39904620 - Telecommunications Industry Association

advertisement
Telecommunications Industry Association
(TIA)
TR-30.3/99-04-620
San Jose, 12-13 April 1999
COMMITTEE CONTRIBUTION
Technical Committee TR-30 Meetings
SOURCE:
AG Communication Systems/Lucent
CONTRIBUTOR:
Randy Brown
TITLE:
Non-Continuous Events in the Telephone Outside Plant
PROJECT:
PN-4254/PN-4255
DISTRIBUTION:
Members of TR30.3 and attendees at San Jose meeting.
Phone:
Fax:
email:
602-581-4125
602-582-7111
brownr@agcs.com
_______________________________
ABSTRACT
Some recent submissions1, 2 to T1E1.4 suggest that non-continuous events, such as power variances, can
be detrimental to services shared within the binder. This contribution characterizes three ubiquitous,
non-continuous Plain Old Telephone Service (POTS) events: ringing, supervision, and dial pulse in
order to illustrate that intra-binder interference in DSL frequency bands has been present for decades in
the Public Switched Telephone Network (PSTN). These normal events represent cross talk impairments
of changing magnitude, which are more severe than the classes currently under consideration for the
Spectral Management standard.
_______________________________
1.
INTRODUCTION
The discussion examines three common, non-continuous POTS events, with some supporting test
measurements, which are known to couple into DSL frequencies on adjacent pairs.
2.
2.1.
DISCUSSION
Ringing
Ringing in North America is an AC voltage superimposed on a DC bias. The majority of installations in
the US use non-sinusoidal 20 Hz ringing with a nominal rms. 90 volts at the ringing source. A
significant number of telephone installations in North America use other frequencies that range from 16
2/3 to 66 2/3 with voltages from 85 to 1353. One ANSI standard sets the maximum voltage limit to
150V rms4 and notes cases where it can attain 175V rms.
Copyright Statement
The contributor grants a free, irrevocable license to the Telecommunications Industry Association (TIA) to incorporate text
contained in this contribution and any modifications thereof in the creation of a TIA standards publication; to copyright in
TIA's name any standards publication even though it may include portions of this contribution; and at TIA's sole discretion
to permit others to reproduce in whole or in part the resulting TIA standards publication
Non-Continuous Events In the Telephone Outside Plant
TR30.3
Ringing is clearly a non-continuous disturber. At the beginning of each ringing burst there is a transition
from -48-Volt battery feed to -48-Volt with superimposed AC ringing. Nominal interrupts are 2 seconds
on and 4 seconds off. Custom ringing cadences with multiple ringing, such as triple cadences, are
common. The ringing waveform is ideally a sine wave with its axis of symmetry shifted -48-Volts from
zero. The ringing burst can be characterized in terms of 100's of milliseconds as shown in Figure 1. In
this depiction, the sine wave starts and stops in unity with the DC bias and represents the best case
relative to instantaneous power changes as a result of ring application and trip.
-138 V
nominal peak
90 Vac rms.
4200 mS
1800 mS
Figure 1. Standard Ringing Potential with Best Case Start/End
Elements of synchronization are related to the application of ringing in many applications, such as the
use of a common ringing bus serving hundreds of lines. Central office implementations, in many cases,
simultaneously ring multiple lines with concurrent cadence. As such, the application and withdraw of
ringing is generally without regard to the phase angle of AC energy. The peak voltage when ringing is
tripped can be the sum of the DC and greatest AC or approximately 170 volts as shown in Figure 2.
20Hz or 50 mS Peak to Peak
~170V worst case
- 90Vrms ac
2
- 48Vdc
0
+ 48Vdc
Figure 2. Standard Ringing Potential Worst Case Start/End
AG Communication Systems/Lucent
Page 2 of 8
02/12/16
Non-Continuous Events In the Telephone Outside Plant
TR30.3
Ringing is not balanced within the pair as it is ordinarily applied on only the ring conductor of the
telephone pair, while the tip conductor is held near earth ground. The unbalanced application of ringing
increases the pair-to-pair coupling within the binder group.
