1.01 Emergency DMX bypass Switch

advertisement
Section 16500 – EMERGENCY DMX BYPASS SWITCH
1.01
EMERGENCY DMX BYPASS SWITCH
A.
GENERAL
Philips Strand Lighting’s Emergency DMX Bypass Switch provides Emergency and
Panic Lighting control solutions for DMX driven House Lights and DMX controlled
Lighting used in emergency and egress lighting. Each Bypass unit can handle Up to
four (4) individual universes of DMX and can also act as a DMX splitter handling 1 in 4
out or 2 in 2 out routing scenarios. Bypass handles more than just emergency and has
a separate trigger for Panic lighting states.
Each state - Panic or Emergency - can be set to trigger “snap shot” loads or can be
set to drive all loads on each DMX path to 100%. Each state (Panic or Emergency)
can be triggered via normally open, normally closed dry contacts, or from a 12VDC
signal. Once the State is returned to Normal Bypass will also return loads to the DMX
switch based upon the configured time. Return states can be timed at 1 second, 10
seconds, 1 minute, 10 minutes, or can be set to return under INTELLIGENT timing.
INTELLIGENT timing will truncate the return to normal time when Valid DMX inputs
are sensed.
B.
FUNCTIONAL
1. The DMX Emergency Bypass Switch shall be capable of overriding a up to four
(4) universes of ANSI E1.11–2008, USITT DMX512-A control signals from
“Normal” to “EMERGENCY” or “PANIC” when a trigger signal is detected via a
dry contact (normally open or normally closed) or a 12VDC signal user
configurable trigger input. Any DMX bypass switch not capable of up to four
universes of DMX control shall not be accepted.
2. Emergency and Panic states can either be a “snap shot” of the incoming DMX
signal or output all 512 outputs of each DMX universe to full intensity.
3. If both Emergency and Panic states are triggered Emergency state will always
take precedence over previous states.
4. The DMX Emergency Bypass Switch shall be capable of three different operating
modes:
a. Normal: Up to 4 separate DMX universes can be routed through the
Interface. The Interface routes the signals from DMX IN directly through
DMX OUT connectors. The signals are routed through DPDT Relays
(Common to Normally Closed contacts). The Interface does not alter the
DMX IN to DMX OUT in any way (direct connect). The interface can also
be configured to support 4 separate DMX circuits, or configured to act as
a Splitter. As a dual 1: 2 splitter, the Interface can route DMX IN A to
DMX OUT A and B, and DMX IN C to DMX OUT C and D. As a single
1:4 splitter, the interface can route a single DMX IN A to DMX OUT A, B,
C, and D.
b. Emergency: When an Emergency signal is detected on the Interface's
isolated Emergency Input port, EDBS will activate the DMX coupling
relays and disconnect the DMX IN from the DMX OUT ports. EDBS will
then output the saved Emergency DMX patterns to the connected
lighting fixtures. It will continue to transmit the DMX patterns until the
Emergency Input is removed and after a configured time delay. After the
Section 16500 – EMERGENCY DMX BYPASS SWITCH
time delay, the Relays are once again relaxed and the system returns to
the Normal Mode.
c.
Panic: Functions the same as the Emergency mode except that it can be
programmed to transmit a different pattern if desired. Panic uses a
separate Panic Input, separate Panic Learn and Test pushbuttons, and
separate configuration DIP Switches.
5. Each EDBS shall be capable of handling and splitting up to four universes of
DMX – systems not capable of more than one universe shall not be accepted.
EDBS’s splitter mode can be configured to support 4 separate DMX circuits, or
configured to act as a Splitter. As a dual 1: 2 splitter, the Interface can route DMX
IN A to DMX OUT A and B, and DMX IN C to DMX OUT C and D. As a single 1:4
splitter, the interface can route a single DMX IN A to DMX OUT A, B, C, and D.
