Uno-3 (110-125) Technical Information & Installation

advertisement
Technical information
Assembly instructions
Uno-3 (95-125)
Oil/gas boilers
These instructions are applicable to the
following types:
7-Uno-3 (95,110,125)
7-Uno-3 b-i* (95,110,125)
* = Burner integrated
Hoval products must be installed and commissioned only
by appropriately qualified experts. These instructions
are intended exclusively for the specialist. Electrical
installations may only be carried out by a qualified
electrician.
Subject to modifications
|
4 205 116 / 02 - 02/14
Uno-3 (95-125) boilers are suitable and licensed for
use as heat generators for hot water heating systems
with a permissible flow temperature of up to 100 °C1).
They are designed for closed-circuit systems, but can
also be installed in open systems as per EN 12828.
1)
See technical data
EN
Table of Contents
1
4 205 116 / 02
Important information
1.1
Other instructions.................................................................................................................................... 3
1.2
Safety information.................................................................................................................................... 3
1.3
Regulations, official approvals............................................................................................................... 3
1.4Guarantee................................................................................................................................................. 4
2.Installation
2.1
2.2
2.3
3
Setting up, levelling................................................................................................................................. 5
Fitting the heat insulation....................................................................................................................... 6
Fitting the casing..................................................................................................................................... 8
Technical information
3.1
Description of the boiler........................................................................................................................ 10
3.1.1
The Uno-3 (95-125) complies with the following directives + standards ................................................. 10
3.2
Technical data Uno-3 (95-110) for Switzerland.................................................................................... 11
3.3
Technical data Uno-3 (110,125) for all other countries....................................................................... 12
3.4Dimensions............................................................................................................................................. 13
3.5
Dimensions without heat insulation and casing (transport dimensions)......................................... 13
4.Installation
4.1
Boiler room requirements..................................................................................................................... 14
4.2
Connection of the flue gas system and flue duct dimensions.......................................................... 14
4.3
Fitting the burner................................................................................................................................... 16
4.3.1
Sound insulation....................................................................................................................................... 16
4.4Fuel.......................................................................................................................................................... 17
4.5
Electrical connection............................................................................................................................. 17
4.5.1
Electrical connection of the burner........................................................................................................... 17
4.6
Flue gas regulator set............................................................................................................................ 17
4.6.1
Flue gas and performance diagrams....................................................................................................... 18
4.7
Flow mixing loop / minimum limitation of the boiler return temperature......................................... 19
4.8
Setting the temperature regulators...................................................................................................... 19
4.9
Safety valves.......................................................................................................................................... 19
4.10
Charging pump (boiler with free-standing calorifier)......................................................................... 19
4.11
Heating pump......................................................................................................................................... 19
5.Commissioning
5.1
Water quality........................................................................................................................................... 20
Heating water........................................................................................................................................... 20
Filling and replacement water.................................................................................................................. 20
5.2
Filling the heating system..................................................................................................................... 21
5.3
Filling the calorifier (if present)............................................................................................................ 21
5.4Commissioning...................................................................................................................................... 21
5.5
Oil/gas burner......................................................................................................................................... 21
5.6
Handover to the operator / storage...................................................................................................... 21
6.Maintenance
6.1
Information for fire inspector / chimney sweep regarding emission monitor key........................... 22
6.2Cleaning.................................................................................................................................................. 23
6.2.1
Preparatory work...................................................................................................................................... 23
6.2.2
Cleaning (dry or wet method)................................................................................................................... 23
6.2.3
Putting into operation again..................................................................................................................... 23
7.
7.1
7.2
2
Overview of settings
Table of parameters............................................................................................................................... 24
Overview of alarms TopTronic®T........................................................................................................... 34
4 205 116 / 02
1
1.1
Important information
Other instructions
All instructions relevant to your system can be found
in the Hoval system manual! In exceptional cases,
the instructions can be found enclosed with the
components.
Further information sources
- Hoval catalogue
- Standards, regulations
1.2
Safety information
The system may only be placed in operation if all the
relevant standards and safety regulations have been
complied with. At least the following conditions must
be satisfied for a trial operation:
1. Safety valve installed (closed system).
2. Control in operation (connected to the mains current
supply system).
3. Sensor for the safety temperature limiter mounted
in the immersion sleeve.
4. System filled with water.
5. Expansion vessel connected.
6.Flue gas connectors connected to the flue gas
pipeline at the chimney or flue.
7. An adequate supply of fresh air must be guaranteed.
8. The burner is preset.
1.3
Regulations, official approvals
The following regulations are to be complied with for
installation and operation:
Germany
- DIN EN 12831 Heating systems in buildings –
Method for calculation of the design heat load.
- EN 303 Heating boilers with forced draught burners.
- DIN EN 12828 Sheet 1 and 2
Heating systems in buildings – design of waterbased heating systems.
- DIN 4755 Oil-fired systems.
Design, construction and safety engineering
requirements.
- DIN 4756 Gas-fired systems; construction,
execution, technical safety requirements, planning
and execution.
- DIN 18160 House chimneys; requirements, planning
and execution.
- TRD 702 Steam boiler plants with calorifiers of
the group II.
- DIN EN 13384 Chimneys – Thermal and fluid
dynamic calculation methods.
Important notes
- TRD 721 Safety devices against excess pressures /
safety valves / for steam boilers of Group II.
- VDI 2035 Prevention of damage by corrosion and
the formation of scale in hot water heating systems.
- DIN 57 116 / VDI 0116 Electrical equipment for
firing systems (VDE Regulation).
- For further standards applicable in Germany, see
appendix N-430 020.
Austria
- ÖNorm 7550
- ÖNorm B 8130 Open water heating systems;
safety devices.
- Norm B 8131 Closed water heating systems; safety,
execution and testing requirements.
- ÖNorm B 8133 Hot water production systems;
technical safety requirements.
- ÖNorm B 8136 Heating systems, space requirements
and other building requirements.
- ÖNorm M 7515 Calculations of dimensions of
chimneys; terminology, calculation procedure.
- ÖNorm H 5171 Heating systems, construction
engineering requirements.
- ÖVGW TR-Gas G1 Technical directives for low
pressure gas installations.
- ÖNorm M 7445 Gas blower burner.
Switzerland
- Requirements of the VKF Cantonal Fire Insurance
Association.
- Fire brigade regulations.
- Requirements of the SVGW Swiss Association of
Gas and Water Suppliers.
- SWKI 91-1 Aeration and ventilation of the boiler
installation room.
- SWKI 88-4 Water treatment for heating, steam and
air conditioning systems.
- SWKI 93-1 Safety engineering installations for
heating systems.
- KRW Corrosion through halogen compounds.
- KRW/VSO/FKR Plug-in electrical connections on
heating boilers and burners
and further regulations and standards issued by
CEN, CEN ELEC, DIN, VDE, DVGW, TRD and the
legislative body.
Also to be complied with are the regulations of the local
building authorities, insurance companies and chimney
sweeping operations.The regulations of the responsible
gas supply company are also to be complied with and
any necessary official approval obtained.
3
Important notes
1.4Guarantee
Proper function is only guaranteed providing these
instructions are followed and the boiler is regularly
maintained by a licensed specialist. (Maintenance
contract). The rectification of faults and damage
as a result of contaminated operating materials
(gas, water, combustion air), unsuitable chemical
additives and an inadmissibly high lime content of the
heating water, improper handling, faulty installation,
unauthorised modifications and damage due to the use
of force do not fall under our guarantee obligations, this
also applies to corrosion due to halogen compounds,
e.g. from spray cans, paints, adhesives, halogenated
fluids, solvents and cleanings agents.
4
4 205 116 / 02
Installation
4 205 116 / 02
2.Installation
2.1
Setting up, levelling
A special foundation plate for the boiler is not an
essential, but it is recommended.
Space requirement
for mounting the thermal insulation and sheet metal
cladding:
at least 40 cm each on the left and right side of
the boiler.
If the space between the boiler and the wall is less,
all heat insulation and casing must be fitted before
the boiler can be pushed into its final position.