In practice, multi-vibrators generate the wave shape of the ringing energy. To smooth the resulting wave
edge, post filtering is applied to the generated waveform. The ringing interrupters switch from the AC
and DC ringing potentials to a DC-only potential during the silent interval as illustrated in Figure 3.
This switching is not synchronized with the ringing waveform.
DC
Bias
-48Vdc
Fuse
Line Frame
Interruption
Time i, i+2...
DC
Source
Driver
Transistor
F
i
138 V
-48Vdc
l
nominal
peak to peak t
e Ringing Bus
r
Time i+1...
-48Vdc
Figure 3. Basic Ringing Generator
In its worst case, a generated ringing waveform is a trapezoidal shape, which means it has higher
frequency components occurring at 25 mS intervals. Transient energies often result from gap switching
in the ringing generator as shown in Figure 4.
The phase at the transition edge of ringing can be > 500Hz
infinity
Time i+2
Time i
< .5 mS
25 mS
Time i+1
1 mS
Figure 4. Ringing Waveforms (Worst Case Generalization)
AG Communication Systems/Lucent
Page 3 of 8
02/12/16
Non-Continuous Events In the Telephone Outside Plant
TR30.3
A square waveform is made of a fundamental frequency f and all the odd harmonics rising to infinity,
that is, 3f, 5f, 7f and so on. As a ringing waveform nears a square or trapezoidal shape together with its
instantaneous application on a line, it can be expected to produce fundamental harmonics across a wide
array of frequencies. This was observed using a spectrum analyzer sampling distinctive ringing
frequencies at 3kHz for approximately 10 minutes, on a copper pair with 135 Ohms termination
impedance adjacent to a continually ringing line, within a binder of 10Kft 24AWG, for the upstream
ADSL bandpass as shown in figure 5:
-58.6 dBm
-90 dBm
noise floor
Max ADSL
Upstream
Transmit Power
-34.5 dBm5
Figure 5. Ringing Impulse Noise within the ADSL Upstream Bandpass
With the noise floor shown of approximately -90dBm along with a peak ringing amplitude of about 58dBm, its clear that over 30dBm of ringing impulse noise within the frequencies of interest to the
spectral management project is not unusual. This effect of ringing was also observed on various lengths
of copper, with randomly selected pairs across a wide array of frequencies using ringing generators, line
circuits and ringing cards in current commercial service as described in appendix A.
Various forms of ringing cadence exist as noted above such as "triple," "double," "long/short," "coded,"
and "teen ringing.6" For example, triple ringing bursts three times within 1800 mS as shown in Figure 6.
These have the effect of increasing random, ring application and removal impulse effects as shown
above. Plainly, one line alone ringing within a binder can represent a significant non-continuous
disturber, which all DSL systems must accommodate.
1800 mS
Figure 6. Triple Ringing Interval
AG Communication Systems/Lucent
Page 4 of 8
02/12/16
Non-Continuous Events In the Telephone Outside Plant
TR30.3
Telephone Switching systems typically have the capability of ringing as many as one-fourth of the
connected lines. Accordingly, in the worst case, an average of 6 of the 25 pairs in a binder group could
be in some phase of ringing application or removal.
2.2.
Supervision (hook flash)
As shown in Figure 7, the DC potential is applied to the customer loop through a battery-feed device
consisting of two inductive coils in series with tip and ring. An idle circuit is nominally 48 Volts with no
current flowing.
48Vdc
Figure 7. Simple Battery Feed Arrangement
During service initiation, the customer closes the loop and a transient voltage migration occurs within
the cable pair of greater than 40 volts, that is, it drops to 6 volts across the telephone set.
A sudden voltage change in the presence of distributed capacitance can couple as not all of it gets
cancelled out. A wave front of the sudden change in loop voltage is unbounded and currently
unrestricted. In a theoretical situation with a short customer loop and no capacative leak between tip and
ring conductors, the instantaneous peak-to-peak value of these potentials can reach 2,000 volts due to the
inductive reactance of the battery feed device. POTS filters for DSL are only on the pair connected to
and adjacent pairs are susceptible to the type of inductive kick as described above. This exists
throughout the network today.