6. The EDBS shall monitor the input trigger, after triggered state is released a
Return to Normal state shall be accomplished via: Return states can be timed at:
a. 1 second
b. 10 seconds
c. 1 minute
d. 10 minutes
7. INTELLIGENT TIMING Return to Normal state: INTELLIGENT timing will
truncate the return to normal time when valid DMX inputs are sensed.
C.
MECHANICAL
1.
Overview: The Emergency DMX Bypass Switch (EDBS) enclosure shall be a
surface mounted, constructed of 16-gauge, formed steel panels with a removable
front cover. Finish: Exterior surfaces shall be finished in fine textured, scratchresistant, powder coat paint.
2. Mounting: The Emergency DMX Bypass Switch can be wall-mounted or rackmounted using the included mounting brackets knockout holes in the unit’s
housing can be used to route power wiring and network cables as required. Unit
may be mounted horizontally or vertically (wall mount) or horizontally (rack mount
- 4U / 7-inches).
3. Wiring: The Emergency DMX Bypass Switch (EDBS) enclosure shall provide
discrete high and low voltage wiring compartments with voltage barrier.
a.
EDBS shall support labeled, terminations for two 24 – 12 AWG solid or
stranded power wires.
b.
EDBS shall support one Grounding Lug for 24-14 AWG solid or stranded
ground wire.
c.
EDBS shall support board labeled, Phoenix connector termination for DMX
Input and DMX Output wiring. Terminations shall support Belden 9729 cable
or equivalent.
d.
EDBS shall support board labeled, Phoenix connector termination for the
bypass contact inputs. Termination shall support two, 30-14 AWG lowvoltage wires (.255 – 1.628mm2)
Section 16500 – EMERGENCY DMX BYPASS SWITCH
4.
The Emergency DMX Bypass Switch (EDBS) shall have a five (5) tri-color LED
indicator visible from the exterior of the enclosure to include one for each DMX
signal as well as an overall system Status.
a.
b.
c.
DMX Status LED (one for each DMX Port)
1)
OFF - No DMX Activity (receiving or transmitting)
2)
GREEN - Receiving DMX IN (Normal State)
3)
RED - (Solid or Blinking) - Emergency DMX pattern is being
Transmitted.
4)
ORANGE - (Solid or Blinking) - Panic DMX pattern is being
Transmitted.
Unit Status LED
1)
OFF - Unit is not powered
2)
Slow GREEN blink for Normal operating mode
DMX Control LED Status will display control information as per
1)
Port LEDs will Turn Green if receiving DMX.
2)
Port LEDs will turn:
a)
GREEN (with a small mix of RED) when controlled by another
Splitter Port
b)
RED blinks indicate Emergency condition (Input or Test)
c)
Red to indicate Emergency (triggered by an Input)
d)
toggle between Red and Green to indicate Emergency (triggered
by a Test Emergency button)
e)
ORANGE blinks indicate Panic condition (Input or Test)
f)
Orange to indicate Panic (triggered by an Input)
g)
5.
The Emergency DMX Bypass System (EDBS) shall have a two recess mounted
test buttons accessible from the front of the enclosure without removing any
panels.
a.
6.
toggle between Orange and Green to indicate Panic (triggered by
a Test Panic button)
Each test button (Emergency or Panic) shall immediately trigger the
selected state after a 3 second hold.
1)
The test button shall stay enabled for ten minutes and then returns
to normal state after the ten minutes has elapsed or after the test
button has been held a second time to exit test mode.
2)
The test button shall be recessed to prevent accidental triggering
The Emergency DMX Bypass System (EDBS) shall have internally accessible,
labeled DIP switches for configuration of:
a.
DMX Splitter Operation
1)
One to One Patch
2)
Two in Two out Patch
3)
One in Four out Patch
Section 16500 – EMERGENCY DMX BYPASS SWITCH
b.
Emergency Timing:
1)
Fixed Timing
a)
2)
2)
g.
7.
Release of Emergency State after:
i)
One (1) Minute Intelligent
ii)
Ten (10) Minute Intelligent
Release of Emergency State after:
i)
One (1) Second
ii)
Ten (10) Seconds
Intelligent Timing: Intelligent Timing Truncates time setting if Valid
DMX input is present
a)
f.
