FIRE AND DOMESTICLINES WILL TERMINATE
WITH FLANGEDENDS INSIDE BUILDING.
ALL FI.TTINGSOUTSIDEBUILDINGSHALL BE M. J.
CAST IRON.
IF THE SERVICE IS OFF A SERVICEMAIN A
TAPPINGSLEEVE & AND VALVE OR TEE AND
AT THE SERV,I.CE
MAIN..
VALVE SHALL BE INSTALLED
CITY OF LONDON STANDARDDRAWING
TYPICAL DETAILS oF lOOmm & LARGERSERVICE
DWG: W-CS-31
SHT.
2
DATE
1999 01 30
CITY ENGINEF_~ , ..,)..
(,,,,~..~
NTS
\
*".,
\
1
1
PROPERTY
1-.11.11-111
WATER
MAIN
LINE
-t
WATER
VALVE
f
1-111-m-m-m
(STANDARD L O C A T I O N )
t
CURB
ROADWAY
NOTES:
T H I S STANDARD MAY NOT APPLY I F CURBS
ARE MORE THAN 5.8m FROM PROPERTY L I N E .
THE O B J E C T I V E I S TO PREVENT VALVES
FROM B E I N G INSTALLED I N THE GUTTER.
CITY
OF
LONDON
STANDARD
DRAWING
STANDARD LOCATION FOR WATER VALVES AT
INTERSECTIONS WITH 9.0m & 10.5m CURB RADII
DWG
w-cs-45
DATE 1999 01 30
APPROVED
BY
CITY ENGINEER:
NTS
al
m
W
az
Sb
L-LZ 1
..
4
0
m
U
0
0
U
0
m
M
0
0
M
0
m
AI
0
0
(v
0
m
c
0
0
-7-
-
Lo
03
v
a3
M
7
IC
N
Q-
u-
N
u-
CD
v
c-
u-
N
0
CD
0
CD
IC
N
u-
c
0
0
Q-
Lo
cn
IC
LD
IC
u-
c-
a
0
a3
0
N
IC
M
u-
Ln
0
&
a3
0
cn
N
Lo
u-
CD
N
cn
N
7
M
IC
M
N
c-
0
N
a
IC
0
M
V ’
N
CD
c-
a3
Ln
Ln
M
M
v
0
0
03
03
7
Lo
M
-
--
M
N
7
cn
N
Ln
0
--Ln
N
---
a.
v)
W
I-
Z
O
v)
z
az
Ia
3I
0
W
ZLL
Z
Z
on
*W
W
c3c3
az
Cn-W
O(3v)
azo
aa
a
L I E
003
I W
I-ZW
c3h-I
z c
WIaaa
I - 0
oz
m>LL
WE>
v)
v)a
I
0
a13
3
O
I
W E
L V
VOCV
CV
Z Z W
a-r
ICII - a
1-3
v)ak
v)
wJa
-la
I a
+no
Zv)
ww
0-LL
n
W
v)
3
m
W
I-
0
a
EKc3
o
LEV)
v)
W
0
I
3
t;
a
I0
i-
z
0
0
W
In
r
-I
n
I
0
I
>
z
c-(
z
W
n
E
0
-I
I
0-4
-I
a
m
W
-I
0
z
I
w a
I
0
0
-I
0
a
z
W
z
E
W
(3
a
I-W
BE
--I
I-+
om
a3
I-m
a
>
a
z
a
I-
n
a
z
z
0
-I
v)
W
0
a
a
W
0
0
z
IC
a
0
W
>
z
+
n
0
v)
a
c3
W
v)
-
a
m
I/)
n
w
a
a
3
I-
F3
z
E
E
0
z
n
v)
-I
2
I-
W
Lo
O
I-
a
LL
W
W
I-
v,
a
z
n
zs
0
I00
0
0
00
no
-2
oa
a
>
I-
a+
a
2
-w
-I
za
a
0
>I
-IX
ao
r L L
ZE
I-
I->
E
W
W
-3
v)
2
W
o
0-
YQ
I-W
5
a
Y
W
m
W
=t,
T
OSL
nv)
0 .
Y
E
I-
aw
h
a
W
0
a
a
Z J
a2
nv)
v)
n
moo
m
- I .
JZLL
-WLL
>I-
ww
I0
v)
005
I-
-E!
z
3:
-J
-I
0
-
a
W
I-
r
a
W
3
a
00
-LQ
W
OI-a
-mz
>wo
aI-0
w w
v)JO
-I
03
k-a
W
Z-lI
3x0
I-
W
E
0
z
az-l
zam
m
.
