Portable Fire Extinguishers

advertisement
1
Portable Fire Extinguishers
References:
29 CFR 1910.157 Portable Fire Extinguishers
NFPA 10
Standard for Portable Fire Extinguishers
Description:
The requirement of the above references applies to the placement, use, maintenance,
and testing of portable fire extinguishers provided for use of employees.
Key Maintenance Procedures:
1.
2.
3.
4.
5.
Monthly Maintenance/Inspection.
Annual Maintenance/Inspection
6-Year Maintenance (DCP), 5-year Maintenance (CO2)
Recharging/Refilling
Hydrotesting
Procedure 1 above is normally performed by a designated employee/Safety
Coordinator of a company.
Procedure 2, 3, 4 & 5 are services provided by Island Equipment Company.
For more information, Please call 565-2485/4574/4575.
Island Equipment Company
Member, NFPA – National Fire Protection Association
Member, NAFED – National Association of Fire Extinguisher Distributor
Registered Cylinder Hydrostatic Testing Facility - U.S. DOT
2
1.
Monthly Maintenance/Inspection Procedure:
Periodic Inspection (monthly) of fire extinguishers shall include a check of at least the
following:
a.
b.
c.
d.
e.
f.
g.
Location in designated place.
No obstruction to access or visibility.
Operating instructions on nameplate legible and facing outward.
Safety seals and tamper indicators not broken or missing.
Fullness determined by weighing or “hefting”.
Examination for obvious physical damage, corrosion, leakage, or clogged
nozzle.
Pressure gauge reading or indicator in the operable range or position.
The date of inspection and the initials of the person performing the inspection shall
be recorded on the monthly inspection tag.
IF:
THEN:
IF:
THEN:
An inspection of any fire extinguisher reveals a deficiency in any of
condition a & b above.
Immediate corrective action shall be taken (i.e. install a new bracket,
remove any obstruction to fire extinguisher access, etc.)
An inspection of any fire extinguisher reveals a deficiency in any of
condition c, d, e, f & g above.
Fire extinguisher shall be subjected to applicable maintenance procedure
as per the references on page 1. You can call Island Equipment
Company @ 565-2485/4574/4575 for more information.
2.
Annual Maintenance/Inspection Procedure.
3.
Six-Year Maintenance
4.
Recharging/Refilling
5.
Hydrotesting
3
Additional Services Provided with an Island Equipment Fire Extinguisher
Contract:
1) Free evaluation of fire extinguishers on existing premises
a. Visual inspection of all identified units ensuring that each cylinder
is compliant with existing NFPA 10 code.
b. Recommendation of items which need to be addressed to be
compliant with NFPA 10 code, if necessary.
2) Free instruction for employees designated by company to conduct
monthly inspections of cylinders.
3) All brand new fire extinguishers come with wall hooks and IECO tags.
Installation is available at no extra charge.
Download