In some cases, on longer loops, the voltage is boosted in order to achieve objective currents while the
telephone is off hook. Therefore, 48 volts is the minimum of voltage change that may be encountered.
This effect was observed on a spectrum analyzer lab setting as described above for ringing with the
collector located at the premise side as shown in Figure 8.
AG Communication Systems/Lucent
Page 5 of 8
-80dBm
02/12/16
Non-Continuous Events In the Telephone Outside Plant
TR30.3
-90dBm
Figure 8. Hook Switch Coupling
2.3.
Dial Pulse
These are periodic transitions from on-hook to off-hook in order to convey numeric values typically at
10 pulses per second in North America. Usually, 40 ms make (close) versus 60 ms break (open) as there
is less time required to build the magnetic flux versus lose it. As soon as the dial on the phone is turned,
all of the resistance in the circuit (all the handset circuitry) is shunted. There is a solid short in the
circuit in order to get ready to go to maximum current.
The shorter the loop the higher the current but the less the cross talk potential. This is just the opposite of
longer loops. These phenomena exist on short and longer loops. The highest value is a zero (10 pulses).
The random, reoccurring cross talk effects of dial pulse were observed on a spectrum analyzer with a lab
setting as described above for supervision signaling with the collector located at the premise side as
shown in Figure 9. In some jurisdictions, all telephone lines must support dial-pulse digit collection
methods.
-74dBm
-90dBm
Figure 9. Dial Pulse Coupling
3.
CONCLUSION
These conditions co-exist with ISDN today. Therefore, ringing, hook flash and dial pulse noncontinuous characteristics exemplify tolerable interferers. Accordingly, services that are frequency
bounded and current limited in order to conform to service classes within the spectral management
project should be permitted independent of their temporal characteristics.
References:
[1] T1E1.4/99-103, "Stationarity and Time-Domain Specifications for Spectrum Management", Bellcore, March
11, 1999, Costa Mesa, California;
[2] J. Stiscia and D. Johnson, "Selected Measurements of Non-Stationary and Stationary Crosstalk Effects Upon
FDM ADSL," T1E1.4/99-040, February 1, 1999.
[3] GTE Customer Handbook - 500, Issue 1, 1972
[4] T1.401-1993, "Interface Between Carriers and Customer Installations--Analog Voicegrade Switched Access
Lines Using Loop-Start and Ground-Start Signaling."
[5] T1.413-1998, " Network and Customer Installation Interfaces - Asymmetric Digital Subscriber Line (ADSL)
Metallic Interface."
[6] ANSI T1.401.02-1995, "Interface between Carriers and Customer Installations--Analog Voicegrade Switched
Access Lines with Distinctive Alerting Features."
AG Communication Systems/Lucent
Page 6 of 8
02/12/16
Non-Continuous Events In the Telephone Outside Plant
TR30.3
[7] Federal Communications Commission Rules and Regulations, Code of Federal Regulations Title 47: Part 68 Connection of Telephone Equipment To The Network
AG Communication Systems/Lucent
Page 7 of 8
02/12/16
Non-Continuous Events In the Telephone Outside Plant
TR30.3
Appendix A - Ringing Loop Simulation Setup & Testing Results
Setup
 Test method: Distinctive ringing on pair 1, read impulse noise on pair 2
 3 kHz sampling frequency, 25kHz - 140kHz & 0-300kHz
 135 Ohms termination impedance on pair 2
 2524 (24 Gauge) SEALPIC-FSF SX08 98C cable
 5REN load on pair 1 at premise during ringing tests
 5 minutes collection for ringing, 1-2 minutes for dial pulse and supervision
 Commercial Line Card & Ringing Generator in use today in major ILEC market
 Measured at CO during ringing and premise during dial pulse and supervision
Results for 0-300kHz Ringing Sampling Frequency
Loop Length ft
18,000
15,000
10,000
5,000
1,000
Noise Floor dBm
-89.6
-90.0
-90.0
-89.0
-89.0
Highest Peak dBm
-60.8
-59.8
-59.8
-55.2
-57.6
Coupling was noted across the frequencies of interest. 6dB variance was observed based on the pair
selected.
AG Communication Systems/Lucent
Page 8 of 8
02/12/16
Download