N
2 3
-00
z
0
-I * E
LL-
-I
I-z
Lon
w w
3aar
m
z-l
-0-l
anWI--B
oa
azz
a-zaa
I-ww
E 0
130-
I-z>
Z3E
0v)W
--Ia
T a m
E m
-ink
waw
I - 0
wv)w
aaz
330
J W -0
a w
a0-I
0C-l
+I-a
azc
a-v)
I - z
v)W-m
-
WLI3
z
--la
W
I-WZi
a3-l
T A W
n--l
W
ZZE
W S
IOLL
I--I-
oi--T:
a-
ozaa
CO
0x0
003
00
I>I
W a c
I-IC-
-
UNI-FLANGEOR KWlK FLANGE
MAY BE USED ABOVE FLOOR ON
STEEL AND DUCTILE IRON PIPE-250mmMIN. WHEN
METER TO BE
INSTALLED AND 150mm
IF NO METER
FINISHED FLOOR
F
¯
¯
FLANGED TO PLAIN END PIPE
55mmx 55mm x 6mm
ANGLEIRON, BOTHSIDES
INSIDE
OF WALL
EDUCTILE
STANDPIPE
16mmROD ON IOOmmSERVICES,
20ram RODON 150ram SERVICES
AND OVER, RODDED
BOTHSIDES
OUTSIDE
INSIDE
THROUGHWALL INSTALLATION
FOOTING
SEE TIE BOLT DETAILS ON W-CS-12
90°M.J. BEND
UNDER FOOTINGINSTALLATION
THRUST BLOCK POURED
AGAINSTUNDISTURBED
SOIL
NOTES:
FOR THE PURPOSE
OF IDENTIFYING THE PIPE MATERIAL
WERE. PLASTIC WATERPIPE IS USEDUNDERGROUND
FOR A
SERVICEPIPE, THE ENDOF THEPIPE INSIDE THE BUILDING
SHALL BE BROUGHTABOVE GROUNDFOR A DISTANCE NOT LESS
THAN 300mm AND NOT GREATERTHAN 450mm IN ACCORDANCE
WITH THE ONTARIOBUILDING CODE.
ALL DIMENSIONSARE SHOWN
IN mm
UNLESSOTHERWISE
SHOWN.
CITY OF LONDON STANDARD DRAWING
TYPICAL SERVICE ENTRANCES
lOOmm TO 200mm
DWG: W-CS-66
J
DATE
I
I
APPROVED BY
CITYENGINEER:
//,~/~.,~,;;.
NTS
REV200402 25
I
ELECTRIC METER LOCATION
/
&
k
J
I
E
09
c
I
,
--;
,_ ,_
1 I I
&
.
FINISHED
GRADE
II
I
I
I
I
I
I
I
BASEMENT
V
1
L
O
0
0
-
V
V
.
v
.
v
v
v 1
-
B
DETAIL AT REMOTE HEAD
INSTALLATION OF REMOTE HEAD AND CONNECTIONS
OF WIRE MADE BY THE CITY OF LONDON
CITY OF
"I\
V
G
LONDON
b
V
.
U
NOTES:
\?-;
G
- *
V
50mm CONDUIT
.
v v
V
I,
V
.
Im COILED WIRE
-
G
- *
WATER METER LOCATION
FRONT WALL
V
.
v v
WATER METER INSTALLATION
0
0
V
.
LREMOTE WATER METER REGISTER TO BE LOCATED
IMMEDIATELY BELOW ELECTRIC METER SECURED TO STACK
2.20 GAUGE-3 COND. SOLID COPPER LVT PLASTIC
INSULATED WIRE WITH OVERALL THERMAL PLASTIC JACKET
TO BE USED IN ALL INSTALLATIONS UNDER 90m.FOR
INSTALLATIONS OVER 90m. CONTACT THE CITY.
3.Im OF COILED WIRE TO BE LEFT AT BOTH WATER
METER AND REMOTE REGISTER LOCATIONS.
4. THE CITY WILL SEAL WIRE IN THE WALL AT THE TIME
OF REMOTE REGISTER INSTALLATION.
5. WHERE ELECTRIC METER IS RECESSED, THE REMOTE
REGISTER SHALL BE SECURED TO THE WALL.
