Technical information Assembly instructions Uno-3 (95-125) Oil/gas boilers These instructions are applicable to the following types: 7-Uno-3 (95,110,125) 7-Uno-3 b-i* (95,110,125) * = Burner integrated Hoval products must be installed and commissioned only by appropriately qualified experts. These instructions are intended exclusively for the specialist. Electrical installations may only be carried out by a qualified electrician. Subject to modifications | 4 205 116 / 02 - 02/14 Uno-3 (95-125) boilers are suitable and licensed for use as heat generators for hot water heating systems with a permissible flow temperature of up to 100 °C1). They are designed for closed-circuit systems, but can also be installed in open systems as per EN 12828. 1) See technical data EN Table of Contents 1 4 205 116 / 02 Important information 1.1 Other instructions.................................................................................................................................... 3 1.2 Safety information.................................................................................................................................... 3 1.3 Regulations, official approvals............................................................................................................... 3 1.4Guarantee................................................................................................................................................. 4 2.Installation 2.1 2.2 2.3 3 Setting up, levelling................................................................................................................................. 5 Fitting the heat insulation....................................................................................................................... 6 Fitting the casing..................................................................................................................................... 8 Technical information 3.1 Description of the boiler........................................................................................................................ 10 3.1.1 The Uno-3 (95-125) complies with the following directives + standards ................................................. 10 3.2 Technical data Uno-3 (95-110) for Switzerland.................................................................................... 11 3.3 Technical data Uno-3 (110,125) for all other countries....................................................................... 12 3.4Dimensions............................................................................................................................................. 13 3.5 Dimensions without heat insulation and casing (transport dimensions)......................................... 13 4.Installation 4.1 Boiler room requirements..................................................................................................................... 14 4.2 Connection of the flue gas system and flue duct dimensions.......................................................... 14 4.3 Fitting the burner................................................................................................................................... 16 4.3.1 Sound insulation....................................................................................................................................... 16 4.4Fuel.......................................................................................................................................................... 17 4.5 Electrical connection............................................................................................................................. 17 4.5.1 Electrical connection of the burner........................................................................................................... 17 4.6 Flue gas regulator set............................................................................................................................ 17 4.6.1 Flue gas and performance diagrams....................................................................................................... 18 4.7 Flow mixing loop / minimum limitation of the boiler return temperature......................................... 19 4.8 Setting the temperature regulators...................................................................................................... 19 4.9 Safety valves.......................................................................................................................................... 19 4.10 Charging pump (boiler with free-standing calorifier)......................................................................... 19 4.11 Heating pump......................................................................................................................................... 19 5.Commissioning 5.1 Water quality........................................................................................................................................... 20 Heating water........................................................................................................................................... 20 Filling and replacement water.................................................................................................................. 20 5.2 Filling the heating system..................................................................................................................... 21 5.3 Filling the calorifier (if present)............................................................................................................ 21 5.4Commissioning...................................................................................................................................... 21 5.5 Oil/gas burner......................................................................................................................................... 21 5.6 Handover to the operator / storage...................................................................................................... 21 6.Maintenance 6.1 Information for fire inspector / chimney sweep regarding emission monitor key........................... 22 6.2Cleaning.................................................................................................................................................. 23 6.2.1 Preparatory work...................................................................................................................................... 23 6.2.2 Cleaning (dry or wet method)................................................................................................................... 23 6.2.3 Putting into operation again..................................................................................................................... 23 7. 7.1 7.2 2 Overview of settings Table of parameters............................................................................................................................... 24 Overview of alarms TopTronic®T........................................................................................................... 34 4 205 116 / 02 1 1.1 Important information Other instructions All instructions relevant to your system can be found in the Hoval system manual! In exceptional cases, the instructions can be found enclosed with the components. Further information sources - Hoval catalogue - Standards, regulations 1.2 Safety information The system may only be placed in operation if all the relevant standards and safety regulations have been complied with. At least the following conditions must be satisfied for a trial operation: 1. Safety valve installed (closed system). 