Energy Efficient Buildings Sizing Air Handlers and Chillers Air handlers, boilers and chillers must be sized to meet peak loads. The quantity of air supplied by the supply air fan must be large enough to meet the greater of the peak cooling or peak heating load. In most large multi-zone buildings, the peak cooling load is greater than the peak heating load since all zones are subject to cooling loads, while only exterior zones are subject to heating loads. This chapter discusses how to calculate the volume flow rate of the supply air fan and the cooling capacity of the chiller required to meet the peak cooling load. Example Consider the single-duct reheat system shown below. To begin, design conditions for the indoor air, outdoor air, required ventilation and incident solar radiation should be determined. Peak sensible and latent cooling loads for each zone are then calculated based on these conditions. In the example below, only design loads for Zone 2 are shown. However, in actual practice, design cooling loads for all zones served by the air handler should be calculated and summed to determine the total sensible and latent loads. In addition to these conditions, the temperature of the cooling water supplied to the chiller and the temperature of the air leaving the cooling coil should be specified. These conditions and peak sensible and cooling loads are shown in the figure below. 1 Return Air Fan Qsen 1 Qsen 2 Zone 1 Zone 2 Qlat 1 Qlat 2 Tz1 Tz2 1' Reheat Box 1 Filter Supply Air Fan Reheat Box 2 Cooling Coil 3 2 0 3-Way Valve 3-Way Valve CW Supply CW Return HW Supply HW Return 3-Way Valve HW supply HW Return 0: T0 = 90 F RH0 = 55% : h0 = 39.8 Btu/lba wo = 0.0167 lbw/lba p0 = 0.07 lba/ft3 1: T1 = 72 F RH1 = 50% : h1 = 26.5 Btu/lba 3: T3 = 58 F Zone 2 : Qs = 42,000 Btu/hr, Ql = 18,000 Btu/hr, 25 people requiring 20 cfm outdoor air /person Chilled Water : TCWSupply = 55 F 1 The process lines on a psychrometric chart are shown below. The mixed air condition, 2, is a mix of the return air, 1, and outdoor air, 0. As the mixed air travels over the cooling coil, some air is cooled all the way to saturation while some air bypasses the coil. The ‘coil conditioning line’ is defined by state point 2 and the temperature of cooling water entering the cooling coil. The average temperature of the air leaving the cooling coil is 58 F. Thus, state point 3 lies on the coil conditioning line at the temperature of the air leaving the coil. The space conditioning line between supply air, 3 and return air, 1, shows the sensible and latent heat added in Zone 2. Coil Condition Line 2 3 0 1 Space Condition Line 58 72 75.1 90 The procedure to calculate the required air flow rate and cooling capacity follows from a series of mass and energy balances on the various systems. In this example, the mass and energy balances can be solved in five steps, by sequentially analyzing systems with only one unknown. Use the following five step method to determine peak loads and the required sizes of the air handling cooling coils and the chiller. Step 1: Find mass flow rate of supply air m3 In most commercial buildings, the total building cooling load is greater than the heating load due to internal heat gains from occupants and electrical equipment and because interior spaces experience only cooling loads. Thus, the mass flow rate of air required to meet the peak building cooling load is usually greater the mass flow rate of air required to meet the peak heating load. When this is the case, air-handler fans are sized to handle peak cooling rather than peak heating loads. A sensible energy balance on the air and heat flows into/from zone 1 gives: 2 m c T m c T 0 Q s1 ,3,1 p 3 ,3,1 p 1 3.1 m Q s1 42,000 Btu 1 lba F 1 lb 12,245 c p T1 T3 1 hr .245 Btu 72 58F hr The total mass flow rate of air through the supply air fan, m3, is the sum of the mass flow rates of air required through each zone. m3 = m3,1 + m3,2 + … Step 2: Find mass flow rate of outdoor air, moa, and fraction outdoor air, foa Next, find the fraction of supply air that must come from the outdoors in order to meet occupant requirements for fresh air. The fraction outdoor air, foa, is: foa = moa / m3 . Outdoor air requirement: 20 cfm person ft 3 lba min lb moa 25 persons 20 2,100 .07 3 60 ft hr hr min person foa fraction outside air 2,100 17% 12,245 Step 3: Fix state point on psychrometric chart Next, find the state of air leaving the cooling coil from the set-point temperature, T3, and an energy balance on the zone. A total energy balance on the zone gives: 3h3 m 3h1 0 Q s Q l m Q Q l Btu 42,000 18,000 Btu hr Btu h3 h1 s 26.5 21.6 3 m 12,245 lba hr lba lba (T3, h3) fix point Step 4: Fix state point on psychrometric chart Next, find the state of mixed air entering the cooling coil from sensible and total energy balances on the mixing box where outdoor and return air are mixed. A sensible energy balance on the mixing box gives the temperature at point 2. 3 m ,0 c p T0 m ,1 c p T1 - m ,2 c p T2 0 o To m 1 T1' 2,100 90 12,245 2,100 72 m T2 75.1F 2 m 12,245 A total energy balance on the mixing box, gives the enthalpy at point 2. oho m 1 h1 m 2h2 0 m h m 1h1 2100 39.8 12,245 2100 26.5 m Btu h2 o o 28.8 2 m 12,245 lb The specific volume of air at point 2 entering the cooling coil can now be determined from the psychrometric chart. ft 3 v 2 (from psychromet ric chart) 13.6 lb Step 5: Find total heat removed from air, Qc Finally, the total heat removed from the air can be determined from a total energy balance on the cooling coil. 2h2 Q c m 3h 3 0 m 1 ton lb Btu Btu 2 h2 h3 12,245 (28.8 21.6 Q c m 7.3tons 88,164 hr lb ) Btu hr 12,000 hr A small fraction of the energy removed from the air leaves the cooling coil as cold condensate; however in design calculations, the energy carried away by the condensate is typically considered to be negligible compared to the energy removed by the cooling coil. Thus, cooling coils are typically sized to handle the total cooling removed from the air. Final Specifications The total cooling coil load, volume flow rate through the supply air fan, cooling coil bypass factor, and cooling coil sensible heat ratio can then be determined. The values for this example are shown below. All of these values are typically required by cooling coil vendors in order to specify the correct cooling coil. In an HVAC system with multiple air handlers, the total peak cooling load on the chiller would be the sum of the peak loads of the air handlers. The total load on the cooling coil is: Q c 88,164 Btu/hr / (12,000 Btu/ton hr) 7.3tons 4 The volume flow rate across the fan is: ft 3 1 hr lb 2 v 2 12,245 13.6 ν 2 m 2,775cfm hr lb 60 min The cooling coil by-pass factor is; BF T3 Tcc 58 55 15% T2 Tcc 75.1 55 The sensible heat ratio across the coil is: SHR (coil) Q s Q tot,coil lb Btu 12,245 .245 75.1 58 F 3 c p T3 T2 m hr lb F 58% 3 h2 h3 m Btu 88,164 hr 5