STANDARD
DRAWING
REMOTE WATER METER REGISTER INSTALLATION
NISHED
I NSUL AT I ON
1
0F
.5m
HAS
GRADE
DOW STYROFOAM HIGHLOAD 1OO
EXTRUDED POLYSTYRENE INSULATION
MI
THE WATERMAIN OR THE INSULTAION SHALL
NOT TO BE INSTALLED IN THE ROADBASE
MIN.150nm
N.
TO EXTEND UNTIL MAIN
NATURAL COVER
450rm
BEND
WATERMA I N
SEE NOTE rf4
OBSTRUCT I ON:
IF OFFSET IS LOCATED UNDERA ROADWAYTHEN ITWILL
BE THE RESPONSIBILITY OF THE DESIGNER TO PROVIDE
ENGINEERED STAMPED LIVE LOAD AND DEAD
cALcuLATtoNs ENSURING THE wATÉRMAIN rs pRõtecreo
FORM FREEZING AND LOADING DAMAGE
LOAD
CULVERT, LARGE
STORM SEWER.
PEDESTRIAN TUNNEL,
I
ETC.
ELEVATION OF JOINT DEFLECTON OFFSET
SAME PROCEDURE ulILL APPLY TO
OFFSETS SHOWN ON DWG. W-CS-12
NOTES:
MI N.
ALL D¡MENSIONS ARE lN
INSULAT
nm UNLESS SHOWN OTHERWISE.
I ON
IIìIATERMA¡N
2.
MINIMUM COMPRESSIVE STRENGTH OF INSULATION TO BE
69OKÞo. INSULATION SHALL BE INSTALLED ¡N THIcKNESS
1
+
SEtt/ER
SEE NOTE
REOU¡RED, IN STRICT ACCORDANCE WITH THE INSULATION
MANUFACTURER,S DIRECTIONS. INSULATION SHALL BE INSTALLED
ÛVER l5OTTm OF FINE GRANULAR FILL SCREEDED SMooTH.
BUTT ¡NSULATION TIGHTLY TOGETHER WITHOUT GAPS, STAGGER
END JOINTS IF MORE THAN ONE LAYER USED.
TO HOLD IN PLACE. SKEWER INSULATION BOARD TO
WITH 200nm HARDWo0D SKEUIERS.
LONG. 2 SKEWERS PER BOARD.
MiN. 6nrn DIA.
]F PIPE IS PVC,
4.
MIN.
W-CS-12 DETAIL.
TOP
AND
FILL ovER
INSULATI0N
OFFSET MUST BE MADE USING
CLEARANCE AS PER
7.4.7.2.
M.O.E.
C OF
L
DESIGN SPECIF¡CATIONS
PROCEDURE
I NSUL AT ] ON
TH I CKNESS
C( m)
ï( mm)
0. 60
0. 75
0. 90
75
75
50
r
.09
50
1
,20
25
1.35
25
F-6-I.
LONDON STANDARD
DRAWING
INSULATION OF SHALLOW WATERMAIN AND OFFSETS
IN BOULEVARDS
DATE
2or
...\standardsW.dgn 2012-03-28 2:lS:13 pM
z 01 26
APPROVED
CITY
AU
AND 20Onm
LONGER THAN THE COMBINED THICKNESS OF THE 2 LAYERS OF
INSULATION. INSERT SKEWERS AT APPROXIMATELY 30" ANGLE.
3.
SECTION "A _
GROUND
IF 2 LAYERS OF INSULATION ARE USED. SKEWER ONLY THE
LAYER THROUGH THE FIRST LAYER USINC A SKEWER rsorffn
PLACE AT LEAST 200n¡m oF FINE GRANULAR
BEFORE USING COMPACT¡ON EOUIPMENT.
5onm
BY
ENGINEER:
I NSULAT I ON
!l/ I DTH
B( m)
0.45
0.60
0,75
0.90
W(
m)
2.44
1 .83
1.54
1.?2
TT4
Additional supports each
side of pipe joint and
at each end of excavation
Label max distance between supports
Min 1.0m from edge oftrench
Detail support system
Specify support spacing,
maximum 1.0m OC
typically hardwood
lumber blocking bolted
together, with steel bearing
plate attached.
il-r r-
Level ground ./undisturbed surface
or if disturbed,
to be compacted to
100%
S.P.M.D.D. and soil bearing capacity
=t'=l
to be measured
Specify how to attach
support roads to beam
Trenching
with M.O.L. guidelines.