2. Control in operation (connected to the mains current supply system). 3. Sensor for the safety temperature limiter mounted in the immersion sleeve. 4. System filled with water. 5. Expansion vessel connected. 6.Flue gas connectors connected to the flue gas pipeline at the chimney or flue. 7. An adequate supply of fresh air must be guaranteed. 8. The burner is preset. 1.3 Regulations, official approvals The following regulations are to be complied with for installation and operation: Germany - DIN EN 12831 Heating systems in buildings – Method for calculation of the design heat load. - EN 303 Heating boilers with forced draught burners. - DIN EN 12828 Sheet 1 and 2 Heating systems in buildings – design of waterbased heating systems. - DIN 4755 Oil-fired systems. Design, construction and safety engineering requirements. - DIN 4756 Gas-fired systems; construction, execution, technical safety requirements, planning and execution. - DIN 18160 House chimneys; requirements, planning and execution. - TRD 702 Steam boiler plants with calorifiers of the group II. - DIN EN 13384 Chimneys – Thermal and fluid dynamic calculation methods. Important notes - TRD 721 Safety devices against excess pressures / safety valves / for steam boilers of Group II. - VDI 2035 Prevention of damage by corrosion and the formation of scale in hot water heating systems. - DIN 57 116 / VDI 0116 Electrical equipment for firing systems (VDE Regulation). - For further standards applicable in Germany, see appendix N-430 020. Austria - ÖNorm 7550 - ÖNorm B 8130 Open water heating systems; safety devices. - Norm B 8131 Closed water heating systems; safety, execution and testing requirements. - ÖNorm B 8133 Hot water production systems; technical safety requirements. - ÖNorm B 8136 Heating systems, space requirements and other building requirements. - ÖNorm M 7515 Calculations of dimensions of chimneys; terminology, calculation procedure. - ÖNorm H 5171 Heating systems, construction engineering requirements. - ÖVGW TR-Gas G1 Technical directives for low pressure gas installations. - ÖNorm M 7445 Gas blower burner. Switzerland - Requirements of the VKF Cantonal Fire Insurance Association. - Fire brigade regulations. - Requirements of the SVGW Swiss Association of Gas and Water Suppliers. - SWKI 91-1 Aeration and ventilation of the boiler installation room. - SWKI 88-4 Water treatment for heating, steam and air conditioning systems. - SWKI 93-1 Safety engineering installations for heating systems. - KRW Corrosion through halogen compounds. - KRW/VSO/FKR Plug-in electrical connections on heating boilers and burners and further regulations and standards issued by CEN, CEN ELEC, DIN, VDE, DVGW, TRD and the legislative body. Also to be complied with are the regulations of the local building authorities, insurance companies and chimney sweeping operations.The regulations of the responsible gas supply company are also to be complied with and any necessary official approval obtained. 3 Important notes 1.4Guarantee Proper function is only guaranteed providing these instructions are followed and the boiler is regularly maintained by a licensed specialist. (Maintenance contract). The rectification of faults and damage as a result of contaminated operating materials (gas, water, combustion air), unsuitable chemical additives and an inadmissibly high lime content of the heating water, improper handling, faulty installation, unauthorised modifications and damage due to the use of force do not fall under our guarantee obligations, this also applies to corrosion due to halogen compounds, e.g. from spray cans, paints, adhesives, halogenated fluids, solvents and cleanings agents. 4 4 205 116 / 02 Installation 4 205 116 / 02 2.Installation 2.1 Setting up, levelling A special foundation plate for the boiler is not an essential, but it is recommended. Space requirement for mounting the thermal insulation and sheet metal cladding: at least 40 cm each on the left and right side of the boiler. If the space between the boiler and the wall is less, all heat insulation and casing must be fitted before the boiler can be pushed into its final position. Boiler door pivotable to the left It is possible to change the attachment of the boiler door so that it opens towards the left. This can be of advantage when installing the boiler in a corner. Proceed as follows: Close the boiler door and lock it in position before changing the attachment of the door. 2 1 Do not connect lines until the heat insulation and casing have been fitted to the boiler! There must always be enough space between the back of the boiler and the wall to allow easy access to the cleaning aperture in the flue gas collector. There must be enough space to swing open the boiler door, incl. the burner. Do not overtighten boiler door screws. Fig. 2 1. Pull up the semicircular rivet (1). 2. Change over the swivel arm (2). 3. Insert the semicircular rivet (1) on the other side. 4. Fit the burner plug and the fire protection switch (if fitted, Austrian version) on the other side (see point 2.3, item 9 and point 4.5.1). The cable must not touch any hot parts! Levelling Using a spirit level, align the upper edge of the boiler water jacket (longitudinal axis of the boiler) until it is precisely horizontal or sloping very slightly upwards towards the rear by inserting the plinth rails correspondingly, to allow the boiler to vent properly. Before fitting the burner, first fit the double door (Pos. 8b, Figure 7) (door casing). 5 6 Fitting the heat insulation The remaining 3 insulation mats (8a,10) are fitted after mounting the casing. Fig. 3a 7. Attach insulation panel (7) to the pins welded onto the front wall of the boiler and secure with the retaining discs (ø 38) provided, Fig. 3a. 6. Attach insulation panels (6/6a/6b/6c) to the pins welded onto the flue gas collector and secure with the retaining discs (ø 38) provided. 5. Attach the insulation mats (5/5a/5b) to the pins provided on the rear wall of the boiler and secure with retaining discs, Fig. 4a (ø 38). 4. Attach the insulation mat (3) using 2 plastic straps (4) and strap fasteners (4a): - Tension springs (4b) serve for additional fixing - Do not overtighten the straps (reduced insulating value) 3. Place the insulation mat (3) around the boiler body (with the joint at the top, black side facing outwards, see Figure 3). 2. Mount the rear retaining bracket (2) with hexagon screws M8, nuts and U-washers aligned horizontally. - Attach C-clips. 1. Mount the front retaining bracket (1) with hexagon screws M8, nuts and U-washers, aligned horizontally, to the front wall of the boiler. - Attach C-clips. 2.2 See separate assembly instructions for boilers with mounted calorifier Installation 4 205 116 / 02 7 Figure 3 4a 4 4b 3 C-clips 5b 6 1 6b 5 5a 2 C-clips 6a 6c 4 205 116 / 02 Installation 7 8 Attention: The capillaries must not be folded or kinked! 9 Figure 4 13a 16. Affix labels and where applicable, mount manual holder on the side. 12c 13a 15. Position cladding cover (15) and fix left and right with 2 self-tapping screws ø 4.8 x 13. 14. Attach cover plate (14) with self-tapping screws ø 3.5 x 6.5 and serrated washers. Figure 5 12b 12a 12 13 13c Figure 6 13. Pull the capillaries with the immersion sensors (13, Fig. 6) through the opening (13a, Fig. 5) in the cover, insert them into the immersion sleeve (13b, Fig. 7) as far as the stop and fix in position with retaining spring (13c, Fig. 6). 2.4 Installation of boiler controller 12. Mount the special screw with nut (12, Fig. 5) on the cover plate (12a). Then place switch control box (12b) on the casing cover (12a) with the recess for the special screw, push back and secure with self-tapping screws ø 3.5 x 6.5 and serrated washers (12c). Position cladding cover (12a, Fig. 7) and fix on the side walls with 2 self-tapping screws ø 4.8 x 12 and C-clips. 