Boiler door pivotable to the left
It is possible to change the attachment of the boiler
door so that it opens towards the left. This can be of
advantage when installing the boiler in a corner.
Proceed as follows:
Close the boiler door and lock it in position
before changing the attachment of the door.
2
1
Do not connect lines until the heat insulation
and casing have been fitted to the boiler!
There must always be enough space between
the back of the boiler and the wall to allow
easy access to the cleaning aperture in the
flue gas collector.
There must be enough space to swing open the
boiler door, incl. the burner.
Do not overtighten boiler door screws.
Fig. 2
1. Pull up the semicircular rivet (1).
2. Change over the swivel arm (2).
3. Insert the semicircular rivet (1) on the other side.
4. Fit the burner plug and the fire protection switch
(if fitted, Austrian version) on the other side
(see point 2.3, item 9 and point 4.5.1).
The cable must not touch any hot
parts!
Levelling
Using a spirit level, align the upper edge of the
boiler water jacket (longitudinal axis of the boiler)
until it is precisely horizontal or sloping very slightly
upwards towards the rear by inserting the plinth
rails correspondingly, to allow the boiler to vent
properly.
Before fitting the burner, first fit the double
door (Pos. 8b, Figure 7) (door casing).
5
6
Fitting the heat insulation
The remaining 3 insulation mats (8a,10) are fitted after mounting the casing.
Fig. 3a
7. Attach insulation panel (7) to the pins welded onto the front wall of the boiler and secure with the retaining discs (ø 38) provided, Fig. 3a.
6. Attach insulation panels (6/6a/6b/6c) to the pins welded onto the flue gas collector and secure with the retaining discs (ø 38) provided.
5. Attach the insulation mats (5/5a/5b) to the pins provided on the rear wall of the boiler and secure with retaining discs, Fig. 4a (ø 38).
4. Attach the insulation mat (3) using 2 plastic straps (4) and strap fasteners (4a):
- Tension springs (4b) serve for additional fixing
- Do not overtighten the straps
(reduced insulating value)
3. Place the insulation mat (3) around the boiler body (with the joint at the top, black side facing outwards, see Figure 3).
2. Mount the rear retaining bracket (2) with hexagon screws M8, nuts and U-washers aligned horizontally.
- Attach C-clips.
1. Mount the front retaining bracket (1) with hexagon screws M8, nuts and U-washers, aligned horizontally, to the front wall of the boiler.
- Attach C-clips.
2.2
See separate assembly instructions for boilers with mounted calorifier
Installation
4 205 116 / 02
7
Figure 3
4a
4
‌4b
3
C-clips
‌5b
6
1
6b
5
5a
2
C-clips
6a
6c
4 205 116 / 02
Installation
7
8
Attention: The capillaries must not be folded or kinked!
9
Figure 4
13a
16. Affix labels and where applicable, mount manual holder on the side.
12c
13a
15. Position cladding cover (15) and fix left and right with 2 self-tapping screws ø 4.8 x 13.
14. Attach cover plate (14) with self-tapping screws ø 3.5 x 6.5 and serrated washers.
Figure 5
12b
12a
12
13
13c
Figure 6
13. Pull the capillaries with the immersion sensors (13, Fig. 6) through the opening (13a, Fig. 5) in the cover, insert them into the immersion sleeve
(13b, Fig. 7) as far as the stop and fix in position with retaining spring (13c, Fig. 6).
2.4 Installation of boiler controller
12. Mount the special screw with nut (12, Fig. 5) on the cover plate (12a). Then place switch control box (12b) on the casing cover (12a) with the recess
for the special screw, push back and secure with self-tapping screws ø 3.5 x 6.5 and serrated washers (12c). Position cladding cover (12a, Fig. 7)
and fix on the side walls with 2 self-tapping screws ø 4.8 x 12 and C-clips.
11. Attach rear wall (11/11a) to the angled edges of the side walls (9a) with self-tapping screws ø 3.5 x 6.5.
10. Place 2 insulating mats (10) left and right in longitudinal direction (to prevent vertical air circulation).
The cable must not touch any hot parts
9. Attach the burner cable (9) to the right or left side wall (9a) (Fig. 4). See also point 4.5.1
Attach right and left side wall (9a) onto the front retaining brackets (1) and rear retaining brackets (2) with self-tapping screws ø 4.8 x 38 and pull
the burner cable upwards.
Fitting the casing
8. Fix hexagon bolts with U-washers and hexagon nuts (8). Insert thermal insulation (8a) into the boiler door. Attach the door casing (8b) to the boiler
door using hexagon cap nut.
2.3
Installation
4 205 116 / 02
‌8b
8a
8
‌13b
9a
10
12a
Figure 7
14
9a
15
11
11a
4 205 116 / 02
Installation
9
Technical information
3
3.1
4 205 116 / 02
Technical information
Description of the boiler
The Uno-3 is a threepass boiler. At the end of the
circular cylindrical combustion chamber, the flame
gases flow through several cylindrical tubes arranged
above the combustion chamber and towards the front
to the turning chamber, from where they flow through
rectangular ducts (thermolytic heating surface) towards
the rear and reach the flue gas collector.
The flue gas temperatures can be varied within
a specific range through the installation of various
regulator combinations.
Figure 8
3.1.1 The Uno-3 (95-125) complies with the following directives + standards
10
We hereby declare that the product described, as an individual appliance, complies with the standards,
guidelines and technical specifications laid down.
Directives:
90/396/EC
92/42/EC
73/23/EEC
89/336/EEC
97/23/EC
"Gas Equipment Directive"
"Efficiency directive"
"Low-voltage directive"
"Electromagnetic compatibility"
"Pressure Equipment Directive" (PED)
Regulations:
Stability
Building requirements
Low voltage
EMC
prEN14394:2001
EN303-1, EN303-2, EN303-3
DIN VDE 0722 / Ed. 04.83
EN 50082 Part 1 / Ed. 01.92
Technical information
4 205 116 / 02
3.2
Technical data Uno-3 (95-110) for Switzerland
(95)
(110)
• Nominal heat output at 80/60 °C 1
• Thermal output
• Maximum heat input
Type
kW
kW
kW
95
60-95
102.1
110
70-110
118.3
• Maximum boiler operating temperature 2
• Safety temperature limiter setting (water side) 2
• Operating/test pressure at max. operating temperature 90 °C 2
°C
°C
bar
90
110
4.0/5.2
90
110
4.0/5.2
• Maximum boiler operating temperature 3
• Safety temperature limiter setting (water side) 3
• Operating pressure at max. operating temperature 105 °C 3
°C
°C
bar
105
120
3.0
105
120
3.0
• Minimum boiler operating temperature
• Minimum boiler return temperature
• Minimum flue gas temperature at boiler
°C
°C
°C
see table of operating conditions (below)
see table of operating conditions (below)
see table of operating conditions (below)
• Regulator set for 160 °C
Flue gas temperature
• Boiler efficiency at full load and 80/60 °C
(related to net/ gross calorific value, heating oil EL)
• Boiler efficiency at partial load 30% and return 37 °C
(acc. to EN 303) (related to lower/upper calorific value heating oil EL)
• Standard efficiency at 75/60 °C (DIN 4702 Part 8)
(related to net/gross calorific value, (heating oil EL))
• Standby losses qB at 70 °C
3R5+
3R5+
1R2/290
2R3/290
%
92.6 / 87.4
92.7 / 89.5
%
94.8 / 89.4
94.8 / 89.5
%
95.7 / 90.3
95.9 / 90.47
Watts
400
400
• Resistance on the heating gas side at nominal output
160 °C flue gas temperature, 12.5 % CO2 , 500 m above sea level
(tolerance ±20 %)
• Flue gas mass flow at nominal output 12.5 % CO2 heating oil
mbar
0.65
0.89
kg/h
162
188
•
•
•
•
•
Flow resistance boiler 4
Hydraulic resistance at 10K
Hydraulic resistance at 20K
Water flow rate at 10K
Water flow rate at 20K
z-value
mbar
mbar
m³/h
m³/h
0.2
13.35
3.34
8.17
4.09
0.2
17.90
4.47
9.46
4.73
•
•
•
•
Boiler water content
Boiler gas content
Insulation thickness of boiler body
Weight (incl. casing)
litres
m³
mm
kg
250
0.1848
80
391
250
0.1848
80
391
dB(A)
77
79
• Sound level 5
- Heating noise without absorber hood (EN 15036 Part 1)
- Heating noise with absorber hood (EN 15036 Part 1)
dB(A)
67
67
- Flue gas noise inside the flue (EN 15036 Part 2)
dB(A)
87
91
- Flue gas noise radiated from the mouth (DIN 45635 Part 47)
• Combustion chamber dimensions Ø-inside x length
• Combustion chamber volume
dB(A)
mm
m³
79
84
ø440x974
0.148
ø440x974
0.148
• Dimensions
see Dimensions
• Maximum depression in flue gas system (boiler connection)
3
4
5
1
2
Pa
30
30
At nominal output, the pollutant limit values and flue gas losses as per regulation LRV 92 (CH) are complied with.