Verify &
label depth
Existing Watermain
ïrench box
to comply
chains are not
acceptable.
if
appropriate.
Proposed pipe to
cross existing wm.
label elevation of
pipe invert
TYPICAL SUPPORT CROSS SECTION
SEE DRAWING W_CS-69,3 FOR REQUIREMENTS
SHEET
CITY
OF LONDON
STANDARD
DRAWING
450mm AND UP TYPICAL WATERMAIN SUPPORT DETAIL
FOR UTILITY CROSSINGS USING OPEN CUT CONSTRUCTION
DWG:
W-CS-og
sHEEr
1
2012-10-11 8:46:52 AM
Min 1.0m from edge of trench
Existing ground
Unshrinkable fill, minimum
0.6m below existing pipe
up to centreline. Depth of
unshrinkable fillto be
Level ground /undisturbed surface
or if disturbed, to be compacted to 100%
S.P.M.D.D. and soil bearing capacity
to be measured
Trenching
=l
to
comply
with M.O.L. guidelines,
determined based on
size of existing wm,
Existing Watermain
Cut
Verify &
into side slopes
0.6m in order to
lableldepth
place
unshrinkable fill
Granular bedding
to be installed to
City of London Standards.
-
Proposed pipe to
cross existing wm.
label elevation of
-
pipe invert.
WPICAL REINSTATEMENT /BEDDING DETAIL CROSS SECTION
-
The watermain shall be protected by the following:
When crossing under or over the watermain there must be a
minimum separation of at least 0.6m between the outside
diameters of the crossing pipes.
A minimum 5.0m length of pipe shall be centered at the point
of crossing so that the watermain joints will be equidistance
and as far as possible from the sewer or PDC. Crossing must
be absolute minimum 2.0m from watermain joint.
All construction methods including excavation and backfill
compaction within 0.6m of existing watermain shall be done by
hand.
should be noted that the support structure is to remain in
place until the watermain is fully supported by the reinstated
bedding (i.e, until SMPa unshrinkable fill is cured, provide bond
It
SEE DRAWING W-CS-69,_
SHEET 3 FOR REQUIREMENTS
break).
CITY
OF
LONDON STANDARD
DRAWING
TYPICAL REINSTATEMENT /BEDDING DETAIL
FOR 450mm AND UP WATERMAIN SUPPORT
...\standardsV7 .dgn 2012-10-1 1 8:48:22 AM
SUPPORT DETAIL REQUIREMENTS
BEDDINGAEINSTATEMENT DETAIL REQUIREMENTS
Submission and Design Requirements
Submission and Design Requirements
When crossing below an existing watermain (450mm Dia. and greater)
using open cut construction, the following must be provided to the City of
London Water Engineering Division for revierar-âpprovala minimum of
two (2) weeks prior to the proposed work taking place:
A) ô lrtit,V supportsystem drawing stamped by a professional Engineer,
including the following: (See W - CS - 69.Sheet# l forTypiõal
Drawing
(D
(ii)
)
Complete plan and cross-section drawings indicating
support system including allappropriate dimensions and
(iv)
Typical Drawing)
(A)
Provide allstructuralcalculations forsupportsyslems
including load and deflection informat¡on for proposed
beam. Provide delails to confirm adequacy of support
mechanism proposed to transferloading ofsupported
(B)
(C)
to
support beam.
Provide calculations for loading transferred
to the end
supportofthe beam structure and confirm adequate soil
bearing capacity forthe system designed forbeam
support beâm.
(D
ldentification of maior act¡vit¡es to be canied out in
association with the utility crossing.
(i¡) A schedule of these works.
ffivffioring-€f support system for deflection.
be allowed to
proceed
The work may notproceed until allofthe above are received and
approved. Please note that traffic control plans affecting the City of
London Right-of-Way, il required, are to be submitted for approval
separately to the Transportation Engineering DMsion. Atalltimes,all
requirements of the Occupational Health & Safety Act must be met.
(iii)
2)
installed.
There is less than 600mm separation between the
utilities crossing each other, OR
Either structure is greater than 1000mm in diameter,
OR
lnsulation is being placed between the utilities.
Contractor's work plan. The work plan shall include the following:
(A)
(B)
ldentif¡cation of major actMties to be carried out in
association with the utilþ crossing.
A schedule ofthese
works.
