Systems Inc. 1935, Lionel-Bertrand Blvd. Boisbriand, Quebec, Canada J7H 1N8 Tel.: (450) 437-3473 Fax: (450) 437-1930 Toll Free: (866) 347-3353 Web Site: http://www.fireflex.com TOTALPAC2 Integrated Fire Protection Systems Standard Specifications Deluge Systems Hydraulic Release (w/o control panel) FM-072D-0-89 C Nov. 2011 Fire Protection Division 13 Remote Controlled Deluge System with Hydraulic Release Section 13940 - Table of Contents Part 1 - GENERAL 1.0 1.1 1.2 1.3 1.4 1.5 1.6 Related Work in Other Sections ...................................................................................... 3 Standards & Rules ........................................................................................................... 3 System Description .......................................................................................................... 3 System Design ................................................................................................................. 3 Drawings & Hydraulic Calculations .................................................................................. 4 Technical Data ................................................................................................................. 4 Maintenance & Operation Manual ................................................................................... 4 Part 2 - COMPONENTS 2.1 2.2 2.3 2.4 2.5 2.6 2.7 2.8 Deluge Cabinet ................................................................................................................ 5 Cabinet Options ............................................................................................................... 5 Detection & Signalling Devices ........................................................................................ 6 System Operation ............................................................................................................ 6 Automatic Sprinklers ........................................................................................................ 6 Hydraulic Releases .......................................................................................................... 6 Piping ............................................................................................................................... 7 System Drain ................................................................................................................... 7 Part 3 - EXECUTION 3.1 3.2 3.3 3.4 Installation ........................................................................................................................ 8 Training ............................................................................................................................ 8 Tests & Verifications ........................................................................................................ 8 Report & Certificate .......................................................................................................... 8 IMPORTANT: Due to variable job conditions or additional requirements requested by owner or authorities having jurisdiction this document is intended as an information guide only and not as a final project design. The consulting engineer should make appropriate adjustments for the project involved. Fire Protection Division 13 Remote Controlled Deluge System with Hydraulic Release Section 13940 3 .1 .2 Fire Protection General Prescription Electrical Division 13, Section 13950 Division 13, Section 13850 .1 .2 NFPA 13 (Installation of Sprinkler Systems) NFPA 25 (Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems) NFPA 72 (Standard for the Installation, Maintenance, and Use of Protective Signaling Systems) NFPA 72E (Standard on Automatic Fire Detectors) CAN/ULC-S524 (Standard for the Installation of Fire Alarm Systems) – For Canada only ! CAN/ULC-S537 (Standard for the Verification of Fire Alarm Systems) – For Canada only ! National Building Code National Fire Code National Electrical Code Part 1 - GENERAL 1.0 Related Work in Other Sections 1.1 Standards & Rules .3 .4 .5 .6 .7 .8 .9 1.2 System Description .1 Supply and install a remote controlled TotalPac2 integrated fire protection system, deluge type as indicated, including: - Deluge cabinet - Open type sprinkler system - Hydraulic fire detection system (pilot line) .2 The integrated unit shall be c-UL-us Listed and FM Approved as an assembled unit. All system components shall be "compatible", UL, C-UL listed or FM approved. Note: The word compatible used in this specification means that the items concerned have been tested and listed and/or approved for their use together. 1.3 System Design .1 .2 .3 The system must be designed for: - occupancy hazard: - density gpm/sq. ft. ( L/min./m²) - area of sprinkler operation sq. ft. ( m²). Water supply: Location: Static pressure: psi ( kPa) Residual pressure: psi ( kPa) Water flow: gal/min. ( L/min.) The maximum area coverage per pilot head shall not exceed the manufacturer's recommendations. Fire Protection Division 13 Remote Controlled Deluge System with Hydraulic Release Section 13940 4 1.4 Drawings & Hydraulic Calculations .1 The fire protection contractor must prepare and submit for the engineer's approval all installation drawings and hydraulic calculations, as required by NFPA. .1 Submit for the engineer's approval a set equipment data sheets which will include all technical data of each essential component of the system such as integrated unit and options, open type sprinklers or nozzles, pilot heads, control system, etc. .1 Supply a standardized and listed Maintenance & Operation manual for the deluge system. This manual must include all necessary instructions to operate and maintain the system, and be explicit regarding the interaction between the hydraulic aspect (deluge valve and trim) and the detection portion, pilot line and heads (remote control panel is provided by others or existing). Emergency procedures must form an integral part of the manual. 1.5 Technical Data 1.6 Maintenance & Operation Manual .2 Fire Protection Division 13 Remote Controlled Deluge System with Hydraulic Release Section 13940 5 Part 2 - COMPONENTS 2.1 Deluge Cabinet .1 .2 Supply and install a remote controlled deluge cabinet with hydraulic release, containing all hydraulic and electrical components required for the control of a deluge system. The cabinet shall include the following: - Remote controlled unit (without control panel) in a sturdy 14 gauge steel cabinet, measuring: - 57" x 36" x 20" (145 x 91 x 51cm) for 1½", 2" & 3" systems; - 57" x 46" x 24" (145 x 117 x 61cm) for 4" & 6" systems. - Textured rust proof coating, inside and outside, fire red, oven baked polyester powder on phosphate base (powder coated). - Two locked access doors to reduce front area required for opening, easily removable without tools to allow easy installation & servicing. - Individual access doors for the hydraulic section and the emergency release with a neoprene gasket to avoid vibrations. - Viking Deluge Valve model E, complete with releasing trim rated at 250 psi and