11. Attach rear wall (11/11a) to the angled edges of the side walls (9a) with self-tapping screws ø 3.5 x 6.5. 10. Place 2 insulating mats (10) left and right in longitudinal direction (to prevent vertical air circulation). The cable must not touch any hot parts 9. Attach the burner cable (9) to the right or left side wall (9a) (Fig. 4). See also point 4.5.1 Attach right and left side wall (9a) onto the front retaining brackets (1) and rear retaining brackets (2) with self-tapping screws ø 4.8 x 38 and pull the burner cable upwards. Fitting the casing 8. Fix hexagon bolts with U-washers and hexagon nuts (8). Insert thermal insulation (8a) into the boiler door. Attach the door casing (8b) to the boiler door using hexagon cap nut. 2.3 Installation 4 205 116 / 02 8b 8a 8 13b 9a 10 12a Figure 7 14 9a 15 11 11a 4 205 116 / 02 Installation 9 Technical information 3 3.1 4 205 116 / 02 Technical information Description of the boiler The Uno-3 is a threepass boiler. At the end of the circular cylindrical combustion chamber, the flame gases flow through several cylindrical tubes arranged above the combustion chamber and towards the front to the turning chamber, from where they flow through rectangular ducts (thermolytic heating surface) towards the rear and reach the flue gas collector. The flue gas temperatures can be varied within a specific range through the installation of various regulator combinations. Figure 8 3.1.1 The Uno-3 (95-125) complies with the following directives + standards 10 We hereby declare that the product described, as an individual appliance, complies with the standards, guidelines and technical specifications laid down. Directives: 90/396/EC 92/42/EC 73/23/EEC 89/336/EEC 97/23/EC "Gas Equipment Directive" "Efficiency directive" "Low-voltage directive" "Electromagnetic compatibility" "Pressure Equipment Directive" (PED) Regulations: Stability Building requirements Low voltage EMC prEN14394:2001 EN303-1, EN303-2, EN303-3 DIN VDE 0722 / Ed. 04.83 EN 50082 Part 1 / Ed. 01.92 Technical information 4 205 116 / 02 3.2 Technical data Uno-3 (95-110) for Switzerland (95) (110) • Nominal heat output at 80/60 °C 1 • Thermal output • Maximum heat input Type kW kW kW 95 60-95 102.1 110 70-110 118.3 • Maximum boiler operating temperature 2 • Safety temperature limiter setting (water side) 2 • Operating/test pressure at max. operating temperature 90 °C 2 °C °C bar 90 110 4.0/5.2 90 110 4.0/5.2 • Maximum boiler operating temperature 3 • Safety temperature limiter setting (water side) 3 • Operating pressure at max. operating temperature 105 °C 3 °C °C bar 105 120 3.0 105 120 3.0 • Minimum boiler operating temperature • Minimum boiler return temperature • Minimum flue gas temperature at boiler °C °C °C see table of operating conditions (below) see table of operating conditions (below) see table of operating conditions (below) • Regulator set for 160 °C Flue gas temperature • Boiler efficiency at full load and 80/60 °C (related to net/ gross calorific value, heating oil EL) • Boiler efficiency at partial load 30% and return 37 °C (acc. to EN 303) (related to lower/upper calorific value heating oil EL) • Standard efficiency at 75/60 °C (DIN 4702 Part 8) (related to net/gross calorific value, (heating oil EL)) • Standby losses qB at 70 °C 3R5+ 3R5+ 1R2/290 2R3/290 % 92.6 / 87.4 92.7 / 89.5 % 94.8 / 89.4 94.8 / 89.5 % 95.7 / 90.3 95.9 / 90.47 Watts 400 400 • Resistance on the heating gas side at nominal output 160 °C flue gas temperature, 12.5 % CO2 , 500 m above sea level (tolerance ±20 %) • Flue gas mass flow at nominal output 12.5 % CO2 heating oil mbar 0.65 0.89 kg/h 162 188 • • • • • Flow resistance boiler 4 Hydraulic resistance at 10K Hydraulic resistance at 20K Water flow rate at 10K Water flow rate at 20K z-value mbar mbar m³/h m³/h 0.2 13.35 3.34 8.17 4.09 0.2 17.90 4.47 9.46 4.73 • • • • Boiler water content Boiler gas content Insulation thickness of boiler body Weight (incl. casing) litres m³ mm kg 250 0.1848 80 391 250 0.1848 80 391 dB(A) 77 79 • Sound level 5 - Heating noise without absorber hood (EN 15036 Part 1) - Heating noise with absorber hood (EN 15036 Part 1) dB(A) 67 67 - Flue gas noise inside the flue (EN 15036 Part 2) dB(A) 87 91 - Flue gas noise radiated from the mouth (DIN 45635 Part 47) • Combustion chamber dimensions Ø-inside x length • Combustion chamber volume dB(A) mm m³ 79 84 ø440x974 0.148 ø440x974 0.148 • Dimensions see Dimensions • Maximum depression in flue gas system (boiler connection) 3 4 5 1 2 Pa 30 30 At nominal output, the pollutant limit values and flue gas losses as per regulation LRV 92 (CH) are complied with. Controller U3.1 and T2.2 Controller U3.2 and T0.2 Flow resistance boiler in mbar = flow rate (m3/h)2 x z Data valid for Hoval oil compact heat station b-i Possible operating conditions Fuel min. flue gas temperature Heating oil EL °C Natural gas H Option 1 Option 2 Option 3 Option 1 Option 2 Option 3 130 110 130 130 110 130 min. boiler temperature °C 48 50 52 58 60 62 min. return temperature °C 35 38 No lower limit 45 48 No lower limit Return temperature controls yes yes no yes yes no Boiler start-up protection 1 no no yes no no yes 1 Boiler minimum temperature limit effective on group actuators 11 Technical information 3.3 4 205 116 / 02 Technical data Uno-3 (110,125) for all other countries Type (110) (125) kW kW kW kW 110 70-110 50-110 118.3 125 70-125 50-125 135.8 • Maximum boiler operating temperature 1 • Safety temperature limiter setting (water side) 1 • Operating/test pressure at max. operating temperature 90 °C 1 °C °C bar 90 110 4.0/ 5.2 90 110 4.0/ 5.2 • Maximum boiler operating temperature 2 • Safety temperature limiter setting (water side) 2 • Operating pressure at max. operating temperature 105 °C 2 °C °C bar 105 120 3.0 105 120 3.0 • Minimum boiler operating temperature • Minimum boiler return temperature • Minimum flue gas temperature at boiler °C °C °C • • • • Nominal heat output at 80/60 °C Heat output range (heating oil EL, natural gas H: variant 1 and 3) Heat output range (heating oil EL, natural gas H: variant 2) Maximum heat input see table of operating conditions (below) see table of operating conditions (below) see table of operating conditions (below) • Regulator set for 170 °C flue gas temperature • Boiler efficiency at full load and 80/60 °C (related to lower/upper calorific value (heating oil EL)) • Boiler efficiency at partial load 30 % and return 37 °C (acc. to EN 303) (related to lower/upper calorific value (heating oil EL)) • Standard efficiency at 75/60 °C (DIN 4702 Part 8) (related to lower/upper calorific value (heating oil EL)) • Standby losses qB at 70 °C • Resistance on the heating gas side at nominal output 180 °C flue gas temperature, 12.5 % CO2 , 500 m above sea level (tolerance ±20 %) • Flue gas mass flow at nominal output 12.5 % CO2 heating oil • • • • • • Maximum flue draught Flow resistance boiler 3 Hydraulic resistance at 10K Hydraulic resistance at 20K Water flow rate at 10K Water flow rate at 20K • • • • Boiler water content Boiler gas content Insulation thickness of boiler body Weight (incl. casing) % % 3R5+2R3 3R5+2R3 92.7/ 87.6 92.8/ 87.6 94.8 /87.6 92.8 /87.6 95.9/ 90.5 95.8/ 90.4 Watts 400 400 mbar 0.89 1.10 kg/h 188 222 Pa z-value mbar mbar m³/h m³/h 20 0.2 17.90 4.47 9.46 4.73 20 0.2 24.80 5.80 11.10 5.40 litres m³ mm kg 250 0.1848 80 391 250 0.1848 80 391 • Sound level 4 - Heating noise without absorber hood (EN 15036 Part 1) dB(A) 79 80 - Heating noise with absorber hood (EN 15036 Part 1) dB(A) 67 67 - Flue gas noise inside the flue (EN 15036 