Controller U3.1 and T2.2
Controller U3.2 and T0.2
Flow resistance boiler in mbar = flow rate (m3/h)2 x z
Data valid for Hoval oil compact heat station b-i
Possible operating conditions
Fuel
min. flue gas temperature
Heating oil EL
°C
Natural gas H
Option 1
Option 2
Option 3
Option 1
Option 2
Option 3
130
110
130
130
110
130
min. boiler temperature
°C
48
50
52
58
60
62
min. return temperature
°C
35
38
No lower limit
45
48
No lower limit
Return temperature controls
yes
yes
no
yes
yes
no
Boiler start-up protection 1
no
no
yes
no
no
yes
1
Boiler minimum temperature limit effective on group actuators
11
Technical information
3.3
4 205 116 / 02
Technical data Uno-3 (110,125) for all other countries
Type
(110)
(125)
kW
kW
kW
kW
110
70-110
50-110
118.3
125
70-125
50-125
135.8
• Maximum boiler operating temperature 1
• Safety temperature limiter setting (water side) 1
• Operating/test pressure at max. operating temperature 90 °C 1
°C
°C
bar
90
110
4.0/ 5.2
90
110
4.0/ 5.2
• Maximum boiler operating temperature 2
• Safety temperature limiter setting (water side) 2
• Operating pressure at max. operating temperature 105 °C 2
°C
°C
bar
105
120
3.0
105
120
3.0
• Minimum boiler operating temperature
• Minimum boiler return temperature
• Minimum flue gas temperature at boiler
°C
°C
°C
•
•
•
•
Nominal heat output at 80/60 °C
Heat output range (heating oil EL, natural gas H: variant 1 and 3)
Heat output range (heating oil EL, natural gas H: variant 2)
Maximum heat input
see table of operating conditions (below)
see table of operating conditions (below)
see table of operating conditions (below)
• Regulator set for 170 °C flue gas temperature
• Boiler efficiency at full load and 80/60 °C
(related to lower/upper calorific value (heating oil EL))
• Boiler efficiency at partial load 30 % and return 37 °C
(acc. to EN 303) (related to lower/upper calorific value (heating oil EL))
• Standard efficiency at 75/60 °C (DIN 4702 Part 8)
(related to lower/upper calorific value (heating oil EL))
• Standby losses qB at 70 °C
• Resistance on the heating gas side at nominal output
180 °C flue gas temperature, 12.5 % CO2 , 500 m above sea level
(tolerance ±20 %)
• Flue gas mass flow at nominal output 12.5 % CO2 heating oil
•
•
•
•
•
•
Maximum flue draught
Flow resistance boiler 3
Hydraulic resistance at 10K
Hydraulic resistance at 20K
Water flow rate at 10K
Water flow rate at 20K
•
•
•
•
Boiler water content
Boiler gas content
Insulation thickness of boiler body
Weight (incl. casing)
%
%
3R5+2R3
3R5+2R3
92.7/ 87.6
92.8/ 87.6
94.8 /87.6
92.8 /87.6
95.9/ 90.5
95.8/ 90.4
Watts
400
400
mbar
0.89
1.10
kg/h
188
222
Pa
z-value
mbar
mbar
m³/h
m³/h
20
0.2
17.90
4.47
9.46
4.73
20
0.2
24.80
5.80
11.10
5.40
litres
m³
mm
kg
250
0.1848
80
391
250
0.1848
80
391
• Sound level 4
- Heating noise without absorber hood (EN 15036 Part 1)
dB(A)
79
80
- Heating noise with absorber hood (EN 15036 Part 1)
dB(A)
67
67
- Flue gas noise inside the flue (EN 15036 Part 2)
dB(A)
91
91
- Flue gas noise radiated from the mouth (DIN 45635 Part 47)
dB(A)
84
84
ø440x974
0.148
ø440x974
0.148
• Combustion chamber dimensions Ø-inside x length
• Combustion chamber volume
mm
m³
• Dimensions
see Dimensions
• Maximum depression in flue gas system (boiler connection)
2
3
4
1
Pa
30
30
Controller U3.1 and T2.2
Controller U3.2 and T0.2, operating pressure may be increased to 4 or 5 bar in countries in which the Pressure Equipment Directive is not in force.
Flow resistance boiler in mbar = flow rate (m³/h)2 x z
Information applies to combinations with Hoval-tested oil burner
Possible operating conditions
Fuel
Heating oil EL
Option 1
Option 2
Natural gas H
Option 3
Option 1
Option 2
Option 3
min. flue gas temperature
°C
130
110
130
130
110
130
min. boiler temperature
°C
48
50
52
58
60
62
min. return temperature
°C
35
38
No lower limit
45
48
No lower limit
Return temperature controls
yes
yes
no
yes
yes
no
Boiler start-up protection 1
no
no
yes
no
no
yes
1
If the boiler temperature is or drops below the minimum boiler temperature (variant 3) and there is no return maintenance then the load must
be switched off using a corresponding control function.
12
Technical information
4 205 116 / 02
3.4Dimensions
9
7
(Third-party burner)
10
12
11
3
1
4
13
1
2
3
4
5
6
7
8
9
10
11
12
13
Flow type 130-160 DN 50, PN 6
Return type DN 50, PN 6
Safety flow R 1 ¼"
Flow for calorifier R 1 ¼"
Return for calorifier R 1 ¼"
Drain pipe R 1"
Flue gas outlet
Cleaning aperture
Boiler controller
Boiler door attached on the right (on the left if desired)
Burner absorber hood
Connection for burner cable
(burner plug)
E-cable infeed
8
5
2
6
3.5
Dimensions without heat insulation and casing (transport dimensions)
Boiler (without calorifier) incl. swivel flange, connections and flue gas collector
13
Technical information
4.Installation
4.1
Boiler room requirements
Regarding the building specifications for boiler rooms
and their supply and extract air handling, the current
building supervisory office regulations specific to the
state or country are to be observed. In Germany the
firing regulations for the individual Bundesländer are
to be complied with.
Make sure there is an adequate supply of fresh
air to the boiler room,
to ensure that the combustion air supply necessary
for all the firing systems operated there can flow in
without hindrance and that no oxygen deficiency
occurs for the operating personnel.
Binding values for the size of supply air openings are
not generally specified in the relevant regulations; it is
merely required that no partial vacuum in excess of 3 N/
m2 occurs. An opening or line leading into the open air
of at least 150 cm2. For every kW in excess of 50 kW,
a further 2 cm2 must be calculated. In rectangular
openings, the ratio of the sides should not exceed
1.5:1; if a grid is fitted, an appropriate allowance must
be added so that the free cross-section area reaches
the amount given above.
In Austria ÖNorm H 5171 additionally stipulates a
flue air aperture. This must have a minimum cross
section of 180 cm2 up to a rated heat output of
100 kW. For every further kW, the cross-section must
be increased by 1 cm2.
4 205 116 / 02
Existing flue gas systems may require upgrading
or adjustment of the flue duct cross-section as
indicated by a chimney engineer.
