QUALITY WATER SUPPLIED FROM GROOTHOEK PLANT IN MODDER RIVER REGION
JANUARY – OCTOBER 2014
Microbiological safety requirements
Count/ml
Limit
HPC
Count/100ml 0
E.Coli
Count/100ml 0
FC
Count/100ml 0
Physical and Chemical Requirements
Conductivity
pH
Turbidity
mS/m
pH units
NTU
Compliance
Target %
Compliance
Achieved %
Number of
tests
99.0
99.0
99.0
100.0
100.0
100.0
360
360
360
Number of
noncompliances
0
0
0
Class 1 Limit
Compliance
Target %
Compliance
Achieved %
Number of
tests
150
5.0 – 9.5
0 – 1.0
95
95
95
100
100
100
150
150
150
Number of
noncompliances
0
0
0
95
95
95
95
95
95
100
100
100
100
100
100
150
150
150
15
150
150
0
0
0
0
0
0
95
95
95
95
95
100
100
100
100
100
15
15
15
150
15
0
0
0
0
0
Chemical Requirements – macro-determinants
Ammonia
mg/l as N
1
Calcium H
mg/l as Ca
500
Chloride
mg/l as Cl
200
Fluoride
mg/l as F
1
Magnesium H
mg/l as Mg
70
Potassium
mg/l as K
50
Chemical Requirements – micro-determinants
Arsenic
µg/L as As
10
Iron
mg/L as Fe
0.2
Manganese
mg/L as Mn
0.1
Aluminium
mg/L as Al
0.3
Copper
mg/L as Cu
1
Chemical Requirements – macro-determinants
DOC
mg/L as C
10
95
100
6
0
Total
µg/L
200
95
100
6
0
Trihalomethanes
Modder River Region at Groothoek plant supplies water to the greater part of Thaba-Nchu Township and ThabaNchu Southern Villages areas. This water is tested regularly and is compared to the SANS 241.