Part 2) dB(A) 91 91 - Flue gas noise radiated from the mouth (DIN 45635 Part 47) dB(A) 84 84 ø440x974 0.148 ø440x974 0.148 • Combustion chamber dimensions Ø-inside x length • Combustion chamber volume mm m³ • Dimensions see Dimensions • Maximum depression in flue gas system (boiler connection) 2 3 4 1 Pa 30 30 Controller U3.1 and T2.2 Controller U3.2 and T0.2, operating pressure may be increased to 4 or 5 bar in countries in which the Pressure Equipment Directive is not in force. Flow resistance boiler in mbar = flow rate (m³/h)2 x z Information applies to combinations with Hoval-tested oil burner Possible operating conditions Fuel Heating oil EL Option 1 Option 2 Natural gas H Option 3 Option 1 Option 2 Option 3 min. flue gas temperature °C 130 110 130 130 110 130 min. boiler temperature °C 48 50 52 58 60 62 min. return temperature °C 35 38 No lower limit 45 48 No lower limit Return temperature controls yes yes no yes yes no Boiler start-up protection 1 no no yes no no yes 1 If the boiler temperature is or drops below the minimum boiler temperature (variant 3) and there is no return maintenance then the load must be switched off using a corresponding control function. 12 Technical information 4 205 116 / 02 3.4Dimensions 9 7 (Third-party burner) 10 12 11 3 1 4 13 1 2 3 4 5 6 7 8 9 10 11 12 13 Flow type 130-160 DN 50, PN 6 Return type DN 50, PN 6 Safety flow R 1 ¼" Flow for calorifier R 1 ¼" Return for calorifier R 1 ¼" Drain pipe R 1" Flue gas outlet Cleaning aperture Boiler controller Boiler door attached on the right (on the left if desired) Burner absorber hood Connection for burner cable (burner plug) E-cable infeed 8 5 2 6 3.5 Dimensions without heat insulation and casing (transport dimensions) Boiler (without calorifier) incl. swivel flange, connections and flue gas collector 13 Technical information 4.Installation 4.1 Boiler room requirements Regarding the building specifications for boiler rooms and their supply and extract air handling, the current building supervisory office regulations specific to the state or country are to be observed. In Germany the firing regulations for the individual Bundesländer are to be complied with. Make sure there is an adequate supply of fresh air to the boiler room, to ensure that the combustion air supply necessary for all the firing systems operated there can flow in without hindrance and that no oxygen deficiency occurs for the operating personnel. Binding values for the size of supply air openings are not generally specified in the relevant regulations; it is merely required that no partial vacuum in excess of 3 N/ m2 occurs. An opening or line leading into the open air of at least 150 cm2. For every kW in excess of 50 kW, a further 2 cm2 must be calculated. In rectangular openings, the ratio of the sides should not exceed 1.5:1; if a grid is fitted, an appropriate allowance must be added so that the free cross-section area reaches the amount given above. In Austria ÖNorm H 5171 additionally stipulates a flue air aperture. This must have a minimum cross section of 180 cm2 up to a rated heat output of 100 kW. For every further kW, the cross-section must be increased by 1 cm2. 4 205 116 / 02 Existing flue gas systems may require upgrading or adjustment of the flue duct cross-section as indicated by a chimney engineer. The correct functioning of the flue duct, i.e. the generation of the required delivery pressure depends on: a) the type (nature) of the chimney (thermal insulation, interior surface roughness, sealing etc.) b)the connection of the boiler to the chimney according to specification c)establishing the correct flue duct cross-section dimension. ref. a) Chimneys according to EN 13384, part 2, execution types I and II are appropriate for modern firing systems (advice from the chimney specialist is necessary). to b) The flue gas pipe connecting the boiler to the flue gas system must be as short as possible and placed at an angle of 30-45°. The entry location of the flue gas pipe must be carefully sealed. The introduction of the flue gas pipe into the chimney (a) must be executed so that no condensate water can flow from the chimney into the flue gas pipe and the boiler. (Fig. 10) The flue gas system must be watertight, acidproof and approved for the corresponding flue gas temperatures. As a general rule, only one heat generator should be connected to the chimney! When using two heat generators, the corresponding regulations must be observed. 4.2 Connection of the flue gas system and flue duct dimensions To guarantee economic and fault-free operation, boiler and chimney must be mutually adapted to create a functional unit. Moisture-resistant and acid-proof flue gas systems must be used in new installations. 14 a Figure 10 Where possible, avoid 90° bends in the flue gas system! Flue gas pipes longer than 1 m are to be insulated. Technical information 4 205 116 / 02 Normally only one heat producer may be connected to the chimney! Flue gas pipes longer than 1 m are to be insulated. If an adapter (reducer) from the flue gas outlet of the boiler to the entry point into the flue gas system is required, it must take the form of a slim cone. from vom the boiler Kessel Basic data: Flue gas pipeline 5 m long, 2 90° elbows and 1 45° elbow, outside air 15°C, height above sea level max. 800 m, flue gas pipeline same ø as flue gas connector on boiler. You are recommended however to use the services of the chimney specialist right from the planning stage! to the zum chimney Schornstein to c) Dimensioning the chimney cross section. The cross sections are to be calculated for boilers without delivery pressure requirement according to EN 13384. (Please also observe DIN 18160, Part 1 "Domestic chimneys"). Take into consideration location-specific factors (hillside location of the building, chimney position, slope of the roof, chimney stack exit shape, etc.)! In Switzerland, take note of SIA Recommendation 384/4! In Austria, calculation is performed as prescribed by ÖNorm M 7515. Non-binding guide values for dimensioning of the flue duct for boiler types Uno-3 (95-125). Inside diameter of flue duct in mm Boiler type Uno-3 kW * Chimney height 11-15 m 95 95 ~ 180 110 110 ~ 180 125 125 ~ 180 *kW = maximum boiler output 15 Technical information 4.3 4 205 116 / 02 Fitting the burner - Depending on the size of the burner flange, an intermediate flange may be required to attach the burner. - To allow the burner to be swung out 90° to the left or right, the connections must be flexible and routed to the burner in sufficiently large loops. - The cavity between burner pipe and boiler flange must be insulated with the fireproof fibre provided. 4.3.1 Sound insulation - Gas pipes must be mounted in such a way that no vibrations are transferred to the building. - The burner can be equipped with a sound-absorbing hood. - We recommend that you install silencers downstream of the boiler in the flue gas pipe. Do not overtighten boiler door screws. Figure 11 H innen G inside J L M E Fill the gap with insulating material Figure 12 A Uno-3 90-125 16 A B Ø Ø 140 170 C D E F G H J L M 974 307 30 25 Ø 400 165 119 248 440 Technical information 4 205 116 / 02 4.4Fuel The boiler is only to be operated with the fuel stated on the boiler rating plate. Uno-3 boilers are suitable for the combustion of the following fuels: - Heating oil EL in accordance with DIN 51 603 / SN 181 160 /2 / ÖNorm C 1109 - Heating oil L in accordance with ÖNorm C 1108 - All fuel gases as defined by DVGW process sheet G 260 4.5 Even in partial load operation, the flue gas temperature must not fall below 100 °C. Regulators Electrical connection A qualified technician must install the electrical supply to the equipment. The electrical circuit diagram is located in the electrical box. Applicable only to Austria and Germany: An electrical circuit diagram is supplied with the boiler controls. Please affix the correct connection diagram to the inside of the terminal cover. Important! A main switch must be installed on-site in the supply line which performs an all-poles cut-out and has a clearance of at least 3 mm between the open contacts. Figure 13 Applicable only to Switzerland: The system-related electrical circuit diagram must be referred to when making the electrical connection! 