The correct functioning of the flue duct, i.e. the generation
of the required delivery pressure depends on:
a) the type (nature) of the chimney (thermal insulation,
interior surface roughness, sealing etc.)
b)the connection of the boiler to the chimney
according to specification
c)establishing the correct flue duct cross-section
dimension.
ref. a)
Chimneys according to EN 13384, part 2, execution
types I and II are appropriate for modern firing systems
(advice from the chimney specialist is necessary).
to b)
The flue gas pipe connecting the boiler to the flue gas
system must be as short as possible and placed at
an angle of 30-45°.
The entry location of the flue gas pipe must be
carefully sealed.
The introduction of the flue gas pipe into the chimney (a)
must be executed so that no condensate water can
flow from the chimney into the flue gas pipe and the
boiler. (Fig. 10)
The flue gas system must be watertight, acidproof and approved for the corresponding
flue gas temperatures.
As a general rule, only one heat generator should
be connected to the chimney! When using two
heat generators, the corresponding regulations
must be observed.
4.2
Connection of the flue gas system
and flue duct dimensions
To guarantee economic and fault-free operation, boiler
and chimney must be mutually adapted to create
a functional unit.
Moisture-resistant and acid-proof flue gas
systems must be used in new installations.
14
a
Figure 10
Where possible, avoid 90° bends in the flue gas system!
Flue gas pipes longer than 1 m are to be insulated.
Technical information
4 205 116 / 02
Normally only one heat producer may
be connected to the chimney!
Flue gas pipes longer than 1 m are to be insulated.
If an adapter (reducer) from the flue gas outlet of the
boiler to the entry point into the flue gas system is
required, it must take the form of a slim cone.
from
vom the
boiler
Kessel
Basic data:
Flue gas pipeline 5 m long, 2 90° elbows and
1 45° elbow, outside air 15°C, height above sea level
max. 800 m, flue gas pipeline same ø as flue gas
connector on boiler.
You are recommended however to use the
services of the chimney specialist right from the
planning stage!
to
the
zum
chimney
Schornstein
to c)
Dimensioning the chimney cross section. The cross
sections are to be calculated for boilers without delivery
pressure requirement according to EN 13384. (Please
also observe DIN 18160, Part 1 "Domestic chimneys").
Take into consideration location-specific factors (hillside
location of the building, chimney position, slope of the
roof, chimney stack exit shape, etc.)!
In Switzerland, take note of SIA Recommendation
384/4!
In Austria, calculation is performed as prescribed by
ÖNorm M 7515.
Non-binding guide values for dimensioning of the
flue duct for boiler types Uno-3 (95-125).
Inside diameter of flue duct in mm
Boiler type
Uno-3
kW *
Chimney height
11-15 m
95
95
~ 180
110
110
~ 180
125
125
~ 180
*kW = maximum boiler output
15
Technical information
4.3
4 205 116 / 02
Fitting the burner
- Depending on the size of the burner flange,
an intermediate flange may be required to attach
the burner.
- To allow the burner to be swung out 90° to the
left or right, the connections must be flexible and
routed to the burner in sufficiently large loops.
- The cavity between burner pipe and boiler flange
must be insulated with the fireproof fibre provided.
4.3.1 Sound insulation
- Gas pipes must be mounted in such a way that no
vibrations are transferred to the building.
- The burner can be equipped with a sound-absorbing
hood.
- We recommend that you install silencers downstream
of the boiler in the flue gas pipe.
Do not overtighten boiler door screws.
Figure 11
H
innen
G inside
J
L
M
E
Fill the gap with insulating material
Figure 12
A
Uno-3
90-125
16
A
B
Ø
Ø
140
170
C
D
E
F
G
H
J
L
M
974
307
30
25
Ø
400
165
119
248
440
Technical information
4 205 116 / 02
4.4Fuel
The boiler is only to be operated with
the fuel stated on the boiler rating plate.
Uno-3 boilers are suitable for the combustion of the
following fuels:
- Heating oil EL in accordance with DIN 51 603 /
SN 181 160 /2 / ÖNorm C 1109
- Heating oil L in accordance with ÖNorm C 1108
- All fuel gases as defined by DVGW process
sheet G 260
4.5
Even in partial load operation, the flue
gas temperature must not fall below
100 °C.
Regulators
Electrical connection
A qualified technician must install the electrical supply
to the equipment. The electrical circuit diagram is
located in the electrical box.
Applicable only to Austria and Germany:
An electrical circuit diagram is supplied with the boiler
controls.
Please affix the correct connection diagram to the
inside of the terminal cover.
Important!
A main switch must be installed on-site in the supply
line which performs an all-poles cut-out and has a
clearance of at least 3 mm between the open contacts.
Figure 13
Applicable only to Switzerland:
The system-related electrical circuit diagram must be
referred to when making the electrical connection!
4.5.1 Electrical connection of the burner
- The burner must be connected to the boiler with
the standard plug-in connection.
- The burner cable must be shortened so that the
plug-in connection has to be parted to swing out
the burner.
4.6
Inspection
hole
Flue gas regulator set
The flue gas regulators fitted in each case are listed
on a label on the boiler casing (side section Figure 7,
Pos. 9a).
The installer can change the flue gas regulator set
fitted and thus vary the flue gas temperature within
a specific range.
17
Technical information
4 205 116 / 02
4.6.1 Flue gas and performance diagrams
Uno-3 (110)
Uno-3 (95)
190
190
170
160
140
160
150
°C
150
140
130
130
120
110
120
110
60
65
70
75
80
85
90
95
100
70
75
80
85
90
95
kW
kW
3R5+1R2/290
3R5+2R3/290
100 105 110
100
190
180
170
160
150
140
130
120
°C
Uno-3 (125)
110
70
80
90
100
110
120
130
100
kW
3R5+2R3/290
The curves shown here represent an average value based on measurements taken with burners from various
manufacturers. Deviations of ±10 % are normal.
kW = Heat capacity
°C = flue gas temperature with heating oil EL,
Boiler flow 80 °C
Return flow 60 °C.
CO2 = 13 %
During the combustion of natural gas or heating oil L, the flue gas temperature is approx. 15 °C higher.
18
°C
180
170
180
Technical information
4 205 116 / 02
Flue gas temperature under other operating
conditions
Influence of the boiler water temperature on the
flue gas temperature
A change in the boiler water temperature of ±10 K
results in a change of approximately ±6 K in the
flue gas temperature.
Influence of the CO2 content in the flue gases
A change in the CO2 content of ±1 % changes the
flue gas temperature by approx. ±8 °C.
Key to regulator designation
No. of regulators
Regulator width (example: 5 units)
3R5/290
Length of the regulators
4.7
Flow mixing loop / minimum limitation
of the boiler return temperature
Hydraulic and control measures must be provided
to ensure that the temperatures do not fall below
the permissible minimum boiler flow and return
temperature under any operating conditions.
4.8
4.9
Safety valves
The heating system and hot water supply must each be
protected with one safety valve against impermissibly
high pressures. The discharge capacity of the heating
system safety valve must correspond to the boiler’s
maximum nominal heat output. The valve is installed
in the safety flow. In Germany, only safety valves
with the code letter "H" in the approval mark may
be connected, and they must always be connected
at the boiler safety flow. Water shortage protection
in accordance with EN 12828 Part 2 Section 9 is
mandatory.
4.10 Charging pump (boiler with freestanding calorifier)
Speed of rotation and output regulation must
correspond to the requirements of the free-standing
calorifier. Setting carried out by the heating installation
engineer.
4.11 Heating pump
Speed of rotation and output regulation must correspond
to the requirements of the system. They are to be set
by the heating installation engineer.
Setting the temperature regulators
- without heating regulator:
Set the boiler temperature in accordance with the
outside temperature.
- with heating regulator:
The heating regulator automatically sets the
correct boiler temperature. The boiler temperature
varies between the minimum and maximum boiler
temperatures entered.
If a calorifier is connected, the priority circuit
disables the boiler temperature regulator
until the temperature is reached. The boiler
temperature can rise to approx. 85 °C.