Ten (10) Seconds
Fixed Timing
a)
e.
One (1) Second
Panic Timing:
1)
d.
i)
ii)
Intelligent Timing: Intelligent Timing Truncates time setting if Valid
DMX input is present
a)
c.
Release of Emergency State after:
Release of Emergency State after:
i)
One (1) Minute Intelligent
ii)
Ten (10) Minute Intelligent
Emergency DMX Output Mode
1)
Output Channels 1-512 @ Full.
2)
Outputs Captured (recorded) DMX state.
Panic DMX Output Mode
1)
Output Channels 1-512 @ Full.
2)
Outputs Captured (recorded) DMX state.
Emergency Input Activation
1)
Normally Open (dip switch)
2)
Normally Closed (dip switch)
3)
12VDC (wiring configuration)
Panic Input Activation
1)
Normally Open (dip switch)
2)
Normally Closed (dip switch)
3)
12VDC (wiring configuration)
The Emergency DMX Bypass System (EDBS) shall have two, internally accessible
buttons for DMX Record (Emergency and Panic) with an indicator LED for record
action.
1)
The record button shall be momentary only and held for at least 3
seconds before activation to prevent accidental recording.
2)
The record LED indicator will flash when record function is active.
Section 16500 – EMERGENCY DMX BYPASS SWITCH
3)
8.
D.
The record LED indicator will illuminate steady when record function
is complete.
The Emergency DMX Bypass System (EDBS) dimensions and weights shall not
exceed:
a.
7” H x 19”(w. Rack Ears)W x 3-3/16” D,
b.
9.7 lb.
ELECTRICAL
1.
The Emergency DMX Bypass System shall be completely internally pre-wired by
the manufacturer.
2.
The contractor shall provide input feed and control wiring.
a.
3.
The Emergency DMX Bypass System shall support up to four (4) DMX inputs and
outputs using two input modes:
a.
4.
Emergency DMX Bypass System (EDBS) shall support 100 to 277 volt
input power, 50/60 Hz, 0.6 A, Single Phase
The Emergency DMX Bypass Switch bypass input shall be configurable for
two functions using the internal dipswitches:
1)
Maintained Normally Open (N.O.), or Maintained Normally Closed
(N.C.).
2)
12VDC Wiring Configuration.
The Emergency DMX Bypass System (EDBS) shall support upto four (4)
Universes (512 channels) of Digital Multiplexing (DMX) in accordance with ANSI
E1.11–2008, USITT DMX512-A.
a.
Units that do not support E1.11–2008 compliant DMX communication shall
not be acceptable
5.
The Emergency DMX Bypass System (EDBS) shall not process (pass-through)
the normal DMX input.
6.
The Emergency DMX Bypass Switch (EDBS) shall internally switch from the
normal DMX input (pass through) to the bypass DMX output using
electromechanical relays when triggered.
a.
7.
The EDBS shall have non-volatile memory for storage of four (4) recorded
sequence of 512 channels.
1)
The recorded sequence shall persist through power outages
2)
The default sequence shall have all 512 channels at “full” if no
sequence is recorded.
The Emergency DMX Bypass System shall be UL and cUL Section 924 Listed for
interaction with similarly listed products and shall comply with and list to: cETLus:
UL924, CSA C22.2#141; CE IEC 60730-1,61347-1&61347-2-3; EMC: FCC
47CFR PT 15 SPT B, EN55022, EN55024, EN61000-3-2, EN61000-3-3
Section 16500 – EMERGENCY DMX BYPASS SWITCH
E.
THERMAL
1.
Ambient room temperature: 0-40°C / 32-104°F
2.
Ambient humidity: 5 to 95% non-condensing
F.
PLEASE PROVIDE:
1.
(XX) 96250 Philips Strand Lighting Emergency DMX Bypass Switch.
END OF EMERGENCY DMX BYPASS SPECIFICATION.
Download