4.5.1 Electrical connection of the burner - The burner must be connected to the boiler with the standard plug-in connection. - The burner cable must be shortened so that the plug-in connection has to be parted to swing out the burner. 4.6 Inspection hole Flue gas regulator set The flue gas regulators fitted in each case are listed on a label on the boiler casing (side section Figure 7, Pos. 9a). The installer can change the flue gas regulator set fitted and thus vary the flue gas temperature within a specific range. 17 Technical information 4 205 116 / 02 4.6.1 Flue gas and performance diagrams Uno-3 (110) Uno-3 (95) 190 190 170 160 140 160 150 °C 150 140 130 130 120 110 120 110 60 65 70 75 80 85 90 95 100 70 75 80 85 90 95 kW kW 3R5+1R2/290 3R5+2R3/290 100 105 110 100 190 180 170 160 150 140 130 120 °C Uno-3 (125) 110 70 80 90 100 110 120 130 100 kW 3R5+2R3/290 The curves shown here represent an average value based on measurements taken with burners from various manufacturers. Deviations of ±10 % are normal. kW = Heat capacity °C = flue gas temperature with heating oil EL, Boiler flow 80 °C Return flow 60 °C. CO2 = 13 % During the combustion of natural gas or heating oil L, the flue gas temperature is approx. 15 °C higher. 18 °C 180 170 180 Technical information 4 205 116 / 02 Flue gas temperature under other operating conditions Influence of the boiler water temperature on the flue gas temperature A change in the boiler water temperature of ±10 K results in a change of approximately ±6 K in the flue gas temperature. Influence of the CO2 content in the flue gases A change in the CO2 content of ±1 % changes the flue gas temperature by approx. ±8 °C. Key to regulator designation No. of regulators Regulator width (example: 5 units) 3R5/290 Length of the regulators 4.7 Flow mixing loop / minimum limitation of the boiler return temperature Hydraulic and control measures must be provided to ensure that the temperatures do not fall below the permissible minimum boiler flow and return temperature under any operating conditions. 4.8 4.9 Safety valves The heating system and hot water supply must each be protected with one safety valve against impermissibly high pressures. The discharge capacity of the heating system safety valve must correspond to the boiler’s maximum nominal heat output. The valve is installed in the safety flow. In Germany, only safety valves with the code letter "H" in the approval mark may be connected, and they must always be connected at the boiler safety flow. Water shortage protection in accordance with EN 12828 Part 2 Section 9 is mandatory. 4.10 Charging pump (boiler with freestanding calorifier) Speed of rotation and output regulation must correspond to the requirements of the free-standing calorifier. Setting carried out by the heating installation engineer. 4.11 Heating pump Speed of rotation and output regulation must correspond to the requirements of the system. They are to be set by the heating installation engineer. Setting the temperature regulators - without heating regulator: Set the boiler temperature in accordance with the outside temperature. - with heating regulator: The heating regulator automatically sets the correct boiler temperature. The boiler temperature varies between the minimum and maximum boiler temperatures entered. If a calorifier is connected, the priority circuit disables the boiler temperature regulator until the temperature is reached. The boiler temperature can rise to approx. 85 °C. 19 Commissioning 4 205 116 / 02 5.Commissioning • Parts of the boiler which have contact with water are made of ferrous materials. Heating Water • On account of the danger of stress cracking corrosion the chloride, nitrate and sulfate contents of the heating water must not exceed 200 mg/l in total. 5.1 Water quality The European Standard EN 14868 and the directive VDI 2035 must be observed. • The pH value of the heating water should lie between 8.3 and 9.5 after 6-12 weeks of heating operation. In particular, attention must be paid to the following stipulations: • Hoval boilers and calorifiers are designed for heating plants without significant oxygen intake (plant type I according to EN 14868). • Plants with - continuous oxygen intake (e.g. underfloor heating systems without diffusion proof plastic piping) or - intermittent oxygen intake (e.g. where frequent refilling is necessary) must be equipped with separate circuits. • Treated filling and replacement water must be tested at least 1x yearly. According to the inhibitor manufacturer‘s instructions, more frequent testing may be necessary. • A refilling is not necessary if the quality of the heating water in existing installations (e.g. exchange of boiler) conforms to VDI 2035. The Directive VDI 2035 applies equally to the replacement water. • New and if applicable existing installations need to be adequately cleaned and flushed befor being filled. The boiler may only be filled after the heating system has been flushed! Filling and replacement water • For a plant using Hoval boilers untreated drinking water is generally best suited as heating medium, i.e. as filling and replacement water. However, as not all drinking water is suitable for use as as filling and replacement water the water quality must fulfil the standard set in VDI 2035. Should the mains water available not be suited for use then it must be desalinated and/or be treated with inhibitors. The stipulations of EN 14868 must be observed. • In order to maintain a high level of boiler efficiency and to avoid overheating of the heating surfaces the values given in the table should not be exceeded (dependent on boiler performance ratings - for multi-boiler plants rating of smallest boiler applies - and on the water content of the plant). • The total amount of filling and replacement water which is used throughout the total service life of the boiler must not exceed three times the water capacity of the plant. Maximum filling capacity based on VDI 2035 Total hardness of the filling water up to ... [mol/m ] f°H d°H e°H ~mg/l Conductance 2 Boiler size of the individual boiler to 50 kW 50 to 200 kW 3 1 1 2 <0,1 <1 <0,56 <0,71 <10 <20 0,5 5 2,8 3,6 50,0 100,0 1 10 5,6 7,1 100,0 200,0 1,5 15 8,4 10,7 150,0 300,0 2 20 11,2 14,2 200,0 400,0 2,5 25 14,0 17,8 250,0 500,0 3 30 16,8 21,3 300,0 600,0 >3,0 >30 >16,8 >21,3 >300 >600 maximum filling quantity without desalination NO REQUIREMENT 50 l/kW 20 l/kW 20 l/kW 20 l/kW always desalinate Sum of alkaline earths If the conductance in µS/cm exceeds the tabular value an analysis of the water is necessary. 20 4 205 116 / 02 5.2 Commissioning Filling the heating system Filling of the heating system must be carried out by trained personnel. The filling and replacement water must comply with the quality requirements in the relevant state or country (VDI 2035 or SWKI 88-4 or ÖNORM H 5195). 5.3 Filling the calorifier (if present) The heating boiler may be put into operation even when the calorifier is not filled. 