all the necessary accessories. Trim shall include a mechanical latching device to prevent system from resetting. Systems provided without this mechanical latching device shall not be accepted. Every valve shall be clearly identified as to its operation with arrows indicating all positions to facilitate system operation. - Pressure gauges to indicate water supply and priming water pressures of the system. Each pressure gauge must be provided with its own shut-off valve and shall be clearly identified on the outside of the cabinet front door. - Schedule 40 galvanized steel release trim with pneumatic actuator and each supervisory and alarm device required. Black pipe will not be accepted. - Schedule 40 steel pipe header painted fire red, with grooved ends to be connected to supply water from either side. - Schedule 40 steel pipe drain manifold of 2" diameter painted fire red, with grooved ends for drain connections from either side. - Properly identified contractor test ports factory mounted into the trim piping to facilitate system testing and commissioning. - Field wiring terminal strips integrated with the cabinet for connection of field wiring for remote detection system, audible devices and auxiliary contacts. The cabinet assembly must be pre-assembled, pre-wired and factory tested under ISO-9001 conditions, as a TotalPac2 system, by FireFlex Systems Inc. It shall also be c-UL-us Listed and FM Approved as an assembled unit. 2.2 Cabinet Options Choose applicable options: Yes No Provide a Listed and Approved isolation butterfly valve installed on the system riser inside the cabinet for full flow test purposes. The valve shall be supervised and wired at the factory. An integrated sight glass shall be part of this arrangement for visually confirming water flow through the main drain upon system actuation. A detailed instructions placard must be provided inside the cabinet door for easy reference. Fire Protection Division 13 Remote Controlled Deluge System with Hydraulic Release Section 13940 6 2.2 Cabinet Options (Cont'd) Yes No Provide a tee connection inside the cabinet with an opening on the right side of the cabinet enclosure for connection to the Fire Department Connection. Yes No Seismic Option The TotalPac2 cabinet shall include a seismicallyrated cabinet construction that meets the highest max earthquake found, location Portageville, Missouri, Site Class "D" Occupancy CATEGORY IV, Importance factor I = 1.50, SDC "D". The cabinet assembly shall have been subjected to seismic testing (ie – shake table test) and be OSHPD pre-approved under OSP-0104-10 The anchors shall be calculated by a structural engineer or utilize anchoring detail as per installation details found in TotalPac2 Seismic Option datapage # FM-076D-0-7. 2.3 Detection & Signalling Devices .1 Supply and install a complete hydraulic detection system including: - Hydraulic release piping network with fixed temperature releases (pilot heads). .2 Supply and install supervisory and alarm connections between the unit field wiring terminals and the building fire alarm panel, including: - System tubing, wiring and signaling devices. .1 The activation of a fixed temperature release (pilot head) is necessary to cause the water discharge. .2 The activation of at least one fixed temperature release (pilot head) will release priming pressure and open the deluge valve. This will cause the system to fill the piping network with water, spray through all open type sprinklers or nozzles and activate alarm and water flow contacts connected to the building fire alarm panel. .3 Operation of the emergency manual release will drain the priming chamber of the deluge valve, causing the system to immediately fill the piping network with water, and activate alarm and water flow contacts connected to the building fire alarm panel. .1 Supply and install all required open type sprinklers. They will be UL/ULC listed and FM approved. Applicable specifications of automatic sprinklers shall be determined as per the manufacturer recommendations, based on the project conditions. 2.4 System Operation 2.5 Automatic Sprinklers .2 2.6 Hydraulic Releases .1 .2 Hydraulically operated systems shall be provided with a separate piping network, equipped with fixed temperature releases (pilot heads) Viking Microfast Model M. Temperature setting, quantity and location of pneumatic releases shall meet the manufacturer's recommendation. Fire Protection Division 13 Remote Controlled Deluge System with Hydraulic Release Section 13940 7 2.7 Piping .1 System piping and fittings shall be as recommended by NFPA 13. .1 The single drain collector of the Viking TotalPac2 system shall be connected to an open drain (open end pipe with an air gap around the drain pipe or equivalent). The drain piping shall not be restricted or reduced and shall be of the same diameter as the drain collector. It shall also be arranged to avoid back-pressurizing the drain trim. Multiple drain collectors and open drain cups inside the cabinet will not be accepted. Manifolding of multiple units is permited provided the manufacturer's recommendations are carefully followed and complied with. 2.8 System Drain .2 Fire Protection Division 13 Remote Controlled Deluge System with Hydraulic Release Section 13940 8 Part 3 - EXECUTION 3.1 Installation .1 .2 The installation must meet all established standards and be according to all applicable laws, regulations and codes. The proper operation and coordination for the system's installation, including the open sprinkler system, detection system, signaling system and initial start-ups are all under the responsibility of the fire protection contractor. 3.2 Training .1 .2 The fire protection contractor must plan and organize a training session of at least two hours for the building maintenance staff, in the presence of building owner or his representative. The training session must include the normal operation, emergency procedures and maintenance of the system. 3.3 Tests and Verifications .1 .2 .3 .4 Hydrostatic tests must be performed on the entire sprinkler piping system, as required by NFPA 13. In addition to the standard hydrostatic test, an air pressure leakage test at 40 psi (2.8 bars) shall be conducted for 24 hours. Any leakage that results in a loss of pressure in excess of 1½ psi (0.1 bar) during the 24 hours shall be corrected. A drain test using the auxiliary drain valve fully open (drain located on water supply side, deluge valve inlet) must be performed to make sure that no back pressure in drain piping exists, which could affect the proper operation of the preaction system. The verification of the fire alarm system must be done in accordance with NFPA 72, Chapter 7 (CAN/ULC-S537 in Canada). 3.4 Report & Certificate .1 An inspection report and a certificate must be supplied to the engineer at the completion of the project. All tests results shall be duly registered in a booklet to be included with the inspection report. Fire Protection Division 13 Remote Controlled Deluge System with Hydraulic Release THIS PAGE LEFT BLANK INTENTIONALLY Section 13940 9