19
Commissioning
4 205 116 / 02
5.Commissioning
• Parts of the boiler which have contact with water are
made of ferrous materials.
Heating Water
• On account of the danger of stress cracking corrosion
the chloride, nitrate and sulfate contents of the heating
water must not exceed 200 mg/l in total.
5.1
Water quality
The European Standard EN 14868 and the
directive VDI 2035 must be observed.
• The pH value of the heating water should lie between
8.3 and 9.5 after 6-12 weeks of heating operation.
In particular, attention must be paid to the following stipulations:
• Hoval boilers and calorifiers are designed for heating
plants without significant oxygen intake (plant type I according to EN 14868).
• Plants with
- continuous oxygen intake (e.g. underfloor heating
systems without diffusion proof plastic piping) or
- intermittent oxygen intake (e.g. where frequent refilling is necessary)
must be equipped with separate circuits.
• Treated filling and replacement water must be tested at
least 1x yearly. According to the inhibitor manufacturer‘s
instructions, more frequent testing may be necessary.
• A refilling is not necessary if the quality of the heating
water in existing installations (e.g. exchange of boiler)
conforms to VDI 2035.
The Directive VDI 2035 applies equally to the replacement water.
• New and if applicable existing installations need to be
adequately cleaned and flushed befor being filled. The
boiler may only be filled after the heating system has
been flushed!
Filling and replacement water
• For a plant using Hoval boilers untreated drinking water
is generally best suited as heating medium, i.e. as filling and replacement water. However, as not all drinking
water is suitable for use as as filling and replacement
water the water quality must fulfil the standard set in
VDI 2035. Should the mains water available not be suited for use then it must be desalinated and/or be treated
with inhibitors. The stipulations of EN 14868 must be
observed.
• In order to maintain a high level of boiler efficiency and
to avoid overheating of the heating surfaces the values
given in the table should not be exceeded (dependent
on boiler performance ratings - for multi-boiler plants
rating of smallest boiler applies - and on the water content of the plant).
• The total amount of filling and replacement water which
is used throughout the total service life of the boiler
must not exceed three times the water capacity of the
plant.
Maximum filling capacity based on VDI 2035
Total hardness of the filling water up to ...
[mol/m ]
f°H
d°H
e°H
~mg/l
Conductance 2
Boiler size of the
individual boiler
to 50 kW
50 to 200 kW
3 1
1
2
<0,1
<1
<0,56
<0,71
<10
<20
0,5
5
2,8
3,6
50,0
100,0
1
10
5,6
7,1
100,0
200,0
1,5
15
8,4
10,7
150,0
300,0
2
20
11,2
14,2
200,0
400,0
2,5
25
14,0
17,8
250,0
500,0
3
30
16,8
21,3
300,0
600,0
>3,0
>30
>16,8
>21,3
>300
>600
maximum filling quantity without desalination
NO REQUIREMENT
50 l/kW 20 l/kW 20 l/kW
20 l/kW
always desalinate
Sum of alkaline earths
If the conductance in µS/cm exceeds the tabular value an analysis of the water is necessary.
20
4 205 116 / 02
5.2
Commissioning
Filling the heating system
Filling of the heating system must be carried out by
trained personnel. The filling and replacement water
must comply with the quality requirements in the
relevant state or country (VDI 2035 or SWKI 88-4 or
ÖNORM H 5195).
5.3
Filling the calorifier (if present)
The heating boiler may be put into operation even
when the calorifier is not filled.
5.4Commissioning
Important:
On first commissioning, check that all safety and control
devices are functioning properly (in accordance with
the operating manual).
The operation and maintenance of the system must
be explained to the user in detail.
In some areas, gas or dual-fuel
systems may only be commissioned by
an engineer from the local gasworks.
Check with the local gasworks to
make sure.
5.5
Oil/gas burner
Setting the burner must also be carried out by
a specialist, and the setting must correspond to the
heat demand of the system.
Please see the technical information / assembly
instructions supplied with the burner.
5.6
Handover to the operator / storage
Have the operator confirm in writing that the
operating and maintenance procedures have been
explained and that he or she has received a copy
of the relevant operating manuals. (See sample on
page 38). The manufacturer of the unit is responsible
for providing operating manuals for the complete
system. This technical information / these installation
instructions must not be destroyed after completing the
commissioning procedures, but should be permanently
stored with the unit.
21
Maintenance
4 205 116 / 02
6.Maintenance
6.1
Information for fire inspector / chimney sweep regarding emission monitor key
All other control elements of the control unit are described in the operating instructions.
The emission monitor key can also be used to change over to manual operating mode.
Emission monitor key / Manual operation
To protect under floor heating systems
against invalid overheating during emission monitoring / manual operation it is
necessary to implement appropriate safety
measures (e.g. safety temperature limiter
with pump switch-off). The duration of the
emission monitoring is limited to 20 minutes and shall be restarted, if necessary.
Scalding hazard due to hot water temperature, since the hot water temperature can
exceed the temperature setpoint!
Emissions metering


PRESS
SHORTLY
Immediate end
Remaining time display
REACTIONS for emissions metering
• Time unit automatically 20 min. – thereafter reverts
• Boiler temperature - > maximum temperature restriction
• Regulate to the maximum temperature… the heating circuits and the water heaters (at the direct heating circle only,
if the warm water mode of operation is adjusted to parallel operation)
• With 2-step heat generator both stages are in operation
Manual operation


Immediate end
PRESS
> 5 seconds
REACTIONS for manual operation
• Set reference boiler temperature with button!
• All heating pumps ON
• Mixer without current - manual setting necessary!
• Note the maximum permissible temperature of the floor heating!
• The hot water temperature reaches the set DHW maximum temperature (expert level standard 65°C).
22
4 205 116 / 02
Maintenance
6.2Cleaning
Cleaning should be performed at least twice per year.
Cleaning at intermediate intervals is necessary if the
flue gas temperature rises.
6.2.1 Preparatory work
- Switch boiler off (controller: set switch to "O,"
pull the burner plug)
- Interrupt the fuel supply
- Open the boiler door
- Remove regulators (Figure 13)
- Remove flue gas collector cleaning cover (back)
6.2.2 Cleaning (dry or wet method)
- Clean combustion chamber, 2-pass (cylindrical
tubes), 3-pass (ribbed heating surface) thoroughly
with a brush or spray and then remove any
combustion residue or sprayed liquid from the flue
gas collector and from the combustion chamber.
For wet cleaning:
Treat seals with graphite before carrying out
wet cleaning.
- Dispose of the cleaning fluid (scrubbing liquid) in
accordance with regulations.
6.2.3 Putting into operation again
- Insert the regulators
- Fit cleaning cover
- Close boiler door and reconnect burner plug.
Do not overtighten boiler door screws.
- Reconnect the fuel supply
- Where applicable, refit front cover
- Reset boiler switch to "autom." or "I".
23
Overview of settings
7.
7.1
4 205 116 / 02
Overview of settings
Table of parameters
Designation
Regulator
Factory
10
20
30
40
50
Setting range /
Setting values
Type of device:
DHW:
SW:
Address:
Surface operation
Key :
Heating curve HC
OFF
OFF, 0,20 .... 3,5
Heating curve MC1
1,0
OFF, 0,20 .... 3,5
Heating curve MC2
1,0
OFF, 0,20 .... 3,5
Daytime target temperature HC
*)
20°C
5 .... 30°C *)
Daytime target temperature MC1
*)
20°C
5 .... 30°C *)
Daytime target temperature MC2
*)
20°C
5 .... 30°C *)
Night-time target temperature HC
*)
16°C
5 .... 30°C *)
Night-time target temperature MC1 *)
16°C
5 .... 30°C *)
Night-time target temperature MC2 *)
16°C
5 .... 30°C *)
DHW target temperature
50°C
5 ... DHW-Max.