5.4Commissioning Important: On first commissioning, check that all safety and control devices are functioning properly (in accordance with the operating manual). The operation and maintenance of the system must be explained to the user in detail. In some areas, gas or dual-fuel systems may only be commissioned by an engineer from the local gasworks. Check with the local gasworks to make sure. 5.5 Oil/gas burner Setting the burner must also be carried out by a specialist, and the setting must correspond to the heat demand of the system. Please see the technical information / assembly instructions supplied with the burner. 5.6 Handover to the operator / storage Have the operator confirm in writing that the operating and maintenance procedures have been explained and that he or she has received a copy of the relevant operating manuals. (See sample on page 38). The manufacturer of the unit is responsible for providing operating manuals for the complete system. This technical information / these installation instructions must not be destroyed after completing the commissioning procedures, but should be permanently stored with the unit. 21 Maintenance 4 205 116 / 02 6.Maintenance 6.1 Information for fire inspector / chimney sweep regarding emission monitor key All other control elements of the control unit are described in the operating instructions. The emission monitor key can also be used to change over to manual operating mode. Emission monitor key / Manual operation To protect under floor heating systems against invalid overheating during emission monitoring / manual operation it is necessary to implement appropriate safety measures (e.g. safety temperature limiter with pump switch-off). The duration of the emission monitoring is limited to 20 minutes and shall be restarted, if necessary. Scalding hazard due to hot water temperature, since the hot water temperature can exceed the temperature setpoint! Emissions metering PRESS SHORTLY Immediate end Remaining time display REACTIONS for emissions metering • Time unit automatically 20 min. – thereafter reverts • Boiler temperature - > maximum temperature restriction • Regulate to the maximum temperature… the heating circuits and the water heaters (at the direct heating circle only, if the warm water mode of operation is adjusted to parallel operation) • With 2-step heat generator both stages are in operation Manual operation Immediate end PRESS > 5 seconds REACTIONS for manual operation • Set reference boiler temperature with button! • All heating pumps ON • Mixer without current - manual setting necessary! • Note the maximum permissible temperature of the floor heating! • The hot water temperature reaches the set DHW maximum temperature (expert level standard 65°C). 22 4 205 116 / 02 Maintenance 6.2Cleaning Cleaning should be performed at least twice per year. Cleaning at intermediate intervals is necessary if the flue gas temperature rises. 6.2.1 Preparatory work - Switch boiler off (controller: set switch to "O," pull the burner plug) - Interrupt the fuel supply - Open the boiler door - Remove regulators (Figure 13) - Remove flue gas collector cleaning cover (back) 6.2.2 Cleaning (dry or wet method) - Clean combustion chamber, 2-pass (cylindrical tubes), 3-pass (ribbed heating surface) thoroughly with a brush or spray and then remove any combustion residue or sprayed liquid from the flue gas collector and from the combustion chamber. For wet cleaning: Treat seals with graphite before carrying out wet cleaning. - Dispose of the cleaning fluid (scrubbing liquid) in accordance with regulations. 6.2.3 Putting into operation again - Insert the regulators - Fit cleaning cover - Close boiler door and reconnect burner plug. Do not overtighten boiler door screws. - Reconnect the fuel supply - Where applicable, refit front cover - Reset boiler switch to "autom." or "I". 23 Overview of settings 7. 7.1 4 205 116 / 02 Overview of settings Table of parameters Designation Regulator Factory 10 20 30 40 50 Setting range / Setting values Type of device: DHW: SW: Address: Surface operation Key : Heating curve HC OFF OFF, 0,20 .... 3,5 Heating curve MC1 1,0 OFF, 0,20 .... 3,5 Heating curve MC2 1,0 OFF, 0,20 .... 3,5 Daytime target temperature HC *) 20°C 5 .... 30°C *) Daytime target temperature MC1 *) 20°C 5 .... 30°C *) Daytime target temperature MC2 *) 20°C 5 .... 30°C *) Night-time target temperature HC *) 16°C 5 .... 30°C *) Night-time target temperature MC1 *) 16°C 5 .... 30°C *) Night-time target temperature MC2 *) 16°C 5 .... 30°C *) DHW target temperature 50°C 5 ... DHW-Max. *) Depending on the setting of system parameters 03 OPERATING MODE Remote operation/room stations Type 24 Heating circuit Address HW SW Overview of settings 4 205 116 / 02 Table for Time programs DHW circuit Time program P1 Tag Cycle 1 from to Cycle 2 from to Time program P2 Cycle 3 from to Cycle 1 from to Cycle 2 from to Time program P3 Cycle 3 from to Cycle 1 from to Cycle 2 from to Cycle 3 from to Mo Tu We Th Fr Sa Su Direct circuit Time program P1 Tag Cycle 1 from to Cycle 2 from to Time program P2 Cycle 3 from to Cycle 1 from to Cycle 2 from to Time program P3 Cycle 3 from to Cycle 1 from to Cycle 2 from to Cycle 3 from to Mo Tu We Th Fr Sa Su Mixer Circuit 1 Time program P1 Tag Cycle 1 from to Cycle 2 from to Time program P2 Cycle 3 from to Cycle 1 from to Cycle 2 from to Time program P3 Cycle 3 from to Cycle 1 from to Cycle 2 from to Cycle 3 from to Mo Tu We Th Fr Sa Su Mixer Circuit 2 Time program P1 Tag Cycle 1 from to Cycle 2 from to Time program P2 Cycle 3 from to Cycle 1 from to Cycle 2 from to Time program P3 Cycle 3 from to Cycle 1 from to Cycle 2 from to Cycle 3 from to Mo Tu We Th Fr Sa Su 25 Overview of settings 4 205 116 / 02 HYDRAULIC Par. Designation Factory 10 20 30 40 50 Lev. 2 Function allocation of the output DHW charging pump 1 HF 3 Function allocation of the output Mixer circuit 1 3 HF 4 Function allocation of the output Mixer circuit 2 3 HF 5 Function allocation of the output Direct circuit Pump 2 HF 6 Function allocation of the variable output 1 OFF HF 7 Function allocation of the variable output 2 OFF/ 4/ 43 HF 8 Function allocation of the variable input 1 OFF HF 9 Function allocation of the variable input 2 OFF HF 10 Function allocation of the variable input 3 OFF/ 2/ 33 HF 11 Indirect return increase OFF HF 12 Maximum limit energy management 80 °C HF 13 Activation cooling buffer OFF HF 14 Release contact cooling to KVLF OFF HF SYSTEM Par. Designation LANGUAGE Selection of the style-language 10 20 30 40 50 Lev. EN BE P1 HF 1 HF 2 Number of cleared switching time programs 3 Clearing for separate operating mode 4 Limit temperature for summer disconnection 22 °C HF 5 System frost protection 3 °C HF 6 Demand contact module for VE1 1 HF 7 Demand contact module for VE2 1 HF 8 Demand contact module for VE3 9 Air conditioning zone 10 Building type Automatic reversion time (surface end user level, except info. level) Pump and mixer compulsory operation 11 12 13 14 15 Logical fault signal Automatic SET function (after 24:00, is automatically set to OFF) Blocking code for heating Installer 1 HF -12 °C HF 2 HF 5 min HF ON HF OFF HF ON/ OFF HF OEM OFF HF 30 min HF 0 HF OFF HF 18 Release cycle temperature 19 Frost protection mode 21 RTC adjustment 23 Blocking code operator level 24 Temperature display in Fahrenheit OFF OEM 26 First commissioning date (after 24:00) - OEM 27 Fault report (only TTT/UG) 2 HF 28 Fault stack 2 ON HF 29 Characteristic curve emergency operation 0 °C HF 30 Thermostat function sensor allocation 31 Thermostat function reference value 32 33 RESET 26 Factory AF HF 1 °C HF Thermostat function switching difference 3K HF Thermostat function anti-blocking protection Top: ArtNo - HW Index Bottom: Code:REV - Software version Reset parameter values ON HF ----- OEM BE Overview of settings 4 205 116 / 02 DHW