Under no circumstances willthe work be allowed
under adverse weather conditions.
to
proceed
The work may not proceed until allof the above are received and
approved. Please note that traffic controlplans affecting the City of
London Right-of-Way, if required, are to be submitted for approval
separately to the Transportation Engineering Division. Atalltimes, all
requirements of the Occupational Health & Safety Act must be met.
LONDON STANDARD
DRAWING
GENERAL SUBMISSION AND DESIGN REQUIREMENTS
FOR WATERMAIN SUPPORT AND BEDDING /REINSTATEMENT
20'l 2-1 0-29 1 0:35:52 AM
to be
To prevent settlement of wate¡main, install0.TMPa unshrinkable fill
with bond breaker (ie 6mil poly) to a minimum 600mm b€low
watermain up to the centreline OR obtain recommendations
regarding watermain bedding from the watermain pipe
(¡D
Contractor's work plan. The work plan shall include the following:
Under no circumstances willthe work
under adverse weather conditions.
lf appropriate, identifo insulation
(i)
ldenti! procedure fortransfening load ofstruclure to be
to
-
Cross
section drawing(s) including allappropriate
dimensions and details.
manufacture, if any of the following apply:
supports.
supported
B)
1) When cross¡ng watermains 450mm and greater a drawing(s) must be
submitted indicating reinstatement and bedding is required. The
drawings shall include the following: (See W - CS - 69, Sheet # 2 for
details.
utility
(¡iD
When crossing below an ex¡sting watormain (450mm Dia. and greater)
using open cut construct¡on, the following must be provided to the City of
London Water Engineering Division for revieurâpprovala minimum of
two (2) weeks prior to the proposed work taking placei
ARMOR CONTROL VALVE ACCESS BOX
EXISTING
AND
FORD TYPE "W" I{ABASH
DOUBLE LID COVER
(OR EOUIVALENT)
GRADE
LID
WAITS DOUBLE CHECK
VALVE BACKFLOVI
PREVENTION
PIT
PREVENTION ASSEMBLY
TO IRRIGATION
CURB VALVE AND
SERVICE
WAÏERMAIN
FOR fHE PROTECTION OF ]HÊ WATER PURVÉYOB'S DISTRIBUTION SYS'TEM, ALL
IRRIGATION SYSTEIVS MUST BE METERED AND MUST IIAVE AN APPROVED BACKFLOW
IS COMPATBLE WTH THE DEGREE OF
300nm
0F 1 gnfn SToNE
2o0nm
AROUND BACKFLoVI
FORD PVC CYLINDER
(OR EOUIVALENT}
ME]-ERED IHRIGATION SYSTEM AND BACKFLOW PREVENTION ASSEMBLY
PBEVENÎION ASSEMBLY THAT
SYSTEM
BOX
25fÍm PEX SERVICE
( MIN. )
EX.
(OR EOUIVALENT)
300nm
0F lgrlm]ST0NE
2oofin
AROUND METER
PIT
AND
PIT
SETTER
ANE
PIT
HAZARD.
BACKFLOW PREVENTION DEVICES SI.{ALL BE INSIALLED IN ACCORDANCE WITÞi
THE ONIARIO BUILDING CODE AND CAN /CAS-864 SEI'.ECTION AND INSTALUTION
OF-IIIE BACKFLOW PREVENTERS /MAINTEMNCE ANO FIELD TESTING OF BACKFLOW
PREVENÍEBS
AND CMY OF LONDON WATER BY-{AW W€,
ALL BACKFLOW PRÉVENTION DEVICES SHALL BE INSPECIED AND IESIED AT
THÉ Ð(PENSE OF THE OWNER, UPON INSTAUÂÏON, AND THEREAFTER ANNUAI-LY,
'
OB MORE OFIEN IF REQUIRED BY-THE CITY, BY PEBSONNEL APPROVED BY THE
CffI TO CARRY OUT SUCH IESTS TO DEMONS'IRATE 'THAT THE DEVICE IS IN
GOOD WORKING ORDER.
WAIER MEIER PITS ARE TO BE IN ACCORDANCE WTH 'ÍHE SECI|ON ,t41,0S.22
OF THE CITY OF LONDON STANDARD CONTRACT DOCUMENTS FOR MUNICIPAL
CONSTRUCTION PROJECTS AND THE MANUFACTURER'S RECOMMENDATIONS.
LONDON STANDARD
DRAWING
METERED IRRIGATION SYSTEM AND BACKFLOW PREVENTION ASSEMBLY
DWG w-cs-71
2012-03-3011:21:11 AM
Download