*) Depending on the setting of system parameters 03 OPERATING MODE
Remote operation/room stations
Type
24
Heating circuit
Address
HW
SW
Overview of settings
4 205 116 / 02
Table for Time programs
DHW circuit
Time program P1
Tag
Cycle 1
from
to
Cycle 2
from
to
Time program P2
Cycle 3
from
to
Cycle 1
from
to
Cycle 2
from
to
Time program P3
Cycle 3
from
to
Cycle 1
from
to
Cycle 2
from
to
Cycle 3
from
to
Mo
Tu
We
Th
Fr
Sa
Su
Direct circuit
Time program P1
Tag
Cycle 1
from
to
Cycle 2
from
to
Time program P2
Cycle 3
from
to
Cycle 1
from
to
Cycle 2
from
to
Time program P3
Cycle 3
from
to
Cycle 1
from
to
Cycle 2
from
to
Cycle 3
from
to
Mo
Tu
We
Th
Fr
Sa
Su
Mixer Circuit 1
Time program P1
Tag
Cycle 1
from
to
Cycle 2
from
to
Time program P2
Cycle 3
from
to
Cycle 1
from
to
Cycle 2
from
to
Time program P3
Cycle 3
from
to
Cycle 1
from
to
Cycle 2
from
to
Cycle 3
from
to
Mo
Tu
We
Th
Fr
Sa
Su
Mixer Circuit 2
Time program P1
Tag
Cycle 1
from
to
Cycle 2
from
to
Time program P2
Cycle 3
from
to
Cycle 1
from
to
Cycle 2
from
to
Time program P3
Cycle 3
from
to
Cycle 1
from
to
Cycle 2
from
to
Cycle 3
from
to
Mo
Tu
We
Th
Fr
Sa
Su
25
Overview of settings
4 205 116 / 02
HYDRAULIC
Par.
Designation
Factory
10
20
30
40
50
Lev.
2
Function allocation of the output DHW charging pump
1
HF
3
Function allocation of the output Mixer circuit 1
3
HF
4
Function allocation of the output Mixer circuit 2
3
HF
5
Function allocation of the output Direct circuit Pump
2
HF
6
Function allocation of the variable output 1
OFF
HF
7
Function allocation of the variable output 2
OFF/ 4/ 43
HF
8
Function allocation of the variable input 1
OFF
HF
9
Function allocation of the variable input 2
OFF
HF
10
Function allocation of the variable input 3
OFF/ 2/ 33
HF
11
Indirect return increase
OFF
HF
12
Maximum limit energy management
80 °C
HF
13
Activation cooling buffer
OFF
HF
14
Release contact cooling to KVLF
OFF
HF
SYSTEM
Par.
Designation
LANGUAGE Selection of the style-language
10
20
30
40
50
Lev.
EN
BE
P1
HF
1
HF
2
Number of cleared switching time programs
3
Clearing for separate operating mode
4
Limit temperature for summer disconnection
22 °C
HF
5
System frost protection
3 °C
HF
6
Demand contact module for VE1
1
HF
7
Demand contact module for VE2
1
HF
8
Demand contact module for VE3
9
Air conditioning zone
10
Building type
Automatic reversion time (surface end user level, except
info. level)
Pump and mixer compulsory operation
11
12
13
14
15
Logical fault signal
Automatic SET function
(after 24:00, is automatically set to OFF)
Blocking code for heating Installer
1
HF
-12 °C
HF
2
HF
5 min
HF
ON
HF
OFF
HF
ON/ OFF
HF
OEM
OFF
HF
30 min
HF
0
HF
OFF
HF
18
Release cycle temperature
19
Frost protection mode
21
RTC adjustment
23
Blocking code operator level
24
Temperature display in Fahrenheit
OFF
OEM
26
First commissioning date (after 24:00)
-
OEM
27
Fault report (only TTT/UG)
2
HF
28
Fault stack 2
ON
HF
29
Characteristic curve emergency operation
0 °C
HF
30
Thermostat function sensor allocation
31
Thermostat function reference value
32
33
RESET
26
Factory
AF
HF
1 °C
HF
Thermostat function switching difference
3K
HF
Thermostat function anti-blocking protection
Top: ArtNo - HW Index
Bottom: Code:REV - Software version
Reset parameter values
ON
HF
-----
OEM
BE
Overview of settings
4 205 116 / 02
DHW
Par.
Designation
Factory
10
20
30
40
50
Lev.
40/ 45 °C
BE
2
DHW-legionella protection-day
OFF
HF
3
DHW-egionella protection-time
HF
4
DHW-legionella protection-temperature
5
DHW-temperature recording
6
DHW-maximum temperature limit
7
DHW-mode of operation
2:00
50/ 55/ 65/
70 °C
1
50/ 55/ 65/
70 °C
1
8
DHW-tank discharge protection
DHW-NIGHT DHW - economy temperature
9
DHW-charging temperature excess
10
DHW-switching difference
11
DHW-charging pump follow-on
12
ZKP-switching time program
13
ZKP-economy interval (pause)
14
ZKP-economy interval (period duration)
17
H-GEN behaviour during SLP follow-on time
18
DHW-parallel loading
19
DHW-time-out
20
PI-reference value control
21
PI-amplification factor, P-portion Xp
22
PI-scanning time Ta
23
PI -reset time Tn
HF
HF
HF
HF
ON/ OFF
HF
7/ 20 K
HF
5K
0.5/ 1/ 2/ 5
min
AUTO
OEM
0 min
HF
OEM
HF
20 min
HF
AUTO/ OFF
HF
OFF
OFF/
30 min
OFF
HF
HF
0,1 %/ K
OEM
20 s
OEM
600 s/ °C
OEM
HF
UNMIXED CIRC
Par.
Designation
Factory
10
20
30
40
50
Lev.
1
Type of reduced operation
ECO/ ABS
HF
2
Heating system (exponent)
DK= 1,30
HF
3
Room override (in connection with room sensor)
3
HF
4
Room factor
OFF
HF
5
Adaptation heating curve
OFF
HF
6
Switch-on optimisation
1
HF
7
Heating limit
0,5
OEM
8
Room frost protection limit
10 °C
HF
OFF
HF
0
HF
20 °C
HF
9
Room thermostat function
10
Outside temperature allocation
11
Constant temperature reference value
12
Minimum temperature limit
10 °C
HF
13
Maximum temperature limit
55/ 75 °C
HF
14
Temperature elevation Heating circuit
DK=0
HF
15
Pump follow-on
5 min
HF
16
Screed function
OFF
HF
23
Room control K-factor
8
HF
24
Room control Tn-factor
35 min
HF
25
Vacation mode
STBY
HF
36
Minimum value override
OFF
HF
XXXXX
HF
Name heating circuit (max. 5 letters)
27
Overview of settings
4 205 116 / 02
MIX. VALVE-1
Par.
Designation
10
20
30
40
50
Lev.
1
Type of reduced operation
ECO/ ABS
HF
2
Heating system (exponent)
MK= 1,10
HF
3
Room override (in connection with room sensor)
4
Room factor
3
HF
100 %
HF
ON
HF
1
HF
5
Adaptation heating curve
6
Switch-on optimisation
7
Heating limit
0,5
OEM
8
Room frost protection limit
10 °C
HF
OFF
HF
0
HF
20 °C
HF
9
Room thermostat function
10
Outside temperature allocation
11
Constant temperature reference value
12
Minimum temperature limit
10 °C
HF
13
Maximum temperature limit
55/ 75 °C
HF
14
Temperature elevation/ abatement heating circuit
0/ 8 K
HF
15
Pump follow-on
5 min
HF
OFF
HF
2,0 %/ K
OEM
Scanning time Ta
20 s
OEM
I-portion Tn
270 s
OEM
21
Running time servomotor
150 s
HF
22
End position function, valve
1
OEM
23
Room control K-factor
8
HF
24
Room control Tn-factor
35 min
HF
25
Vacation mode
STBY
HF
36
Minimum value override
OFF
HF
37
Mixer lead time
OFF
HF
38
Regulation offset
0
HF
50
Cooling switch-on point, OT
OFF
HF
51
Cooling max. point, OT
35 °C
HF
52
Cooling reference flow temp. at switch-on point
18 °C
HF
53
Cooling reference flow temp. at max. point
24 °C
HF
54
Cooling reference room temp. at switch-on point
23 °C
HF
55
Cooling reference room temp. at max. point
28 °C
HF
18 °C
OEM
XXXXX
HF
16
Screed function
18
P-portion Xp
19
20
56
Min. temp. cooling
Name heating circuit (max. 5 letters)
28
Factory
Overview of settings
4 205 116 / 02
MIX. VALVE-2
Par.
Designation
Factory
10
20
30
40
50
Lev.
1
Type of reduced operation
ECO/ ABS
HF
2
Heating system (exponent)
MK= 1,10
HF
3
Room override (in connection with room sensor)
4
Room factor
3
HF
100 %
HF
ON
HF
1
HF
5
Adaptation heating curve
6
Switch-on optimisation
7
Heating limit
0,5
OEM
8
Room frost protection limit
10 °C
HF
OFF
HF
0
HF
20 °C
HF
9
Room thermostat function
10
Outside temperature allocation
11
Constant temperature reference value
12
Minimum temperature limit
10 °C
HF
13
Maximum temperature limit
55/ 75 °C
HF
14
Temperature elevation/ abatement heating circuit
0/ 8 K
HF
15
Pump follow-on
5 min
HF
OFF
HF
2,0 %/ K
OEM
Scanning time Ta
20 s
OEM
I-portion Tn
270 s
OEM
21
Running time servomotor
150 s
HF
22
End position function, valve
1
OEM
23
Room control K-factor
8
HF
24
Room control Tn-factor
35 min
HF
25
Vacation mode
STBY
HF
36
Minimum value override
OFF
HF
37
Mixer lead time
OFF
HF
38
Regulation offset
0
HF
50
Cooling switch-on point, OT
OFF
HF
51
Cooling max. point, OT
35 °C
HF
52
Cooling reference flow temp. at switch-on point
18 °C
HF
53
Cooling reference flow temp. at max. point
24 °C
HF
54
Cooling reference room temp. at switch-on point
23 °C
HF
55
Cooling reference room temp. at max. point
28 °C
HF
18 °C
OEM
XXXXX
HF
16
Screed function
18
P-portion Xp
19
20
56
Min. temp. cooling
Name heating circuit (max. 5 letters)
29
Overview of settings
4 205 116 / 02
HEAT GENER.
Par.
Designation
Factory
10
20
30
40
50
Lev.
1/ 2/ 5
HF
OFF/ 3
5/ 48/ 65/ 75
°C
75/ 85 °C
HF
HF
1
HF
1
H-GEN model
2
Start-up protection H-GEN
3
Minimum temperature limit H-GEN
4
Maximum temperature limit H-GEN
5
Mode of action minimum temperature limit H-GEN
6
Sensor mode operation for H-GEN
7
Minimum burner running time
8
9
10
11
12
DHW charging mode 1-2 stage
13
Lead time, boiler circuit pump
14
Follow-on time, boiler circuit pump or parallel boiler release
5 min
HF
15
Search time feed pump, primary pump
5 min
HF
16
Exhaust gas temperature monitoring
OFF
HF
17
Exhaust gas limit value
18
Boiler gradient
19
Modulation P-portion Xp
20
Modulation scanning time Ta
21
Modulation adjustment time Tn
22
Modulation running time
23
Modulation starting time
24
Modulation start-up output
25
Outside temperature block
26
Basic charge elevation
27
29
Minimum temperature limit, heating circuits
Switching difference, minimum temperature limit Heating
circuits
H-GEN forced discharge
30
OEM Maximum limit
110 °C
OEM
31
Minimum load control
OFF
OEM
34
Output limitation heating
100 %
HF
35
Output limitation hot water
100 %
HF
36
ET blocking 2.burner stage
OFF
HF
37
Running time meter
38
DHW release regulator (CD)
39
Emergency operation temperature H-Gen (e.g. for 70-8)
40
Heat balance (from V3.2)
41
Reset heat balance
28
HF
1
OEM
2 min
HF
Burner switching difference I
6K
HF
Burner switching difference II
12 K
HF
Time-out stage II
10
HF
Release mode stage II
1
HF
2
HF
1 min
HF
42
Volumetric flow rate
43
Density, medium
44
Specific thermal capacity, medium
200 °C
HF
OFF
OEM
5 %/ K
OEM
20 s
OEM
180 s/ °C
OEM
12 s
HF
200 s
HF
70
HF
OFF
OEM
0 K/ 10K
OEM
5/ 38/ 65 °C
HF
2K
OEM
OFF
HF
1
HF
ON
HF
70 °C
HF
ON
HF
HF
0,0 l/ min
0,0 l/ IMP
1,00 kg/ l
4,2
HF
HF
HF
RESET ST-1 Reset counters starts and running time, stage 1
OEM
RESET ST-2 Reset counters starts and running time, stage 2
OEM
30
Overview of settings
4 205 116 / 02
RETURN CONTR
Par.
2
Designation
Minimum limit return temperature / reference value return
temperature
Switch-off difference
3
Pump follow-on time
1
Factory
10
20
30
40
50
Lev.
38 °C
HF
2K
HF
1 min
HF
SOLAR
Par.
Designation
Factory
10
20
30
40
50
Lev.
1
Switch-on difference
10 K
HF
2
Switch-off difference
5K
HF
3
Minimum running time SOP
3 min
HF
4
Solar collector maximum temperature
100 °C
HF
5
Solar tank maximum limit (KSPF)
65 °C
HF
6
Solar mode of operation
2
HF
7
Heat generator cycle lock (only when parameter 06=1,3,4)
0,5 h
HF
8
Solar priority parallel changeover
10 K
HF
Solar heat balance
OFF
HF
9
SOLAR
RESET
Reset heat balance
HF
0,0 l/ min
0,0 l/ IMP
1,05 kg/ l
11
Volumetric flow rate
12
Density, medium
13
Specific thermal capacity, medium
14
15
16
Switch-over temperature (SLVF)
60 °C
HF
17
Solar minimum temperature
OFF
HF
HF
HF
3,6 KJ/ kgK
HF
Final switching-off temperature
120 °C
HF
Test cycle solar charging switch-over
10 min
HF
SOLID FUEL
Par.
Designation
Factory
10
20
30
40
50
Lev.
1
Minimum temperature
60 °C
HF
2
Maximum temperature
95 °C
HF
3
Switch-on difference
10 K
HF
4
Switch-off difference
5K
HF
5
Clock block, heat generator
15
HF
31
Overview of settings
4 205 116 / 02
BUFFER
Par.
Designation
Factory
10
20
30
40
50
Lev.
1
Minimum temperature
5/ 20 °C
HF
2
Maximum temperature
95 °C
HF
3
Temperature elevation, H-GEN
8/ 10/ 12K
HF
4
Switching difference
2/ 5/ 10K
HF
5
Forced discharge
OFF
HF
6
Skimming function switch-on difference
10 K
HF
7
Skimming function switch-off difference
5K
HF
8
Start-up protection
OFF
HF
9
Discharge protection
OFF
HF
10
Buffer mode of operation
2/ 3
HF
11
Pump follow-on time
3 min
HF
12
Switch-off reference value temp.
70 °C
HF
13
H-GEN release temp. skimming function
60 °C
HF
MAIN SUPPLY
Par.
Designation
Factory
10
Lev.
0 %/ K
HF
20 s
HF
600 s/ °C
HF
1
PI-amplification factor, P-portion Xp
2
PI-scanning time Ta
3
PI -reset time Tn
Designation
Factory
CASCADE
Par.
10
Lev.
1
Switch-off difference
3K
OEM
2
Connecting delay
20
OEM
3
Switch-off delay
5
OEM
4
Switching output stage sequence
65
OEM
5
Stage reversal
OFF
OEM
6
Control stage
1
BE
7
Peak load stage
OFF
OEM
8
Group switch-over
OFF
OEM
9
DHW fast activation
OFF
OEM
10
Peak load elevation
10 K
OEM
BUS
Par.