Par. Designation Factory 10 20 30 40 50 Lev. 40/ 45 °C BE 2 DHW-legionella protection-day OFF HF 3 DHW-egionella protection-time HF 4 DHW-legionella protection-temperature 5 DHW-temperature recording 6 DHW-maximum temperature limit 7 DHW-mode of operation 2:00 50/ 55/ 65/ 70 °C 1 50/ 55/ 65/ 70 °C 1 8 DHW-tank discharge protection DHW-NIGHT DHW - economy temperature 9 DHW-charging temperature excess 10 DHW-switching difference 11 DHW-charging pump follow-on 12 ZKP-switching time program 13 ZKP-economy interval (pause) 14 ZKP-economy interval (period duration) 17 H-GEN behaviour during SLP follow-on time 18 DHW-parallel loading 19 DHW-time-out 20 PI-reference value control 21 PI-amplification factor, P-portion Xp 22 PI-scanning time Ta 23 PI -reset time Tn HF HF HF HF ON/ OFF HF 7/ 20 K HF 5K 0.5/ 1/ 2/ 5 min AUTO OEM 0 min HF OEM HF 20 min HF AUTO/ OFF HF OFF OFF/ 30 min OFF HF HF 0,1 %/ K OEM 20 s OEM 600 s/ °C OEM HF UNMIXED CIRC Par. Designation Factory 10 20 30 40 50 Lev. 1 Type of reduced operation ECO/ ABS HF 2 Heating system (exponent) DK= 1,30 HF 3 Room override (in connection with room sensor) 3 HF 4 Room factor OFF HF 5 Adaptation heating curve OFF HF 6 Switch-on optimisation 1 HF 7 Heating limit 0,5 OEM 8 Room frost protection limit 10 °C HF OFF HF 0 HF 20 °C HF 9 Room thermostat function 10 Outside temperature allocation 11 Constant temperature reference value 12 Minimum temperature limit 10 °C HF 13 Maximum temperature limit 55/ 75 °C HF 14 Temperature elevation Heating circuit DK=0 HF 15 Pump follow-on 5 min HF 16 Screed function OFF HF 23 Room control K-factor 8 HF 24 Room control Tn-factor 35 min HF 25 Vacation mode STBY HF 36 Minimum value override OFF HF XXXXX HF Name heating circuit (max. 5 letters) 27 Overview of settings 4 205 116 / 02 MIX. VALVE-1 Par. Designation 10 20 30 40 50 Lev. 1 Type of reduced operation ECO/ ABS HF 2 Heating system (exponent) MK= 1,10 HF 3 Room override (in connection with room sensor) 4 Room factor 3 HF 100 % HF ON HF 1 HF 5 Adaptation heating curve 6 Switch-on optimisation 7 Heating limit 0,5 OEM 8 Room frost protection limit 10 °C HF OFF HF 0 HF 20 °C HF 9 Room thermostat function 10 Outside temperature allocation 11 Constant temperature reference value 12 Minimum temperature limit 10 °C HF 13 Maximum temperature limit 55/ 75 °C HF 14 Temperature elevation/ abatement heating circuit 0/ 8 K HF 15 Pump follow-on 5 min HF OFF HF 2,0 %/ K OEM Scanning time Ta 20 s OEM I-portion Tn 270 s OEM 21 Running time servomotor 150 s HF 22 End position function, valve 1 OEM 23 Room control K-factor 8 HF 24 Room control Tn-factor 35 min HF 25 Vacation mode STBY HF 36 Minimum value override OFF HF 37 Mixer lead time OFF HF 38 Regulation offset 0 HF 50 Cooling switch-on point, OT OFF HF 51 Cooling max. point, OT 35 °C HF 52 Cooling reference flow temp. at switch-on point 18 °C HF 53 Cooling reference flow temp. at max. point 24 °C HF 54 Cooling reference room temp. at switch-on point 23 °C HF 55 Cooling reference room temp. at max. point 28 °C HF 18 °C OEM XXXXX HF 16 Screed function 18 P-portion Xp 19 20 56 Min. temp. cooling Name heating circuit (max. 5 letters) 28 Factory Overview of settings 4 205 116 / 02 MIX. VALVE-2 Par. Designation Factory 10 20 30 40 50 Lev. 1 Type of reduced operation ECO/ ABS HF 2 Heating system (exponent) MK= 1,10 HF 3 Room override (in connection with room sensor) 4 Room factor 3 HF 100 % HF ON HF 1 HF 5 Adaptation heating curve 6 Switch-on optimisation 7 Heating limit 0,5 OEM 8 Room frost protection limit 10 °C HF OFF HF 0 HF 20 °C HF 9 Room thermostat function 10 Outside temperature allocation 11 Constant temperature reference value 12 Minimum temperature limit 10 °C HF 13 Maximum temperature limit 55/ 75 °C HF 14 Temperature elevation/ abatement heating circuit 0/ 8 K HF 15 Pump follow-on 5 min HF OFF HF 2,0 %/ K OEM Scanning time Ta 20 s OEM I-portion Tn 270 s OEM 21 Running time servomotor 150 s HF 22 End position function, valve 1 OEM 23 Room control K-factor 8 HF 24 Room control Tn-factor 35 min HF 25 Vacation mode STBY HF 36 Minimum value override OFF HF 37 Mixer lead time OFF HF 38 Regulation offset 0 HF 50 Cooling switch-on point, OT OFF HF 51 Cooling max. point, OT 35 °C HF 52 Cooling reference flow temp. at switch-on point 18 °C HF 53 Cooling reference flow temp. at max. point 24 °C HF 54 Cooling reference room temp. at switch-on point 23 °C HF 55 Cooling reference room temp. at max. point 28 °C HF 18 °C OEM XXXXX HF 16 Screed function 18 P-portion Xp 19 20 56 Min. temp. cooling Name heating circuit (max. 5 letters) 29 Overview of settings 4 205 116 / 02 HEAT GENER. Par. Designation Factory 10 20 30 40 50 Lev. 1/ 2/ 5 HF OFF/ 3 5/ 48/ 65/ 75 °C 75/ 85 °C HF HF 1 HF 1 H-GEN model 2 Start-up protection H-GEN 3 Minimum temperature limit H-GEN 4 Maximum temperature limit H-GEN 5 Mode of action minimum temperature limit H-GEN 6 Sensor mode operation for H-GEN 7 Minimum burner running time 8 9 10 11 12 DHW charging mode 1-2 stage 13 Lead time, boiler circuit pump 14 Follow-on time, boiler circuit pump or parallel boiler release 5 min HF 15 Search time feed pump, primary pump 5 min HF 16 Exhaust gas temperature monitoring OFF HF 17 Exhaust gas limit value 18 Boiler gradient 19 Modulation P-portion Xp 20 Modulation scanning time Ta 21 Modulation adjustment time Tn 22 Modulation running time 23 Modulation starting time 24 Modulation start-up output 25 Outside temperature block 26 Basic charge elevation 27 29 Minimum temperature limit, heating circuits Switching difference, minimum temperature limit Heating circuits H-GEN forced discharge 30 OEM Maximum limit 110 °C OEM 31 Minimum load control OFF OEM 34 Output limitation heating 100 % HF 35 Output limitation hot water 100 % HF 36 ET blocking 2.burner stage OFF HF 37 Running time meter 38 DHW release regulator (CD) 39 Emergency operation temperature H-Gen (e.g. for 70-8) 40 Heat balance (from V3.2) 41 Reset heat balance 28 HF 1 OEM 2 min HF Burner switching difference I 6K HF Burner switching difference II 12 K HF Time-out stage II 10 HF Release mode stage II 1 HF 2 HF 1 min HF 42 Volumetric flow rate 43 Density, medium 44 Specific thermal capacity, medium 200 °C HF OFF OEM 5 %/ K OEM 20 s OEM 180 s/ °C OEM 12 s HF 200 s HF 70 HF OFF OEM 0 K/ 10K OEM 5/ 38/ 65 °C HF 2K OEM OFF HF 1 HF ON HF 70 °C HF ON HF HF 0,0 l/ min 0,0 l/ IMP 1,00 kg/ l 4,2 HF HF HF RESET ST-1 Reset counters starts and running time, stage 1 OEM RESET ST-2 Reset counters starts and running time, stage 2 OEM 30 Overview of settings 4 205 116 / 02 RETURN CONTR Par. 2 Designation Minimum limit return temperature / reference value return temperature Switch-off difference 3 Pump follow-on time 1 Factory 10 20 30 40 50 Lev. 38 °C HF 2K HF 1 min HF SOLAR Par. Designation Factory 10 20 30 40 50 Lev. 1 Switch-on difference 10 K HF 2 Switch-off difference 5K HF 3 Minimum running time SOP 3 min HF 4 Solar collector maximum temperature 100 °C HF 5 Solar tank maximum limit (KSPF) 65 °C HF 6 Solar mode of operation 2 HF 7 Heat generator cycle lock (only when parameter 06=1,3,4) 0,5 h HF 8 Solar priority parallel changeover 10 K HF Solar heat balance OFF HF 9 SOLAR RESET Reset heat balance HF 0,0 l/ min 0,0 l/ IMP 1,05 kg/ l 11 Volumetric flow rate 12 Density, medium 13 Specific thermal capacity, medium 14 15 16 Switch-over temperature (SLVF) 60 °C HF 17 Solar minimum temperature OFF HF HF HF 3,6 KJ/ kgK HF Final switching-off temperature 120 °C HF Test cycle solar charging switch-over 10 min HF SOLID FUEL Par. Designation Factory 10 20 30 40 50 Lev. 1 Minimum temperature 60 °C HF 2 Maximum temperature 95 °C HF 3 Switch-on difference 10 K HF 4 Switch-off difference 5K HF 5 Clock block, heat generator 15 HF 31 Overview of settings 4 205 