32
Designation
Factory
10
20
30
40
50
Lev.
1
Bus address central device
10
HF
2
Bus right RS direct circuit
1
HF
3
Bus right RS mixer circuit 1
1
HF
4
Bus right RS mixer circuit 2
1
HF
Overview of settings
4 205 116 / 02
SERVICE
Par.
Designation
Factory
10
20
30
40
50
Lev.
Service 1 (Cleaning ST1 )
7
BE
Cleaning according to fixed date
OFF
BE
Cleaning according to fixed interval
OFF
BE
4
Cleaning according to cleaning counter
OFF
BE
5
Reset cleaning display 1
1
Suspend message «CLEANING ST-1» for X days
2
3
BE
Service 2 (Cleaning ST2)
7
BE
Cleaning according to fixed date
OFF
BE
Cleaning according to fixed interval
OFF
BE
9
Cleaning according to cleaning counter
OFF
BE
10
Reset cleaning display 2
6
Suspend message «CLEANING ST-2» for X days
7
8
BE
Service 3 (maintenance ST1 )
11
Suspend message «MAINTENANCE ST-1» for X days
7
HF
12
Maintenance according to fixed date
OFF
HF
13
Maintenance according to fixed interval
OFF
HF
14
Maintenance according to maintenance counter
OFF
HF
15
Reset maintenance display 1
HF
Service 2 (maintenance ST2 )
16
Suspend message «MAINTENANCE ST-2» for X days
7
HF
17
Maintenance according to fixed date
OFF
HF
18
Maintenance according to fixed interval
OFF
HF
19
Maintenance according to maintenance counter
OFF
HF
20
Reset maintenance display 2
HF
ALARM 1
Par.
Designation
10
20
30
40
50
Lev.
1
Alarm 1
OEM
2
Alarm 2
OEM
3
Alarm 3
OEM
4
Alarm 4
OEM
Alarm 5 - 20
OEM
Reset fault signals
OEM
5 ... 20
21
ALARM 2
Par.
(can ony be activated with H-Gen 5)
Designation
10
20
30
40
50
Lev.
1
Alarm 1
OEM
2
Alarm 2
OEM
3
Alarm 3
OEM
4
Alarm 4
OEM
Alarm 5 - 20
OEM
Reset fault signals
OEM
5 ... 20
21
33
Overview of settings
4 205 116 / 02
FAULT REPORTING OVERVIEW TopTronic®T
Status
34
Designation
Fault type
Code
System
External sensor
Interruption
10-0
System
External sensor
Short-circuit
10-1
System
Boiler sensor
Interruption
11-0
System
Boiler sensor
Short-circuit
11-1
Remark
System
Flow sensor 1
Interruption
12-0
MC1=off, YK1=no current
System
Flow sensor 1
Short-circuit
12-1
MC1=off, YK1=no current
System
Storage sensor
Interruption
13-0
System
Storage sensor
Short-circuit
13-1
System
VE 2
Interruption
14-0
System
VE 2
Short-circuit
14-1
System
VE 2
Alarm
14-7
System
VE 3
Interruption
15-0
System
VE 3
Short-circuit
15-1
System
VE 3
Alarm
15-7
System
VE 1
Interruption
16-0
System
VE 1
Short-circuit
16-1
System
VE 1
Alarm
16-7
System
Solar tank sensor
Interruption (KSPF)
17-0
System
Solar tank sensor
Short-circuit (KSPF)
17-1
System
Flow sensor 2
Interruption
18-0
MC2=off, YK2=no current
System
Flow sensor 2
Short-circuit
18-1
MC2=off, YK2=no current
System
Collector sensor
Interruption (KVLF)
19-0
System
Collector sensor
Short-circuit (KVLF)
19-1
System
Room sensor (RS)
Interruption
20-0
System
Room sensor (RS)
Short-circuit
20-1
System
Burner 1
No switching off (1 min)
30-2
With par. log. alarm can be switched off
System
Burner 1
No switching on (10 min)
30-3
With par. log. alarm can be switched off
System
Burner 2
No switching off (1 min)
31-2
With par. log. alarm can be switched off
With par. log. alarm can be switched off
System
Burner 2
No switching on (10 min)
31-3
System
Exhaust gas temperature
Exceeding
33-5
System
Exhaust gas temperature
SLT triggered
33-8
System
Cleaning stage 1
Triggering by date
40-1
System
Cleaning stage 1
Triggering by interval
40-2
System
Cleaning stage 1
Triggering by counter
40-4
System
Maintenance stage 1
Triggering by date
41-1
System
Maintenance stage 1
Triggering by interval
41-2
System
Maintenance stage 1
Triggering by counter
41-4
System
Cleaning stage 2
Triggering by date
42-1
System
Cleaning stage 2
Triggering by interval
42-2
System
Cleaning stage 2
Triggering by counter
42-4
System
Maintenance stage 2
Triggering by date
43-1
System
Maintenance stage 2
Triggering by interval
43-2
System
Maintenance stage 2
Triggering by counter
43-4
Overview of settings
4 205 116 / 02
FAULT REPORTING OVERVIEW TopTronic®T
Status
Designation
Fault type
Code
Logical
Boiler temperature
Not reached (90 min)
50-4
Logical
Tank temperature
Not reached (4 h)
51-4
Logical
Flow temperature MC1
Not reached (1 h)
52-4
Logical
Flow temperature MC2
Not reached (1 h)
53-4
Logical
Room temperature HC
Not reached (3 h)
54-4
Logical
Room temperature MC1
Not reached (3 h)
55-4
Logical
Not reached (3 h)
56-4
Address collision
70-0
System
Room temperature MC2
Lock by energy supply company
ST 2
Activity
No T2B signal
70-1
System
Activity
70-6
System
Activity
System
System
Activity
HP return sensor
No FA signal
Regulator with address 10 is
missing
Data bus error
Return min. temp. below setpoint
System
HP return sensor
85-5
System
QF
System
QF
Return max. temp. exceeded
Heat source min. temp. below
setpoint
Heat source max. temp. exceeded
(cooling operation)
System
System
QF
WPS
Fault heat source sensor
Variable input HP fault
-87-7
System
System
System
System
Pulse counter
Fault
Fault
Fault
No pulse (5 min)
Warning
Lock-out
Blocking
90-0
W:XX
E:XX
B:XX
System
Remark
70-8
70-9
85-4
No Hoval regulator
86-4
86-5
Standard signal «VE-x»
Warning in automatic firing device
Fault in automatic firing device
Fault in automatic firing device
SENSOR ALLOC.
Par.
1
Designation
Factory
10
20
30
40
50
Lev.
Balancing external sensor
0
OEM
Balancing room sensor (only adjustable with RS-T)
0
HF
2
Balancing heat generator
0
OEM
3
Balancing tank sensor
0
OEM
4
Balancing flow sensor 1
0
OEM
5
Balancing flow sensor 2
0
OEM
6
Balancing solar collector sensor
0
OEM
7
Balancing solar buffer sensor
0
OEM
8
Balancing variable input 1
0
OEM
9
Balancing variable input 2
0
OEM
10
Balancing variable input 3
0
OEM
RS-T
35
4 205 116 / 02
36
4 205 116 / 02
37
COPY FOR PLANT USER
Confirmation
The user (owner) of the system herewith confirms that
• he has received adequate instruction in the operating and maintenance of the installation,
• received and taken note of the operating and maintenance instructions and, where applicable other documents concerning the heat generator and any further components.
• and is consequently sufficiently familiar with the installation.
Installation address:
Type:
Serial number:
Year of manufacture:
Place, Date:
System installer:
System user:
COPY OF SYSTEM INSTALLER
Confirmation
The user (owner) of the system herewith confirms that
• he has received adequate instruction in the operating and maintenance of the installation,
• received and taken note of the operating and maintenance instructions and, where applicable other documents concerning the heat generator and any further components.
• and is consequently sufficiently familiar with the installation.
Installation address:
Type:
Serial number:
Year of manufacture:
Place, Date:
System installer:
System user:
Download