116 / 02 BUFFER Par. Designation Factory 10 20 30 40 50 Lev. 1 Minimum temperature 5/ 20 °C HF 2 Maximum temperature 95 °C HF 3 Temperature elevation, H-GEN 8/ 10/ 12K HF 4 Switching difference 2/ 5/ 10K HF 5 Forced discharge OFF HF 6 Skimming function switch-on difference 10 K HF 7 Skimming function switch-off difference 5K HF 8 Start-up protection OFF HF 9 Discharge protection OFF HF 10 Buffer mode of operation 2/ 3 HF 11 Pump follow-on time 3 min HF 12 Switch-off reference value temp. 70 °C HF 13 H-GEN release temp. skimming function 60 °C HF MAIN SUPPLY Par. Designation Factory 10 Lev. 0 %/ K HF 20 s HF 600 s/ °C HF 1 PI-amplification factor, P-portion Xp 2 PI-scanning time Ta 3 PI -reset time Tn Designation Factory CASCADE Par. 10 Lev. 1 Switch-off difference 3K OEM 2 Connecting delay 20 OEM 3 Switch-off delay 5 OEM 4 Switching output stage sequence 65 OEM 5 Stage reversal OFF OEM 6 Control stage 1 BE 7 Peak load stage OFF OEM 8 Group switch-over OFF OEM 9 DHW fast activation OFF OEM 10 Peak load elevation 10 K OEM BUS Par. 32 Designation Factory 10 20 30 40 50 Lev. 1 Bus address central device 10 HF 2 Bus right RS direct circuit 1 HF 3 Bus right RS mixer circuit 1 1 HF 4 Bus right RS mixer circuit 2 1 HF Overview of settings 4 205 116 / 02 SERVICE Par. Designation Factory 10 20 30 40 50 Lev. Service 1 (Cleaning ST1 ) 7 BE Cleaning according to fixed date OFF BE Cleaning according to fixed interval OFF BE 4 Cleaning according to cleaning counter OFF BE 5 Reset cleaning display 1 1 Suspend message «CLEANING ST-1» for X days 2 3 BE Service 2 (Cleaning ST2) 7 BE Cleaning according to fixed date OFF BE Cleaning according to fixed interval OFF BE 9 Cleaning according to cleaning counter OFF BE 10 Reset cleaning display 2 6 Suspend message «CLEANING ST-2» for X days 7 8 BE Service 3 (maintenance ST1 ) 11 Suspend message «MAINTENANCE ST-1» for X days 7 HF 12 Maintenance according to fixed date OFF HF 13 Maintenance according to fixed interval OFF HF 14 Maintenance according to maintenance counter OFF HF 15 Reset maintenance display 1 HF Service 2 (maintenance ST2 ) 16 Suspend message «MAINTENANCE ST-2» for X days 7 HF 17 Maintenance according to fixed date OFF HF 18 Maintenance according to fixed interval OFF HF 19 Maintenance according to maintenance counter OFF HF 20 Reset maintenance display 2 HF ALARM 1 Par. Designation 10 20 30 40 50 Lev. 1 Alarm 1 OEM 2 Alarm 2 OEM 3 Alarm 3 OEM 4 Alarm 4 OEM Alarm 5 - 20 OEM Reset fault signals OEM 5 ... 20 21 ALARM 2 Par. (can ony be activated with H-Gen 5) Designation 10 20 30 40 50 Lev. 1 Alarm 1 OEM 2 Alarm 2 OEM 3 Alarm 3 OEM 4 Alarm 4 OEM Alarm 5 - 20 OEM Reset fault signals OEM 5 ... 20 21 33 Overview of settings 4 205 116 / 02 FAULT REPORTING OVERVIEW TopTronic®T Status 34 Designation Fault type Code System External sensor Interruption 10-0 System External sensor Short-circuit 10-1 System Boiler sensor Interruption 11-0 System Boiler sensor Short-circuit 11-1 Remark System Flow sensor 1 Interruption 12-0 MC1=off, YK1=no current System Flow sensor 1 Short-circuit 12-1 MC1=off, YK1=no current System Storage sensor Interruption 13-0 System Storage sensor Short-circuit 13-1 System VE 2 Interruption 14-0 System VE 2 Short-circuit 14-1 System VE 2 Alarm 14-7 System VE 3 Interruption 15-0 System VE 3 Short-circuit 15-1 System VE 3 Alarm 15-7 System VE 1 Interruption 16-0 System VE 1 Short-circuit 16-1 System VE 1 Alarm 16-7 System Solar tank sensor Interruption (KSPF) 17-0 System Solar tank sensor Short-circuit (KSPF) 17-1 System Flow sensor 2 Interruption 18-0 MC2=off, YK2=no current System Flow sensor 2 Short-circuit 18-1 MC2=off, YK2=no current System Collector sensor Interruption (KVLF) 19-0 System Collector sensor Short-circuit (KVLF) 19-1 System Room sensor (RS) Interruption 20-0 System Room sensor (RS) Short-circuit 20-1 System Burner 1 No switching off (1 min) 30-2 With par. log. alarm can be switched off System Burner 1 No switching on (10 min) 30-3 With par. log. alarm can be switched off System Burner 2 No switching off (1 min) 31-2 With par. log. alarm can be switched off With par. log. alarm can be switched off System Burner 2 No switching on (10 min) 31-3 System Exhaust gas temperature Exceeding 33-5 System Exhaust gas temperature SLT triggered 33-8 System Cleaning stage 1 Triggering by date 40-1 System Cleaning stage 1 Triggering by interval 40-2 System Cleaning stage 1 Triggering by counter 40-4 System Maintenance stage 1 Triggering by date 41-1 System Maintenance stage 1 Triggering by interval 41-2 System Maintenance stage 1 Triggering by counter 41-4 System Cleaning stage 2 Triggering by date 42-1 System Cleaning stage 2 Triggering by interval 42-2 System Cleaning stage 2 Triggering by counter 42-4 System Maintenance stage 2 Triggering by date 43-1 System Maintenance stage 2 Triggering by interval 43-2 System Maintenance stage 2 Triggering by counter 43-4 Overview of settings 4 205 116 / 02 FAULT REPORTING OVERVIEW TopTronic®T Status Designation Fault type Code Logical Boiler temperature Not reached (90 min) 50-4 Logical Tank temperature Not reached (4 h) 51-4 Logical Flow temperature MC1 Not reached (1 h) 52-4 Logical Flow temperature MC2 Not reached (1 h) 53-4 Logical Room temperature HC Not reached (3 h) 54-4 Logical Room temperature MC1 Not reached (3 h) 55-4 Logical Not reached (3 h) 56-4 Address collision 70-0 System Room temperature MC2 Lock by energy supply company ST 2 Activity No T2B signal 70-1 System Activity 70-6 System Activity System System Activity HP return sensor No FA signal Regulator with address 10 is missing Data bus error Return min. temp. below setpoint System HP return sensor 85-5 System QF System QF Return max. temp. exceeded Heat source min. temp. below setpoint Heat source max. temp. exceeded (cooling operation) System System QF WPS Fault heat source sensor Variable input HP fault -87-7 System System System System Pulse counter Fault Fault Fault No pulse (5 min) Warning Lock-out Blocking 90-0 W:XX E:XX B:XX System Remark 70-8 70-9 85-4 No Hoval regulator 86-4 86-5 Standard signal «VE-x» Warning in automatic firing device Fault in automatic firing device Fault in automatic firing device SENSOR ALLOC. Par. 1 Designation Factory 10 20 30 40 50 Lev. Balancing external sensor 0 OEM Balancing room sensor (only adjustable with RS-T) 0 HF 2 Balancing heat generator 0 OEM 3 Balancing tank sensor 0 OEM 4 Balancing flow sensor 1 0 OEM 5 Balancing flow sensor 2 0 OEM 6 Balancing solar collector sensor 0 OEM 7 Balancing solar buffer sensor 0 OEM 8 Balancing variable input 1 0 OEM 9 Balancing variable input 2 0 OEM 10 Balancing variable input 3 0 OEM RS-T 35 4 205 116 / 02 36 4 205 116 / 02 37 COPY FOR PLANT USER Confirmation The user (owner) of the system herewith confirms that • he has received adequate instruction in the operating and maintenance of the installation, • received and taken note of the operating and maintenance instructions and, where applicable other documents concerning the heat generator and any further components. • and is consequently sufficiently familiar with the installation. Installation address: Type: Serial number: Year of manufacture: Place, Date: System installer: System user: COPY OF SYSTEM INSTALLER Confirmation The user (owner) of the system herewith confirms that • he has received adequate instruction in the operating and maintenance of the installation, • received and taken note of the operating and maintenance instructions and, where applicable other documents concerning the heat generator and any further components. • and is consequently sufficiently familiar with the installation. Installation address: Type: Serial number: Year of manufacture: Place, Date: System installer: System user: